BS-1632, 1 1 BS-634, BS - 636: Conventional Fire Alarm Panels 2, 4 and 6 Zone
BS-1632, 1 1 BS-634, BS - 636: Conventional Fire Alarm Panels 2, 4 and 6 Zone
BS-1632, 1 1 BS-634, BS - 636: Conventional Fire Alarm Panels 2, 4 and 6 Zone
Thank you for purchasing this product of Olympia Electronics. A European manufacturer.
GENERAL
The family of fire detection panels consist of 3 types (2, 4 and 6 zone) with identical operation and indications. The panels have
2 independent siren outputs, Alarm, Fault Relay and a programmable AUX relay. The required batteries for the panels are two
A-920 (12V/2.6Ah). All functions and indications are according to European Norms EN 54-2 and EN 54-4.
Top cover
retaining screws
Mounting holes
MODE selection
microswitch
Relay outputs
connection terminals
Battery compartment Extra earth
two Α-920 Mounting hole
terminals
Below is the indicator “POWER” which is on when the panel is working and blinks when there is mains supply failure.
On the right of the “POWER” indicator is the “Delays ON” indicator which shows if the delays of the output are enabled
or disabled.
Below the `General` indicator group we can find the indication group called `Fault`. The 'Battery ' LED and 'Mains' LED
in combination, show us faults concerning the power supply. These combinations are shown in the panel below.
Lack of Battery Battery Battery Charger Bad
AC voltage Overcharging Discharged Absent Error Battery
The 'System LED lights to indicate a problem with the main processor unit (System fault).
The LEDs marked 'Siren1' and 'Siren2' correspond to the siren outputs. If a siren out has a short circuit or open circuit then
the corresponding LED will blink. If a siren is disabled the corresponding LED will light.
The panel is controlled/ operated using the six numeric keys (1 to 6) found on the front panel. When a key is pressed a short
tone is issued.
The panel has three access levels.
Access level 1:
has all the functions that can be done directly from the user without using a code. These operations are:
Buzzer silence / Buzzer reactivation: If an alarm of fault condition is issued then the internal buzzer will sound. Pressing
the key "1" will silence the buzzer. ( The buzzer sounds periodically once every minute.) Pressing this key again will reactive
the buzzer.
Lamp test: Pressing the key "2" a lamp test is conducted by lighting the LEDs. The panel then returns to normal operation.
The above tests can be conducted only if the panel is in quiescent state (No fault or alarm conditions).
Override Delays: If an alarm occurs and the delays are active the user can overrride the delays by pressing the key “4" .
The output will be immediately activated.
Siren Silence: When an alarm is issued and we want to silence the sirens then we must enter the user code
( 34 ) and then the keys '5' and '5'. The sirens are silenced but the internal buzzer continues to sound. The panel remains
in normal operation. A new alarm from another zone will resound the sirens. To resound the sirens press again the same
code.
Panel Reset: When an alarm or fault condition has occurred and we want to reset the panel we must enter the user code
(34) and then the keys '5' and '6’. The panel lights all LEDs in sequence and then enters normal operation.
Zone enable/disable: If we want to disable the operation of specific zones then we must enter the user code
( 34 ) and then the keys number '5' and '4'. The LED marked 'General disable' start to blink, and if a zone is disabled the
corresponding 'Fault' LED lights to indicate this. Using the keys 1, 2, 3, 4, 5 and 6 we can enable or disable the respective
zones. The disabled zones light the corresponding LED. The panel exits this mode if no key is pressed for more than 30
seconds. The panel then conducts an automatic RESET and enters normal operation mode. Disabled zones does not
give alarm or fault condition. If we have disabled zones then this is indicated with the indicators 'General disable' and the
corresponding Disable LED zone and the buzzer sounds once every minute.
Siren enable/disable: If we want to disable the operation of specific sirens we must enter the code (34) and then the
keys '6' and ‘6’. The LED marked 'General Test' start to blink, and if a siren is disabled Siren1 LED lights for siren 1 and
Siren2 LED lights for the siren 2. Using the keys 1 and 2 we can enable or disable the respective sirens. The disabled
sirens have a LED lighted. The panel exits this mode if no key is pressed for more than 30 seconds. The panel then
conducts an automatic RESET and enters normal operation mode. All disabled sirens are supplied with the proper
voltage but the panel can not enable them or read their condition. If we have disabled sirens then this is indicated with the
indicator 'General disable' and the buzzer sounds once every minute.
Delays ON/OFF: If we want to disable the delays of the outputs. We must enter the code (34) and then the keys '6' and
‘4’. Then the delays will be disable, the LED marked “Delays ON” will turn off. To enable the delays we must press again
the code.
