Chapter 1 Problems and Chapter 2 PSPO
Chapter 1 Problems and Chapter 2 PSPO
Chapter 1 Problems and Chapter 2 PSPO
, AASTU
kw
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
kw
kw
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
kw
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
kw
kw
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
Perhaps the estimated no. of IC boards is equal to 50, then the forecasted
electrical demand is 6.683 KW
Home Work:
No. of Electrical
I.C
Period(t) Demand Dt2 Xt2 XtDt
boards
(Dt)
(Xt)
KW
1 20 4 400 16 80
2 25 8 625 64 200
3 15 1 225 1 15
4 18 3 324 9 54
5 22 6 484 36 132
6 30 9 900 81 270
7 40 12 1600 144 480
8 50 14 2500 196 700
9 60 15 3600 225 900
10 80 17 6400 289 1360
Σ 360 89 17058 1061 4191
Perhaps the estimated no. of IC boards is equal to 100, then the forecasted
electrical demand is _____ KW
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
Introduction:
Electricity has become an indivisible part of our life today. We all know how much we are
dependent on the electricity for almost everything. It is required for many domestic, commercial
as well as industrial purposes. And the requirement is still increasing day by day. There are
various types of energy sources which are used to generate electrical power. Most of the power
stations use fossil fuels such as coal, oil or natural gas to generate electricity. There are others
sources too, such as nuclear power, hydro power, renewable energy sources etc. The type of
power plant is defined by the type of main energy source. Today, most of the electric energy is
generated from the three major types of power plants - Thermal Power Plant, Nuclear Power
Plant and Hydroelectric Power Plant.
The pie chart shows in Fig. 2.1 indicates the share of different types of power plant in
electricity generation of the world. It clearly shows that about two third of total electricity of
the world is generated in thermal power plants. Hydro plants and Nuclear plants also play major
role in electricity generation.
There are many other renewable energy sources which are used for electricity generation such as
Geothermal energy, Solar energy, Wind energy, Tidal energy etc. Due to some technical
difficulties these energy sources are currently contributing less than 5% of the total electricity
generation. The use of these renewable energy sources is being increased day by day.
Economizer:
An economizer is essentially a feed water heater which heats the water before supplying to the
boiler.
Air pre-heater:
The primary air fan takes air from the atmosphere and it is then warmed in the air pre-heater.
Pre-heated air is injected with coal in the boiler. The advantage of pre-heating the air is that it
improves the coal combustion.
Steam turbine:
High pressure super heated steam is fed to the steam turbine which causes turbine blades to
rotate. Energy in the steam is converted into mechanical energy in the steam turbine which acts
as the prime mover. The pressure and temperature of the steam falls to a lower value and it
expands in volume as it passes through the turbine. The expanded low pressure steam is
exhausted in the condenser.
Condenser:
The exhausted steam is condensed in the condenser by means of cold water circulation. Here, the
steam loses it's pressure as well as temperature and it is converted back into water. Condensing is
essential because, compressing a fluid which is in gaseous state requires a huge amount of
energy with respect to the energy required in compressing liquid. Thus, condensing increases
efficiency of the cycle.
Alternator:
The steam turbine is coupled to an alternator. When the turbine rotates the alternator, electrical
energy is generated. This generated electrical voltage is then stepped up with the help of
a transformer and then transmitted where it is to be utilized.
Feed water pump: The condensed water is again fed to the boiler by a feed water pump. Some
water may be lost during the cycle, which is suitably supplied from an external water source.
This is the basic working principle of a thermal power station and its typical components.
A practical thermal plant possess more complicated design and multiple stages of turbine such as
High Pressure Turbine (HPT), Intermediate Pressure Turbine (IPT) and Low Pressure Turbine
(LPT).
Advantages and Disadvantages of a Thermal Power Plant
Advantages:
Less initial cost as compared to other generating stations.
It requires less land as compared to hydro power plant.
The fuel (i.e. coal) is cheaper.
The cost of generation is lesser than that of diesel power plants.
Disadvantages:
It pollutes the atmosphere due to the production of large amount of smoke. This is one of
the causes of global warming.
The overall efficiency of a thermal power station is low (less than 30%).
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
Thermal efficiency of modern thermal power stations is about 30%. It means, if 100 calories of
heat are produced by coal combustion, the mechanical energy equivalent of 30 calories will be
available at the turbine shaft.
Overall Efficiency:
The ratio of 'heat equivalent of electrical output' to the 'heat of coal combustion' is called as
overall efficiency.
