Water Transmission Oil (Type-H) : Cold Fluid

This document provides information about two shell and tube heat exchangers. It includes specifications for the hot and cold fluids in the tubes and shell, as well as calculations related to heat transfer, pressure drop, effectiveness, and other parameters. The key details are that water and transmission oil are used as the hot and cold fluids, respectively, in a counter-current heat exchanger with a heat transfer of 7006975 W.

Uploaded by

nilesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
161 views6 pages

Water Transmission Oil (Type-H) : Cold Fluid

This document provides information about two shell and tube heat exchangers. It includes specifications for the hot and cold fluids in the tubes and shell, as well as calculations related to heat transfer, pressure drop, effectiveness, and other parameters. The key details are that water and transmission oil are used as the hot and cold fluids, respectively, in a counter-current heat exchanger with a heat transfer of 7006975 W.

Uploaded by

nilesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 6

Shell and Tube Heat Exhanger

Tube Calculations Hot Fluid Shell Calculations Cold Fluid

Flow Characteristics Flow Characteristics


Inlet Temperature Tin = 30.00 C Inlet Temperature Tin = 275.00 C
Outlet Temperature Tout = 40.00 C Outlet Temperature Tout = 150.00 C
Mean Temperature Tmean = 308.15 K Mean Temperature Tmean = 485.65 K

Fluid Fluid
Water k = 0.63 W/mK Transmission Oil (Type-H) k = 0.12 W/mK
Cp = 4068.47 J/(kg K) Cp = 2547.99 J/(kg K)
m = 0.000701 Pa s m = 0.000453 Pa s
r = 993.59 kg/m3 r = 741.60 kg/m3
Pr = 4.55 Pr = 9.88

Mass Flow Rate m= 172.226 kg/s Mass Flow Rate m= 22.000 kg/s
Capacity mCp = 700697.5 W/K Capacity mCp = 56055.8 W/K
Heat Transfer Q= 7006975 W Heat Transfer Q= 7006975 W

Internal Flow External Flow


Inside Diameter di = 0.0160 m Inside Diameter di = 0.3652 m
Outside Diameter do = 0.0190 m Outside Diameter do = 0.0190 m
Flow Area Ac = 0.0002 m2 Flow Area Ac = N/A m2
Hydraulic Diameter Dh = 0.0160 m Hydraulic Diameter Dh = N/A m
Heat Transfer Surface Area As = 0.2011 m2 Heat Transfer Surface Area As = 4.5892 m2
Pipe Conductivity kw = 400.0 W/mK Pipe Conductivity kw = 400.0 W/mK
Fluid Velocity V= 5.747 m/s Fluid Velocity V= N/A m/s

Calculations Calculations
Reynolds Number Re = 130419.97 Reynolds Number Re = N/A
Loss Coefficient K= N/A Loss Coefficient K= N/A
Friction Factor f= 0.00426 Friction Factor f= N/A
Nusselt Number Nu = 598.79 Nusselt Number Nu = N/A
Heat Transfer Coefficient h= 23432.64 W/m2K Heat Transfer Coefficient h= 5000.00 W/m2K
Pressure Drop DP = 69828.58 Pa Pressure Drop DP = N/A Pa

Heat Exchanger Parameters


Log Mean Temperature Difference DTLMTD = 171.11 C
Mimimum Fluid Cmin = 56056 W/K
Cr=Cmin/Cmax Cr = 0.08
Q max Qmax = -13733671 W
Overall Heat Transfer Coefficient UA = 549601 W/K
Effectiveness e= 1.00
Number of Transfer Units NTU = 9.80
Required Transfer Coefficient UA = -80255 W/K
Heat Transfer Q= -13732143 W
Length L= 4.0000 m
Number of Tubes N= 150.0
Shell and Tube Heat Exhanger

Tube Calculations Hot Fluid Shell Calculations Cold Fluid

Flow Characteristics Flow Characteristics


Inlet Temperature Tin = 30.00 C Inlet Temperature Tin = 150.00 C
Outlet Temperature Tout = 50.00 C Outlet Temperature Tout = 40.00 C
Mean Temperature Tmean = 313.15 K Mean Temperature Tmean = 368.15 K

Fluid Fluid
Water k = 0.63 W/mK Transmission Oil (Type-H) k = 0.12 W/mK
Cp = 4068.47 J/(kg K) Cp = 2547.99 J/(kg K)
m = 0.000701 Pa s m = 0.000453 Pa s
r = 993.59 kg/m3 r = 741.60 kg/m3
Pr = 4.55 Pr = 9.88

Mass Flow Rate m= 75.780 kg/s Mass Flow Rate m= 22.000 kg/s
Capacity mCp = 308306.9 W/K Capacity mCp = 56055.8 W/K
Heat Transfer Q= 6166138 W Heat Transfer Q= 6166138 W