Access level 3:
These functions are implemented during the installation and need the technical code to be accessed. The technical code is
"364", it is the same for all panels and can not be changed. These functions can be implemented using the technical code
are activation methods used for the relays and can be done only if the panel has not issued an alarm or fault condition.
These functions are ancillary and not required by the EN 54-2.These methods of programming are:
AUX RELAY programming: If we want to program the operation behaviour of the AUX RELAY we must enter the technical
code ( 364 ) and then press the key '5'. The 'General fault' and 'General alarm' LEDs start to blink. The Alarm zone LEDs
and the fault LED zone show the way the AUX RELAY . If the Alarm led of the zone is on then we have logic AND for the aux
relay activation. If the fault led of the zone is on then we have logic OR for the aux activation.
For example if Alarm Zone 1 and 2 is on and Fault Zone 3 and 4 is on, then the relay will be activated when Z1 and Z2 is in
alarm condition or Z3 or Z4 are in alarm condition
To change the state of each zone, press the corresponding number each time.
In order to exit this programming mode and to store the settings in memory do not press any key for more than 30 seconds.
This system will conduct an automatic RESET and will enter normal operation mode.
Alarm zone 1 LED ON LED Blink LED Off LED Off LED Off LED Off
Fault zone 1 LED Off LED Off LED On LED Blink LED Off LED Off
Fault zone 2 LED Off LED Off LED Off LED Off LED On LED Blink
RESOUND sirens: It is possible to configure to automatically resound the sirens following an alarm in another zone. You
must enter the technical code (364) and then press the key '4'.
The 'General fault' ,'General Disable' and 'General alarm' LEDs start to blink. The Alarm LED of zone 2 led is off the sirens
resound following an alarm in another zone else if the led is on the sirens does not resound. By pressing the key '5' you can
change the configuration.
Programming the delay of general relay (AUX RELAY). If you want to program the delay of the AUX RELAY must enter
the technical code ( 364 ) and then press '6' . The LED " General fault " ," General Alarm " and “DELAYS ON” begin to blink .
The indicative Zone " Alarm" and " Fault LED” indicates delay activation of “AUX RELAY”.
To change the mode press ' 1 ' 2' , ' 3' and '4'. To exit the programming mode and store the settings in memory , press the
button <5 > . The system will automatically RESET and will enter normal operation.
Below is a table that summarizes all the code and corresponding functions.
Code Function
3-4-4-4 Evacuate
3-4-5-4 Enable/Disable Zones
3-4-5-5 Silence/Resound Sirens
3-4-5-6 Reset
3-4-6-4 Delays ON/OFF
3-4-6-6 Enable/Disable Sirens
By default each zone terminal block has a preinstalled terminal resistor (8Κ2). This resistor must be removed and
installed on the last device of the zone or is left connected on the zone terminals if the zone is not used. The connections
to all the zones are identical. What is shown in figures 2, 3 and 4 for zone 1 is valid for all the zones.
The total number of connected devices per zone is 20.
All cable zones must be insulated, to earth ground, to meet EMC requirements.
The cable length for each zone must not exceed the 1.5 kilometres with a cross section cable of 1.5mm².
-R I -R I -R I -R I
N
N
+L
+L
+L
+L
Ζ1
+R
+R
+R
+R
IN-
IN-
IN-
IN-
OU
OU
OU
UT
UT
UT
UT
U
T T T T
O
O
-L -L -L -L
Ζ2
8Κ2
R
Terminal
resistor
BS-572
remote
LED
Figure 2. Connecting 4 detector bases to zone 1. Each base can accept BS-655, BS-660 or BS-657
detectors. A remote indication LED BS-572 is connected to one of the detectors.
Detector Detector
base base Break-glass Break-glass
call point call point
BS-536 BS-536
-R I -R I
N
N
+L
+L
Ζ1
R
+R
IN-
IN-
OUT IN OUT IN
T+
O
UT
U
U
U
T T
O
-L -L
Ζ2
8Κ2
Terminal
resistor
Figure 3. Connecting 2 call points BS-536 and 2 detector bases to the same zone.
24V_M
1 0- 3 0V ZO NE N O C N C 1 0 - 30 V Z O N E N O C N C 1 0 -30 V Z O N E N O C N C
Ζ1
8Κ2
Terminal
resistor
Ζ2
Figure 4. Connecting 3 Gas detectors BS-685 or BS-686. Besides the connections to the zone terminals
these detectors must also be connected to the terminals 24V_M in order to be supplied with power.
BS-531 BS-531
Siren with Siren with Terminal
Beacon Beacon Resistor
8Κ2
ALARM1 ALARM2
Terminal
Resistor 8Κ2
Figure 5. Connecting 2 BS-531 sirens to the ALARM 2 output. This connection requires polarity.