The overall efficiency of a thermal plant is about 29% (slightly less than the thermal efficiency).
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
The Fig. 2.3 shows the typical layout of a hydroelectric power plant and its basic components.
The details of each part are illustrated in the following:
Dam and Reservoir:
The dam is constructed on a large river in hilly areas to ensure sufficient water storage at height.
The dam forms a large reservoir behind it. The height of water level (called as water head) in the
reservoir determines how much of potential energy is stored in it.
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
Control Gate:
Water from the reservoir is allowed to flow through the penstock to the turbine. The amount of
water which is to be released in the penstock can be controlled by a control gate. When the
control gate is fully opened, maximum amount of water is released through the penstock.
Penstock:
A penstock is a huge steel pipe which carries water from the reservoir to the turbine. Potential
energy of the water is converted into kinetic energy as it flows down through the penstock due to
gravity.
Water Turbine:
Water from the penstock is taken into the water turbine. The turbine is mechanically coupled to
an electric generator. Kinetic energy of the water drives the turbine and consequently the
generator gets driven. There are two main types of water turbine; (i) Impulse turbine and (ii)
Reaction turbine. Impulse turbines are used for large heads and reaction turbines are used for low
and medium heads.
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
Generator:
A generator is mounted in the power house and it is mechanically coupled to the turbine shaft.
When the turbine blades are rotated, it drives the generator and electricity is generated which is
then stepped up with the help of a transformer for the transmission purpose.
Surge Tank:
Surge tanks are usually provided in high or medium head power plants when considerably long
penstock is required. A surge tank is a small reservoir or tank which is open at the top. It is fitted
between the reservoir and the power house. The water level in the surge tank rises or falls to
reduce the pressure swings in the penstock. When there is sudden reduction in load on the
turbine, the governor closes the gates of the turbine to reduce the water flow. This causes
pressure to increase abnormally in the penstock. This is prevented by using a surge tank, in
which the water level rises to reduce the pressure. On the other hand, the surge tank provides
excess water needed when the gates are suddenly opened to meet the increased load demand.
Types of Hydro-Power Plants
Conventional Plants:
Conventional plants use potential energy from dammed water. The energy extracted depends on
the volume and head of the water. The difference between height of water level in the reservoir
and the water outflow level is called as water head.
Pumped Storage Plant:
In pumped storage plant, a second reservoir is constructed near the water outflow from the
turbine. When the demand of electricity is low, the water from lower reservoir is pumped into the
upper (main) reservoir. This is to ensure sufficient amount of water available in the main
reservoir to fulfil the peak loads.
Run-Of-River Plant:
In this type of facility, no dam is constructed and, hence, reservoir is absent. A portion of river is
diverted through a penstock or canal to the turbine. Thus, only the water flowing from the river is
available for the generation. And due to absence of reservoir, any oversupply of water is passed
unused.
Advantages of a Hydroelectric Power Plant
No fuel is required as potential energy is stored water is used for electricity generation
Neat and clean source of energy
Very small running charges - as water is available free of cost
Comparatively less maintenance is required and has longer life
Serves other purposes too, such as irrigation
Disadvantages
Very high capital cost due to construction of dam
High cost of transmission – as hydro plants are located in hilly areas which are quite away
from the consumers
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
Electrical power is normally generated at 11kV in a power station. While in some cases, power
may be generated at 33 kV. This generating voltage is then stepped up to 132kV, 220kV, 400kV
or 765kV etc. Stepping up the voltage level depends upon the distance at which power is to be
transmitted. Longer the distance, higher will be the voltage level. Stepping up of voltage is to
reduce the I2R losses in transmitting the power (when voltage is stepped up, the current reduces
by a relative amount so that the power remains constant, and hence I2R loss also reduces). This
stage is called as primary transmission.
The voltage is the stepped down at a receiving station to 33kV or 66kV. Secondary
transmission lines emerge from this receiving station to connect substations located near load
centers (cities etc.).
The voltage is stepped down again to 11kV at a substation. Large industrial consumers can be
supplied at 11kV directly from these substations. Also, feeders emerge from these substations.
This stage is called as primary distribution.
Feeders are either overhead lines or underground cables which carry power close to the load
points (end consumers) up to a couple of kilometers. Finally, the voltage is stepped down to 415
volts by a pole-mounted distribution transformer and delivered to the distributors. End
consumers are supplied through a service mains line from distributors. The secondary
distribution system consists of feeders, distributors and service mains.
