HTW-1030 T5
MEDIUM-VOLTAGE RANGE
Open Skid
Powered by MITSUBISHI
OPEN SKID
WATER-COOLED
THREE PHASE
50 HZ
DIESEL
Generating Rates
SERVICE PRP STANDBY
Power kVA 1065 1173
Power kW 852 938
Rated Speed r.p.m. 1.500 01
Standard Voltage KV 11
Available Voltages KV 3,3kV · 6kV · 6,3 · 6,6 · 10 · 11
Rated at power factor Cos Phi 0,8
Ambient conditions of reference according to ISO 8528-1:2005 normative: 1000 mbar, 25ºC, 30% relative humidity.
Continuous Power (COP): According to Standard ISO 8528-1:2005, this is the maximum power available for continuous loads for unlimited running
hours a year between the maintenance times recommended by the manufacturer under the environmental conditions established by the same.
HIMOINSA HEADQUARTERS:
Fábrica: Ctra. Murcia - San Javier, Km. 23,6 | 30730 SAN JAVIER (Murcia) Spain
Tel.+34 968 19 11 28 Fax +34 968 19 12 17 Fax +34 968 19 04 20 [email protected] www.himoinsa.com
Manufacture facilities:
SPAIN • FRANCE • INDIA • CHINA • USA • BRASIL
Subsidiaries:
ITALY | PORTUGAL | POLAND | GERMANY | SINGAPORE | UAE | MEXICO | PANAMÁ | ARGENTINA | UK
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL
HTW-1030 T5
MEDIUM-VOLTAGE RANGE
Open Skid
Available Voltages Powered by MITSUBISHI
3,3kV
COP KVA COP KW Amps
958 766 167,6
Prime KVA Prime KW Amps
1000 800 175
Standby KVA Standby KW Amps
1100 880 192,5
6 kV
COP KVA COP KW Amps
962 769 92,6
Prime KVA Prime KW Amps
1070 856 103
Standby KVA Standby KW Amps
1176 940 113,2
6,3 KV
02
COP KVA COP KW Amps
961 768 88,1
Prime KVA Prime KW Amps
1069 855 98
Standby KVA Standby KW Amps
1174 939 107,6
6,6 KV
COP KVA COP KW Amps
961 768 84,1
Prime KVA Prime KW Amps
1069 855 93,5
Standby KVA Standby KW Amps
1176 940 102,9
10 KV
COP KVA COP KW Amps
958 766 55,3
Prime KVA Prime KW Amps
1065 852 61,5
Standby KVA Standby KW Amps
1172 937 67,7
11 KV
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
HTW-1030 T5
MEDIUM-VOLTAGE RANGE
Open Skid
Powered by MITSUBISHI
Generator
Generator
Poles No. 4
Connection type (standard) Star
Insulation Class F class
Enclosure (according IEC-34-5) IP23
Exciter system Self-excited, brushless
Voltage regulator A.V.R. (Electronic)
Bracket type Double drive-shaft
Coupling system Elastic Coupling
Coating type Standard (Vacuum impregnation)
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL
HTW-1030 T5
MEDIUM-VOLTAGE RANGE
Open Skid
Powered by MITSUBISHI
Application Data
Exhaust System
Maximum exhaust temperature ºC 515
Exhaust Gas Flow m3/min 220
Maximum allowed back pressure mm H2o 600
Heat dissipated by exhaust pipe KCal/Kwh 616,71
Starting System
Starting power kW 7,5 x 2
Starting power CV 10,2 x 2 04
Recommended battery Ah 300
Auxiliary Voltage Vdc 24
Starter current peak A 720
Nominal starter current A 380
Fuel System
Fuel Oil Specifications Diesel
Maximum power suction pump mm Hg 75
Maximum return feed pump mm Hg 220
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL
HTW-1030 T5
MEDIUM-VOLTAGE RANGE
Open Skid
Dimensions Powered by MITSUBISHI
05
Himoinsa has the right to modify any feature without prior notice.
Weights and dimensions based on standard products. Illustrations may include optional equipment.
Technical data described in this catalogue correspond to the available information at the moment of printing.
Industrial design under patent.
