Reference Ice Plant
Reference Ice Plant
Reference Ice Plant
College of Engineering
Department of Mechanical Engineering
City of Batac
ME161
DESIGN OF ICE PLANT
Submitted by:
Neal Janus R. Pacis
BSME 4
Submitted to:
Engr. Robert M. Martin
FREEZING TIME
6.2 (thickness)2
tf =
32 − (t brine )
6.2 (8")2
tf =
32 − (10.4o F)
t f = 18.37 hrs.
NUMBER OF CANS
tf
N = production rate 𝐱
weight of ice block
N = 392.91 cans
HEIGHT OF FREEZING TANK
Q1 = heat to be removed from the available water to 0oC by means of sensible cooling
Q2 = latent heat required to convert water into ice at 0oC
Q3 = heat to be removed from 0oC to ice temperature by means of sensible cooling
Q2 = mH2O 𝐱 L
KJ
Q2 = 0.40509 kg⁄s (335 )
kg
Q2 = 135.71 KW
Q P = Q1 + Q 2 + Q 3
QP = 44.09 KW + 135.71 KW + 7.63 KW
QP = 187.43 KW
Qpt = 1.10(Qp )
Qpt = 1.10(187.43 KW)
1 ton of Refrigeration
Qpt = 206.173 KW 𝐱 = 58.64 TOR
3.516 KW
GPM
BAC = 65 𝐱 58.64 TOR
TOR
1.0 HP
BAP = 𝐱 35 tons⁄day
17.5 tons⁄day
BAP = 2.0 HP
VOLUME OF AIR
ft 3 ⁄min
Vair = 0.5 𝐱 no. of cans
can
ft 3 ⁄min
Vair = 0.5 𝐱 384 cans
can
ft 3
Vair = 192
min
AIR POWER
lb in2
2 𝐱 144 𝐱 Vair
AP = in2 ft 2
ft. lb
33000 HP. min
lb in2 ft 3
2 𝐱 144 𝐱 192
AP = in2 ft 2 min
ft. lb
33000 HP. min
AP = 1.68 HP
AP
BHP =
efficiency
1.68 HP
BHP =
0.90
BHP = 1.87 HP or 2 HP
Suction Line
4” NPS or 100mm
Outside Diameter: 114.3mm
Inside Diameter: 102.3mm
Discharge Line
3” NPS or 75mm
Outside Diameter: 88.90mm
Inside Diameter: 77.92mm
Liquid Line
2” NPS or 50mm
Outside Diameter: 60.33mm
Inside Diameter: 52.51mm
QTOTAL 206.173 KW
Refrigerant NH3 (Ammonia)
Evaporating Temperature -15oC
Condensing Temperature 35oC
Discharge Temperature (T2) 100oC
Polytropic Constant (n) 1.2
Percentage Clearance (c) 5%
Bore and Stroke (D/L) 1.0
No. of Cylinders 4 cylinders, single acting
Speed (N) 1200 RPM
QA
mr =
(h1 − h4 )
206.173 KW
mr =
KJ KJ
(1443.9 − 366.072 )
kg kg
mr = 0.1913 kg⁄s
n−1
n P2 n
Qw = [ (P1 v1 ) ([ ] − 1) − (h2 − h1 )] (mr)
n−1 P1
1.2−1
1.2 m3 1352.2 kPa 1.2 KJ KJ
Qw = [ (237.09 kPa 𝐱 0.508 ) ([ ] − 1) − (1685 − 1443.9 )]
1.2 − 1 kg 237.09 kPa kg kg
KJ kg
Qw = 2.1944 𝐱 0.1913
kg s
Qw = 0.4198 KW
Qw = mw (cpw )(∆T)
Qw
mw =
(cpw )(∆T)
0.4198 KW
mw =
KJ
(4.1866 ) (5K)
kg. K
mw = 0.0201 kg⁄s
WORK OF COMPRESSION
Wc + mr(h1 ) = Qw + mr(h2 )
Wc = Qw + [mr(h2 − h1 )]
kg KJ KJ
Wc = 0.4198 KW + [0.1913 (1685 − 1443.9 )]
s kg kg
Wc = 46.54 KW
Wc
ACP =
efficiency of compressor
46.54 KW
ACP =
0.80
ACP = 58.18 KW
ACP
Power Transmitted =
efficiency
58.18 KW
Power Transmitted =
0.90
Vf v1 𝐱 mr
PD = =
Nva Nva
m3 kg
0.508013 𝐱 0.1913 s
kg
PD =
0.8367
PD = 0.11615 m3 ⁄s
π 2
PD = (D )(L)(N)(No. of Cylinders)(No. of Acting)
4
m3 π rev 1 min
0.11615 = (D2 )(D) (1200 )( ) (4)(1)
s 4 min 60 sec
D = L = 0.12273m
D = L = 122.73mm
