TFP1315 07 2014

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Worldwide Contacts

Worldwide
www.tyco-fire.com
www.tyco-fire.com Contacts

DV-5 Deluge Valve, Diaphragm Style,


1-1/2 thru 8 Inch (DN40 thru DN200),
Deluge System – Dry Pilot Actuation
General
Description
The DV-5 Deluge Valve (described in
Technical Data Sheet TFP1305) is a
diaphragm style valve that depends
upon water pressure in the Diaphragm
Chamber to hold the Diaphragm closed
against the water supply pressure.
When the DV-5 Valve is set for service,
the Diaphragm Chamber is pressurized
through the trim connections from the
inlet side of the system’s main con-
trol valve, for example an O.S.&Y. gate
valve or butterfly valve (Ref. Figures 1
and 4).
Opening of a dry pilot sprinkler releas-
es pneumatic pressure from the pi-
lot line. In turn, the Dry Pilot Actuator
(Item D3 - Fig. 3A and 5) opens and
releases water from the Diaphragm
Chamber faster than it can be replen-
ished through the 1/8 inch (3,2 mm) re-
striction provided by the Model ASV-1
Automatic Shut-Off Valve in the dia-
phragm supply connections (Item 5 -
Fig. 3A and 5, also described in Tech-
by preventing inadvertent closing of the The owner is responsible for maintain-
nical Data Sheet TFP1384). This results
DV-5 during a fire (as may be the case ing their fire protection system and de-
in a rapid pressure drop in the Dia-
if an actuation device other than a pi- vices in proper operating condition.
phragm Chamber, and the force differ-
lot sprinkler were to be closed after its Contact the installing contractor or
ential applied through the Diaphragm
initial operation, e.g., a remote manual manufacturer with any questions.
that holds it in the set position is re-
control station).
duced below the valve trip point. The
water supply pressure then forces the
Diaphragm open permitting water to NOTICE
flow into the system piping, as well as The DV-5 Deluge Valve with Dry Pilot
through the Alarm Port to actuate the Actuation Trim described herein must
system alarms. be installed and maintained in compli-
As water flows into the system, the pi- ance with this document, as well as
lot chamber of the Model ASV-1 Auto- with the applicable standards of the
matic Shut-Off Valve (Item 5 - Fig. 3A National Fire Protection Association, in
and 5) becomes pressurized and the addition to the standards of any other
ASV-1 automatically shuts off the di- authorities having jurisdiction. Failure
aphragm chamber supply flow to the to do so may impair the performance
DV-5 Diaphragm Chamber. Shutting of these devices.
off the diaphragm chamber supply flow
prevents the DV-5 Diaphragm Chamber
from becoming re-pressurized, there-

Page 1 of 16 JULY 2014 TFP1315


TFP1315
Page 2 of 16

13

6
5

15
11

14

7
8

3
9

2 4

16

1 - DV-5 Deluge Valve 7 - Water Supply Pressure Gauge 12 - Waterflow Pressure Alarm Switch
2 - Main Control Valve (N.O.) 8 - Diaphragm Chamber Pressure (Shown at Rear of Valve)
3 - Diaphragm Chamber Supply Gauge 13 - Water Motor Alarm (Optional)
Control Valve (N.O.) 9 - System Drain Valve (N.C.) 14 - Dry Pilot Actuator
4 - Local Manual Control Station 10 - Main Drain Valve (N.C.) 15 - Low Pressure Alarm Switch
5 - Open Nozzles or Sprinklers (Shown at Rear of Valve) 16 - Automatic Air/Nitrogen Supply
6 - Dry Pilot Line Sprinklers 11 - Diaphragm Chamber Automatic
(Fire Detection) Shut-Off Valve

FIGURE 1 (1 OF 2)
SYSTEM SCHEMATIC (FRONT VIEW)
DRY PILOT ACTUATION
TFP1315
Page 3 of 16

15
13

11
14

12

3
16

10
1

1 - DV-5 Deluge Valve 7 - Water Supply Pressure Gauge 13 - Water Motor Alarm (Optional)
2 - Main Control Valve (N.O.) (Shown at Front of Valve) 14 - Dry Pilot Actuator
3 - Diaphragm Chamber Supply 8 - Diaphragm Chamber Pressure 15 - Low Pressure Alarm Switch
Control Valve (N.O.) Gauge (Shown at Front of Valve)
16 - Automatic Air/Nitrogen Supply
4 - Local Manual Control Station 9 - System Drain Valve (N.C.)
(Shown at Front of Valve) 10 - Main Drain Valve (N.C.)
5 - Open Nozzles or Sprinklers 11 - Diaphragm Chamber Automatic
6 - Dry Pilot Line Sprinklers Shut-Off Valve
(Fire Detection) 12 - Waterflow Pressure Alarm Switch

