Standard Review Plan: NUREG-0800 U.S. Nuclear Regulatory Commission

Download as pdf or txt
Download as pdf or txt
You are on page 1of 23

NUREG-0800

U.S. NUCLEAR REGULATORY COMMISSION

STANDARD REVIEW PLAN

8.4 STATION BLACKOUT

REVIEW RESPONSIBILITIES

Primary - Organization responsible for the electrical engineering review

Secondary - None

I. AREAS OF REVIEW

The term Astation blackout@ (SBO) refers to the complete loss of alternating current (ac) electric
power to the essential and nonessential switchgear buses in a nuclear power plant (NPP). An
SBO; therefore, involves the loss of the offsite electric power system (referred to in industry
standards and regulatory guides (RGs) as the Apreferred power system@) concurrent with a
turbine trip and unavailability of the emergency ac (EAC) power system (typically emergency
diesel generators (EDGs)). An SBO does not include the loss of available ac power to buses
fed by station batteries through inverters or by alternate ac (AAC) sources specifically provided
for SBO mitigation. Because many safety systems necessary for reactor core decay heat
removal depend on ac power, an SBO could result in a severe core damage accident. The risk

Revision 1 - May 2010

USNRC STANDARD REVIEW PLAN


This Standard Review Plan, NUREG-0800, has been prepared to establish criteria that the U.S. Nuclear Regulatory Commission
staff responsible for the review of applications to construct and operate nuclear power plants intends to use in evaluating whether an
applicant/licensee meets the NRC's regulations. The Standard Review Plan is not a substitute for the NRC's regulations, and
compliance with it is not required. However, an applicant is required to identify differences between the design features, analytical
techniques, and procedural measures proposed for its facility and the SRP acceptance criteria and evaluate how the proposed
alternatives to the SRP acceptance criteria provide an acceptable method of complying with the NRC regulations.

The standard review plan sections are numbered in accordance with corresponding sections in Regulatory Guide 1.70, "Standard
Format and Content of Safety Analysis Reports for Nuclear Power Plants (LWR Edition)." Not all sections of Regulatory Guide 1.70
have a corresponding review plan section. The SRP sections applicable to a combined license application for a new light-water
reactor (LWR) are based on Regulatory Guide 1.206, "Combined License Applications for Nuclear Power Plants (LWR Edition)."

These documents are made available to the public as part of the NRC's policy to inform the nuclear industry and the general public of
regulatory procedures and policies. Individual sections of NUREG-0800 will be revised periodically, as appropriate, to accommodate
comments and to reflect new information and experience. Comments may be submitted electronically by email to
[email protected].

Requests for single copies of SRP sections (which may be reproduced) should be made to the U.S. Nuclear Regulatory Commission,
Washington, DC 20555, Attention: Reproduction and Distribution Services Section, or by fax to (301) 415-2289; or by email to
[email protected]. Electronic copies of this section are available through the NRC's public Web site at
http://www.nrc.gov/reading-rm/doc-collections/nuregs/staff/sr0800/, or in the NRC's Agencywide Documents Access and
Management System (ADAMS), at http://www.nrc.gov/reading-rm/adams.html, under Accession # ML100740424.
of SBO involves the likelihood and duration of the loss of all ac power and the potential for
severe core damage after a loss of all ac power.

In 1980, the NRC designated SBO as an unresolved safety issue (USI A-44). The agency
documented the findings of the technical studies completed for USI A-44 in NUREG-1032
(Ref. 30). In June 1988, the NRC resolved USI A-44 with the publication of a new rule under
Title 10 of the Code of Federal Regulations (CFR), Section 50.63 (Ref. 2) (53 FR 23203) and an
accompanying RG (RG 1.155 (Ref. 7)).

Concurrently, the Nuclear Management and Resources Council (NUMARC) (now the Nuclear
Energy Institute (NEI)) developed NUMARC-8700, Revision 0 (Ref. 38), which RG 1.155
endorses with certain exceptions. Table 1 of RG 1.155 provides a cross-reference to NUMARC-
8700, Revision 0, and it notes when the RG takes precedence.

The information presented in the safety analysis report (SAR) should be sufficient to support the
conclusion that the plant is capable of withstanding and recovering from a complete loss of ac
electric power to the essential and nonessential switchgear buses for a specified period of time.
The staff will perform the review to ensure conformance with the requirements of 10 CFR 50.63,
10 CFR 50.65, and General Design Criteria (GDCs) 17 and 18 in Appendix A to 10 CFR Part 50
by verifying that the licensee is implementing the relevant guidance of RG 1.155, as
supplemented by the guidance and criteria herein.

The analyses performed to demonstrate compliance with 10 CFR 50.63 should remain valid for
the life of the NPP. Therefore, if the underlying assumptions change during the life of the NPP,
licensees are expected to reevaluate the specified coping duration for their NPPs and the
accompanying coping analyses using RG 1.155 or NUMARC-8700, Revision 0, as endorsed by
RG 1.155.

The specific areas of review are as follows:

1. SBO Coping Duration. The SBO coping duration is defined as the time from the onset of
an SBO to the time when either offsite (preferred) or onsite (EDGs) ac power is restored
to at least one of the safe shutdown buses. The SBO rule requires each plant to specify
an SBO coping duration that is justified by an analysis of site- and plant-specific factors
that contribute to the likelihood and duration of an SBO. Because passive plants will not
have EAC power sources, applicants for such plants need not evaluate SBO coping
duration as long as they are able to demonstrate that the design selected is capable of
performing safety-related functions for 72 hours. The 72 hour approach is consistent
with the duration approved by the NRC staff for the AP 1000 design. The review should
determine that the selected minimum coping duration conforms to the guidance provided
in Section C.3.1 of RG 1.155.

2. SBO Coping Capability. The review should determine that the capability to achieve and
maintain safe shutdown (non-design-basis accident (DBA)) during an SBO conforms to
the guidance provided in Section C.3.2 of RG 1.155 and that appropriate procedures and
training have been developed to implement this capability.

3. AAC Power Sources. Use of an AAC power source that is consistent with the guidance
in RG 1.155 and capable of powering at least one complete set of normal shutdown
loads is the preferred approach for complying with the requirements of 10 CFR 50.63.

8.4-2 Revision 1 - May 2010


The review conducted herein should determine that the information submitted and
commitments made regarding the AAC power source provide reasonable assurance of
the licensee=s conformance with the rule. To do this, the staff will verify that the design of
the AAC power source conforms to the guidelines in Section C.3.3.5 of RG 1.155.