Besides the terminals that were described up to now the panel also has the following outputs :
24V_M: A 24VDC output that is interrupted in the event of a panel reset. It is mainly used for powering gas
detectors or other devices that need an interrupted power supply when the panel is resetting. If this output
is short circuited then the LED marked 'General fault' is lighted.
24V_P: A 24VDC power output that is not interrupted in the event of a reset. It can be used to power
electromagnetic door latches.
Relay Alarm : Voltage free relay contacts are activated when there is an alarm condition.
Relay Fault : Voltage free relay contacts are deactivated when there is an fault condition.
Relay AUX : Voltage free relay contacts that by default when one zone is in alarm condition.
ATTENTION: The relays are rated at 30VDC and 5A maximum. No 230VAC signals can be connected
to these relays.
BS-510/24 BS-510/24
24V_P
24V DC 24V DC
NO C NC NO C NC
ALARM FAULT
Fire Detection
Panel
+ - NO C NC NO C NC
Installation
The installation of the panel must be carried out by qualified personnel only.
Disconnect power before servicing.
Never insert or remove boards or componets with the power on.
During installation use grounded antistatic wrist band to protect this equipment form ESD.
The panel must be installed permanetly. It is not allowed to connect the device directly to any socket-
outlet.
Cabling
In order to meet EMC requirements , connections of peripherals to the panel must be done using
shielded cables.
Each screen or shield braid must properly be connected to the earth terminal block provided, thus
ensuring the shortest posible path.
The maximum conductor diameter size, which can be used, is 2,5mm²
Battery connection
The battery compartment has the appropriate dimensions for Α-920
batteries of Olympia Electronics.
The charging unit on PCB is also calculated for the specific batteries.
Replace them only with batteries of the same type.
From the PCB, are connected two battery wires with a special terminal on the
edge. They must be connected to the two battery poles. Connect the black wire
to the negative pole (marked (-) or a black mark), the red wire to positive pole
(marked (+) or a red mark) and connect the included wire for the link as showed Link
in the side figure.
1 cm
Figure 8. Panels connection with 220-240V AC. Figure 9. Panels connection with 220-240V AC
Battery disposal .
I t i s not allowed to discard batteries into common trash bins, they must be discarded only in battery
recycling points.
Warnings .
1. Service and maintence activities should be done only when the device is disconneted from the
mains power supply and the battery.
2. During the installation the connections to the mains power supply and the battery must be
done after all other connections are finished.
3. The panel connection with the mains supply must be done via a10A external fuse or an
automatic circuit breaker rated at 10A.This fuse has to be a separate, labeled fuse.
4. Always use cables with double insulation.
5. The diameter of the cable must be at least 1mm.(Figure 9)
6. The inner insulation of each cable must not be cut more than 1cm (Figure 9)
7. The outer insulation must not be cut more than 1cm away from the internal insulation.
8. The panel's internal fuse is T630mAL250V with 5x20 dimensions.
9. The batery fuse is a resetable fuse 900mA inside the panel.
Initial Installation
When the connections to zones, sirens and other required outputs are finished then we must connect the mains
power supply. In order to aid the installer during the initial installation, the panel offers a special configuration. This
configuration is entered by setting MODE switch 1 to the ON position. After entering this mode the panel conducts
an auto reset and the 'Power', 'Zone disable' and 'General disable' LEDs blink. The special functions that aid in
working out various problems that might arise are:
When a zone has an open circuit then the internal buzzer sounds and the corresponding LED lights. If the
problem is corrected then the buzzer is deactivated and the LED is turned off.
When a zone has a short circuit then the internal buzzer sounds and the corresponding LED blinks. If the problem
is corrected then the buzzer is deactivated and the LED is turned off.
When a siren output has an open circuit then the internal buzzer is activated and the corresponding fault LED
lights. If the problem is corrected then the buzzer is deactivated and the LED is turned off.
When a siren output has a short circuit then the internal buzzer sounds and the corresponding LED blinks. If the
problem is corrected then the buzzer is deactivated and the LED is turned off.
When a battery fault exists then the 'Batt fault' LED lights and the 'Power fault' LED blinks. If the problem is
corrected then the LEDs are deactivated.
If all the problems are corrected and the installation is operating normally then the MODE switch 1 must be placed in
the OFF position. The panel conducts an auto-reset and is ready for operation.