FIGURE 1 (2 OF 2)
SYSTEM SCHEMATIC (REAR VIEW)
DRY PILOT ACTUATION
TFP1315
Page 4 of 16

Stations are to be the Model MC-1


described in Technical Data Sheet
WATERFLOW TFP1382.
PRESSURE DELUGE
ALARM DRY PILOT
The Dry Pilot Actuation Trim is provided
SWITCH ACTUATION with a listed and approved Model DP-1
TRIM Dry Pilot Actuator, which is described
in Technical Data Sheet TFP1380. The
Actuator is rated for use at a maximum
NOTES: pilot service pressure of 50 psi (3,4 bar)
and a maximum water supply service
1. SEE FIGURE 3, PER VALVE SIZE
AS APPLICABLE, FOR TRIM pressure of 250 psi (17,2 bar).
ARRANGEMENT WITH BILL OF Graph A shows the minimum pilot line
MATERIALS AND COMPONENT
PART NUMBERS.
service pressure as a function of the
water supply pressure. The pressure in
2. TRIM SHOWN FULLY ASSEMBLED;
COMPONENTS SUCH AS GAUGES
the dry pilot actuation system must be
DV-5 AND SWITCHES MAY REQUIRE automatically maintained using one of
DELUGE ASSEMBLY IN TRIM AT VALVE the following maintenance devices, as
VALVE INSTALLATION. appropriate:
• Model AMD-1 Air Maintenance De-
SYSTEM vice (pressure reducing type), refer to
SHUT-OFF
GROOVED
VALVE
Technical Data Sheet TFP1221
COUPLING
• Model AMD-2 Air Maintenance De-
FIGURE 2 vice (compressor control type), refer
DV-5 PRE-TRIMMED DELUGE VALVE, to Technical Data Sheet TFP1231
DRY PILOT ACTUATION • Model AMD-3 Nitrogen Maintenance
Device (high pressure reducing
Technical • Model BFV-N Butterfly Valve
• Waterflow Pressure Alarm Switch
type), refer to Technical Data Sheet
TFP1241
Data (PS10-2) NOTES: The dew point of the pilot line
• Low Pressure Alarm Switch air pressure must be maintained be-
Approvals (PS40-2) low the lowest ambient temperature
UL and C-UL Listed to which the dry pilot actuation system
FM Approved. • Figure 577 Grooved Coupling will be exposed. Accumulation of water
To ease field assembly of the trim ar- in the pilot line connection to the Actu-
Valve Trim
rangement, the vertical trim compo- ator will lower the air pressure at which
The Vertical Dry Pilot Actuation Trim
nents are provided partially assembled the Actuator will open and possibly
(Fig. 3A/3B) and Horizontal Dry Pilot
as shown in Figure 3B. prevent proper operation. Also, intro-
Actuation Trim (Fig. 5) form a part of
duction of moisture into the pilot lines
the laboratory listings and approvals The trim arrangement is provided with
exposed to freezing temperatures can
for the DV-5 Valve and are necessary galvanized, black, or brass nipples and
create an ice buildup that could pre-
for its proper operation. fittings. The galvanized and brass trim
vent proper operation of the Actuator.
are intended for non-corrosive or cor-
Each package of trim includes the fol-
rosive conditions, whereas the black An air dryer must be installed where
lowing items:
trim is principally intended for use with the moisture content of the air supply
• Water Supply Pressure Gauge AFFF systems. is not properly controlled at less than
• Diaphragm Chamber the required value.
NOTE: When the system pressure is
Pressure Gauge greater than 175 psi (12,1 bar), provision It is recommended that an AMD-3 Ni-
• Diaphragm Chamber Connections is to be made to replace the standard trogen Maintenance Device be utilized
order 300 psi (20,7 bar) Water Pressure in dry pilot actuation system applica-
• Manual Control Station Gauges, shown in Figure 3A/3B and 5, tions where the dew point must be
• Main Drain Valve with separately ordered 600 psi (41,4 maintained below -20°F (-29°C). See
bar) Water Pressure Gauges. Technical Data Sheet TFP1241.
• System Drain Valve
The Dry Pilot Actuation Trim provides At a minimum, it is recommended that
• Alarm Test Valve for installation of a detection system internally galvanized pipe and cast iron
• Automatic Drain Valve consisting of pilot sprinklers (heat de- fittings be used for dry pilot lines.
tectors) and manual control stations Supervision of the pressure in the dry
• Dry Pilot Actuator interconnected with minimum 1/2 inch pilot actuation system and/or alarm
• Dry Pilot Line Pressure Gauge (DN15) steel pipe. The dry pilot line, that separately indicates operation of
which is to be pressurized with air or the detection system is recommended
The following items are included in the nitrogen, is connected to the Dry Pilot
Pre-trimmed Valve Assembly and can and may be required by the authority
Detection connection shown in Figure having jurisdiction. A dual setting low
be ordered separately for the valve 3B. Nominal installation dimensions
trim: pressure alarm switch, such a Potter
for Vertical Dry Pilot Actuation Trim are Electric PS40-2, is suitable for this ser-
shown in Figure 4. vice. The recommended pressure set-
Pilot sprinklers are to be minimum 5.6 tings are as follows:
K-factor orifice listed or approved au- Continued on Page 9
tomatic sprinklers. Manual Control
TFP1315
Page 5 of 16

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 31 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH D15 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 32 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 3 CH D16 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 33 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 10 CH D17 1/2" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 34 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 35 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 4 CH COMPONENTS INCLUDED ONLY IN
6 Item No. Not Used 36 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH PRE-TRIMMED VALVE ASSEMBLIES:
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 37 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH A1 Waterflow Pressure Alarm Switch,
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 38 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 39 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH A2 Low Air Pressure Alarm Switch,
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 40 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730
11 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 2 46-048-1-005 41 3/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 1 CH A3 Butterfly Valve, Power Ball 300:
12 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 42 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 8 CH 1-1/2" (DN40) . . . . . . . . . . . . . . . . . . . . . . . . 1 51024A
13 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 43 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH 2" (DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 51021A
14 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 44 3/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH A4 Figure 577 Coupling:
15 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 45 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH 1-1/2" (DN40) . . . . . . . . . . . . . . . . . . . . . . . . 1 57715ACP
16 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 2" (DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 57720ACP
17 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH D1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012
18 1/2" x 12" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH D2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002
19 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001 D5
20 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D4 Item No. Not Used
21 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH D5 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004 D15 D6 A2
22 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH D6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020
23 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D7 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
24 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH D8 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH D15 D1
25 3/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D9 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
26 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH D10 1/2" 45° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D13
27 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH D11 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D12
28 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH D12 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
29 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH D13 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH D17 D9
30 3/4" x 3/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH D14 1/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
D13 D15

D12 D2
16 11 D10
41 D14
A1 D8
30
27 42 45 D15
15 D16
29 (GREEN 24 D7 D15 D3
LOCATION 20 TINT) 35
FOR OPTIONAL 4
ELECTRICALLY 35 28 42 33 D11 D15
SUPERVISED 42 22 21
N.O. ALARM 43 36 21 32
CONTROL 42 25 33
VALVE 42
22 26
33 10 26
42 42 24 40
24 42 35 24 24
29 12 1
14 26
38 28 33 32
11 44 33 27
7
13 37
35 1 5 33 3
A4
NOTES:
21 8
1. Dry Pilot Actuation Trim is 19 2 21
comprised of Items 1-45 A3
36 24 32
plus Items D1-D17. Items 34
A1-A4 included only in 39 18
pre-trimmed valve assemblies 9
31 27 33 17
33 24 24
as applicable; otherwise
31 33
ordered separately. 23 2" (DN50)
2. All Fittings and Nipples are GROOVE x GROOVE Nipple
Select Appropriate Nipple Sizes
galvanized (Standard Order). DV-5 DELUGE VALVE 21 Number
per DV-5 Deluge Valve Size
1-1/2" (DN40) 2" (DN50)
3. CH: Common Hardware. SHOWN 38 1/2" x 1-1/2" 1/2" x 2"
4. See Figure 2 of TFP1305 for 33 39 1/2" x 2" 1/2" x 1-1/2"
40 1/2" x 5" 1/2" x 5-1/2"
Valve Port identification.
45 3/4" x 1-1/2" 3/4" x 2-1/2"
5. Route all Tubing to Drip Funnel, 7
Item 14.
FIGURE 3A (1 OF 3)
1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 DELUGE VALVES
EXPLODED VIEW OF VERTICAL DRY PILOT ACTUATION TRIM
TFP1315
Page 6 of 16