As described in SECY-90-016 (Ref. 23), new advanced light-water reactor (ALWR)


applications, other than plant designs that use passive safety systems (such as the
AP1000), should have a spare, full-capacity, AAC power source that meets the
guidelines in Section 3.3.5 of RG 1.155 (Ref. 23). Passive plant designs need not
include an AAC power source if it can be demonstrated that all safety-related functions
can be performed without reliance on ac power for 72 hours after the initiating event and
the applicant has implemented a regulatory treatment of nonsafety system (RTNSS)
process that conforms to Chapter C.IV.10 of Draft Guide (DG)-1145 (Ref. 28). For
combined license (COL) applicants that reference a certified design, the certification will
have addressed the implementation of the RTNSS process.

4. Procedures and Training. The review should determine that procedures and training
conform to the guidance in Sections C.1.3, C.2, and C.3.4 of RG 1.155. Procedures and
training should address all operator actions necessary to (a) restore EAC power when
the EAC power system is unavailable, (b) cope with AAC or battery power on the
occurrence of an SBO for the specified coping duration during all modes of plant
operation, (c) restore offsite power and use of nearby power sources (which may include
such items as nearby or onsite gas turbine generators, portable generators, or
hydrogenerators) in the event of a loss of offsite power (LOOP), and (d) restore normal
long-term core cooling/decay heat removal once power is restored.

The review should determine that communication agreements and protocols between the
plant and its transmission system operator provide assurance that the NPP operator will
be kept aware of (a) changes in the plant switchyard and offsite power grid and (b) local
power sources and transmission paths that could be made available to resupply the plant
following a LOOP (Ref. 15).

5. Quality Assurance (QA) and Specifications for Non-Safety-Related Equipment. The


review should determine that QA activities and specifications for non-safety-related
equipment used to meet the requirements of 10 CFR 50.63 conform to the
recommendations in Section C.3.5 and Appendix A to RG 1.155. The review should also
determine that systems and equipment used to meet the requirements of 10 CFR 50.63
conform to the system and station equipment specification recommendations of Appendix
A to RG 1.155. Additionally, the review should ensure that non-safety equipment installed
to meet the SBO rule does not degrade the existing safety-related systems. This is
accomplished by ensuring that the non-safety equipment is as independent as practicable
from existing safety-related systems. The staff reviews the electrical independence of the
AAC power source (if provided) under Standard Review Plan (SRP) Section 8.2.

6. Inspections, Tests, Analyses, and Acceptance Criteria (ITAAC). For design certification
(DC) and COL reviews, the staff reviews the applicant's proposed ITAAC associated with
the structures, systems, and components (SSCs) related to this SRP section in
accordance with SRP Section 14.3, "Inspections, Tests, Analyses, and Acceptance
Criteria." The staff recognizes that the review of ITAAC cannot be completed until after
the rest of this portion of the application has been reviewed against acceptance criteria

8.4-3 Revision 1- May 2010


contained in this SRP section. Furthermore, the staff reviews the ITAAC to ensure that
all SSCs in this area of review are identified and addressed as appropriate in accordance
with SRP Section 14.3.

7. COL Action Items and Certification Requirements and Restrictions. For a DC


application, the review will also address COL action items and requirements and
restrictions (e.g., interface requirements and site parameters).

For a COL application referencing a DC, a COL applicant must address COL action
items (referred to as COL license information in certain DCs) included in the referenced
DC. Additionally, a COL applicant must address requirements and restrictions (e.g.,
interface requirements and site parameters) included in the referenced DC.

Review Interfaces

Other SRP sections interface with this section as follows:

1. The adequacy of the onsite power system, including standby EAC power sources,
safety-related ac distribution systems, station batteries and associated direct current (dc)
systems, and instrumentation and control power systems, is reviewed by the organization
responsible for electrical engineering as part of its primary review responsibility for SRP
Sections 8.3.1 and 8.3.2.

2. The adequacy of the offsite power system, including necessary preferred power circuits
to the onsite power system and independence of the preferred power system and AAC
power source(s) provided for SBO (if used), is reviewed by the organization responsible
for electrical engineering as part of its primary review responsibility for SRP Section 8.2.

3. The organization responsible for the review of SRP Sections 4.6, 5.4.6, 5.4.7, 5.4.12, 6.3,
and 9.3.5 determines those system components needing electric power as a function of
time for each mode of reactor operation and accident condition.

4. The organization responsible for the review of SRP Sections 6.5.1, 6.7, 9.1.3, 9.1.4,
9.2.1, 9.2.2, 9.2.4, 9.2.5, 9.2.6, 9.3.1, 9.3.3, 9.4.1 through 9.4.5, 9.5.1, 10.4.5, 10.4.7,
and 10.4.9 determines those system components needing electric power as a function of
time for each mode of reactor operation and accident condition.

5. The organization responsible for the review of SRP Sections 9.1.3, 9.1.4, 9.2.1, 9.2.2,
9.2.4, 9.2.5, 9.2.6, 9.3.1, 9.3.3, and 9.4.1 through 9.4.5 also verifies, on request, the
design adequacy and capability of systems and equipment needed to cope with an SBO
for the required duration and recovery period.

6. The organization responsible for the review of SRP Section 7.2 determines those system
components needing electric power as a function of time for each mode of reactor
operation and accident condition and, upon request, also verifies the adequacy of the
instrumentation and controls used to cope with and recover from an SBO condition.

7. The organization responsible for the review of SRP Section 16.0 coordinates and
performs reviews of technical specifications.

8.4-4 Revision 1- May 2010


8. The organization responsible for the review of SRP Sections 6.2.2, 6.2.3, 6.2.4, and 6.2.5
determines those system components needing electric power as a function of time for
each mode of reactor operation and accident condition.

9. The organization responsible for the review of SRP Section 14.2 determines the
acceptability of the preoperational and initial startup tests and programs.

10. The organization responsible for the review of SRP Sections 13.5.1.2 and 13.5.2.2
evaluates the adequacy of administrative, maintenance, testing, and operating procedure
programs. In addition, on request, the organization responsible for SRP Sections
13.5.1.1 and 13.5.2.1 reviews potential habitability concerns for those areas that would
need operator access during the SBO and recovery period.

11. The organization responsible for the review of SRP Section 17 evaluates the design,
construction, and operations phases of QA programs, including the general methods for
addressing periodic testing, and RTNSS in passive plant designs. In addition, while
conducting regulatory audits in accordance with Office Instructions NRR-LIC-111 or
NRO-REG-108, “Regulatory Audits,” the technical staff may identify quality-related
issues. If this occurs, the technical staff should contact the organization responsible for
quality assurance to determine if an inspection should be conducted.

The specific acceptance criteria and review procedures are contained in the referenced SRP
sections.

II. ACCEPTANCE CRITERIA

Requirements

Acceptance criteria are based on meeting the relevant requirements of the following
Commission regulations:

1. GDC 17, as it relates to (a) the capacity and capability of onsite and offsite power
systems to permit functioning of SSCs important to safety in the event of anticipated
operational occurrences and postulated accidents and (b) provisions to minimize the
probability of losing electric power from the transmission network (grid) as a result of, or
coincident with, the loss of power generated by the nuclear power unit or loss of power
from the onsite electric power supplies.

