MGS100 Technical Datasheet Final Rev-A ABB
MGS100 Technical Datasheet Final Rev-A ABB
MGS100 Technical Datasheet Final Rev-A ABB
MICROGRID SOLUTIONS
Specification
MGS100 Microgrid System
General Data
Nominal load power 20 kW 40 kW 60 kW
Max. recommended PV input power 24 kW 32 kW 53 kW
Max. rated PV output power 20 kW 27.6 kW 50 kW
Max. battery charging power 12 kW 24 kW 48 kW
Max. input battery capacity @ C10 charging 138 kWh 276 kWh 552 kWh
PV Input
MPPT operating range 440 – 800 V 500 - 800 V 480 - 800 V
Max. PV input DC voltage 1000 V 1000 V 1000 V
No. of independent MPPT 2 2 3
No. of DC input pairs/MPPT 5 5 5
PV input current protection for each input Yes, DC Fuses, 15 A Yes, DC Fuses, 15 A Yes, DC Fuses, 15 A
PV input over voltage protection Yes, Type II Yes, Type II Yes, Type II
AC Input
3 × 380/220 V + N 3 × 380/220 V + N 3 × 380/220 V + N
Nominal input voltage 3 × 400/230 V + N 3 × 400/230 V + N 3 × 400/230 V + N
3 × 415/240 V + N 3 × 415/240 V + N 3 × 415/240 V + N
Voltage tolerance ±15% ±15% ±15%
Input frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz
Frequency tolerance (Generator operation) -30% / +40% -30% / +40% -30% / +40%
Frequency tolerance (Grid export) ±5% ±5% ±5%
Maximum input current 36 A 71 A 108 A
AC input current protection Yes, MCCB Yes, MCCB Yes, MCCB
Rated short-time withstand current (Icw) 10kA for 1.5 seconds 10kA for 1.5 seconds 10kA for 1.5 seconds
Output
3 × 380/220 V + N 3 × 380/220 V + N 3 × 380/220 V + N
Nominal rated output voltage 3 × 400/230 V + N 3 × 400/230 V + N 3 × 400/230 V + N
3 × 415/240 V + N 3 × 415/240 V + N 3 × 415/240 V + N
Output frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz
Output rated current (In) 29 A 58 A 87 A
Output short capability on generator (RMS) for 100ms 2.7 x In A 2.7 x In A 2.7 x In A
Output short term overload capability on grid (RMS) for
10 x In A 10 x In A 10 x In A
20ms
Permissible unbalanced load (ɸ-ɸ) 100% 100% 100%
Output protection Yes, MCCB Yes, MCCB Yes, MCCB
Transfer time from GeneratorBatteryGrid <5 ms <5 ms <5 ms
Battery
Nominal battery voltage 504 to 576 V DC 504 to 576 V DC 504 to 576 V DC
Battery type VRLA, Ni-Cd, Li-ion VRLA, Ni-Cd, Li-ion VRLA, Ni-Cd, Li-ion
Maximum charging current 24 A 48 A 96 A
Battery protection Yes, MCB Yes, MCB Yes, MCB
Efficiency
Max. PV to load >98% >98% >98%
Max. grid to load >99% >99% >99%
Max. generator to load >95% >95% >95%
Max. PV to battery >94% >94% >94%
Max. grid to battery >95% >95% >95%
Environmental
Humidity (Non-condensing) <95% <95% <95%
-5 to 45 °C without -5 to 45 °C without -5 to 50 °C without
Ambient temperature
derating derating derating
Max. Ambient temperature 50 °C 50 °C 50 °C
Temperature derating -5%/°C after 45 °C -5%/°C after 45 °C N.A.
Altitude 1000 m 1000 m 1000 m
Altitude derating -5%/1000m -5%/1000m -5%/1000m
Audible noise at 1 m from front, 100% load < 70 dB < 70 dB < 70 dB
Electrical/Mechanical
Degree of protection IP31 IP31 IP31
Cable entry Bottom Bottom Bottom
Color RAL 7035 RAL 7035 RAL 7035
Weight, dimensions
Weight – Unpacked 620 kg 640 kg 745 kg
9AKK106930A8920 MGS100 datasheet
Cabinet Dimensions w x h x d (mm) 1500 x 1800x 800 1500 x 1800x 800 1200 x 2200 x 800
Separate solar section dimensions w x h x d (mm) N.A. N.A. 1491 x725 x 315
— —
ABB India Contact Center We reserve the right to make technical We reserve all rights in this document and
Toll free number within India changes or modify the contents of this in the subject matter and illustrations
1 800 420 0707 document without prior notice. With regard contained therein. Any reproduction,
International number to purchase orders, the agreed particulars disclosure to third parties or utilization of
+91 80 67 143 000 shall prevail. ABB does not accept any its contents – in whole or in parts – is
[email protected] responsibility whatsoever for potential forbidden without prior written consent of
errors or possible lack of information in ABB. Copyright© 2017 ABB.
this document. All rights reserved.
abb.com/microgrids