Local Distributor
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL
HTW-1030 T5
MEDIUM-VOLTAGE RANGE
Open Skid
Powered by MITSUBISHI
CM CENTRAL AUTOMATIC AGC‐4.
Automatic control panel WITHOUT ATS (Automatic Transfer Switch) and WITHOUT
mains control. No power circuits.
The AGC‐4 center is a control unit containing all necessary measures for the protection
and control functions of a generator. It can be used as a single unit for a generator, or
connect into a complete energy management system for synchronization projects,
island type or in parallel with the mains. The AGC‐4 contains all the circuitry necessary
3‐phase measuring, and all values and alarms are presented on the LCD screen.
The AGC‐4 has been successfully developed an innovative facility management
solution that can handle up to 256 generators in
an application generator circuit breakers, 16 mains
feeders with mains and tie breaker and 8 bus tie
breakers on the generatorbus or load bus.
06
KEY LOAD SHARE FEATURES:
Start sequential set kW and kV Ar load sharing Opción
Peak lopping Power Management (PMS)
Manual voltage/frequency Start and stop on demand
adjustment Selection priorities generators in
R.O.C.O.F. and vector shift parallel
Generator load demand Selection priorities parallel networks
Automatic hours run balancing Cargo Control
Mains (Utility) de‐coupling Group Multiboot
Mains (Utility) de‐coupling test mode Control relay earthed neutral
Dead bus sensing Large consumindores Control
Bus failure detection (management of requests)
Direct governor and AVR control Shot nonessential loads in
Volts and frequency matching switchingQuick setup
KEY FEATURES
Comprehensive loadshare Voltage measurement
capabilities Built‐in governor and AVR control
Configurable inputs ( 33 ) kW overload alarms
Configurable outputs( 24 )
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL
HTW-1030 T5
MEDIUM-VOLTAGE RANGE
Open Skid
Powered by MITSUBISHI
Comprehensive electrical Event log ( 256 )
protection Engine protection
Magnetic pick‐up Fault condition notification to a
Electronic engine capability designated PC
Remote communication system up Front panel mounting
to two channels (redundant Protected front panel
system) programming
RS485 y RS 23 remote PC configuration
comunications Configurable alarms and timers
Modbus RTU Configurable start and stop itmers
PLC functionality SMS alert messaging
Multi event exercise timer Remote monitoring
Back‐lit LCD 4‐line text display Compatible with AGC‐100 Y 200.
Multiple display languages Allows synchronization Dynamics,
Automatic start/Manual start static and close before excitation
Audible alarm (CBE).
Fixed and flexible LED indicators
KEY BENEFITS
RS232 & RS485 can be used at the Process Emulation 07
same time Derating function parameters for
DSENet connection for system temperature rise in warm areas
expansion Function Idle running in freezing
PLC functionality temperatures (preheating at low
Auto voltage sensing rpm)
Five step dummy load support Auto battery test status, check the
Five step load shedding support battery ramp feature
High number of inputs and outputs Asymmetry of batteries, battery
Worldwide language support for discriminating shabby
Configuration Suite PC software Control fan motor and living
Direct USB connection to PC Error Detection in switchgear
Ethernet monitoring Control pump fuel tank
USB host Connection redundancy controllers
Data logging & trending without any additional equipment
ENGINE ALARMS
High coolant temperature. Fuel storage.
Low oil pressure. Overspeed.
Battery charge alternator Under speed.
Start failure. Low battery voltage.
Low water level.
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL
HTW-1030 T5
MEDIUM-VOLTAGE RANGE
Open Skid
Powered by MITSUBISHI
High coolant temperature by Stop failure.
sensor. Low engine temperature.
Low oil pressure by sensor. Genset voltage drops.
Low fuel level by sensor. Emergency stop.
Unexpected shutdown.
GENERATOR ALARMS
Over‐load Over load
Unbalanced voltage Short‐circuit
Over voltage Inverse Power
Under voltage Incorrect phase sequence
Over frequency Asymmetry among phases
Under frequency Emergency stop
GENSET READINGS
Voltage among phases Apparent power (kVA)
Voltage among phases and neutral Active power (kW)
Amperage Reactive power (kVAr)
Frequency Power factor
08
ENGINE READINGS
Coolant temperature Battery voltage
Oil pressure R.P.M.