Internal Flow External Flow


Inside Diameter di = 0.0160 m Inside Diameter di = 0.3652 m
Outside Diameter do = 0.0190 m Outside Diameter do = 0.0190 m
Flow Area Ac = 0.0002 m2 Flow Area Ac = N/A m2
Hydraulic Diameter Dh = 0.0160 m Hydraulic Diameter Dh = N/A m
Heat Transfer Surface Area As = 0.3016 m2 Heat Transfer Surface Area As = 6.8839 m2
Pipe Conductivity kw = 400.0 W/mK Pipe Conductivity kw = 400.0 W/mK
Fluid Velocity V= 2.529 m/s Fluid Velocity V= N/A m/s

Calculations Calculations
Reynolds Number Re = 57384.78 Reynolds Number Re = N/A
Loss Coefficient K= N/A Loss Coefficient K= N/A
Friction Factor f= 0.00508 Friction Factor f= N/A
Nusselt Number Nu = 297.87 Nusselt Number Nu = N/A
Heat Transfer Coefficient h= 11656.82 W/m2K Heat Transfer Coefficient h= 5000.00 W/m2K
Pressure Drop DP = 24200.37 Pa Pressure Drop DP = N/A Pa

Heat Exchanger Parameters


Log Mean Temperature Difference DTLMTD = 39.09 C
Mimimum Fluid Cmin = 56056 W/K
Cr=Cmin/Cmax Cr = 0.18
Q max Qmax = -6726696 W
Overall Heat Transfer Coefficient UA = 461688 W/K
Effectiveness e= 1.00
Number of Transfer Units NTU = 8.24
Required Transfer Coefficient UA = -171931 W/K
Heat Transfer Q= -6720178 W
Length L= 6.0000 m
Number of Tubes N= 150.0
Fluid k (W/mK) Cp (J/kgK) m (kg/ms) r (kg/m3) Pr
none
Engine Oil 5w30 0.142959284 1945.6948942603 0.06147894 878.4376 836.7365633
Transmission Oil (Type-F) 0.130001223 1941.7582178737 0.051641322 854.9144 771.3385983
Diesel Fuel 0.136146162 1958.2029843926 0.0019222496 831.2033 27.64789611
Kerosene 0.169135331 2043.2851492475 0.0019222496 870.5881 23.22225684
Marlotherm S 0.12949793 1623.8620626463 0.0197056076 1018.005 247.1019315
Water 0.626138032 4068.4682787233 0.0007005747 993.5883 4.55213664
Ethylene Glycol 0.254602538 2452.9338062842 0.011817947 1105.175 113.8584162
Air 0.026919946 1007.2128152651 1.888924E-05 1.129178 0.706743055
Freon 114 0.06162392 1035.2308303102 0.0003259907 1464.974 5.476373685
CO2 0.017373131 860.7459471694 1.525376E-05 1.718471 0.755742394
Gasoline 0.184067402 2108.8883253396 0.0005642955 739.6725 6.465219241
Ethylene Glycol 30% 0.492185008 3760.9151729638 0.0014279414 1029.561 10.91127628
Ethylene Glycol 50% 0.437954981 3318.5020619738 0.0025644891 1047.567 19.43182022
Transmission Oil (Type-H) 0.130001223 1941.7582178737 0.0462458032 854.9144 690.748642
Transmission Oil (Type-B) 0.130001223 1941.7582178737 0.0413318491 854.9144 617.3515569
Exxon 2389 (jet engine oil) 0.147609899 1841.6021703534 0.0127855391 958.4817 159.5142099
7
15
Fluid k (W/mK) Cp (J/kgK) m (kg/ms) r (kg/m3) Pr
none
Engine Oil 5w30 0.126548174 2727.5612169505 0.0001284901 772.4399 2.769417468
Transmission Oil (Type-F) 0.1168507018 2547.9909655151 0.0056996667 741.6038 124.2842288
Diesel Fuel 0.122810878 1958.2029843926 0.0002484014 706.4733 3.960726609
Kerosene 0.152528996 2759.6211790892 0.0002484014 763.117 4.494186091
Marlotherm S 0.1109631743 2257.3673345892 0.0014393918 894.3573 29.28211179
Water 0.663092731 3572.0752216559 0.0002134124 839.6314 1.1496507
Ethylene Glycol 0.239138171 3244.5071151511 1.4039133349 991.5614 19047.59403
Air 0.03987953 1032.7805512268 2.633965E-05 0.757471 0.682131435
Freon 114 0.018044305 1473.5625865783 8.43912E-05 -23.57169 6.891688145
CO2 0.031278333 1007.9102241686 2.250126E-05 1.065041 0.725078529
Gasoline 0.166007637 2905.2842823042 0.0001331647 581.9332 2.3305024311
Ethylene Glycol 30% 0.457399031 4186.4861294841 0.0016236325 890.559 14.86079916
Ethylene Glycol 50% 0.486799533 3803.7270603448 0.0009020219 960.3408 7.048168277
Transmission Oil (Type-H) 0.1168507018 2547.9909655151 0.0004532604 741.6038 9.88358202
Transmission Oil (Type-B) 0.1168507018 2547.9909655151 0.0014770331 741.6038 32.20748385
Exxon 2389 (jet engine oil) 0.126035558 2417.0777496002 0.0034489475 833.2028 66.14303355
16
T
308.15

T
485.65