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 32 1-1/4" x 3/4" x 1-1/4" Tee. . . . . . . . . . . . . . . 1 CH D14 1/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 33 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH D15 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 34 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH D16 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 35 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 13 CH D17 1/2" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 36 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
6 Item No. Not Used 37 1/2" x 3-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH COMPONENTS INCLUDED ONLY IN
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 38 1/2" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH PRE-TRIMMED VALVE ASSEMBLIES:
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 39 1/2" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH A1 Waterflow Pressure Alarm Switch,
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 40 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 41 1/2" x 5-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH A2 Low Air Pressure Alarm Switch,
11 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-005 42 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730
12 1-1/4" Angle Valve . . . . . . . . . . . . . . . . . . . . 1 46-048-1-007 43 3/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 3 CH A3 Model BFV-N Butterfly Valve, 3" (DN80) . . . 1 59300F030N
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 44 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 5 CH A4 Figure 577 Coupling, 3" (DN80) . . . . . . . . . . 1 57730ACP
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 45 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 46 3/4" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 47 1-1/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
17 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 48 1-1/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH D5
18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
19 1/2" x 12" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH D1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012 D15 D6 A2
20 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002
21 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001
22 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH D4 Item No. Not Used D15 D1
23 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH D5 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004
24 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020 D13
25 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH D7 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
26 3/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D8 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH D12
27 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH D9 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D17 D9
28 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH D10 1/2" 45° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
29 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D11 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D13 D15
30 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH D12 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
31 3/4" x 3/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH D13 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
D12 D2
D10
17 11 D14
43 D8
A1
31
D15
28 44 46 D16
16 25
30 D7 D15 D3
(GREEN
LOCATION 21 TINT)
FOR OPTIONAL 36 26 35
D11 D15
ELECTRICALLY 36 29
SUPERVISED 44 22
23 27 4 41 22 35
N.O. ALARM 45 35
CONTROL 44 43
VALVE 44 27
23 38
35 10 25 42
43 13
44 25 25
25 15 1
30 27
35 35 34
32 35 28
7 47 48 14
42
12 5 35 3
40
NOTES: 1
8
1. Dry Pilot Actuation Trim is 22
comprised of Items 1-48 22
20 2 A4
25 34
plus Items D1-D17. Items 37
A1-A4 included only in 19
39 A3 9
pre-trimmed valve assemblies 35 18
35 25 25
as applicable; otherwise 35
33 28 35
ordered separately.
2. All Fittings and Nipples are 33
24
galvanized (Standard Order). 3" (DN80) 22
3. CH: Common Hardware. GROOVE x GROOVE
DV-5 DELUGE VALVE 35
4. See Figure 2 of TFP1305 for
SHOWN
Valve Port identification.
5. Route all Tubing to Drip Funnel, 7
Item 15.
FIGURE 3A (2 OF 3)
3 INCH (DN80) DV-5 DELUGE VALVE
EXPLODED VIEW OF VERTICAL DRY PILOT ACTUATION TRIM
TFP1315
Page 7 of 16

Select Appropriate Tube Size


NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
Tube per DV-5 Deluge Valve Size
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 44 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH No. 4" 6" 8"
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 45 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH (DN100) (DN150) (DN200)
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 46 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH 17 1/4" x 24" 1/4" x 24" 1/4" x 32"
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 47 1" x Close Nipple . . . . . . . . . . . . . . . . . . . . . 5 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 48 1" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
6 Item No. Not Used 49 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH Select Appropriate Nipple Sizes
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 50 2" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH per DV-5 Deluge Valve Size
Nipple
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 51 2" x 5" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 52 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH No. 4" 6" 8"
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 (DN100) (DN150) (DN200)
11 1" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-006 D1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012 37 1/2" x 3" 1/2" x 3" 1/2" x 5"
12 2" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-009 D2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 41 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8-1/2"
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 D3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001
D4 Item No. Not Used 42 1/2" x 2" 1/2" x 3" 1/2" x 3-1/2"
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003
D5 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004 43 1/2" x 6-1/2" 1/2" x 7-1/2" 1/2" x 9"
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007
16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 D6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020 46 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
17 Select Tubing per Table . . . . . . . . . . . . . . . . 1 CH D7 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH 49 1" x 6" 1" x 9" 1" x 12"
18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH D8 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
52 1/2" x 7" 1/2" x 7" 1/2" x 9"
19 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH D9 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
20 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D10 1/2" 45° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
21 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D11 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
22 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH D12 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
23 1" Union . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH D13 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
24 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D14 1/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
25 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH D15 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH
26 1" 90° Elbow. . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D16 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
27 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH D17 1/2" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
28 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH COMPONENTS INCLUDED ONLY IN
29 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH D5
PRE-TRIMMED VALVE ASSEMBLIES:
30 1" x 1" x 1/2" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH
31 1" x 3/4" x 1" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH
D15 D6 A2
A1 Waterflow Pressure Alarm Switch,
32 2" x 1" x 2" Tee . . . . . . . . . . . . . . . . . . . . . . . 1 CH Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710
33 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH A2 Low Air Pressure Alarm Switch,
34 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730
D15 D1
35 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 10 CH A3 Model BFV-N Butterfly Valve: D13
36 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 3 CH 4" (DN100) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F040N
37 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH 6" (DN150) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F060N D12
38 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH 8" (DN200) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F080N
39 1/2" x 6" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH A4 Figure 577 Coupling: D17 D9
40 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH 4" (DN100) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 57740ACP D15
41 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH 6" (DN150) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 57760ACP
D13
42 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH 8" (DN200) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 57780ACP
43 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
D12 D2
D10 D14
17 47 11 D8
A1 30 D15
47 49 D16
28
D7 D15 D3
29 16 25
LOCATION 21 (GREEN 36
FOR OPTIONAL TINT) 26 D11 D15
37
ELECTRICALLY 36 47
SUPERVISED 44 4 39 22 42 22
23 23 27 35
N.O. ALARM 45
CONTROL 47
31 36 27
VALVE 25 43
10 47 13
35 25 25
25 46 15 1
48 27
29
35 34
41 35 28
14 52
7 32
50 51 5 35 3
NOTES: 12
8
1. Dry Pilot Actuation Trim is 1 9 22
40
comprised of Items 1-52
22 25 34
plus Items D1-D17. Items 2 38
20 19
A1-A4 included only in A4
pre-trimmed valve assemblies 38 35 18
as applicable; otherwise 25 25
35 A3 35
ordered separately. 35
33 28
2. All Fittings and Nipples are
galvanized (Standard Order). 33 22
24
3. CH: Common Hardware. 4" (DN100)
4. See Figure 2 of TFP1305 for GROOVE x GROOVE 35
Valve Port identification. DV-5 DELUGE VALVE
SHOWN 7
5. Route all Tubing to Drip Funnel,
Item 15.
FIGURE 3A (3 OF 3)
4, 6, AND 8 INCH (DN100, DN150 AND DN200) DV-5 DELUGE VALVES
EXPLODED VIEW OF VERTICAL DRY PILOT ACTUATION TRIM
TFP1315
Page 8 of 16