Plants not licensed in accordance with the GDC in Appendix A to 10 CFR Part 50 were
licensed to satisfy plant-specific principal design criteria presented in the updated final
SAR. These criteria are similar to GDC 17.

2. GDC 18, as it relates to periodic testing and inspection of offsite and onsite power
systems important to safety.

3. 10 CFR 50.63, as it relates to the capability to withstand and recover from an SBO.

4. 10 CFR 50.65(a)(4), as it relates to the assessment and management of the increase in


risk that may result from proposed maintenance activities before performing the

8.4-5 Revision 1- May 2010


maintenance activities. These activities include, but are not limited to, surveillances, post
maintenance testing, and corrective and preventive maintenance. Compliance with the
maintenance rule, including verification that appropriate maintenance activities are
covered therein, is reviewed under SRP Chapter 17.

5. 10 CFR 52.47(b)(1), which requires that a DC application contain the proposed ITAACs
that are necessary and sufficient to provide reasonable assurance that, if the inspections,
tests, and analyses are performed and the acceptance criteria met, a plant that
incorporates the design certification is built and will operate in accordance with the
design certification, the provisions of the Atomic Energy Act (AEA), and the U.S. Nuclear
Regulatory Commission’s (NRC's) regulations;

6. 10 CFR 52.80(a), which requires that a COL application contain the proposed
inspections, tests, and analyses, including those applicable to emergency planning, that
the licensee shall perform, and the acceptance criteria that are necessary and sufficient
to provide reasonable assurance that, if the inspections, tests, and analyses are
performed and the acceptance criteria met, the facility has been constructed and will
operate in conformity with the combined license, the provisions of the AEA, and the
NRC's regulations.

SRP Acceptance Criteria

Specific SRP acceptance criteria acceptable to meet the relevant requirements of the NRC=s
regulations identified above are as follows for the review described in this SRP section. The
SRP is not a substitute for the NRC=s regulations, and compliance with it is not required.
However, an applicant is required to identify differences between the design features, analytical
techniques, and procedural measures proposed for its facility and the SRP acceptance criteria
and evaluate how the proposed alternatives to the SRP acceptance criteria provide acceptable
methods of compliance with the NRC regulations.

1. The guidelines of RG 1.155, as they relate to compliance to 10 CFR 50.63.


NUMARC-8700, Revision 0, also provides guidance acceptable to the staff for meeting
these requirements. Table 1 of RG 1.155 provides a cross-reference to NUMARC-8700,
Revision 0, and notes when the RG takes precedence.

2. The guidelines and criteria of SECY-90-016 and SECY-94-084 (Ref. 25), as they relate
to the use of AAC power sources and RTNSS at plants provided with passive safety
systems.

3. The guidelines of RGs 1.9 (Ref. 6) and 1.155, as they relate to the reliability program
implemented to ensure that the target reliability goals for onsite EAC power sources
(typically diesel generator units) are adequately maintained.

4. The guidelines of RG 1.160 (Ref. 8), as they relate to the effectiveness of maintenance
activities for onsite EAC power sources, including grid-risk-sensitive maintenance
activities (i.e., activities that tend to increase the likelihood of a plant trip, increase LOOP
frequency, or reduce the capability to cope with a LOOP or SBO). Compliance with the
maintenance rule, including verification that appropriate maintenance activities are
covered therein, is reviewed under SRP Chapter 17.

8.4-6 Revision 1- May 2010


5. The guidelines of RG 1.182 (Ref. 9), as they relate to conformance to the requirements
of 10 CFR 50.65(a)(4) for assessing and managing risk when performing maintenance.

Technical Rationale

The technical rationale for application of these acceptance criteria to the areas of review
addressed by this SRP section is discussed in the following paragraphs:

1. Compliance with GDC 17 requires that onsite and offsite electrical power be provided to
facilitate the functioning of SSCs important to safety. Each electric power system,
assuming the other system is not functioning, must provide sufficient capacity and
capability to ensure that specified acceptable fuel design limits and the design conditions
of the reactor coolant pressure boundary are not exceeded as a result of anticipated
operational occurrences and that the core is cooled and containment integrity and other
vital functions are maintained in the event of postulated accidents. GDC 17 also requires
the inclusion of provisions to minimize the probability of losing electric power from any of
the remaining supplies as a result of, or coincident with, the loss of power generated by
the nuclear power unit, the loss of power from the transmission network, or the loss of
power from the onsite electric power supplies.

Meeting the requirements of GDC 17 provides assurance that a reliable electric power
supply will be provided for all facility operating modes, including anticipated operational
occurrences and DBAs, to permit the performance of safety functions and other vital
functions, even in the event of a single failure. SRP Sections 8.1, 8.2, 8.3.1, and 8.3.2
contain additional information related to the review of compliance with GDC 17.

2. Compliance with GDC 18 requires that electric power systems important to safety be
designed to permit appropriate periodic inspection and testing of key areas and features
to assess their continuity and the condition of their components. These systems shall be
designed to test periodically (a) the operability and functional performance of the
components of the systems, such as onsite power sources, relays, switches, and buses,
and (b) the operability of the systems as a whole and, under conditions as close to
design as practical, the full operation sequence that brings the systems into operation,
including operation of applicable portions of the protection system, and the transfer of
power among the nuclear power unit, the offsite power system, and the onsite power
system. Consequently, the ac power system must provide the capability to perform
integral testing on a periodic basis.

Meeting the requirements of GDC 18 provides assurance that, when necessary, offsite
power systems can be appropriately and unobtrusively accessed for required periodic
inspection and testing, enabling verification of important system parameters,
performance characteristics, and features and detection of degradation and/or impending
failure under controlled conditions.

3. Compliance with 10 CFR 50.63 requires that each light-water-cooled NPP be able to
withstand and recover from an SBO (as defined in 10 CFR 50.2 (Ref. 1)). Meeting the
requirements of 10 CFR 50.63 provides assurance that the NPP will be able to withstand
(cope with) and recover from an SBO and will ensure that core cooling and appropriate
containment integrity are maintained.

8.4-7 Revision 1- May 2010


4. Pursuant to 10 CFR 50.65, the NPP operator should know the grid=s condition before
taking a risk-significant piece of equipment out of service and should monitor the grid for
as long as the equipment remains out of service. This provides assurance that grid
reliability evaluations are performed before undertaking grid-risk-sensitive maintenance
activities (such as surveillances, postmaintenance testing, and preventive and corrective
maintenance) under existing or imminent degraded grid reliability conditions that could
increase the likelihood of an SBO or impact the plant=s ability to cope with an SBO, such
as out-of-service risk-significant equipment (e.g., an EDG, a battery, a steam-driven
pump, an AAC power source).

III. REVIEW PROCEDURES

The reviewer will select material from the procedures described below, as may be appropriate
for a particular case.

