F700 Quick Set Up Guide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Mitsubishi F700 inverter quick set-up guide

Mitsubishi inverters are factory set for EXTernal control.


When a START signal is connected across the STF-PC input terminals the inverter will run to a Display Hz/A/V
speed set by a potentiometer on terminals 10, 2, and 5, see below.
When START is pressed the FWD run status LED should flash and the Hz display increase. Control Mode
10
Check list :- + Run status
The EXT LED should be ON (PU is Parameter Unit mode for set-up). PU to EXT key
2 (swipe)
Use the correct common for the control signals, PC is the default, not SD.
The inverter will not run if the MRS signal is connected. -
5
Control mode Parameter Pr.79 is set to either 0 or 2 for EXT control.
Potentiometer

To change parameters
1) Change to PU operation ( )
2) Scroll to select the parameter (1) (2) (3) (4)
3) Press SET to display the current value
4) Scroll to change the value
5) Press SET button to write the value
Note - Mode change only possible when motor stopped.
Parameter setting only possible in PU mode. (5)

Basic Parameters, the A B C Note : Set Pr. 160 Extended function = 0 C - Basic operational settings
A - Motor details Mitsubishi Electric Motor Pr.1&2 Maximum & Minimum speeds (Hz)
Enter the details from the motor nameplate
SF-JR160 15kW 4Pole Pr.7&8 Acceleration & Deceleration time(sec)
Pr.3 Rated frequency (50Hz as default) Frequency 50Hz

Frequency / Speed
Motor Amps 29.2A
Pr.9 Rated current (Inverter max as default) Voltage 415V Pr.1
Pr.19 Rated voltage (Same as VIN as default) Operation
V Zone
B - Pump load type Pr.2
Pr.19
Match the inverter output to the pump duty -
Pr.14 = 1 for clean water centrifugal pumps & fans Pr.14=0
Pr.14 = 0 for all other pumps.
Pr.14=1
For better motor and system efficiency - t
Pr.7 Pr.8
Pr.60 = 9 for Energy saving control selection f
Pr.3 Note : These parameters have been and are the same for all Mitsubishi inverters.
Mitsubishi F740 inverter quick set-up guide
Alarm History
The previous FOUR alarms are retrievable using the FR-DU07
To access the Alarm menu
Press the mode button twice - E--- is displayed
Scroll through the alarm codes.
Press SET to read the Hz, Amps and Volts for each alarm.
SET

SET
Note - Alarm code and Hz, V and A information is important for diagnosis.
E.0 indicates there are no alarms.
General causes of alarms
For full information on alarm codes, please refer to the installation manual for the specific inverter.
Inverter Overload
Over current (OC1, OC2), and transistor thermal alarms (THT) are caused by too much current
flowing in the inverter transistor circuits.
CHECK - Monitor the current during start-up and running.
Hz
1. E.OC1 Immediate over-current - output short-circuit or already rotating motor.
2. E.OC1 Over-current after 1 second - stalled motor, jammed pump, high friction, Pr.14 may be
set to 1, torque boost (Pr.0) set too high, constant pressure pump. 12 3 4
3. E.OC1 Overload after half speed - high inertia, acceleration too fast, Pr.14 may be set to 1.
4. E.OC2 Overload at steady speed - high motor current, sudden load increase (valve opening),
incorrect pump rotation, single-phasing of the output.
t
Motor thermal overload
Pr.9 is set to the motor rated current. The inverter calculates the level of current at reduced speeds that will cause a temperature build-up in
the motor. If the E.THM alarm occurs but the motor is NOT hot, then the value can be increased to avoid nuisance tripping.
CHECK - Pr.0 - should be set as low as possible, while still allowing the motor to start
Pr.14 - can be set to 1 for clean water pumps
For a high load and low speed operation extra ventilation on the motor and Pr.71=1 can be used.

NOTE - This guide is designed as a simple guide and is not designed to replace the technical information in the product manuals.
For further help - Mitsubishi Help Desk  01707 278990  www.mitsubishi-automation.co.uk  [email protected]

You might also like