DESIGN OF V-BELT
B + √B2 − 32(D2 − D1 )2
C=
16
311.08 + √(311.08)2 − 32(16 − 13)2
C=
16
C = 38.86"
DESIGN HP
BELT SPEED
Vm = π(D1 )(N)
1ft
Vm = π(13") ( ) (1200 RPM)
12"
Vm = 4084.07 fpm
RATED HP/BELT
0.09
Rated HP 103 c Vm 2 Vm
= [a ( ) − − e 6 ] ( 3)
Belt Vm K d (D1 ) 10 10
0.09
Rated HP 103 137.7 (4084.07fpm)2 4084.07fpm
= [18.788 ( ) − − 0.0848 ]( )
Belt 4084.07fpm 1.08(13") 106 103
Rated HP
= 21.77 HP
Belt
Adjusted Rated HP
= (0.9923)(0.86)(21.77 HP)
Belt
Adjusted Rated HP
= 18.58 HP
Belt
NUMBER OF V-BELTS
Design HP
No. of V − Belts =
Adjusted Rated HP⁄Belt
120 HP
No. of V − Belts =
18.58 HP
DESIGN OF CONDENSER
(Btu⁄hr) Watts
UO = 253.125 2
= 1437.31 2
ft . F m .K
25mm NPS
Outside Diameter: 33.40mm
Inside Diameter: 26.64mm
HEAT REJECTED
QR = mr (h2 − h3 )
kg KJ KJ
QR = 0.1913 (1685 − 366.072 )
s kg kg
QR = 252.31 KW
QR
mw =
cpw (∆T)
252.31 KW
mw =
KJ
(4.1866 ) (5K)
kg. K
mw = 12.05 kg⁄s
t entering + t leaving
t average =
2
25o C + 30o C
t average =
2
t average = 27.5o C
1
ρH2O =
vf
m3
vf = 0.0010036
kg
1
ρH2O =
m3
0.0010036
kg
ρH2O = 996.41 kg⁄m3
m
NT ( ρ H2O )
H2O
= π
pass 2
(ID )(water velocity)
4
NT 0.01209 m3 ⁄s
=
pass π ft 1m
(0.02664m)2 (5.5 ) (
4 s 3.281ft)
NT
= 12.94 or 13
pass
∆tmax − ∆tmin
LMTD =
∆tmax
ln ( ∆tmin )
10℃ − 5℃
LMTD =
10℃
ln ( )
5℃
LMTD = 7.21℃
QR
AO =
UO (LMTD)
252310 Watts
AO =
Watts
1437.31 2 (7.21K)
m .K
AO = 24.35m2
AO
L=
NT
π(OD)(No. of Pass) (pass )
24.35m2
L=
π(0.03340m)(7)(13)
L = 2.55m
AS = 0.0245m2
DIAMETER OF SHELL
π
AS = (D )2
4 S
0.0245m2
DS = √ π
4
DS = 0.17662m or 176.62mm
LIQUID RECEIVER
According to Moyer, Liquid Receivers must hold at least 0.50 gal of refrigerant
per ton of refrigeration. For convenience, dimension of Liquid Receiver must be
proportioned to the size of the condenser shell.
L
Assume = 3.5
D
gallons
VLR = 0.5 𝐱 58.64 TOR
TOR
3.785L 1m3
VLR = 29.32 gallons 𝐱 x
1 gallon 1000L
VLR = 0.1110m3
3
3 0.1110m
D= √ π
(4) (3.5)
D = 0.3431m or 343.07mm
L = 3.5(D)
L = 3.5(343.07mm)
L = 1200.76mm
DESIGN OF EVAPORATOR
(Btu⁄hr) Watts
UO = 105 2
= 596.22 2
ft . F m .K
SURFACE AREA OF EVAPORATOR
QPT
AE =
(UO )(LMTD)
206173 Watts
AE =
Watts
(596.22 2 ) (3K)
m .K
AE = 115.27m2
LENGTH OF HEADERS
DESIGN OF CRANE
FORMULAS
Wr = 1.6Dr 2 (Lr)
Minimum Ds = 30Dr
Dw = 0.067Dr
Am = 0.4Dr 2
TOTAL LOAD
TENSILE FORCE
Wr + W
Ft − Wr − W = ( ) (a)
32.2 ft⁄s 2
m ft
Vf = 0.15 = 0.49
s s
Vf − Vo
a=
t
0.49 ft⁄s − 0
a=
10 sec
a = 0.049 ft⁄s 2
((1.6Dr 2 (16.41ft)) + 660lb)
2
Ft − 1.6Dr (16.41ft) − 660lb = ( ) (0.049 ft⁄s 2 )
32.2 ft⁄s 2
Ft = 26.28Dr 2 + 661
BENDING FORCE
(Em)(Dw)(Am)
Fb =
Ds
(12x106 psi)(0.067Dr)(0.4Dr 2 )
Fb =
30Dr
Fb = 10720Dr 2
BREAKING STRENGTH
N=7
Fu = 42Dr 2 = tons
Fu − Fb
N=
Ft
2000 lbs
(42Dr 2 𝐱 2
7= 1 ton ) − 10720Dr
26.28Dr 2 + 661
Dr = 0.25 in.
