Viper - S Solid Dielectric, Three Phase Reclosers: Typical Specifications
Viper - S Solid Dielectric, Three Phase Reclosers: Typical Specifications
Viper - S Solid Dielectric, Three Phase Reclosers: Typical Specifications
®
VIPER -S SOLID DIELECTRIC, THREE PHASE RECLOSERS
PART 1- GENERAL
1.1 DESCRIPTION
This specification covers the requirements for an electronically controlled, automatic three phase, solid
dielectric vacuum recloser for distribution systems through 38kV. The recloser shall be manufactured by
®
G&W Electric Company and designated as the Viper -S Solid Dielectric Recloser.
A. Manufacturer Qualifications: The chosen manufacturer shall have at least 10 years experience in
manufacturing solid dielectric reclosers. The manufacturer of the reclosers shall be completely
and solely responsible for the performance of the reclosers well as the complete integrated
assembly as rated.
B. The manufacturer shall furnish certification of ratings of the reclosers upon request.
C. The recloser shall comply with requirements of the latest revisions of applicable industry
standards, including:
a) IEEE C37.60
b) IEEE 386
D. The recloser manufacturer shall be ISO 9001:2008 and ISO 14001:2004 certified.
A. Reclosers shall be shipped preassembled at the factory. No field assembly shall be required.
B. The contractor, if applicable, shall handle, transfer and move the reclosers in accordance
with
manufacturer’s recommendations.
PART 2- PRODUCTS
- 1 of 5 -
2.2 RECLOSER CONSTRUCTION
A. Mechanism Enclosure
The magnetic actuator and corresponding linkage assembly shall be housed within an integral,
air insulated, stainless steel enclosure. A bolted panel at the bottom of the mechanism enclosure
shall permit easy access if maintenance is required. All hardware shall be made of stainless steel
or brass for maximum corrosion-resistance. An air vent shall be provided. The mechanism
enclosure shall be painted light gray using a corrosion-resistant epoxy paint. Ground bosses
shall be provided for system ground.
B. Operating Mechanism
The operating mechanism shall utilize a magnetic actuator for opening and closing of the vacuum
interrupters. The actuator shall be powered by capacitors located in the mechanism enclosure.
The manual trip and lockout handle shall be made of stainless steel for maximum corrosion
resistance. Manual trip and lockout shall be provided by an external, hook-stick operable handle.
Operation of the manual trip handle shall activate a mechanical block device, disabling any local or
remote closing operation until the handle is reset. The operating temperature range shall be -40°C
to +65°C. Vacuum interrupter contact position indication shall be accomplished using green
(open) and red (closed) indicators located at the bottom of the mechanism enclosure.
C. Vacuum Interrupters
Interruption of the fault or load current shall be accomplished through vacuum interrupters located
inside the solid dielectric modules.
F. Electronic Control
The recloser shall be controlled using the following control (choose one):
• SEL-351 R
• SEL-651 R
• SEL-351 S package including painted steel enclosure, relay, connectorized control cable
and 24V control power supply
• GE URC
• None (ordered separately)
2.3 DESIGN RATINGS
A. Reclosers
The recloser shall be rated (choose appropriate column):
*1000A continuous current available with the following conditions: L-shaped module configuration, NEMA-4 hole or clamp
style lugs, and operating temperature range of -60°C through +40°C
15-20% 2000 44
45-55% 6000 56
90-100% 12000 16
Each individual recloser shall undergo a mechanical operation check verifying contact trip/close velocity,
travel profile, timing and phase synchronicity. The recloser shall be AC hi-pot tested one minute phase-
to-phase and across the open contacts. Circuit resistance shall be checked on all phases. Timing tests
shall be conducted to verify TCC performance.