NOTES: Nipple Select Appropriate Nipple and Tube Sizes per DV-5 Deluge Valve Size
1. Install subassemblies in alphabetical order. Number 1-1/2" (DN40) 2" (DN50) 3" (DN80) 4" (DN100) 6" (DN150) 8" (DN200)
2. See Figure 2 of TFP1305 for Valve Port 1 1/2" x Close 1/2" x 2" 1/2" x 1-1/2" 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8-1/2"
identification.
2 1/2" x Close 1/2" x Close 1/2" x 1-1/2" 1/2" x 2" 1/2" x 3" 1/2" x 3-1/2"
3. Route all Tubing to Drip Funnel.
3 1/2" x 5" 1/2" x 5-1/2" 1/2" x 7" 1/2" x 6-1/2" 1/2" x 7-1/2" 1/2" x 9"
4. When DV-5 trips, Automatic Shut-Off Valve
4 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
shuts off diaphragm chamber supply.
5 3/4" x 1-1/2" 3/4" x 2-1/2" 3/4" x 4-1/2" 1" x 6" 1" x 9" 1" x 12"
5. Nipples 1-7 and Tube 1 vary in length relative
to DV-5 size. Select per table. All other nipples 6 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 3" 1/2" x 3" 1/2" x 5"
and tubing packed unassembled shall be 7 1/2" x 7" 1/2" x 7" 1/2" x 7" 1/2" x 7" 1/2" x 7" 1/2" x 9"
installed per appropriate trim exploded view, Main Drain
Figure 3A Part 1, 2, or 3. 3/4" NPT 3/4" NPT 1-1/4" NPT 2" NPT 2" NPT 2" NPT
Size
Tube 1 1/4" x 18" 1/4" x 18" 1/4" x 18" 1/4" x 24" 1/4" x 24" 1/4" x 32"
WATERFLOW
PRESSURE ALARM VENT FITTING
(GREEN TINT)
SWITCH, ORDERED
1/2 INCH NPT
SEPARATELY CONNECTION LOW AIR
SYSTEM
TUBE 1 DRAIN VALVE 1/2 INCH NPT FOR "DRY PILOT PRESSURE
3/4 INCH NPT (NORMALLY CONNECTION DETECTION" ALARM SWITCH,
CONNECTION FOR CLOSED) FOR DRY PILOT ORDERED
B SEPARATELY
WATER MOTOR AIR SUPPLY
ALARM NIPPLE
4 DRY
AUTOMATIC PILOT LINE
LOCATION DRY PILOT PRESSURE
DRAIN VALVE
FOR OPTIONAL AIR SUPPLY GAUGE
CONTROL VALVE E
ELECTRICALLY
SUPERVISED NIPPLE (NORMALLY DRY PILOT
N.O. ALARM NIPPLE 5 OPEN) ACTUATOR
CONTROL 6 (NORMALLY
VALVE CLOSED)
4" (DN100)
DRIP
FLANGE x FLANGE
FUNNEL
NIPPLE DV-5 DELUGE NIPPLE
1 VALVE SHOWN 2
1-1/4 INCH NPT
CONNECTION NIPPLE
TO DRAIN 3
MAIN A
DRAIN VALVE DIAPHRAGM
(NORMALLY D CHAMBER
CLOSED) PRESSURE
GAUGE
ALARM MAIN DRAIN NIPPLE
TEST VALVE CONNECTION 7
(NORMALLY (SIZED PER MANUAL
CLOSED) TABLE) CONTROL
STATION
SYSTEM
WATER C AUTOMATIC
SUPPLY DIAPHRAGM
CHAMBER SUPPLY SHUT-OFF VALVE
PRESSURE (NORMALLY
GAUGE CONTROL VALVE
(NORMALLY OPEN)
OPEN) 1/2 INCH NPT
CONNECTION FROM
WATER SUPPLY
FIGURE 3B
1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 DELUGE VALVES
OPERATIONAL COMPONENTS OF VERTICAL DRY PILOT ACTUATION TRIM
EXPLODED ARRANGEMENT OF SEMI-PREASSEMBLED TRIM
TFP1315
Page 9 of 16

Valve Nominal Installation Dimensions in Inches and (mm)


Size A B C D E F G H J K L M N
1-1/2" 7.00 8.88 13.19 13.13 24.69 1.25 5.81 1.81 3.00 7.00 3.88 8.00 4.02
(DN40) (177,8) (225,4) (335,0) (333,4) (627,1) (31,8) (147,6) (46,0) (76,2) (177,8) (98,4) (204,0) (102,1)
2" 7.13 9.13 13.19 13.13 25.00 0.94 6.00 2.00 3.00 7.00 3.00 8.63 4.09
(DN50) (181,0) (231,8) (335,0) (333,4) (635,0) (23,8) (152,4) (50,8) (76,2) (177,8) (76,2) (220,0) (103,9)
3" 7.81 10.44 13.19 13.13 28.56 1.63 6.69 2.69 4.25 7.00 0.88 12.75 3.85
(DN80) (198,4) (265,1) (335,0) (333,4) (725,5) (41,3) (170,0) (68,3) (108,0) (177,8) (22,2) (324,0) (98,0)
4" 10.00 11.75 14.31 13.13 31.50 1.75 8.56 4.44 6.25 7.13 0.63 15.75 4.56
(DN100) (254,0) (298,5) (363,5) (333,4) (800,1) (44,5) (217,5) (112,7) (158,8) (181,0) (15,9) (400,0) (116,0)
6" 11.38 14.31 15.31 13.13 32.69 3.50 9.94 5.81 6.25 7.13 1.81 18.13 5.86
(DN150) (289,0) (363,5) (388,9) (333,4) (830,3) (88,9) (252,4) (147,6) (158,8) (181,0) (46,0) (460,4) (149,0)
8" 12.00 16.00 16.25 13.13 35.00 1.75 10.75 6.50 6.25 7.13 7.38 22.50 5.26
(DN200) (304,8) (406,4) (412,8) (333,4) (889,0) (44,5) (273,1) (165,1) (158,8) (181,0) (187,3) (570,0) (134,0)

* MINIMUM CLEARANCE

A* B C* D*

E*

M
L

N
F
H K

G J

LEFT VIEW FRONT VIEW


FIGURE 4
1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 DELUGE VALVES
VERTICAL DRY PILOT ACTUATION / NOMINAL INSTALLATION DIMENSIONS

• Low pressure alarm setting at ap-


proximately 6 psi (0,4 bar) below the Materials of Systems using a seawater or brackish
water supply require special consid-
minimum pilot line service pressure
requirement shown in Graph A Construction erations in order to extend the life of
the valve and trim. This type of system
NOTES: The galvanized or brass, ideally should be configured with a pri-
• Fire alarm setting at approximately
nipples and fittings for the Valve Trim mary source of clean fresh water (e.g.,
15 psi (1,0 bar) below the minimum
provide corrosion resistance and are a pressurized water tank) and that only
pilot line service pressure require-
intended to extend the life of the instal- upon system operation is the second-
ment shown in Graph A
lation of the DV-5 Valve when exposed ary water supply (seawater or brack-
The Pressure Relief Valve (Ref. Item D6 to internal and external corrosive con- ish water) allowed to enter the system.
- Fig. 3A and 5) is factory set to relieve ditions. Although these selections are After the system operation, the sys-
at a pressure of approximately 45 psi intended to resist corrosion, it is rec- tem should be thoroughly flushed with
(3,1 bar); however, it may be field ad- ommended that the end user or oth- clean fresh water. Following this rec-
justed to a lower pressure, if required. er technical expert familiar with con- ommendation will increase the service
ditions at the proposed installation be life of the DV-5 Valve and Valve Trim.
consulted with respect to these selec- Pressure Gauges. Bronze bourdon
tions for a given corrosive condition. tube with brass socket.
TFP1315
Page 10 of 16