These review procedures are based on the identified SRP acceptance criteria. For deviations
from these acceptance criteria, the staff should review the applicant=s evaluation of how the
proposed alternatives provide an acceptable method of complying with the relevant NRC
requirements identified in Subsection II.

The SBO rule (10 CFR 50.63) requires each plant to demonstrate the capability to withstand
(cope with) and recover from an SBO condition lasting for a specified duration (coping duration).
Specifically, all licensees and applicants should do the following:

1. Determine the duration of an SBO that the plant should be able to withstand (coping
duration).

2. Evaluate the plant=s capability to withstand and recover from an SBO (coping capability)
and, if necessary, make modifications to improve the coping ability.

3. Establish minimum reliability goals for onsite EAC power supplies (typically EDGs) and
establish a program to ensure the reliability goals are maintained.

4. Develop procedures and training to cope with and recover from an SBO.

The analyses performed to demonstrate compliance with 10 CFR 50.63 should remain valid for
the life of the NPP. If the underlying assumptions change during the life of the NPP, licensees
are expected to reevaluate the specified coping duration of their NPPs and the accompanying
coping analyses using RG 1.155 or NUMARC-8700, Revision 0.

To ensure that the requirements of 10 CFR 50.63 are satisfied, the staff should take the
following review steps:

1. SBO Coping Duration. The SBO rule requires each plant to justify its specified coping
duration by an analysis of site- and plant-specific factors that contribute to the likelihood
and duration of an SBO. Because passive plants will not have EAC power sources,
applicants for such plants need not evaluate SBO coping duration as long as they are
able to demonstrate that the design selected is capable of performing safety-related
functions for 72 hours. The 72 hour approach is consistent with the duration approved
by the NRC staff for the AP 1000 design. The rule identifies these factors as follows:

8.4-8 Revision 1- May 2010


$ The redundancy of the onsite EAC power sources
$ The reliability of the onsite EAC power sources
$ The expected frequency of a LOOP
$ The probable time needed to restore offsite power

The staff will review applicant submittals on SBO (i.e., SBO analysis) to determine that
the selected coping duration conforms to the guidance provided in Section C.3.1 of
RG 1.155, as supplemented by the criteria contained herein. A series of tables in
RG 1.155 define each of the above factors and provide a method for determining an
acceptable minimum SBO coping duration for the plant. The following summarizes this
process:

A. Characteristics of the offsite power system that have been found to contribute to
the expected frequency of a LOOP are examined and an appropriate AOffsite
Power Configuration Group@ (designated P1, P2, and P3) is selected from
Table 4 of RG 1.155. The assumptions used in meeting 10 CFR 50.63 should
remain valid for the life of the NPP.

B. The redundancy of the onsite EAC power sources (i.e., the number available for
decay heat removal minus the number needed for decay heat removal) is
determined and an appropriate AEmergency AC Power Configuration Group@
(designated A, B, C, or D) is selected from Table 3 of RG 1.155. The number of
EAC power supplies needed for SBO should be based on the ac loads necessary
at each unit to achieve and maintain safe shutdown with offsite power
unavailable.

For single unit or multiunit sites having normally dedicated power supplies, the
number of EAC power sources needed is determined by counting the number of
EAC power supplies on a per-unit basis that are necessary to operate
safe-shutdown equipment following a LOOP. For multiunit sites having shared
power supplies, the number of EAC power sources needed is determined by
counting the total number of standby power supplies necessary to operate
safe-shutdown equipment following a LOOP. The determination of EAC power
configuration groups does not count special-purpose dedicated diesel generators,
such as those associated with high-pressure core spray systems at some boiling-
water reactors.

C. The reliability of each EAC power source is determined in accordance with the
guidance in Section C.1.1 of RG 1.155. The minimum target reliabilities of EAC
power sources should be targeted at 0.95 per demand for each EDG for plants in
EAC Groups A, B, and C and at 0.975 per demand for each EDG for plants in
EAC Group D.

D. Using the results of the above evaluations (offsite power design characteristic
group, EAC power configuration group, and unit average EAC reliability values),
an appropriate AMinimum Acceptable Coping Duration@ may be selected from
Table 2 of RG 1.155.

2. SBO Coping Capability. The staff will review the SAR to determine that the capability to
cope with an SBO lasting for the duration determined in Subsection III.1, above,

8.4-9 Revision 1- May 2010


conforms to the guidance in Section C.3.2 of RG 1.155. The review should ensure that
the capability to maintain adequate core cooling and appropriate containment integrity for
the specified coping duration is adequately demonstrated and appropriate procedures
and training are implemented to withstand (cope with) the event.

In general, two options are available to cope with an SBOCan ac-independent approach
and an AAC approach. In the ac-independent approach, the plant relies on available
sources of energy that are independent of ac power (e.g., process steam, dc power, and
compressed air). If this approach is selected, the review should determine that an
analysis conforming to the guidance in Sections C.3.2.1 to C.3.2.4 of RG 1.155
demonstrates the capability to achieve and maintain safe shutdown until ac power is
restored. The AAC approach involves the provision of an independent AAC power
source. If this approach is selected, the review should ensure that the design conforms
to the recommendations in Sections C.3.2.5, C.3.3, and C.3.5 and Appendices A and B
to RG 1.155, as described in Subsection III.3 below. Except for passive ALWR plant
designs (such as the AP1000), an AAC power source that is fully capable of powering
one complete set of normal shutdown loads should be the preferred method of
demonstrating compliance with 10 CFR 50.63 (Ref. 25) for new applications licensed
under 10 CFR Part 52 (Ref. 5). These plants cannot use the ac-independent approach
(i.e., coping with battery power).

The determination of the plant=s ability to cope with an SBO should be based on the
following general criteria and baseline assumptions (Refs. 7 and 38):

A. Because of the presence of substantial decay heat, events initiated from


100-percent power bound the potential for core damage from an SBO.
Therefore, the coping analysis should be performed assuming that the SBO event
occurs while the reactor is operating at 100-percent rated thermal power and has
been at this power level for at least 100 days.

B. Immediately before the postulated SBO event, the reactor and supporting
systems are within normal operating ranges for pressure, temperature, and water
level. All plant equipment is either normally operating or available from the
standby state.

C. It is assumed that a reasonable set of operator actions will occur to mitigate the
effects of an SBO and recover from the event. Operator actions are assumed to
follow plant operating procedures for the underlying symptoms or identified event
scenario associated with an SBO. Operator actions to strip nonessential loads
from batteries should not be credited to commence during the first 30 minutes of
the SBO event.

D. Actions specified in procedures for SBO are predicated on the use of


instrumentation and controls powered by vital buses supplied by station batteries.