HOIST POWER
Vf = π(Ds)(Ns)
Vf
Ns =
(π)(Ds)
Ds = 30(Dr)
Ds = 30(0.25")
Ds = 7.5"
m 3.281ft 60sec
(0.15 s ) ( 1m ) ( 1min )
Ns =
1ft
(π)(7.5in) (12in)
Ns = 15.04 RPM
Ds
(2π) ( (Ns)(Ft)
Hoist Power = 2)
ft. lb
33000 HP. min
0.625ft rev
(2π) (
Hoist Power = 2 ) (15.04 min) (662.64 lbs)
ft. lb
33000 HP. min
Hoist Power
Hoist Motor Power =
efficiency
0.59 HP
Hoist Motor Power =
0.90
mw = mwcondenser + mwcompressor
mw = 12.05 kg⁄s + 0.0201 kg⁄s
mw = 12.0701 kg⁄s
@26℃ 65% RH
h3 = 61 KJ⁄kg
HR 3 = 0.013
@32℃ 98% RH
h4 = 108 KJ⁄kg
HR 4 = 0.029
MASS OF AIR
KJ KJ kg KJ
(ma) (108 − 61 ) − [(12.0701 s ) (4.1866 ) (30℃ − 25℃)]
kg kg kg. K
mw5 =
KJ
(4.1866 ) (23℃)
kg. K
KJ
47 (ma) − 252.66 KW
kg
mw5 =
KJ
96.29
kg
mw5 = ma (HR 4 − HR 3 )
mw5
ma =
(HR 4 − HR 3 )
KJ
47 (ma) − 252.66 KW
kg
( KJ )
96.29
kg
ma =
(0.029 − 0.013)
KJ KJ
ma ((0.029 − 0.013) (96.29 ) − 47 ) = −252.66 KW
kg kg
ma = 5.56 kg⁄s
MASS OF MAKE-UP WATER
mw5 = ma (HR 4 − HR 3 )
mw5 = 5.56 kg⁄s (0.029 − 0.013)
mw5 = 0.089 kg⁄s
KJ
5.56 kg⁄s (0.287 ) (299K)
kg. K
Vair =
101.325 kPa − 3.363 kPa
Vair = 4.87 m3 ⁄s
COOLING TOWER
25℃ + 30℃
t average =
2
t average = 27.5℃
ρH2O = 996.41 kg⁄m3
12.0701 kg⁄s
VH2O =
996.41 kg⁄m3
m3 1000L 1 gallon 60 s
VH2O = 0.0121 𝐱 𝐱 𝐱
s 1 m3 3.785 L 1 min
VH2O = 191.81 GPM
VH2O
Cooling Tower Area =
3 GPM⁄ft 2
191.81 GPM
Cooling Tower Area =
3 GPM⁄ft 2
Assume L = 4.5 m
Cooling Tower Area = L 𝐱 W
Cooling Tower Area
W=
L
2
5.94 m
W=
4.5 m
W = 1.32 m
NUMBER OF NOZZLES
From Refrigeration and Air-conditioning by Jordan page 276, nozzles are spaces
to deliver a 0.10 to 0.40 GPM/ft2 of pool surface, and about 7 to 10 GPM capacity per
nozzle.
VH2O
No. of Nozzles =
8 GPM⁄nozzle
191.81 GPM
No. of Nozzles =
8 GPM⁄nozzle
NOZZLE ARRANGEMENT
Rows = 4
Nozzle/Row = 6
DIMENSION OF HEADERS
For the design of headers, economical H2O velocity is 1.2 m/s to 2.1 m/s.