Walk - Testing
By using a special operation mode we can conduct a walk test of the system. To enter walk-test mode set the MODE switch 1
to the ON position. The 'Power', 'Zone disable' and 'General disable' LEDs blink. If an alarm is manually given by either
activating a BS-536 call point or by activating a smoke detector with smoke or simulated smoke particles the corresponding
Alarm LED of the zone will light and the siren will sound for 2 seconds. Using this method we can test the operation of the
zones.
After finishing the walk test set the MODE switch 1 to the OFF position. The panel conducts an automatic reset and enters
normal operation mode.
Optional Function of EN 54-2.
The optional function which is provided by the panel is the fire alarm devices paragraph 7.8 of EN 54-2 and delays to
outputs (paragraph 7.11 of EN 54-2).
Design
Components of the panels have been selected for the intended purpose, and are expected to operate within their
specification when the environmental conditions outside the cabinet of the panel comply with class 3k5 of
EN 60721-3-3:1995.
Consumption 50VA
Zone circuits 2 circuits monitored for 4 circuits monitored for 6 circuits monitored for
short and open circuit short and open circuit short and open circuit
conditions (maximum current 35mA) conditions (maximum current 35mA) conditions (maximum current 35mA)
Alarm circuits Two 24V circuits that are monitored for open and short circuit conditions
(maximum current 300mA each). Each output is protected
with a self-reseting electronic fuse.
Output 24P 24VDC ( ±3VDC) permanent output with maximum current output 0.3 A
The output is protected with a self-reseting electronic fuse.
Output 24M 24VDC ( ±3VDC) reset interrupted output with maximum current output 0.3 A
The output is protected with a self-reseting electronic fuse.
Outputs Relays Three relays contacts are rated at 30VDC and 5A maximum
each. Under no circumstances should voltages or currents outside limits
be connected. All relays output must be protected with a fuse of the same rating.
The total output current ( zones circuits, siren circuit, outputs 24P, 24M)
Total load must not exceed 600mA.
(ImaxA = ImaxB = 600mA, Imin = 30mA)
Maximum current
900mA
batteries discharge
IP IP 30
Cables Cables for fire rated cables systems such a FIP200,MICC, PYROFIL
The panel has only one serviceable fuse to protect incoming mains supply.
Fuse ratings This fuse is T 630 mAL250V must be replaced with a fuse
of the same type and rating
o
Operation temperature 0 to 50 C
Weight 1345gr (3065gr with battery) 1350gr (3070gr with battery ) 1360gr (3080gr with battery )
Guarantee 2 years
The panels BS-1632, BS-1634 and BS-1636 are certified from HEEQAC. Also HEEQAC controls the
production under CPR number: 0848-CPR-002 for the panel BS-1632, 0848-CPR-003 for the panel
BS-1634 and 0848-CPR-004 for the panel BS-1636. Below are the markings:
BS-1632
CONVENTIONAL 2-ZONE
BS-1634
CONVENTIONAL 4-ZONE
BS-1636
CONVENTIONAL 6-ZONE
FIRE ALARM PANEL FIRE ALARM PANEL FIRE ALARM PANEL
INSTALL IN ACCORDANCE WITH INSTALL IN ACCORDANCE WITH INSTALL IN ACCORDANCE WITH
PRODUCT MANUAL: PRODUCT MANUAL: PRODUCT MANUAL:
921163600_08_019 (GREEK) 921163600_08_019 (GREEK) 921163600_08_019 (GREEK)
921163600_09_020 (ENGLISH) 921163600_09_020 (ENGLISH) 921163600_09_020 (ENGLISH)
POWER SUPPLY: POWER SUPPLY: POWER SUPPLY:
220-240V AC/50-60Hz 220-240V AC/50-60Hz 220-240V AC/50-60Hz 14
14 14
EN 54-2:1997 +A1:2006 0848 EN 54-2:1997 +A1:2006 0848 EN 54-2:1997 +A1:2006 0848
EN 54-4:1997 +A1:2002 +A2:2006 EN 54-4:1997 +A1:2002 +A2:2006 EN 54-4:1997 +A1:2002 +A2:2006
0848-CPR-002 0848-CPR-003 0848-CPR-004
DoP No: 921163200_59_003 DoP No: 921163400_59_003 DoP No: 921163600_59_003
Provided option: Provided option: Provided option:
Output to fire alarm device(s), Output to fire alarm device(s), Output to fire alarm device(s),
delays to outputs delays to outputs delays to outputs
DISCONNECT POWER BEFORE DISCONNECT POWER BEFORE DISCONNECT POWER BEFORE
SERVICING SERVICING SERVICING
Production Production Production
Date: Date: Date:
/ / / / / /
KOLINDROS PIERIAS KOLINDROS PIERIAS KOLINDROS PIERIAS
60061 GREECE 60061 GREECE 60061 GREECE