Stop Log
Stop Log
Stop Log
SERIES 95
STOP LOGS
Low leakage rate
Installation in new or existing channel
Sealing system completely mounted on log
***
The Fontaine SERIES 95 Stop Logs are an easy and economical way to control flow in a channel. Their
lightweight construction makes them easy to handle and the UHMWPE (ultra high molecular weight
polyethylene) guide eliminates all metal-to-metal contact between the slide and frame, thereby
allowing the logs to slide up and down with minimal friction.
SERIES 95
STOP LOGS
A A
CHANNEL
HEIGHT
FLOW
B
CHANNEL WIDTH
FRAME WIDTH
BOXOUT WIDTH Figure 95-01
Frame embedded arrangement of a set of
Stop Logs and frame (FE)
D
EPDM
SEAL
FRAME
W
FRAME
GROUT
ADJUSTING NUTS
FLOW TO LEVEL FRAME
BEFORE GROUTING W
Detail 95-01
Detail 95-02
Side section “A-A” of a frame embedded
Bottom section “B-B” of a frame embedded
SERIES 95
STOP LOGS
OPENING
FRAME
A A
CHANNEL
HEIGHT
FLOW
INVERT
B
FRAME WIDTH
CHANNEL WIDTH ANCHOR
Figure 95-02
Channel mounted arrangement of a
stop logs and frame (EC)
EPDM
SEAL
EPDM SEAL
UHMWPE
SIDE SEAL
EPDM GASKET
FLOW
STIFFENER
GROUT
Detail 95-03
Detail 95-04
Side section “A-A” of a frame in channel
Bottom section “B-B” of a frame in channel
SERIES 95
STOP LOGS
A A
CHANNEL
HEIGHT
INVERT
CHANNEL WIDTH
FRAME WIDTH
Figure 95-03
Wall mounted arrangement of a set
of stop logs and frame (CW)
EPDM GASKET
EPDM GASKET
S.S. FRAME
UHMWPE GUIDE
Detail 95-05
Side section “A-A” of a wall mounted Detail 95-06
Bottom section “B-B” of a wall mounted
SERIES 95
STOP LOGS
Section “A-A”
A
Figure 95-04
Frame width
Size Channel less than 84" (2134 mm) wide Channel equal to or more than 84" (2134 mm) wide
Bottom = 8 1/4" (210 mm) wide x 3 1/4" (83 mm) deep 9 1/4" (235 mm) wide x 3 1/4" (83 mm) deep
Sides = 8 1/4" (210 mm) wide x 3 3/4" (95 mm) deep 9 1/4" (235 mm) wide x 3 3/4" (95 mm) deep
(*) These dimensions are for information only. Do not use for installation or submittal purposes.
SERIES 95
STOP LOGS
1.1. SCOPE. This section covers Stainless Steel Stop 2.1. LEAKAGE. Stop logs shall be substantially
Logs. watertight under the design head conditions. Leakage
shall not exceed 0.1 U.S. gallon per minute per foot
1.2. GENERAL. The equipment provided under this (1.25 l/min per meter) of periphery for the rated seating
section shall be fabricated, assembled, erected, and head.
placed in proper operating condition in full conformity
with the drawings, specifications, engineering data, 2.2. DESIGN HEAD. For the purpose of these
instructions and recommendations of the equipment specifications, stop logs shall be defined as meeting
manufacturer unless exceptions are noted by the the leakage requirements maximum water level (height
engineer. of stop logs in channel).
Stop logs shall be supplied with all the necessary parts 3. PRODUCT
and accessories indicated on the drawings, specified
or otherwise required for a complete, properly
operating installation, and shall be the latest standard 3.1. STOP LOGS
product of a manufacturer regularly engaged in the
production of stop logs. 3.1.1. GENERAL DESIGN. Stop logs shall be
constructed entirely of stainless steel. All hardware
The stop logs supplied under this section shall be shall be stainless steel.
Series 95 Stainless Steel Stop Logs as manufactured
by H. Fontaine Ltd. 3.1.2. FRAME. The frame shall be made of stainless
steel channels. The frame shall be suitable for
1.3. QUALITY ASSURANCE mounting on a concrete wall (CW), embedding in a
channel (FE), or installation inside an existing channel
1.3.1. The manufacturer shall have experience in the (EC).
production of substantially similar equipment and shall
show evidence of satisfactory operation in at least 5 3.1.3. LOGS. The logs shall consist of a flat plate
installations. The manufacturer's shop welds, welding reinforced with formed plates or structural members to
procedures and welders shall be qualified and certified limit their deflection to 1/360 of the gate's span under
in accordance with the requirement of the latest edition the design head. The guide shall be of UHMWPE (ultra
of ASME, Section IX. high molecular weight polyethylene).
1.3.2. The fully assembled stop logs shall be shop 3.1.5. SEALS. Seals shall be made of EPDM attached
inspected before shipping. to the logs by means of a UHMWPE retainer guide. The
bottom seal is attached to the log with a stainless steel
1.3.3. The manufacturer shall be ISO 9001 : 2000 retainer and seal on top of the log immediately
certified. underneath.
1.4. SUBMITTALS. The manufacturer shall submit, for 3.2. LIFTING DEVICE. When required, a stainless
approval by the purchaser, drawings showing the steel lifting device shall be supplied for each log width.
principal dimensions, general construction and The width of the lifting device will be the same as the log
materials used in the gate and lift mechanism. channel. The lifting device shall be equipped with a
device to allow releasing of the stop log from the
operating floor. This device shall grab the log
automatically.
SERIES 95
STOP LOGS
4. MATERIALS
Part Material
5. SCHEDULE
Stop log
Identification
Channel
width
Channel invert
elevation
Top of channel
elevation
Mounting:
FE - Frame-embedded
EC - Existing channel
CW - Concrete wall mounted
6. EXECUTION