PRIMARY HEADERS
mw π
= (ID)2 (vH2O )
ρH2O 4
mw
ID = √π
4 (ρH2O )(vH2O )
12.0701 kg⁄s
ID = √π
⁄ 3 ⁄
4 (996.41 kg m )(1.8 m s)
100mm NPS
Outside Diameter: 114.3mm
Inside Diameter: 102.3mm
SECONDARY HEADERS
mw π
= (ID)2 (vH2O )(no. of nozzles)
ρH2O 4
mw
ID = √π
4 (ρH2O )(vH2O )(no. of nozzles)
12.0701 kg⁄s
ID = √π
⁄ 3 ⁄
4 (996.41 kg m )(1.8 m s)(24)
20mm NPS
Outside Diameter: 26.67mm
Inside Diameter: 20.93mm
Range
CTE = 𝐱 100%
Range + Approach
t hot − t cold
CTE = 𝐱 100%
(t hot − t cold ) + (t cold − t wet bulb )
t hot − t cold
CTE = 𝐱 100%
t hot − t wet bulb
30℃ − 25℃
CTE = 𝐱 100%
30℃ − 21℃
CTE = 55.56%
FORCED DRAFT FAN
From Mechanical Handbook, P-194, Wheel Diameter ranges from 15” to 71”. Its
rated capacity ranges up to 150 cubic feet per minute of air against a static pressure of
less than 12” of water.
Pstatic v 2
Hta = +
γair 2g
Vair Vair
vair = =π
Area of Wheel 2
4 (Dw)
4.87 m3 ⁄s
vair =
π 1ft 1m 2
4 (35in 𝐱 12in 𝐱 3.281ft)
248.84 Pa
Ps = 1.5 in H2 O x = 373.26 Pa
1 in H2 O
2
373.26 Pa (7.85 m⁄s)
Hta = +
11.772 N⁄m3 2(9.81 m⁄s2 )
Hta = 34.85m
FAN POWER
FAN MOTOR
Fan Power
Fan Motor =
efficiency
1.9 KW
Fan Motor =
0.85
DISCHARGE DUCT
Vair
Area of Duct =
vair
4.87 m3 ⁄s
Area of Duct =
7.85 m⁄s
Assume H = 0.75m
Area of Duct = H 𝐱 W
Area of Duct
W=
H
0.62m2
W=
0.75m
W = 0.83m
Psuction
Elevation = + Allowance for fittings
γH2O
55 kPa
Elevation = + 4.6m
9.81 KN⁄m3
Elevation = 10.21m
m3
Vtank = 57.69
day
DIMENSION OF TANK
Assume H: 6m
D 2
Vtank = π ( ) (H)
2
4(Vtank )
D=√
π(H)
m3
4 (57.69 )
√ day
D=
π(6m)
D = 3.50m
Su
Sd =
Nu
310.18 MPa
Sd =
5
Sd = 62.04 Mpa
t = 3.43mm
Q
D = √π
4 (v)
0.00067 m3 ⁄s
D=√ π
⁄
4 (1.2 m s)
Q 0.00067 m3 ⁄s
v=π =π = 1.20 m⁄s
(D) 2 (0.02664m) 2
4 4
ρ(D)(v)
NS =
μ
NS = 31904.19
1
ε 106 3
fs = 0.0055 (1 + (20000 + ) )
D NR
1
0.5mm 106 3
fs = 0.0055 (1 + (20000 ( )+ ) )
26.64mm 31904.19
fs = 0.046
Ls = 100m
Standard Elbow = 0.76m
Gate Valve (Fully Open) = 0.18m
L v2
hfs = f
D 2g
2
100.94m (1.20 m⁄s)
hfs = 0.046 𝐱 𝐱
0.02664m 2(9.81 m⁄s 2 )
hfs = 12.79m
Q
D = √π
4 (v)
0.00067 m3 ⁄s
D=√ π
⁄
4 (2.1 m s)
Q 0.00067 m3 ⁄s
v=π =π = 1.95 m⁄s
(D) 2 (0.02093m) 2
4 4
ρ(D)(v)
ND =
μ
1 gm⁄cm3 (2.093cm)(195 cm⁄s)
ND = gm. cm
0.01002 s
ND = 40732.04
1
ε 106 3
fd = 0.0055 (1 + (20000 + ) )
D NR
1
0.5mm 106 3
fd = 0.0055 (1 + (20000 ( )+ ) )
20.93mm 40732.04
fd = 0.049
Ld = 100m
Standard Elbow = 0.69m
Standard Elbow = 0.69m
Check Valve = 1.52m
Gate Valve (Fully Open) = 0.15m
L v2
hfd = f
D 2g
2
103.05m (1.95 m⁄s)
hfd = 0.049 𝐱 𝐱
0.02093m 2(9.81 m⁄s2 )
hfd = 46.76m
Pd − Ps Vd2 − Vs 2
TDH = + + (Zd + Zs) + hfs + hfd
γ 2g
TDH = 81.39m
WATER POWER
WP = Q 𝐱 TDH 𝐱 γ
m3 KN
WP = 0.00067 𝐱 81.39m 𝐱 9.81 3
s m
WP = 0.53 KW
BRAKE POWER
WP
ep =
BP
WP 0.53 KW
BP = =
ep 0.80
BP = 0.67KW ≈ 1KW