Condensate System
Condensate System
4.5.4.2.1 GENERAL
Two 100% motor driven condensate extraction pumps and motors shall
be provided. They shall be of the vertical “canned” type, mounted in a
steel pipe barrel extending below the basement floor.
These pumps shall start automatically as required; the time taken to bring
in a standby pump shall be stated. Each pump shall be capable of
continuously operating on its own against run-out or on stand by. The
capacity and mode of operation of the low load recirculation lines shall be
described.
Each pump shall be provided with suction and discharge pressure gauges
together with any other local instrumentation required.
Each pump shall be provided with a temporary fine mesh strainer in the
suction line for preliminary operator and commissioning.
A vent pipe shall be supplied for each pump to equalize the pressure
between the pump suction and the condenser vapour space, the
Contractor shall confirm that any loss of prime is automatically rectified.
The Contractor shall be responsible for the pump and motor combination
operating in dynamic balance without undue vibration or noise. The critical
speed of the complete unit (pump and motor) shall be at least 25 % above
or below the operating speed.