Thermatrac Air-To-Water Heat Pump Water Heater: Key Features
Thermatrac Air-To-Water Heat Pump Water Heater: Key Features
Thermatrac Air-To-Water Heat Pump Water Heater: Key Features
Key Features:
1. World renowned compressors with Eco-friendly HFC refrigerant to match high COP achieved
2. High quality heat exchanger (tube-in-tube and stainless steel flat plate), ideal for direct potable water heating
3. Easily accessible control box
4. Large access panels for easy servicing
5. Robust UV resistant GI. Cabinet construction – suitable for outdoor installation
6. User-friendly LCD electronic controls monitor operation for reliability and easy interaction
7. Standard safety features to ensure trouble-free operation; high-low pressure switch, flow switch, overheat cut-off
protection, etc.
8. Environmental friendly hot water system – cost only 1/4 of similar fossil fuel system
Technical Specifications
Outdoor
Compressor Heat exchanger Dimension
Fan
Ref Model Heating Rated Rated Max. Max. Volts Noise Operating
Water Water Pressure
To Capacity Input Amps Input Amps Phase Refrigerant Level Weight
Type No. No. Conn. Flow Drop Length Width Height
Pic kW kW A kW A Hertz dB(A) kg
BSP Rate mm mm mm
mm m3/h kPa
TRT-7 7.0 1.7 8.0 2.6 11.8 220-240/1/50 R-417A Rotary 1 1 20 4 22 53 64 567 503 783
1 TRT-10 9.5 2.3 10.9 3.6 16.5 220-240/1/50 R-417A Rotary 1 1 25 6 25 56 110 710 710 908
TRT-18 17.9 4.5 8.8 6.9 13.5 380-415/3/50 R-417A Scroll 1 1 40 8 27 58 145 810 810 975
TRT-35 35.0 8.9 17.6 12.8 25.5 380-415/3/50 R-417A Scroll 2 2 40 10 32 62 293 1450 705 1290
2
TRT-40 40.7 10.5 19.8 13.8 26.2 380-415/3/50 R-417A Scroll 2 2 40 10 32 62 325 1450 705 1290
3 TRT-75 74.4 19.1 39.5 25.0 46.0 380-415/3/50 R-417A Scroll 2 2 65 25 40 72 650 2000 1100 1980
Note:
• Preset water temperature: 55°C
• Maximum water temperature: 60°C
• Maximum working pressure (water side): 3.0 MPa
• Testing conditions: ambient temperature: dry bulb:20°C, wet bulb:15°C, water temperature raised 15°C to 55°C
• Ambient temperature operation range: -7 to 43°C
Technical Specifications
Heat exchanger
Model Heating Rated Rated Max. Max. Volts Condenser Evaporator Noise Operating
Capacity Input Amps Input Amps Phase Refrigerant Water Water Pressure Water Water Pressure Level Weight
kW kW A kW A Hertz Type No. Conn. Flow Drop Conn. Flow Drop dB(A ) kg Length Width Height
TRW-42 42.0 9.8 18.5 14.7 27.8 380-415/3/50 R-417A Scroll 2 40 7.2 50 40 7.2 50 40 320 1530 815 800
TRW-82 82.5 19.0 38.5 28.5 57.8 380-415/3/50 R-417A Scroll 2 40 14.5 50 40 14.5 50 40 680 2000 1100 1100
TRW-220 220.0 51.2 108.0 76.8 162.0 380-415/3/50 R-417A Scroll 4 100 36.0 50 100 36.0 50 40 1500 2500 1800 1100
Note:
• Preset water temperature: 55°C
• Maximum water temperature: 60°C
• Maximum working pressure (water side): 3.0MPa
• Testing conditions: cooling side: inlet: 15°C, outlet:10°C; water heated from 15°C to 55°C
Rheem Manufacturing Company (Singapore) Pte Ltd
8 Pandan Crescent, UE Tech Park #02-02 Singapore 128464 Authorised Dealer