Gauge Test Valve. Bronze body per


45
ASTM B584.
Manual Control Station. Corrosion URE
IR P RESS
resistant copper alloys and glass filled EM A

AIR PRESSURE IN PSI


YST
PTFE seals. Thermoplastic enclosure. UM S
30 MINIM
Automatic Drain Valve. Brass body
SURE
per ASTM B584, Type 440 stainless
ING PRES
steel or brass per ASTM B134 Ball, and OPEN
TOR
galvanized steel inlet. CTUA
15 E OF A
Automatic Shut-Off Valve. Brass RANG
body, cover, and center seat per UNS
C36000, Type 316 stainless steel
spring, and Nylon fabric reinforced,
natural rubber diaphragm per ASTM 0
D2000. 20 60 100 140 180 200 250
Ball Valve. Corrosion resistant copper
WATER SUPPLY PRESSURE IN PSI
alloys and glass filled PTFE seals.
Spring Loaded Check Valve. Brass GRAPH A
body and buna-n seal. DV-5 DELUGE VALVE
DRY PILOT LINE PRESSURE REQUIREMENTS
Y-Strainer. Bronze body per ASTM
B584 and Type 304 stainless steel
screen. Installation Step 5. The main drain and Drip Funnel
drain may be interconnected provided
Swing Check Valve. Bronze body per a check valve is located at least 12
ASTM B584 and buna-n seal. General Instructions inches (300 mm) below the Drip Funnel.
Proper operation of the DV-5 Deluge
Angle Valve. Bronze body per ASTM Valves depends upon their trim being Step 6. Suitable provision must be
B584 and nitrile disc (TEFLON disc for installed in accordance with the in- made for disposal of drain water. Drain-
2 inch size valve). structions given in this Technical Data age water must be directed such that
3/32” Vent Fitting. Brass per ASTM Sheet. Failure to follow the appropri- it will not cause accidental damage to
B16. ate trim diagram may prevent the DV-5 property or danger to persons.
Valve from functioning properly, as well Step 7. Connect the Diaphragm Cham-
Tubing Connector. Brass per ASTM as void listings, approvals, and the
B16. ber Supply Control Valve to the inlet
manufacturer’s warranties. side of the system’s Main Control Valve
Tubing. Type L copper per ASTM B88. The DV-5 Valve must be installed in a in order to facilitate setting of the DV-5
Dry Pilot Actuator. Bronze body per readily visible and accessible location. Valve (Ref. Figure 4).
ASTM B62, Type 302 stainless steel The DV-5 Valve and associated trim Step 8. An Inspector’s Test Connec-
spring, Type 304 seat and guide, brass must be maintained at a minimum tem- tion, as described in the Technical Data
per ASTM diaphragm retainer, nitrile perature of 40°F (4°C). section, must be provided for Dry Pilot
diaphragm, and buna-n seal. Actuation systems.
Heat tracing of the DV-5 Valve or its
Globe Valve. Bronze body per ASTM associated trim is not permitted. Heat Step 9. An Air Maintenance Device, as
B584 and nitrile disc. tracing can result in the formation of described in the Technical Data Sec-
Pressure Relief Valve. Brass body, hardened mineral deposits that are ca- tion, must be provided for Dry Pilot
stainless steel spring, and buna-n disc. pable of preventing proper operation. Actuation.
Pipe Fittings. Galvanized mallea- The DV-5 Deluge Valve is to be in- Step 10. A desiccant dryer, when
ble iron per ANSI B16.3 or cast iron stalled in accordance with the follow- specified for Dry Pilot Actuation, is to
per ANSI B16.4; black malleable iron ing criteria: be installed between a drip leg and the
per ANSI B16.3 or cast iron per ANSI Air Maintenance Device.
Step 1. All nipples, fittings, and de-
B16.4; or, bronze per ANSI B16.15. vices must be clean and free of scale Step 11. The Low Pressure Alarm
Pipe Nipples. Schedule 40 galvanized and burrs before installation. Use pipe Switch for Dry Pilot Actuation is to be
steel per ASTM A53 or A135; Sched- thread sealant sparingly on male pipe adjusted as follows:
ule 40 black steel per ASTM A53 or threads only. • Low pressure alarm setting at ap-
A135; or, Schedule 40 red brass pipe Step 2. The DV-5 Valve must be proximately 6 psi (0,4 bar) below the
per ASTM B43. trimmed in accordance with Figure minimum pilot line service pressure
3A/3B or 5. requirement shown in Graph A
Step 3. Care must be taken to ensure • Fire alarm setting at approximately
that check valves, strainers, globe 15 psi (1,0 bar) below the minimum
valves, etc. are installed with the flow pilot line service pressure require-
arrows in the proper direction. ment shown in Graph A
Step 4. Drain tubing to the Drip Funnel Step 12. Unused pressure alarm
must be installed with smooth bends switch connections must be plugged.
that will not restrict flow. Step 13. The Pressure Relief Valve pro-
vided with the Dry Pilot Actuation Trim
is factory set to relieve at a pressure
Continued on Page 14
TFP1315
Page 11 of 16

NO. DESCRIPTION QTY. P/N A2 NO. DESCRIPTION QTY. P/N


D13 D6 (ORDERED
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 23 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 SEPARATELY) 24 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 D5 25 3/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 D15 26 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 27 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH
6 Item No. Not Used D15 28 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 29 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 D12 D1 30 3/4" x 3/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 31 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005
D17 32 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 3 CH
11 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 2 46-048-1-005 D13 D15 D9 33 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 10 CH
12 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 34 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
13 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 35 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 4 CH
14 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 36 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH
15 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 D12 D2 37 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
16 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH D10 D14 38 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
17 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH 39 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
18 1/2" x 12" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH D7 40 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
19 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D8 D15 41 3/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
20 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 42 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 8 CH
21 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH 43 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
22 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH D16 D3 44 3/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
45 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH

33 33 D1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012


33 24 D15 D15
D2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002
33 D3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001
24 5 40 D4 Item No. Not Used
1 7 D5 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004
21 9 D11 D6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020
D7 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
2 8 26 D8 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
19 D9 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
2" (DN50) 24 D10 1/2" 45° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
GROOVE x GROOVE 32 D11 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
33 1 D12 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
DV-5 DELUGE VALVE 34 D13 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
31 31 SHOWN 37
24 33
D14 1/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
39 21 D15 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH
21 D16 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
23 21 32 D17 1/2" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
26
36 33 COMPONENTS ORDERED SEPARATELY:
27 33 27
A1 Waterflow Pressure Alarm Switch,
Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710
21 A2 Low Air Pressure Alarm Switch,
35 35 3 Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730
7
36
Select Appropriate Nipple Sizes
LOCATION 38 Nipple per DV-5 Deluge Valve Size
FOR OPTIONAL Number
24 32 1-1/2" (DN40) 2" (DN50)
ELECTRICALLY 33 38 1/2" x 1-1/2" 1/2" x 2"
SUPERVISED 39 1/2" x 2" 1/2" x 1-1/2"
N.O. ALARM 29 24 40 1/2" x 5" 1/2" x 5-1/2"

CONTROL 24 17 45 3/4" x 1-1/2" 3/4" x 2-1/2"


22 42
VALVE 43 18
10 NOTES:
42 42 4 1. Dry Pilot Actuation Trim is comprised of
20 27 26 Items 1-45 plus Items D1-D17. Items A1
29 35 and A2 ordered separately.
28
42 14 2. All Fittings and Nipples are galvanized
30
35 15 (Standard Order).
(GREEN 3. CH: Common Hardware.
A1 44 TINT) 16 12
(ORDERED 4. See Figure 2 of TFP1305 for Valve Port
SEPARATELY) 42 identification.
41 5. Route all Tubing to Drip Funnel, Item 14.
11 22
6. Horizontal Arrangement uses only 7 out of
42 42 45 13 8 of Item 24, and 9 out of 10 of Item 33.
28 25 11 Discard unused material.
42

FIGURE 5 (1 OF 3)
1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 DELUGE VALVES
EXPLODED VIEW OF HORIZONTAL DRY PILOT ACTUATION TRIM
TFP1315
Page 12 of 16