E. The dc power needs for SBO may be estimated using the same methodology for
which the plant is licensed; Institute for Electrical and Electronics Engineers
(IEEE) Std. 485 (Ref. 14) describes the generally accepted methodology. For
passive plant designs (e.g., AP1000), where steady-state loads should operate
for up to 72 hours under SBO conditions, the staff considers the steady-state

8.4-10 Revision 1- May 2010


loading condition to be the governing factor for determining the Class 1E battery
size (Refs. 28 and 34).

F. Since the capacity of battery storage varies with electrolyte temperature,


calculations should assume the lowest temperature normally expected of the
battery.

G. The capability of all systems and components necessary to provide core cooling
and decay heat removal following an SBO should be determined, including
station battery capacity, condensate storage tank (CST) capacity, compressed air
capacity, and instrumentation and control needs. The non-safety systems
identified in Appendix A to RG 1.155 are acceptable to the NRC staff for
responding to an SBO.

H. The ability to maintain adequate reactor coolant system inventory to ensure that
the core is cooled should be evaluated, taking into consideration shrinkage,
leakage from pump seals, and inventory loss from letdown or other normally open
lines dependent on ac power for isolation.

I. The design adequacy and capability of equipment needed to cope with an SBO
for the required duration and recovery period should be addressed and evaluated
as appropriate for the associated environmental conditions. This should include
consideration of the following:

i. Potential failures of equipment necessary to cope with the SBO

ii. Potential environmental effects on the operability and reliability of


equipment necessary to cope with the SBO, including possible effects of
fire protection systems

iii. Potential effects of other hazards, such as weather, on SBO response


equipment (e.g., auxiliary equipment to operate onsite buses or to recover
EDGs and other equipment as needed)

iv. Potential habitability concerns for those areas that would need operator
access during the SBO and recovery period

J. Equipment will be considered acceptable for SBO temperature environments if an


assessment has been performed that provides reasonable assurance that the
necessary equipment will remain operable.

K. In general, equipment necessary to cope with an SBO during the first 8 hours
should be available on site. Consideration should be given to the availability and
accessibility of offsite equipment in the time required, including consideration of
weather conditions likely to prevail during a LOOP.

L. Consideration should be given to timely operator actions inside or outside the


control room that would increase the length of time that the plant can cope with
an SBO, provided it can be demonstrated that these actions can be carried out in
a timely fashion. For example, if station battery capacity is a limiting factor in

8.4-11 Revision 1- May 2010


coping with an SBO, shedding nonessential loads on the batteries could extend
the time until the battery is depleted. If load shedding or other operator actions
are considered, the plant-specific technical guidelines and emergency operating
procedures should incorporate corresponding procedures. Load shedding should
not commence during the first 30 minutes of the SBO event.

M. The ability to maintain appropriate containment integrity should be addressed.


Appropriate containment integrity for SBO means that adequate containment
integrity is ensured by providing the capability, independent of the preferred and
blacked-out unit=s onsite EAC power supplies, for valve position indication and
closure for containment isolation valves that may be in the open position at the
onset of an SBO. This does not include the following valves:

i. Valves normally locked closed during operation

ii. Valves that fail closed on a loss of power

iii. Check valves

iv. Valves in nonradioactive closed-loop systems not expected to be


breached in an SBO (not including lines that communicate directly with
containment atmosphere)

v. Valves of less than 3-inch nominal diameter

3. AAC Power Sources. One acceptable means of complying with the requirements in
10 CFR 50.63 involves the provision of an AAC source of sufficient capacity, capability,
and reliability (for operation of all systems necessary for coping with SBO and for the
time necessary to bring the plant to, and maintain it in, safe-shutdown condition
(non-DBA)) that will be available on a sufficiently timely basis.

For new ALWR plants, the Commission has established a policy (Ref. 23) that such
plants should have an AAC power source of diverse design and capable of powering at
least one complete set of normal shutdown loads. In SECY-94-084 and SECY-95-132
(Ref. 26), the Commission modified this criterion for ALWRs that use passive safety
systems. Specifically, an AAC power source is not necessary for passive plant designs
(such as the AP1000) that (a) do not need ac power to perform safety-related functions
for 72 hours following the onset of an SBO and (b) meet the guidelines in Section
C.IV.10 of RG 1.206 regarding RTNSS.

8.4-12 Revision 1- May 2010


EDGs in excess of minimum redundancy criteria for NPP onsite power systems, nearby
or onsite gas turbine generators, portable or other available compatible diesel
generators, or hydrogenerators may serve as AAC power sources. The design should
meet the recommendations in Sections C.3.2.5, C.3.3, and C.3.5 and Appendices A and
B to RG 1.155. It is acceptable for AAC power sources to be normally used for other
purposes and they do not need to be solely dedicated to use as an AAC power source.
However, the requisite procedures and interface agreements need to be in place such
that the AAC power source is available in an SBO event.

The AAC power source should be available in a timely manner after the onset of SBO
and have provisions to be manually connected to one or all of the redundant safety
buses as necessary to power all equipment necessary to achieve and maintain safe
shutdown (non-DBA). The time necessary for making this equipment available should
not exceed 1 hour and should be demonstrated by test. If tests can show the AAC power
source to be available in less than 10 minutes, no coping analysis is needed. Otherwise,
a coping analysis should be performed for the duration from the onset of the SBO until
the AAC power source or sources are started and lined up to operate all equipment
necessary to achieve and maintain safe shutdown. The phrase Aavailable within 10
minutes of the onset of SBO@ means that circuit breakers necessary to bring power to
safe-shutdown buses can be actuated in the control room within that period.

To ensure that the requirements of 10 CFR 50.63 regarding the AAC source are
satisfied, the staff will evaluate and verify the applicant=s submittal on SBO regarding the
following issues:

A. In accordance with Section C.3.3.5 of RG 1.155, the AAC power source should
be capable of supplying power, as necessary, to all loads that are necessary for
safe shutdown (non-DBA) in the event of an SBO at any nuclear unit it is credited
to serve. The AAC power source should have sufficient capacity to operate the
systems necessary for coping with an SBO for the time necessary to bring and
maintain the plant in a safe-shutdown condition. The plant systems, functions,
and features discussed in Sections C.2 and C.3.3.1 to C.3.3.4 of RG 1.155
should be appropriately addressed as safe-shutdown non-DBA loads (including
loads associated with any alternative or added capacity battery charging, water,
or air sources to handle SBO). For new applications, the AAC source should be
of diverse design (with respect to onsite sources); have adequate capacity,
independence, and reliability; and have capability for powering at least one
complete set of normal safe-shutdown loads. At sites where units share onsite
emergency sources, the AAC power sources should have the capacity and
capability to ensure that all units can be brought to and maintained in a
safe-shutdown (non-DBA) condition.