Fuel level (%) Battery charge alternator voltage
ENGINE PROTECTIONS
High water temperature Fuel storage by sensor
High coolant temperature by Stop failure
sensor Battery voltage failure
Low engine temperature by sensor Battery charge alternator failure
Low oil pressure Overspeed
Low oil pressure by sensor Under speed
Low coolant level Start failure
Unexpected shutdown Emergency Stop
Fuel storage
ALTERNATOR PROTECTIONS
High frequency Asymmetry among phases
Low frequency Incorrect phase sequence
High voltage Inverse power
Low voltage Overload
Short‐circuit Genset signal droop
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL
HTW-1030 T5
MEDIUM-VOLTAGE RANGE
Open Skid
Powered by MITSUBISHI
Operating Mode
1. Locked | OFF.
In this operating mode the controller is disconnected from the system, while this mode is
impossible that this selected group start automatically or manually. It should select this mode
whenever required to do some work or maintenance to avoid starting the group.
2. Manual Mode | MAN.
In this mode of operation the group started through the manual controls of the controller.
Also closing the switch will manually if the driver supports operation whether we are isolated
from the network as if we already have it synchronized.
3. Automatic Mode | AUTO.
a. Parallel with main | LOAD SHARING.
In this mode group and network working in parallel, the load is shared between the
two. The group will take a load ramp weighting process, this means that load slowly
thereafter are equally true of the loss of load or load shedding.
b. Parallel with main | BASE LOAD.
In this mode of operation the group will produce the base system power for this group 09
should be adjusted to produce a given load and this will remain unchanged over time,
or until you change the setting. This mode means that the group must be running in
parallel with the main.
c. Parallel with main | PEAK SHAVING.
This active mode and set the threshold settings and times to be confirmed. The plant is
kept fed through the network at all times to monitor the system from imported energy
does not exceed a set threshold. Exceeded this threshold and time confirmation, the
system gives the boot order for the group need imported power remains below the
threshold setting.
d. Parallel with main | LOAD TAKEOVER.
Installation Mode where cargo moves from mains to generator, for example, periods
of peak demand periods or at risk of power outages.
e. Parallel with main to fixed power| MAINS POWER EXPORT.
Power plant with fixed setpoint power in kW (excluding building load).
f. Group REMOTE SHOCK:
Used when the generator has to supply the load of a distribution transformer has to be
disconnected for maintenance service.
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL
HTW-1030 T5
MEDIUM-VOLTAGE RANGE
Open Skid
Powered by MITSUBISHI
MEDIUM VOLTAGE SWITCHGEAR
Constructive characteristics
The basic version of medium voltage switchboards (metal clad according to the 60298 standard), belongs to LSC2x
Fitted integral SF6 gas insulated busbar, breaker and switch (1).
Dimensions and weight: To be advised.
General Electrical Characteristics
Rated insulation voltage .................................................... 24 KV
Rated operating voltage ..................................................... 3…20 KV
Rated power frequency withstand voltage ........................ 50 KV
Rated impulse withstand voltage ....................................... 125 KV
Rated frequency ................................................................ 50 Hz/60Hz
Rated main busbar current ................................................. 400/630 A (2)
Rated short time current (RMS) ........................................ 16KA 1s/20 KA 1 s
Rated peak short circuit current ......................................... 50 KA for 1 s
Power supply auxiliary circuit ............................................. 24…230 Vcc o 230Vca 10
Protection degree ............................................................... IP 33 + IPX7
Installation .......................................................................... INDOOR
Applicable standar .............................................................. IEC (3)
Ambient desing temperature ............................................ 40 ° C
Number of phases ............................................................. 3P
Measure, switch and protection devices, Genset inlet:
1. Out main cell :
- Three (3) voltage transformers insulation up to 13,6KV, cast resin type with:
Value X***:3/110:3 V, 50/60hz, burden and accuary 40 VA C 1.0,5, 50VA 3P fixed versión.