Tel (For Sale) : (65) 6872 1161
Tel (Service) : (65) 6872 2043
Fax : (65) 6872 1151
E-mail : [email protected]
Website : http//www.rheemmfg.com.sg
Thermatrac air-to-water heat pump spa/pool heater
Features:
1. Exclusive powder-coated cabinet
2. Large air evaporator coil
3. Scroll or rotary compressor depending model
4. Spiral titanium/coaxial tube
5. Plumbing connections: easy installation
6. Controls – digital: on board diagnostics
7. Multiple safety features, trouble-free operation
Picture 1 Picture 2
Picture 3 Picture 4
Technical Specifications
Outdoor
Compressor Heat exchanger Dimension
Fan
Ref Model Heating Rated Rated Max. Max. Volts Noise Net
Water Water Pressure
To Capacity Input Amps Input Amps Phase Refrigerant Level Weight
Type No. No. Conn. Flow Drop Length Width Height
Pic kW kW A kW A Hertz dB(A) kg
Rate mm mm mm
3
mm m /h kPa
TRP-9 8.9 1.7 8.0 2.6 12.0 220-240/1/50 R417A Rotary 1 1 50 6 12 53 64 567 503 783
1
TRP-13 12.9 2.4 11.0 3.6 16.5 220-240/1/50 R417A Rotary 1 1 50 7 12 56 110 710 710 908
2 TRP-21 21.0 4.3 8.8 6.5 13.2 380-415/3/50 R417A Scroll 1 1 50 8 12 62 145 810 810 975
3 TRP-51 50.8 9.9 18.0 14.9 27.0 380-415/3/50 R417A Scroll 2 2 63 15 15 62 325 1450 705 1290
4 TRP-100 100.0 20.0 38.0 30.0 57.0 380-415/3/50 R417A Scroll 2 2 110 30 16 72 650 2000 1100 1980
Note:
• Titanium heat exchanger
• Testing conditions: ambient temperature: dry bulb:24°C, wet bulb:19°C, inlet water temperature: 27°C
• Ambient temperature operation range: -7 to 43°C
Thermatrac residential air-to-water heat pump water heater
Standard features:
1. Absorbs environmental heat and transfers it to the water, at the same time cold air can be delivered to the space
(kitchen, basement, garage, etc.) through duct
2. One-piece design c/w rotary compressor, user-friendly LCD controller for easy interaction
3. Stainless steel jacket
4. Floor mounted
5. SS304 water tank, durable and corrosion resistant
6. Efficient heat exchanger (Ni-Ti alloy SS321) inside tank, efficient heat transfer
7. Heating element: 2 kW x 220 Volt
8. Pressure relief valve
TRRD35-200 200 3.5 0.89 4.0 1.3 6.0 220-240/1/50 R417A Rotary 1 1 15 45 60 650 1500 150
TRRD35-300 300 3.5 0.89 4.0 1.3 6.0 220-240/1/50 R417A Rotary 1 1 15 45 60 650 1800 150
Note:
• Preset water temperature: 55°C
• Maximum water temperature: 60°C
• Maximum working pressure (water tank): 0.7 MPa
• Ambient temperature operation range: -7 to 43°C
• Testing conditions: ambient temperature: dry bulb:20°C, wet bulb:15°C; water heated from 15 to 55°C
STANDARD FEATURES
• SUS316L tank material
• 0.6MPa maximum working pressure
• Flanged Manhole
• Flanged water connec�ons (DIN standard)
• Li�ing lugs
• Angle legs
• Drain
• Pressure relief valve
OPTION:
• 1.0MPa maximum working pressure
SUS316L tank: 1.0MPa Mild steel tank with copper lining: 1.0MPa
Max. Max. Copper
Mild steel
capacity Working thickness material capacity Working sheet
thickness
pressure pressure thickness
2m3 1.0MPa 6mm SUS316L 2m3 1.0MPa 8mm 1mm