B. The staff reviews the independence of the AAC power source under SRP Section
8.2 to verify that the AAC source (or sources) will not adversely affect the
preferred power system or its specified functions, and will not adversely affect the
onsite power system or its specified safety functions. The review should
determine that sufficient information has been provided to demonstrate adequate
AAC source independence as follows:

8.4-13 Revision 1- May 2010


i. With respect to independence between the AAC power source used for
SBO and the preferred and onsite power systems, electrical ties between
these systems and the physical arrangement of the interface equipment
should minimize the potential for the loss of any system (i.e., preferred,
onsite, or AAC) preventing access to any other system and the potential
for such a loss to cause further failures in other systems.

ii. An acceptable design should not have the AAC power source normally
directly connected to the preferred power system or to the blacked-out
unit=s onsite EAC power system. No single point of vulnerability should
exist whereby a single active failure or weather-related event could
simultaneously fail the AAC and preferred power sources or the AAC and
onsite sources. The power sources should have minimum potential for
common failure modes.

iii. The AAC components should be physically separated and electrically


isolated from safety-related components or equipment, as specified in the
separation and isolation criteria applicable to the unit=s licensing basis and
the guidelines in Appendix A to RG 1.155. Based upon compliance with
all relevant independence criteria and guidelines, it should be
demonstrated that provisions for the AAC source will not, at any time,
adversely affect the functioning of offsite and/or Class 1E onsite power
systems. Also, failure of the AAC power components should not
adversely affect the Class 1E ac power systems.

iv. Careful examination should be made of the physical arrangement of


circuits and incoming source breakers (to the affected Class 1E bus or
buses), separation and isolation provisions (control and main power),
permissive and interlock schemes proposed for source breakers, source
initiation/transfer logic, Class 1E load shedding and sequencing schemes
that could affect AAC source ability to power safe-shutdown loads, source
lockout schemes, and bus lockout schemes.

C. The AAC power source(s) is not automatically loaded for SBO but should have
provisions to be manually connected to one or all of the redundant safety buses
as necessary.

D. Plant staff in the control room monitor the performance of the AAC power source.
As a minimum, monitoring should include the voltage, current, frequency, and
circuit breaker position.

E. The AAC source components are enclosed within structures that conform to the
Uniform Building Code. Electrical cables connecting the AAC power source to
the shutdown buses are protected against the events that affect the preferred ac
power system. Buried cables or other appropriate methods can be used to
accomplish this.

F. Nonsafety-related AAC power source(s) and associated dedicated dc system(s)


should meet the QA guidance in Section 3.5, Appendix A, and Appendix B to
RG 1.155.

8.4-14 Revision 1- May 2010


G. The AAC power system is equipped with a dedicated dc power system that is
electrically independent from the blacked-out unit=s preferred and Class 1E power
systems and is of sufficient capability and capacity for operation of dc loads
associated with the AAC source for the maximum necessary duration of AAC
source operation.

H. The AAC power system is equipped with a starting system (and motive energy
source for starting) that is independent from the blacked-out unit=s preferred and
Class 1E ac power systems.

I. The AAC power system is provided with a fuel supply that is separate from the
fuel supply for the onsite EAC power system. A separate day tank, supplied from
a common storage tank, is acceptable if the fuel is sampled and analyzed using
methods consistent with applicable standards before its transfer to the day tank.

J. If the AAC power source and an emergency onsite ac power source are identical,
procedures are provided to ensure that active failures of each identical power
source will be evaluated for common cause applicability and that corrective action
has been taken to reduce subsequent failures.

K. The AAC power system is capable of operating during and after an SBO without
any support system receiving power from the preferred power supply or the
blacked-out unit=s EAC power sources. The capability of the AAC to start on
demand depends on the availability of the necessary support systems to fulfill
their required function. These support systems may need varying combinations
of dc or ac power for varying periods to maintain operational readiness.
Information Notice (IN) 97-21 (Ref. 17) discusses two examples of a failure of the
AAC to start on demand because of an extended loss of auxiliary electrical power
sources.

L. The portions of the AAC power system subjected to maintenance activities


are/will be tested before returning the AAC power system to service.

M. Plant-specific technical guidelines and emergency operating procedures will be


implemented (or are in place, as applicable) that identify those actions necessary
for placing the AAC power source in service.

N. The AAC power system will be inspected, maintained, and tested periodically to
demonstrate operability and reliability. The reliability of the AAC power system
should meet or exceed 95 percent as determined in accordance with NSAC-108
(Ref. 37) or equivalent methodology.

O. Where EDGs are identified as AAC power sources, they should meet the
following criteria:

i. At single unit sites, any EAC power source(s) in excess of the number
required to meet the minimum redundancy criteria (i.e., single failure) for
safe shutdown may be assumed to be available. These EAC power
sources may be designated as AAC power sources, provided the
guidelines identified in Section C.3.3.5 of RG 1.155 are met.

8.4-15 Revision 1- May 2010


ii. A single unit that needs one EAC source to place the plant in safe
shutdown needs one redundant EAC power source. For SBO, both the
EAC power source and the redundant EAC power source are unavailable.
An EDG may be designated as an AAC power source only if that EDG is
neither the necessary EAC power source nor the redundant EAC power
source. Therefore, a single unit requiring one EAC source for safe
shutdown should have at least three EDGs, with one EDG that may be
designated as the AAC power source meeting RG 1.155 guidance for
AAC power sources.

iii. At multiunit sites, where the combination of EAC sources exceeds the
minimum redundancy criteria (on a per-nuclear-unit basis) for normal safe
shutdown of all units, the excess EAC power sources may be used as
AAC power sources, provided they meet the AAC power source guidance
in Section C.3.3.5 of RG 1.155. If no EAC power source in excess of the
minimum redundancy criteria remains, the occurrence of SBO must be
assumed for all of the units.

iv. When an SBO occurs at one unit of a multiunit site, the EAC power
source(s) and the redundant EAC power source(s) are unavailable. An
SBO on one unit does not assume a concurrent single failure; however,
the remaining unit(s) should still meet the normal operating single failure
criteria. Therefore, an EDG could be designated as an AAC only if (1) the
EDG is neither the necessary EAC power source nor the redundant EAC
power source for the unit experiencing the SBO and (2) the EDG is not
necessary as an emergency or redundant EAC power source for the
remaining units. Where an EDG is used as an AAC, it is desirable that
the EDG be connectable to all buses essential for normal safe shutdown.
Review of the applicant=s station onsite ac power system should
determine whether such a capability exists.

v. Multiunit sites may not use EDGs with 1-out-of-2 (shared) and 2-out-of-3
(shared) ac power configurations as AAC power sources.

vi. For EDGs used as an AAC source, the engine support systems should
conform with the relevant criteria used to evaluate them under SRP
Sections 9.5.4 through 9.5.8.