Different Types Of Transmission Systems
1. Single phase AC system
single phase, two wires
single phase, two wires with midpoint earthed
single phase, three wires
2. Two phase AC system
two-phase, three wires
two-phase, four wires
3. Three phase AC system
three-phase, three wires
three-phase, four wires
4. DC system
DC two wires
DC two wires with midpoint earthed
DC three wires
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
Electric power transmission can also be carried out using underground cables. But,
construction of an underground transmission line generally costs 4 to 10 times than an equivalent
distance overhead line. However, it is to be noted that, the cost of constructing underground
transmission lines highly depends upon the local environment. Also, the cost of conductor
material required is one of the most considerable charges in a transmission system. Since
conductor cost is a major part of the total cost, it has to be taken into consideration while
designing. The choice of transmission system is made by keeping in mind various factors such as
reliability, efficiency and economy. Usually, overhead transmission system is used.
Distribution feeders: The stepped-down voltage from the substation is carried to distribution
transformers via feeder conductors. Generally, no tappings are taken from the feeders so that the
current remains same throughout. The main consideration in designing of a feeder conductor is
its current carrying capacity.
Distribution transformer: A distribution transformer, also called as service transformer,
provides final transformation in the electric power distribution system. It is basically a step-
down 3-phase transformer. Distribution transformer steps down the voltage to 400Y/230 volts.
Here it means, voltage between any one phase and the neutral is 230 volts and phase to phase
voltage is 400 volts. However, in USA and some other countries, 120/240 .
Distributors: Output from a distribution transformer is carried by distributor conductor.
Tappings are taken from a distributor conductor for power supply to the end consumers. The
current through a distributor is not constant as tappings are taken at various places throughout its
length. So, voltage drop along the length is the main consideration while designing a distributor
conductor.
Service mains: It is a small cable which connects the distributor conductor at the nearest pole to
the consumer's end.
Primary Distribution
It is that part of an AC distribution system which operates at somewhat higher voltages than
general residential consumer utilization. Commonly used primary distribution voltages in most
countries are 11 kV, 6.6 kV and 3.3 kV. Primary distribution handles large consumers such as
factories and industries. It also feeds small substation from where secondary distribution is
carried out. Primary distribution is carried out by 3-phase, 3-wire system.
Secondary Distribution
This part directly supplies to the residential end consumers. Domestic consumers are fed with
single phase supply at 230 volts (120 volts in USA and some other countries). Three phase
supply may also be provided at 400 volts for big properties, commercial buildings, small
factories etc. Secondary transmission in most countries is carried out by 3-phase, 4-wire system.
Classification of Power Distribution Systems
According to nature of current:
DC distribution system
AC distribution system
According to type of construction:
Overhead distribution system
Underground distribution system
On the basis of scheme of connection:
Radial distribution system
Ring main distribution system
Inter-connected distribution system
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
Ring main distribution system is the most preferred due to its following advantages.
Advantages:
1. This is very simple in design.
2. This is very cost effective scheme.
3. This is very convenient to operate.
Disadvantages:
1. One but major difficulty of these type of arrangement is that, maintenance of equipment of
any bay cannot be possible without interrupting the feeder or transformer connected to that
bay.
2. The indoor 11 KV switch boards have quite often single bus bar arrangement.
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
Advantages :
If any of the sources is out of system, still all loads can be fed by switching on the sectional
circuit breaker or bus coupler breaker. If one section of the bus bar system is under maintenance,
part load of the substation can be fed by energizing the other section of bus bar.
Disadvantages:
1. As in the case of single bus system, maintenance of equipment of any bay cannot be
possible without interrupting the feeder or transformer connected to that bay.
2. The use of isolator for bus sectionalizing does not fulfill the purpose. The isolators have
to be operated „off circuit‟ and which is not possible without total interruption of bus –
bar. So investment for bus-coupler breaker is required.
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
1. In double bus bar system two identical bus bars are used in such a way that any outgoing
or incoming feeder can be taken from any of the bus.
2. Actually every feeder is connected to both of the buses in parallel through individual
isolator as shown in the figure.
3. By closing any of the isolators one can put the feeder to associated bus. Both of the buses
are energized and total feeders are divided into two groups, one group is fed from one bus
and other from other bus. But any feeder at any time can be transferred from one bus to
other. There is one bus coupler breaker which should be kept close during bus transfer
operation. For transfer operation, one should first close the bus coupler circuit breaker
then close the isolator associated with the bus to where the feeder would be transferred
and then open the isolator associated with the bus from where feeder is transferred. Lastly
after this transfer operation he or she should open the bus coupler breaker.