(1) Only in protection cell
(2) The rated current is to a máximum ambient temeperature of 40ºC. Consult other temperaturas.
(3 ) Standards: IEC 62271‐1, IEC 62271‐200, IEC 60265‐1, IEC 62271‐102, IEC 62271‐105, IEC 62271‐100,
IEC 602255, IEC 60259 e IEC 61958.
X*** to define the order according to rated voltage from 3 a 13,80KV.
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL
HTW-1030 T5
MEDIUM-VOLTAGE RANGE
Open Skid
Powered by MITSUBISHI
2. Cell protection, switching and measurent :
One (1) break‐switch :
Rated breaking ................................................................. 400/630ª
Rated closure power ........................................................ 40/52KA
One (1) earth switch :
Rated Clousure power ...................................................... 40/50KA
One (1) Vacuum circuit breaker:
Rated insulation voltaje ......................................................... 24 KV
Rated current ................................................................. 400/630 A
Rated short time current (RMS) for 1 s ............................ 16/20 KA
Electrical operated
Auxiliary contacs
Microprocessor protecction: 50/51 +50N/51N and comunications RS232 and RS485.
Current sensors installed on bushing for microprorecessor readings.
Three (3) voltage transformers insulation up to 13, cast resin type with:
Value X***:3/110:3 V, 50/60hz, burden and accuary 40 VA C 1.0,5, 50VA 3P fixed versión.
One (1) self‐powered voltage presence indicator light according IEC 61958.
3. Screw terminals:
‐ Six (6) screw terminals for máximum wire section 1x240mm2.
11
4. Optional:
Protecction according to group ANSI:
Phase overcurrent (50‐51.)
Neutral overcurrent (50N‐51N)
Maximum and mínimum voltage (27/59)
Maximum displacement voltage (59N)
Maximum and mínimum frequency (81M/m)
46, 49RMS, 48/51LR, 66, 32
With communications RS‐485
Minimum impedance protection (21B)
Loss of field (40)
Ground fault protection ( 64REF)
Differential protection generator (87G)
Other configurations avialble: indoor, outdoor, multiple parallel, etc… to consult.
(1) Only in protection cell
(2) The rated current is to a máximum ambient temeperature of 40ºC. Consult other temperaturas.
(3 ) Standards: IEC 62271‐1, IEC 62271‐200, IEC 60265‐1, IEC 62271‐102, IEC 62271‐105, IEC 62271‐100,
IEC 602255, IEC 60259 e IEC 61958.
X*** to define the order according to rated voltage from 3 a 13,80KV.
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL
HTW-1030 T5
MEDIUM-VOLTAGE RANGE
Open Skid
Powered by MITSUBISHI
Alternator
· Self-excited and self-regulated
· IP23 protection
· H class insulation
12
Electrical system
· Maintenance-free and anti-explosion battery
· Battery isolator
· Medium voltage cubicle separated with overcurrent protections and measurement transformers
· Battery charger
· Heating resistor
· Control panel and emergency stop button
· Battery charger alternator with ground connection
· Starter battery/ies installed (cables and bracket included)
· Ground connection electrical installation with connection ready for ground spike (not supplied)
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL
HTW-1030 T5
MEDIUM-VOLTAGE RANGE
Open Skid
Powered by MITSUBISHI
PDF Summary
Created : 23/05/2017 16:27
Author : Himoinsa
Number of pages : 13
Report Type: Data Sheet - Medium-voltage range
Generated by: HIMOINSA Engineering Dept.
Page 1. Genset data
Page 2. Available Voltages
Page 3. Engine Specifications. Generator Specifications.
Page 4. Installation Data
Page 5. Dimensions
Page 6. Central Automatic AGC 4
Page 7. Central Automatic AGC 4
Page 8. Central Automatic AGC 4
Page 9. Central Automatic AGC 4
Page 10. Medium Voltage Switchgear
Page 11. Medium Voltage Switchgear
Page 12. Generator Features & Options
Page 13. PDF Summary (ID454E37363335373530)
http://www.himoinsa.com/generating-sets/763_22/diesel-generator-htw-1030_t5-mitsubishi-50hz-medium-voltage-range-prp_1065kva.aspx
13
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com