4. Procedures and Training. The staff will review procedures and training to ensure that
they conform to the guidance in Sections C.1.3, C.2, and C.3.4 and Appendix B to
RG 1.155 and include all operator actions necessary to do the following:

8.4-16 Revision 1- May 2010


A. Cope with the occurrence of an SBO for the specified coping duration during all
modes of plant operation and include actions necessary to place AAC power
sources in service (if used) and maintain acceptable environmental conditions for
equipment necessary to mitigate the event. Procedures developed to cope with
an SBO should be integrated with the plant-specific technical guidelines and
emergency operating procedures developed using the emergency operating
procedure upgrade program established in response to Supplement 1 of
NUREG-0737. The task analysis portion of the emergency operating procedure
upgrade program should include an analysis of instrumentation adequacy during
an SBO.

B. Restore standby (Class 1E) power sources when the EAC power system is
unavailable.

C. Restore offsite power sources and use of nearby power sources (which may
include nearby or onsite gas turbine generators, portable generators,
hydrogenerators, and black start fossil power plants) in the event of a LOOP.
As a minimum, the reviewer should consider the following potential causes for
a LOOP:

i. Grid undervoltage and collapse.

ii. Weather-induced power loss.

iii. Preferred power distribution system faults that could result in the loss of
normal power to essential switchgear buses. This includes such failures
as distribution system hardware, switching and maintenance errors, and
lightning-induced faults.

D. Actions necessary to restore normal long-term core cooling/decay heat removal


once ac power is restored.

In addition, the reviewer should determine that plant operating procedures developed to respond
to an SBO event are consistent with the following general guidelines:

E. The procedure should specify actions necessary to assure that shutdown


equipment (including support systems) necessary in an SBO can operate without
ac power.

F. The procedure should recognize the importance of decay heat removal systems
(auxiliary feedwater, high-pressure coolant injection, high-pressure core spray,
reactor core isolation cooling) during the early stages of the event and direct
operators to invest appropriate attention to ensuring their continued reliable
operation throughout the event.

G. Plant operating procedures should identify the sources of potential inventory loss
and specify actions to prevent or limit significant loss.

H. Plant operating procedures should ensure the prompt establishment of a flowpath


for makeup flow from the CST to the steam generator/nuclear boiler and identify

8.4-17 Revision 1- May 2010


backup sources to the CST in order of intended use. In addition, plant operating
procedures should specify clear criteria for transferring to the next preferred
source of water.

I. The procedure should identify individual loads that need to be stripped from the
plant dc buses (both Class 1E and non-Class 1E) to conserve dc power.

J. Plant operating procedures should specify actions to permit appropriate


containment isolation and safe-shutdown valve operations while ac power is
unavailable.

K. Plant operating procedures should identify the portable lighting necessary for
ingress and egress to plant areas containing shutdown or AAC equipment
requiring manual operation.

L. Plant operating procedures should consider the effects of ac power loss on area
access, as well as the need to gain entry to other locked areas where remote
equipment operation is necessary.

M. Plant operating procedures should consider the effects of a loss of ac power on


communications capabilities, including the potential for a loss of communications
with offsite agencies.

N. Plant operating procedures should consider the loss of heat tracing effects for
equipment necessary to cope with an SBO.

O. To provide assurance that the NPP operator will be kept aware of changes in the
plant switchyard and offsite power grid, plant or site procedures should establish
appropriate communication protocols between the NPP and its transmission
system operator (Ref. 15). With regard to SBO, these protocols should aid the
operator in determining the following:

i. The performance of grid-risk-sensitive maintenance activities (such as


surveillances, postmaintenance testing, and preventive and corrective
maintenance) that could increase the likelihood of an SBO or impact the
plant=s ability to cope with an SBO, such as out-of-service risk-significant
equipment (e.g., an EDG, a battery, a steam-driven pump, an AAC power
source)

ii. The availability of local power sources and transmission paths that could
be made available to resupply the plant following a LOOP event

5. QA and Specification Guidance for SBO Equipment That Is Not Safety-Related. The
staff will review QA activities and specifications for non-safety-related equipment used to
meet the requirements of 10 CFR 50.63 to ensure that they conform to the
recommendations in Section C.3.5 and Appendix A to RG 1.155. The review should also
determine that systems and equipment used to meet the requirements of 10 CFR 50.63
conform to the system and station equipment specification recommendations of
Appendix B to RG 1.155. The NRC staff will accept the nonsafety systems identified in
Appendix B to RG 1.155 for responding to an SBO.

8.4-18 Revision 1- May 2010


Applicants that propose a design that includes passive safety systems should define the
active systems that are relied upon for defense in depth and that are necessary to meet
passive ALWR plant safety and investment protection goals. The agency describes this
process, referred to as RTNSS, in SECY-94-084 and SECY-95-132. The staff reviews
QA controls applicable to the SSCs within the RTNSS process under SRP Section 17.5.

6. For review of a DC application, the reviewer should follow the above procedures to verify
that the design, including requirements and restrictions (e.g., interface requirements and
site parameters), set forth in the final safety analysis report (FSAR) meets the
acceptance criteria. DCs have referred to the FSAR as the design control document.
The reviewer should also consider the appropriateness of identified COL action items.
The reviewer may identify additional COL action items; however, to ensure these COL
action items are addressed during a COL application, they should be added to the DC
FSAR.

For review of a COL application, the scope of the review is dependent on whether the
COL applicant references a DC, an early site permit (ESP) or other NRC approvals (e.g.,
manufacturing license, site suitability report or topical report).

For review of both DC and COL applications, SRP Section 14.3 should be followed for
the review of ITAAC. The review of ITAAC cannot be completed until after the
completion of this section.

IV. EVALUATION FINDINGS

The reviewer verifies that the applicant has provided sufficient information and that the review
and calculations (if applicable) support conclusions of the following type to be included in the
staff's safety evaluation report (SER). The reviewer also states the bases for those conclusions.

On the basis of the staff=s detailed review and evaluation of the station blackout
capability described in the SAR for (Facility) , the staff concludes that the
(applicant/licensee) has appropriately evaluated the facility against the guidelines
of RG 1.155 and this SRP section. Alternatives to or differences from these
recommendations, as described in the applicable section of this safety evaluation,
are acceptable. The SAR acceptably demonstrates that the plant is in
compliance with the provisions of GDCs 17 and 18 and 10 CFR 50.63, as they
relate to the capability to achieve and maintain safe shutdown (non-DBA) in the
event of a station blackout.

Accordingly, the staff concludes that the plant design is acceptable and meets the
requirements of GDCs 17 and 18 of Appendix A to 10 CFR Part 50, as they relate
to the requirements of 10 CFR 50.63 and 10 CFR 50.65.

For DC and COL reviews, the findings will also summarize the staff=s evaluation of requirements
and restrictions (e.g., interface requirements and site parameters) and COL action items relevant
to this SRP section.

In addition, to the extent that the review is not discussed in other SER sections, the findings will
summarize the staff's evaluation of the ITAAC, including design acceptance criteria, as
applicable.