Advantages:
Double Bus Bar Arrangement increases the flexibility of system.
Disadvantages:
The arrangement does not permit breaker maintenance with out interruption.
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
In double breaker bus bar system two identical bus bars are used in such a way that any outgoing
or incoming feeder can be taken from any of the bus similar to double bus bar system. Only
difference is that here every feeder is connected to both of the buses in parallel through
individual breaker instead only isolator as shown in the figure. By closing any of the breakers
and its associated isolators one can put the feeder to respective bus. Both of the buses are
energized and total feeders are divided into two groups, one group is fed from one bus and other
from other bus similar to previous case. But any feeder at any time can be transferred from one
bus to other. There is no need of bus coupler as because the operation is done by breakers instead
of isolator. For transfer operation, one should first close the isolators and then the breaker
associated with the bus to where the feeder would be transferred and then he or she opens the
breaker and then isolators associated with the bus from where feeder is transferred.
Normally all the three breakers are closed and power is fed to both the circuits from two buses
which are operated in parallel. The tie breaker acts as coupler for the two feeder circuits. During
failure of any feeder breaker, the power is fed through the breaker of the second feeder and tie
breaker, therefore each feeder breaker has to be rated to feed both the feeders, coupled by tie
breaker.
This is an alternative of double bus system. The main conception of Main and Transfer Bus
System is, here every feeder line is directly connected through an isolator to a second bus called
transfer bus. The said isolator in between transfer bus and feeder line is generally called bypass
isolator. The main bus is as usual connected to each feeder through a bay consists of circuit
breaker and associated isolators at both side of the breaker. There is one bus coupler bay which
couples transfer bus and main bus through a circuit breaker and associated isolators at both sides
of the breaker. If necessary the transfer bus can be energized by main bus power by closing the
transfer bus coupler isolators and then breaker. Then the power in transfer bus can directly be fed
to the feeder line by closing the bypass isolator. If the main circuit breaker associated with feeder
is switched off or isolated from system, the feeder can still be fed in this way by transferring it to
transfer bus.
Switching Operation for Transferring a Feeder to Transfer Bus from Main Bus without
Interruption of Power
1. First close the isolators at both side of the bus coupler breaker.
2. Then close the bypass isolator of the feeder which is to be transferred to transfer bus.
3. Now energized the transfer bus by closing the bus coupler circuit breaker from remote.
4. After bus coupler breaker is closed, now the power from main bus flows to the feeder line
through its main
5. breaker as well as bus coupler breaker via transfer bus.
6. Now if main breaker of the feeder is switched off, total power flow will instantaneously
shift to the bus coupler breaker and hence this breaker will serve the purpose of
protection for the feeder.
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
7. At last the operating personnel open the isolators at both sides of the main circuit breaker
to make it isolated from rest of the live system.
So, it can be concluded that in Main and Transfer Bus System the maintenance of circuit breaker
is possible without any interruption of power. Because of this advantage the scheme is very
popular for 33 KV and 13 KV system.
6.7 Double Bus System with Bypass Isolators
This is combination of the double bus system and main and transfer bus system. In Double Bus
System with Bypass Isolators either bus can act as main bus and second bus as transfer bus. It
permits breaker maintenance without interruption of power which is not possible in double bus
system but it provides all the advantages of double bus system. It however requires one
additional isolator (bypass isolator) for each feeder circuit and introduces slight complication in
system layout. Still this scheme is best for optimum economy of system and it is best optimum
choice for 220 KV system.
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
7. Lightning Arrester: To discharge lightning over voltages and switching over voltages to earth
8. Shunt reactor: To control over voltages by providing reactive power compensation
Prepared by Dr. GopiKrishna P, Dept. of Elec. & Comp. Engg. , AASTU
References:
1. https://www.electricaleasy.com/2015/08/thermal-power-plant.html
2. https://www.electricaleasy.com/2015/09/hydroelectric-power-plant-layout.html
3. https://www.electricaleasy.com/2015/09/nuclear-power-plant.html
4. https://www.electricaleasy.com/2016/03/basics-of-electrical-power-transmission.html
5. https://www.electricaleasy.com/2018/01/electric-power-distribution-system.html
6. https://www.electricaleasy.com/2018/02/radial-parallel-ring-main-interconneted-
distribution.html
7. https://www.electrical4u.com/electrical-bus-system-and-electrical-substation-layout/