Disclosure To Promote The Right To Information
Disclosure To Promote The Right To Information
Disclosure To Promote The Right To Information
hdian Standard
GUIDE FOR CONSTRUCTION
AND USE OF ROOMS OR BUILDINGS
PROTECTED BY PRESSURlZATlON, FOR
INSTALLATION OF ELECTRTCAL APPARATUS
FOR EXPLOSIVE GAS ATMOSPHERES
( Continuedfrompage 1)
Members Representing
2
IS:11064- 1984
Indian Standard
GUIDE FOR CONSTRUCTION
AND USE OF ROOMS OR BUILDINGS
PROTECTED BY PRESSURIZATION, FOR
INSTALLATION OF ELECTRICAL APPARATUS
FOR EXPLOSIVE GAS ATMOSPHERES
0. FOREWORD
0.1 This Indian Standard was adopted by the Indian Standaras
Institution on 23 August 1984, after the draft finalized by the ,Electrical
Apparatus for Explosive Atmospheres Sectional Committee had been
approved by the Electrotechnical Division Council.
0.2 This standard is one of a series of standards on pressurized enclosures.
The requirements of pressurized enclosures with no internal source of
flammable gas or vapour are covered in IS : 7389 ( Part 1 )-1976*.
0.3 The object of this guide is to lay down the principles of protection of
electrical apparatus by pressurization, adapting them to suit in the case of
rooms or buildings containing electrical apparatus and protecteJ by internal
over-pressure against the iugress of the potcntia!ly explosive external
atmosphere.
0.4 In the preparation of this guide, assistance has been derived from IEC
Publication 79-13 ( 1982 ) Electrical apparatus for explosive gas atmos-
pheres: Part 13 Construction and use of rooms or buildings protected by
pressurization, issued by International Electrotechnical Commission.
1. SCOPE
1.1 This guide defines the conditions in which an electrical apparatus liable
to cause an ignition may be used in a room or building situated where
flammable gases or vapours may bc present, the ingress of these gases or
vapours into the room being prevented by maint*ililing inside it a protec-
tive gas at a higher pressure than that of the outside atmosphere.
*Specification for pressurized enclosures of electrical equipment for use in hazardous
areas : Part I Pressurized enclosures with no internal source of 11ammabk gas or
vapour (first revision ).
IS : 11064- 1984
1.4 This guide concerns only rooms and buildings in the interior of which
there is no internal release ( actual or potential ) of flammable gases and
vapours.
2. TERMINOLOGY
2.0 For the purpose of this guide, the following definitions shall apply.
2.1 Room or Building - An enclosure ( or enclosures ) provided with
doors, cable ducts. conduits, etc, containing electrical apparatus and of
sufficient size to permit the entry of a person who may be expected to
work or remain inside the enclosure for a prol(,nged period.
NOTE -Throughout the rest of this guide, the term ‘room’ is employed
without distinction to designate rooms or buildings.
2.2 Opening - Any aperture, door, window or non-airtight fixed panel.
2.3 Protective Gas - The gas used to maintain an overpressure within the
room, or to purge air in these circumstances.
4
IS:llC64 - 1984
3.3 Pressurization of the room after purging, permits the use of electrical
equipment, which is not otherwise suitably protected for the area
classification.
NOTE - The atmospheres inside a rcom which is partially situated in a
hazardous zone, but all of whose openings lead into non-hazardous zones, is
considered as non-hazardous.
5. PROTECTIVE MEASURES
6
TABLE 1 SUMMARY OF PROTECTIVE MEASURES TO BE TAKEN IN THE EVENT OF
FAILURE OF PRESSURIZATION SYSTEM
( Clause 5.0 )
ELECTRICAL EQUIPMENT INSTALLED
8
IS : 11064 - 1984
9
IS : 11054- 1984
The design of a pressuriz:d room will also need to consider :
NOTE 2 -
ai the number of persons expected to stay in the room in order to ensure
the necessary renewai of the air; and
b) the type of amaratm to b: installed in the room and their need for
coohng air, if any.
7. PROTECHVE GAS SUPPLY
7.1 The protective gas should not, by virtue of any chemical products or
impurities which it may contain, produce deleterious effects or introduce a
risk of reduced safety.
NOTE - The protective gas may also be u;ed for other purposes, such as for
cooling the appsratus.
8. VERIFICAI‘ION A ND TESTS
8.1 Before putting a pressurized room into service, the technical documen-
tation should be examixd and ii‘ necessary, a test shall be carried out.
8.2 In particular, it should be assured that:
a) the construction of the installation and the protective measures
are such that purging can be eRected, and
b) the minimum over pressure ( see 6.2 ) can be maintained at the
minimum flow rate of the pressurization system with all the
openings closed, in normal working conditions.
9. MARKING
9.1 All doors I^rom the pressurized room should be clearly marked on the
outside, by the following notice or an equivalent:
‘WARNING - PRESSURIZED ROOM - CLOSE THIS DOOR’.
9.2 Inside thz room, the following inFormation should be displayed:
Minimum required overprrssurs, or corresponding rate of flow of
protective gas.
9.3 Rules to be observed for the installation in question:
a) When switching on:
In accordance with 5.1, a notice should be displayed close to the
switch of the pressurization fan and to the general circuit-breaker
for the room, with the following or equivalent wording:
‘WARNING - The pressurization fan should be allowed to run
for t minutes before switchiug on the installation, unless it has been
checked that the atmosphere in ths room is not hazardous.’
NOTE- t is the time required for purging at minimum flow rate.
b) In case of pressurization failure:
Jn accordance with 5.2, a detailed list should be given indicating
the apparatus to be switched off, the delays, if any, allowed for
each operation, and any other measures to be taken particularly
in the event of pressurization failure.
10