NO. DESCRIPTION QTY. P/N A2 NO. DESCRIPTION QTY. P/N


D13 D6 (ORDERED
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 24 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 SEPARATELY) 25 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 D5 26 3/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 D15 27 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 28 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH
6 Item No. Not Used D15 29 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 30 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 D12 D1 31 3/4" x 3/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 32 1-1/4" x 3/4" x 1-1/4" Tee. . . . . . . . . . . . . . . 1 CH
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005
D17 33 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
11 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-005 D13 D15 D9 34 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
12 1-1/4" Angle Valve . . . . . . . . . . . . . . . . . . . . 1 46-048-1-007 35 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 13 CH
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 36 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 37 1/2" x 3-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 D12 D2 38 1/2" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 D10 D14 39 1/2" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
17 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 40 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH D7 41 1/2" x 5-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
19 1/2" x 12" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH D8 D15 42 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH
20 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 43 3/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 3 CH
21 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 44 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 5 CH
22 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH D16 D3 45 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
23 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH 46 3/4" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
47 1-1/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
48 1-1/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
35 35 25 D15 D15 D1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012
D2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002
35 D3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001
25 D11 D4 Item No. Not Used
22 9 D5 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004
34 D6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020
35 8 D7 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
42 D8 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
1 5 D9 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
7 25 35 D10 1/2" 45° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
20 37 1 D11 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
3" (DN80)
2 25 27
D12 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
GROOVE x GROOVE D13 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
35 22 D14 1/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
DV-5 DELUGE VALVE 42 D15 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH
33 SHOWN 22
33 35 27
D16 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
D17 1/2" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
35
35 28 COMPONENTS ORDERED SEPARATELY:
24 22
35 A1 Waterflow Pressure Alarm Switch,
39
28 Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710
3 A2 Low Air Pressure Alarm Switch,
22 Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730
38
40 NOTES:
7 41
34 1. Dry Pilot Actuation Trim is comprised of
LOCATION 35 25 Items 1-48 plus Items D1-D17. Items A1
FOR OPTIONAL and A2 ordered separately.
25
ELECTRICALLY 35 2. All Fittings and Nipples are galvanized
SUPERVISED 18
(Standard Order).
N.O. ALARM 30 19
25 3. CH: Common Hardware.
CONTROL 23
45 44 4. See Figure 2 of TFP1305 for Valve Port
VALVE
10 identification.
44 44 4 5. Route all Tubing to Drip Funnel, Item 15.
21 28 27 6. Horizontal Arrangement uses only 7 out of
30 29 36 8 of Item 25, and 12 out of 13 of Item 35.
44 15 Discard unused material.
31
36 16
(GREEN
A1 48 TINT) 17 13
(ORDERED
SEPARATELY) 44
43
23
12
47 43 46 14
32 26 11
43

FIGURE 5 (2 OF 3)
3 INCH (DN80) DV-5 DELUGE VALVE
EXPLODED VIEW OF HORIZONTAL DRY PILOT ACTUATION TRIM
TFP1315
Page 13 of 16

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N


1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 29 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 30 1" x 1" x 1/2" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 31 1" x 3/4" x 1" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004
A2 32 2" x 1" x 2" Tee . . . . . . . . . . . . . . . . . . . . . . . 1 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 D13 D6 (ORDERED 33 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
6 Item No. Not Used SEPARATELY) 34 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 D5 35 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 10 CH
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 36 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 3 CH
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 D15 37 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 D15 38 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH
11 1" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-006 39 1/2" x 6" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
12 2" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-009 D12 D1 40 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 41 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 D17 42 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 43 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 D13 D15 D9 44 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
17 Select Tubing per Table . . . . . . . . . . . . . . . . 1 CH 45 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH 46 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
19 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH D12 D2 47 1" x Close Nipple . . . . . . . . . . . . . . . . . . . . . 5 CH
20 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D10 D14 48 1" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
21 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 49 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
22 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH D7 50 2" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
23 1" Union . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH 51 2" x 5" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
24 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D8 D15 52 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
25 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH
26 1" 90° Elbow. . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012
27 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH D16 D3 D2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002
28 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH D3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001
D4 Item No. Not Used
D5 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004
35 35 D15 D15 D6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020
25 D7 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
D8 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
35 D9 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
25 D11 D10 1/2" 45° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
D11 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
22 9
34 D12 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
35 8 D13 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
43 D14 1/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
5 D15 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH
7 25 35
1 1 D16 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
38 D17 1/2" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
20 4" (DN100) 27 COMPONENTS ORDERED SEPARATELY:
25 35
2 22
GROOVE x GROOVE 52 A1 Waterflow Pressure Alarm Switch,
DV-5 DELUGE VALVE 22 Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710

33 SHOWN 35 27 A2 Low Air Pressure Alarm Switch,


33 Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730
35 35 28
24 22 42 Select Appropriate Tube Size
Tube per DV-5 Deluge Valve Size
38 3
28 22 No. 4" 6" 8"
(DN100) (DN150) (DN200)
39 17 1/4" x 24" 1/4" x 24" 1/4" x 32"
40
7
34 Select Appropriate Nipple Sizes
Nipple per DV-5 Deluge Valve Size
LOCATION 36 No. 4" 6" 8"
FOR OPTIONAL 41 25 (DN100) (DN150) (DN200)
25
ELECTRICALLY 35 18 37 1/2" x 3" 1/2" x 3" 1/2" x 5"
41 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8-1/2"
SUPERVISED
29 19 42 1/2" x 2" 1/2" x 3" 1/2" x 3-1/2"
N.O. ALARM 43 1/2" x 6-1/2" 1/2" x 7-1/2" 1/2" x 9"
CONTROL 25
46 23 48 46 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
VALVE 45 49 1" x 6" 1" x 9" 1" x 12"
10 52 1/2" x 7" 1/2" x 7" 1/2" x 9"
44 47 4
21 28 27 NOTES:
29 31 37 1. Dry Pilot Actuation Trim is comprised of
51 30 15 Items 1-52 plus Items D1-D17. Items A1
36 16 and A2 ordered separately.
(GREEN
50 2. All Fittings and Nipples are galvanized
A1 TINT) 17 13
(ORDERED (Standard Order).
SEPARATELY) 47 3. CH: Common Hardware.
12
47 4. See Figure 2 of TFP1305 for Valve Port
23
identification.
47 49 11 14 5. Route all Tubing to Drip Funnel, Item 15.
32 26
6. Horizontal Arrangement uses only 7 out of
47 8 of Item 25, and 2 out of 3 of Item 36.
Discard unused material.
FIGURE 5 (3 OF 3)
4, 6, AND 8 INCH (DN100, DN150, AND DN200) DV-5 DELUGE VALVES
EXPLODED VIEW OF HORIZONTAL DRY PILOT ACTUATION TRIM
TFP1315
Page 14 of 16

