HVAC Design CheckList
HVAC Design CheckList
HVAC Design CheckList
8
Collect the following Building Data
Arch. Plan (Furniture preferred)
Zoning
Economizer exists?
Humidifier exists?
Dehumidifier exists?
Equipment Type (Constant flow or variable flow)
* Verify that the AHU results (Supply CFM, OA CFM & cooling load capacity) are available in market
by vendors, otherwise re-distribute connected spaces till you reach the max. values available
** Incase of following the non dedicate smoke removal method, verify that AHU serving only spaces
in the same fire zone
Chilled water Temp. Difference
Calculation Method (Cooling only or heating either)
People Diversity factor
Ventilation value
Ventilation value
Ventilation value
Ventilation value
Ventilation value
Ventilation value
Ventilation value
Ventilation value
Ventilation value
Ventilation value
Ventilation value
Ventilation value
DESIGN DRAWING
General Before Starting (Verify the following)
Arch. Plans are comply with the latest edition
Mechanical shafts' size are suitable for duct riser as per load calculation result
Takedrawing
care from the maintenance
of lighting door access
complete false ceiling drawing, this consist position , fire alarm detectors , sprinklers
and speakers ....... etc
Inside each space verify the following
Air flow complying the load calc. result
No. of air outlet suitable for air flow required
Flexible diameter for each outlet
Space HVAC data written (CFM, Flex. Diameter, No. & size of air outlet)
Duct height that connected to flex. Is more than flex. Dia. (2" minimum)
Fire damper installed on opening of free return air paths through fire zone walls
Duct distance (From AHU to the first fitting) at roof comply with min. distance allowed by code
Chilled water pipes works (Supply & Return), check the following
Chillers Qty. & capacity are enough for the required cooling load calculated
before any check , please make sure from the HVAC equipment flow access
Spacing between equipment, walls & roof comply with manfacturer recommendation
Chilled water pumps' Qty. & Capacity are the same of chiller quantity & Capacity
Exhaust fans are away from any FA duct intake and FAF
AHU
Cooling capacity comply with the load caculation
Tag No. comply with drawings
Location comply with drawings
Supply CFM comply with the load caculation
FA CFM comply with the load caculation
Type comply with the load caculation
Ambient Temp. comply with the load caculation
ESP comply with caculation
Chilled water Temp. comply with the load caculation
Chilled water Flow comply with the load caculation
Chiller
Cooling capacity comply with the load caculation
Qty. comply with drawings
Tag No. comply with drawings
Location comply with drawings
Type comply with selection
Chilled water Temp. comply with the load caculation
Chilled water Flow comply with the load caculation
Ambient Temp. comply with the selection
chiller control completely intergrated with BMS or Not, this point must be clear.
Pump
Qty. comply with drawings
Tag No. comply with drawings
Location comply with drawings
Type comply with selection
Chilled water Flow comply with the load caculation
Pump Head comply with the caculation
VAV
Qty. comply with drawings
Tag No. comply with drawings
Flow CFM comply with the Tag. No.
NC comply with code
Fans
Tag No. comply with drawings
Qty. comply with drawings
Flow CFM comply drawings
Type comply with selection
Location comply with drawings
ESP comply with caculation
Riser Diagram, Verify the following
All Risers are shown
All equipment are shown in correctfloor as per plans
Size at riser comply with size on plan.
Size of each floor entrance comply with size on plan.
SRF & FAF are connected to main duct
Equipment data comply with equipment schdule
Title block comply with the project title project of other departments
striction by code
kk kk
striction by code