S464G1007

Addressable Manual Pull Station

General
The S464G1007 is a state-of-the-art, dual-action (i.e., requires
two motions to activate the station) pull station that includes an
addressable interface for use with Honeywell’s compatible

6643hcov1.j
Intelligent Fire Alarm Control Panels Because the S464G1007
is addressable, the control panel can display the exact location
of the activated manual station. This leads fire personnel
quickly to the location of the alarm.

Features
• Maintenance personnel can open station for inspection and
address setting without causing an alarm condition.
The S464G1007
• Built-in bicolor LED, which is visible through the handle of
Addressable Manual Pull Station
the station, flashes in normal operation and latches steady
red when in alarm.
• Handle latches in down position and the word “ACTIVATED” Installation
appears to clearly indicate the station has been operated.
The S464G1007 will mount semi-flush into a single-gang, dou-
• Captive screw terminals wire-ready for easy connection to ble-gang, or standard 4" (10.16 cm) square electrical outlet
SLC loop (accepts up to 12 AWG/3.25 mm² wire). box, or will surface mount to the model SB-10 or SB-I/O sur-
• Can be surface mounted (with SB-10 or SB-I/O) or semi- face backbox. If the S464G1007 is being semi-flush mounted,
flush mounted. Semi-flush mount to a standard single- then the optional trim ring (BG12TR) may be used. The
gang, double-gang, or 4" (10.16 cm) square electrical box. BG12TR is usually needed for semi-flush mounting with 4"
• Smooth dual-action design. (10.16 cm) or double-gang boxes (not with single-gang boxes).
• Meets ADAAG controls and operating mechanisms guide-
lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. Operation
maximum activation force. Pushing in, then pulling down on the handle causes it to latch
• Highly visible. in the down/activated position. Once latched, the word “ACTI-
• Attractive shape and textured finish. VATED” (in bright yellow) appears at the top of the handle,
• Key reset. while a portion of the handle protrudes from the bottom of the
station. To reset the station, simply unlock the station with the
• Includes Braille text on station handle. key and pull the door open. This action resets the handle; clos-
• Optional trim ring (BG12TR). ing the door automatically resets the switch.
• Meets UL 38, Standard for Manually Actuated Signaling Each manual station, on command from the control panel,
Boxes. sends data to the panel representing the state of the manual
• Up to 99 S464G1007 stations per loop on CLIP protocol switch. Two rotary decimal switches allow address settings
loops. (1 – 159 on FlashScan® systems, 1 – 99 on CLIP systems).
• Up to 159 S464G1007 stations per loop on FlashScan®
protocol loops. Architectural/Engineering
• Dual-color LED blinks green to indicate normal on Specifications
FlashScan® systems.
Manual Fire Alarm Stations shall be non-coded, with a key-
operated reset lock in order that they may be tested, and so
Construction designed that after actual Emergency Operation, they cannot
Shell, door, and handle are molded of durable polycarbonate be restored to normal except by use of a key. An operated sta-
material with a textured finish. tion shall automatically condition itself so as to be visually
detected as activated. Manual stations shall be constructed of
red-colored polycarbonate material with clearly visible operat-
Specifications ing instructions provided on the cover. The word FIRE shall
• Shipping Weight: 9.6 oz. (272.15 g) appear on the front of the stations in white letters, 1.00 inches
• Normal operating voltage: 24 VDC. (2.54 cm) or larger. Stations shall be suitable for surface
mounting on matching backbox SB-10 or SB-I/O; or semi-flush
• Maximum SLC loop voltage: 28.0 VDC.
mounting on a standard single-gang, double-gang, or
• Maximum SLC standby current: 375 μA. 4" (10.16 cm) square electrical box, and shall be installed
• Maximum SLC alarm current: 5 mA. within the limits defined by the Americans with Disabilities Act
• Temperature Range: 32°F to 120°F (0°C to 49°C) (ADA) or per national/local requirements. Manual Stations
shall be Underwriters Laboratories listed.
• Relative Humidity: 10% to 93% (noncondensing)
• For use indoors in a dry location (Note: Use Manual stations shall connect with two wires to one of the con-
S464F1008WP for outdoor applications; see 85-3055.) trol panel SLC loops. The manual station shall, on command
from the control panel, send data to the panel representing the
state of the manual switch. Manual stations shall provide NOTE: For S464 series conventional, non-addressable models
address setting by use of rotary decimal switches. including weatherproof S464F1008WP, see 85-3055.
The loop poll LED shall be clearly visible through the front of
the station. The LED shall flash while in the normal condition, Agency Listings and Approvals
and stay steadily illuminated when in alarm. In some cases, certain modules or applications may not be
listed by certain approval agencies, or listing may be in pro-
Product Line Information cess. Consult factory for latest listing status.
S464G1007: Dual-action addressable pull station. Includes • UL/ULC Listed: S749 (listed for Canadian and non-Cana-
key locking feature. (Listed for Canadian and non-Canadian dian applications).
applications.) • MEA: 67-02-E Vol. II.
SB-10: Surface backbox; metal. • CSFM: 7150-1130:0209.
SB-I/O: Surface backbox; plastic. • FDNY: COA #6098, COA #6100.
BG12TR: Optional trim ring. • FM Approved.
Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772;
17051: Keys, set of two.
6,632,108.
NY-Plate: New York City trim plate.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific
applications or anticipate all requirements. All specifications are subject to change without notice.
FlashScan® is a trademark and Eclipse™ is a registered trademark of Honeywell International Inc.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

Automation and Control Solutions


Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9
www.honeywell.com 74-3365-6 Rev. 04-12
April 2012
Made in the U.S.A.
® U.S. Registered Trademark
© 2012 Honeywell International Inc.