of approximately 45 psi (3,1 bar), which Step 4. Depress the plunger of the Au- Step 11. Slowly open the Main Con-
can typically be used for a maximum tomatic Drain Valve to verify that it is trol Valve. Close the Main Drain Valve
dry pilot actuation system pressure of open and that the DV-5 Valve is com- as soon as water discharges from the
40 psi (2,8 bar). The Pressure Relief pletely drained. drain connection. Observe the Auto-
Valve may be reset; however, it must Step 5. Clean the Strainer in the Dia- matic Drain Valve for leaks. If there are
be reset to relieve at a pressure which phragm Chamber Supply connection leaks, determine/correct the cause of
is in accordance with the requirements by removing the clean-out plug and the leakage problem. If there are no
of the authority having jurisdiction. strainer basket. The Strainer may be leaks, the DV-5 Valve is ready to be
placed in service and the Main Control
To reset the Pressure Relief Valve, first flushed out by momentarily opening
Valve must then be fully opened.
loosen the jam nut and then adjust the the Diaphragm Chamber Supply Con-
cap accordingly, clockwise for a high- trol Valve. NOTE: When the Main Control Valve
er pressure setting or counter-clock- is opened, the pressure on the Dia-
Step 6. Reset the actuation system.
wise for a lower pressure setting. After phragm Chamber may increase. This
verifying the desired pressure setting, Manual Actuation — Push the operat- increase in pressure is normal, and if
tighten the jam nut. ing lever up; however, do not close the the pressure is greater than 250 psi
hinged cover at this time. (17,2 bar), the pressure is to be relieved
Step 14. Conduit and electrical con-
Dry Pilot Actuation — Replace oper- by partially and temporarily opening
nections are to be made in accordance
ated pilot sprinklers and/or reset the the Manual Control Station; however,
with the requirements of the authority
manual control stations. Re-establish do not allow the pressure as indicated
having jurisdiction and/or the National
dry pilot pneumatic pressure. on the Diaphragm Chamber Pressure
Electric Code.
Gauge to drop below the supply pres-
Step 15. Before a system hydrostatic NOTE: In order to prevent the possi- sure shown on the Water Supply Pres-
test is performed in accordance with bility of a subsequent operation of an sure Gauge, since this action may re-
NFPA 13 system acceptance test re- over-heated solder type pilot sprinkler, sult in tripping of the DV-5 Valve.
quirements, the DV-5 Diaphragm any solder type pilot sprinklers that
were possibly exposed to a tempera- After setting a fire protection system,
Chamber is to be depressurized, the
ture greater than their maximum rated notify the proper authorities and advise
Automatic Drain Valve (Item 4, Fig. 3A
ambient must be replaced. those responsible for monitoring pro-
and 5) is to be temporarily replaced
prietary and/or central station alarms.
with a 1/2 inch NPT plug, the 3/32 Step 7. Open the Diaphragm Chamber
inch Vent Fitting (16 - Fig. 3A and 5)
is to be temporarily replaced with a
1/4 inch NPT plug, and the Diaphragm
Supply Control Valve and allow time
for full pressure to build up in the Dia- Care and
Cover Bolts must be uniformly and se-
curely tightened using a cross-draw
phragm Chamber.
Step 8. Operate (open) the Manu-
Maintenance
sequence. After tightening, double- al Control Station to vent trapped air The following procedures and inspec-
check to make certain that all of the from the Diaphragm Chamber. If nec- tions must be performed as indicated,
Diaphragm Cover Bolts are securely essary, first open the hinged cover, and in addition to any specific requirements
tightened. then fully pull down on the operating of the NFPA, and any impairment must
lever. Slowly close the operating lever, be immediately corrected.
Valve Setting by pushing it up, after aerated water
ceases to discharge from the Manual Before closing a fire protection system
main control valve for maintenance
Procedure Control Station drain tubing. Close the
hinged cover and insert a new break work on the fire protection system that
it controls, permission to shut down the
rod in the small hole through the top of
Steps 1 through 11 are to be performed the enclosing box. affected fire protection systems must
when initially setting the DV-5 Deluge first be obtained from the proper au-
Valve, after an operational test of the Step 9. Inspect the drain connections thorities and all personnel who may be
fire protection system, or after system from the Manual Control Station and affected by this action must be notified.
operation due to a fire. the Dry Pilot Actuator. Any leaks must Reset the DV-5 Deluge Valve in accor-
be corrected before proceeding to the dance with the Valve Setting Procedure
NOTE: When the system is using ei- next step. section.
ther a seawater or brackish water sup-
ply, it is recommended that the system Step 10. Verify the ability of the DV-5 The owner is responsible for the in-
be thoroughly flushed with clean fresh Diaphragm to hold pressure as follows: spection, testing, and maintenance of
water. Following this recommendation • With the Diaphragm Chamber pres- their fire protection system and devices
will increase the service life of the DV-5 surized per Step 8, temporarily in compliance with this document, as
Valve and Trim. close the Diaphragm Chamber Sup- well as with the applicable standards
ply Control Valve, and then observe of the National Fire Protection Associa-
Step 1. Close the Main Control Valve.
the Diaphragm Chamber Pressure tion (e.g., NFPA 25), in addition to the
Step 2. Close the Diaphragm Chamber Gauge for a drop in pressure. standards of any authority having juris-
Supply Control Valve, and close the Air diction. Contact the installing contrac-
Supply Control Valve (Ref. Fig. 3B). • If a drop in pressure is noted, the tor or product manufacturer with any
DV-5 Diaphragm is to be replaced questions.
Step 3. Open the Main Drain Valve, and/or any leaks must be corrected
System Drain Valve, and all auxiliary before proceeding to the next step. It is recommended that automatic
drains in the system. Close the System sprinkler systems be inspected, tested,
Drain Valve and auxiliary drain valves • If the Diaphragm Chamber Pressure and maintained by a qualified Inspec-
after water ceases to discharge. Leave Gauge indicates no drop in pressure, tion Service in accordance with local
the Main Drain Valve open. re-open the Diaphragm Chamber requirements and/or national codes.
Supply Control Valve and proceed
to the next step.
TFP1315
Page 15 of 16

