Scope: This procedure explains the Emergency activities to be performed at the time of Station
Shutdown.
Procedure:
** IF THE DG is not started when Both Selector Switches are in REMOTE, then (i) we have
to start it from CCR by taking CCR selector switch in Manual mode OR (ii) we can start it from
DG Panel by keeping Local Selector Switch in Manual Mode
Important: The DG will not start when Both Selector Switches are in Manual Mode.
Charge EMBus-1&2 from DGDB after ensuring EMB incomer circuit breaker (from UAB)
are open.
Break vacuum through vacuum breaker valve manually if possible.
Charge UB through SB, after checking that SB has been powered up through ST.
Air Compressors are running.
CW, ACW, DMCW and DMCW booster pump are running.
Charge EMB from NORMAL source after starting all DC drives.
Switch over all DC drives to AC drives again.
Ensure M/C drains are open.
Then follow normal start up procedure.
Reference documents:
CCR/ BOP/ DG/ O&M MANUAL