8.4-19 Revision 1- May 2010


V. IMPLEMENTATION

The staff will use this SRP section in performing safety evaluations of DC applications and
license applications submitted by applicants pursuant to 10 CFR Part 50 or 10 CFR Part 52.
Except when the applicant proposes an acceptable alternative method for complying with
specified portions of the Commission=s regulations, the staff will use the method described
herein to evaluate conformance with Commission regulations.

The provisions of this SRP section apply to reviews of applications submitted 6 months or more
after the date of issuance of this SRP section, unless superseded by a later revision.

VI. REFERENCES

8. 10 CFR 50.2, ADefinitions.@

9. 10 CFR 50.63, ALoss of All Alternating Current Power.@

10. 10 CFR Part 50, Appendix A, GDC 17, AElectric Power Systems.@

11. 10 CFR Part 50, Appendix A, GDC 18, AInspection and Testing of Electric Power
Systems.@

12. 10 CFR Part 52, AEarly Site Permits; Standard Design Certifications; and Combined
Licenses for Nuclear Power Plants.@

13. RG 1.9, ASelection, Design, Qualification, and Testing of Emergency Diesel Generator
Units Used as Class 1E Onsite Electric Power Systems at Nuclear Power Plants.@

14. RG 1.155, AStation Blackout.@

15. RG 1.160, AMonitoring the Effectiveness of Maintenance at Nuclear Power Plants.@

16. RG 1.182, AAssessing and Managing Risk Before Maintenance Activities at Nuclear
Power Plants.@

17. SRP Section 8.1, Table 8-1, AAcceptance Criteria for Electric Power.@

18. SRP Section 8.2, AOffsite Power.@

19. IEEE Standard 308-2001, AIEEE Standard Criteria for Class 1E Power Systems for
Nuclear Power Generating Stations.@

20.
21. IEEE Standard 765-1983, AIEEE Standard for Preferred Power Supply (PPS) for Nuclear
Power Generating Stations.@ (2002 is latest revision)

22. IEEE Standard 485-1987, ARecommended Practice for Sizing Lead-Acid Batteries for
Stationary Applications.@

23. Generic Letter 2006-02, AGrid Reliability and the Impact on Plant Risk and the Operability
of Offsite Power,@ February 1, 2006.

8.4-20 Revision 1- May 2010


24. Information Notice 97-05, AOffsite Notification Capabilities,@ February 27, 1997.

25. Information Notice 97-21, AAvailability of Alternate AC Power Source Designed for
Station Blackout Event,@ April 18, 1997.

26. Information Notice 98-07, AOffsite Power Reliability Challenges from Industry
Deregulation,@ February 27, 1998.

27. Information Notice 2000-06, AOffsite Power Voltage Inadequacies,@ March 27, 2000.

28. Information Notice 2006-06, ALoss of Offsite Power and Station Blackout Are More
Probable During Summer Period,@ March 3, 2006.

29. Regulatory Issue Summary 2000-24, AConcerns About Offsite Power Voltage
Inadequacies and Grid Reliability Challenges Due to Industry Deregulation,@
December 21, 2000.

30. Regulatory Issue Summary 2004-05, AGrid Reliability and the Impact on Plant Risk and
the Operability of Offsite Power,@ April 15, 2004.

31. SECY-90-016, AEvolutionary Light Water Reactor (LWR) Certification Issues and Their
Relationship to Current Regulatory Requirements,@ January 12, 1990. Approved in the
staff requirements memorandum dated June 26, 1990.

32. SECY-91-078, AEPRI=s Requirements Document and Additional Evolutionary LWR


Certification Issues,@ 1991. Approved in the staff requirements memorandum dated
August 15, 1991.

33. SECY-94-084, APolicy and Technical Issues Associated with the Regulatory Treatment of
Non-Safety Systems in Passive Plant Designs,@ March 28, 1994. Approved in the staff
requirements memorandum dated June 30, 1994.

34. SECY-95-132, APolicy and Technical Issues Associated with the Regulatory Treatment of
Non-Safety Systems (RTNSS) in Passive Plant Designs.@ Approved in the staff
requirements memorandum dated June 28, 1995.

35. NRC Memorandum from D. Crutchfield to File, Subject: Consolidation of SECY-94-084


and SECY-95-132, July 24, 1995. SECY-94-084 was approved in the staff requirements
memorandum dated June 30, 1994. SECY-95-132 was approved in the staff
requirements memorandum dated June 28, 1995.

36. RG 1.206 ACombined License Applications for Nuclear Power Plants (LWR Edition),@
June 30, 2006.

37. NUREG-0933, AA Prioritization of Generic Safety Issues,@ Supplement 29, June 2005.

38. NUREG-1032, AEvaluation of Station Blackout Accidents at Nuclear Power Plants,@ June
1998.

39. NUREG-1776, ARegulatory Effectiveness of the Station Blackout Rule,@ August 2003.

8.4-21 Revision 1- May 2010


40. Electric Power Research Institute ALWR Utility Requirements Document, Volume II,
AEvolutionary Plants,@ Chapter 11, AElectric Power Systems,@ Revision 6, December
1993.

41. NUREG-1784, AOperating Experience AssessmentCEffects of Grid Events on Nuclear


Power Plant Performance,@ December 2003.

42. NUREG-1793, AFinal Safety Evaluation Report Related to Certification of the AP1000
Standard Design,@ September 2004.

43. NUREG/CR-6890, AReevaluation of Station Blackout Risk at Nuclear Power Plants -


Analysis of Loss of Offsite Power Events: 1986-2004,@ December 2005.

44. Temporary Instruction 2515/120, AInspection of Implementation of Station Blackout Rule.@

45. NSAC-108, AThe Reliability of Emergency Diesel at U.S. Nuclear Power Plants,@
September 1986.

46. NUMARC-8700, AGuidelines and Technical Bases for NUMARC Initiatives Addressing
Station Blackout in Light Water Reactors,@ Revision 0, November 1997.

PAPERWORK REDUCTION ACT STATEMENT

The information collections contained in the Standard Review Plan are covered by the requirements of 10 CFR Part 50 and
10 CFR Part 52, and were approved by the Office of Management and Budget, approval number 3150-0011 and 3150-0151.

PUBLIC PROTECTION NOTIFICATION

The NRC may not conduct or sponsor, and a person is not required to respond to, a request for information or an information
collection requirement unless the requesting document displays a currently valid OMB control number.

8.4-22 Revision 1- May 2010


SRP Section 8.4
"Station Blackout"
Description of Changes

Revision 1 to SRP Section 8.4 updates Revision 0 of this section, dated March 2007, to reflect
the following changes:

1. This SRP section is administratively updated by the Office of New Reactors, per request
from Juan D. Peralta, Branch Chief, Quality and Vendor Branch 1, Division of Construction,
Inspection, and Operational Programs, memorandum dated February 17, 2010 (ADAMS
Accession No. ML10090148).

8.4-23 Revision 1- May 2010

You might also like