NOTICE Step 3. Open the Inspector’s Test Con- Step 6. Close the Inspector’s Test Con-
Some of the procedures outlined in nection on the Dry Pilot Line. nection, and allow the Dry Pilot Line to
this section will result in operation of automatically repressurize.
Step 4. Verify that the flow of water
the associated alarms. Consequently, from the Dry Pilot Actuator drain con- Step 7. Open the Diaphragm Chamber
notification must first be given to the nection increases to a full flow. Supply Control Valve.
owner and the fire department, central
station, or other signal station to which Step 5. Verify that the Diaphragm Step 8. Slowly open the Main Con-
the alarms are connected. Chamber pressure has decreased trol Valve. Close the Main Drain Valve
to below 25% of the water supply as soon as water discharges from the
When the system is using either a sea- pressure. drain connection. Observe the Au-
water or brackish water supply, inter- tomatic Drain Valve for leaks. If there
nal and external inspection of the DV-5 Step 6. Close the Inspector’s Test
are leaks, determine/correct the cause
Valve and Trim is essential. Parts show- Connection and allow the dry pilot line
of the leakage problem. If there are
ing any signs of corrosion must be re- pressure to re-establish. Check the Dry
no leaks, fully open the Main Control
placed to ensure the integrity of the Pilot Actuator drain for leaks. Any leaks
Valve.
system. must be corrected before proceeding
to the next step.
Annual Operation Test Procedure Step 7. Slowly open the Main Con-
Proper operation of the DV-5 Valve (i.e., trol Valve. Close the Main Drain Valve
opening of the DV-5 Valve as during a as soon as water discharges from the
fire condition) must be verified at least drain connection. Observe the Auto-
once a year as follows: matic Drain Valve for leaks. If there are
Step 1. If water must be prevented leaks, determine/correct the cause of
from flowing beyond the riser, perform the leakage problem. If there are no
the following steps: leaks, the DV-5 Valve is ready to be
placed in service and the Main Control
• Close the Main Control Valve. Valve must then be fully opened.
• Open the Main Drain Valve.
Quarterly Low Pressure Alarm Test
• Open the Main Control Valve one turn Procedure and Condensate Drain
beyond the position at which water Procedure for Dry Pilot Actuation
just begins to flow from the Main For Dry Pilot Actuation, testing of the
Drain Valve. Low Pressure Alarm Switch and drain-
• Close the Main Drain Valve. age of the pilot line condensate must
be performed quarterly as follows.
Step 2. Open the Inspector’s Test
Connection. Step 1. Close the Main Control Valve.
NOTE: Be prepared to quickly perform Step 2. Close the Diaphragm Chamber
Steps 3, 4, and 5 if water must be pre- Supply Control Valve.
vented from flowing beyond the riser. Step 3. Open the Main Drain Valve.
Step 3. Verify that the DV-5 Valve has Step 4. Drain the dry pilot line conden-
tripped, as indicated by the flow of wa- sate as follows:
ter into the system.
• Close the Gauge Test Valve locat-
Step 4. Close the Diaphragm Chamber ed below the Dry Pilot Line Pressure
Supply Control Valve. Gauge.
Step 5. Close the system’s Main Con- • Remove the 1/4 inch Plug from the
trol Valve. Gauge Test Valve.
Step 6. Reset the DV-5 Deluge Valve • Crack Open the Gauge Test Valve
in accordance with the Valve Setting and allow all condensate, if any, to
Procedure. drain out.
Quarterly Waterflow Alarm Test • Close the Gauge Test Valve, replace
Procedure the Plug, and then open the Gauge
Testing of the system waterflow alarms Test Valve.
must be performed quarterly. To test Step 5. Open the Inspector’s Test Con-
the waterflow alarm, open the Alarm nection, and slowly relieve pneumatic
Test Valve, which will allow a flow of pressure. Verify that the Low pres-
water to the Pressure Alarm Switch sure Alarm Switch is operational and
and/or Water Motor Alarm. Upon sat- that the low pressure set points are as
isfactory completion of the test, close follows:
the Alarm Test Valve.
• Low pressure alarm setting at ap-
Quarterly Dry Pilot Actuator Test proximately 6 psi (0,4 bar) below the
Procedure for Dry Pilot Actuation minimum pilot line service pressure
Proper operation of the Dry Pilot Ac- requirement shown in Graph A.
tuator for dry pilot actuation must be
verified at least quarterly as follows: • Fire alarm setting at approximately
15 psi (1,0 bar) below the minimum
Step 1. Close the Main Control Valve. pilot line service pressure require-
Step 2. Open the Main Drain Valve. ment shown in Graph A.
TFP1315
Page 16 of 16

Limited DV-5 Pre-trimmed Assembly Dry


Pilot Actuation Trim
Warranty without Butterfly Valve
Specify: (specify size), (specify) End
For warranty terms and conditions, visit Connection, Pre-trimmed DV-5 As-
www.tyco-fire.com. sembly without Butterfly Valve, P/N
(specify):

Ordering 1-1/2 Inch T x T . . . . . . . . . . . . P/N 52-912-3-1AP


2 Inch T x T . . . . . . . . . . . . . . . P/N 52-922-3-1AP

Procedure
3 Inch F x F . . . . . . . . . . . . . . . P/N 52-932-1-1AP
3 Inch F x G . . . . . . . . . . . . . . . P/N 52-932-2-1AP
4 Inch F x F . . . . . . . . . . . . . . . P/N 52-942-1-1AP
NOTE: Part Numbers for factory pre- 4 Inch F x G . . . . . . . . . . . . . . . P/N 52-942-2-1AP
trimmed DV-5 Valves are provided in 6 Inch F x F . . . . . . . . . . . . . . . P/N 52-962-1-1AP
6 Inch F x G . . . . . . . . . . . . . . . P/N 52-962-2-1AP
the Price Book. 8 Inch F x F . . . . . . . . . . . . . . . P/N 52-982-1-1AP
8 Inch F x G . . . . . . . . . . . . . . . P/N 52-982-2-1AP
DV-5 Semi-Pre-assembled Vertical
Dry Pilot Actuation Trim Accessories
Specify: (specify size and finish — gal- Refer to the Technical Data Sheets for
vanized is standard) Semi-Preassem- the following, as applicable, for details
bled Vertical Dry Pilot Actuation Trim and additional accessories:
for DV-5 Deluge Valves, P/N (specify): 600 psi Water
Pressure Gauge . . . . . . . . . . . P/N 92-343-1-004
1-1/2 & 2 Inch Galvanized . . . . P/N 52-477-2-308 Model PS10-2
1-1/2 & 2 Inch Black . . . . . . . . P/N 52-477-1-308 Potter Electric
1-1/2 & 2 Inch Brass . . . . . . . . P/N 52-477-3-308 Waterflow
Pressure
3 Inch Galvanized . . . . . . . . . . P/N 52-477-2-105 Alarm Switch . . . . . . . . . . . . . . . . . . . . P/N 25710
3 Inch Black . . . . . . . . . . . . . . P/N 52-477-1-105 Model PS40-2
3 Inch Brass . . . . . . . . . . . . . . P/N 52-477-3-105 Potter Electric
Dry Pilot Low Air
Pressure
4, 6 & 8 Inch Galvanized . . . . . P/N 52-477-2-302 Alarm Switch . . . . . . . . . . . . . . . . . . . . P/N 25730
4, 6 & 8 Inch Black . . . . . . . . . P/N 52-477-1-302 Model WMA-1 Water
4, 6 & 8 Inch Brass . . . . . . . . . P/N 52-477-3-302 Motor Alarm . . . . . . . . . . . . . P/N 52-630-1-001P
Model AMD-1
DV-5 Unassembled Dry Pilot Air Maint. Device . . . . . . . . . . . P/N 52-324-2-002
Actuation Trim for Vertical or Model AMD-2
Air Maint. Device . . . . . . . . . . . P/N 52-326-2-001
Horizontal Installation Model AMD-3
Specify: (specify size and finish — gal- Nitrogen
vanized is standard) Unassembled Maint. Device. . . . . . . . . . . . . . P/N 52-328-2-001
Dry Pilot Actuation Trim for vertical or Model MC-1
horizontal installation of DV-5 Deluge Manual Control
Stations with
Valves, P/N (specify): galvanized
1-1/2 & 2 Inch Galvanized . . . . P/N 52-477-2-208 connections for
1-1/2 & 2 Inch Black . . . . . . . . P/N 52-477-1-208 remote dry pilot
1-1/2 & 2 Inch Brass . . . . . . . . P/N 52-477-3-208 actuation . . . . . . . . . . . . . . . . . P/N 52-289-2-001
Replacement Trim Parts
3 Inch Galvanized . . . . . . . . . . P/N 52-477-2-205 Specify: (description) for use with DV-5
3 Inch Black . . . . . . . . . . . . . . P/N 52-477-1-205 Deluge Valve, P/N (see Figure 3A or 5).
3 Inch Brass . . . . . . . . . . . . . . P/N 52-477-3-205

4, 6 & 8 Inch Galvanized . . . . . P/N 52-477-2-202


4, 6 & 8 Inch Black . . . . . . . . . P/N 52-477-1-202
4, 6 & 8 Inch Brass . . . . . . . . . P/N 52-477-3-202
DV-5 Pre-trimmed Assembly Dry
Pilot Actuation Trim
with Butterfly Valve
Specify: (size), G x G End Connection,
Pre-trimmed DV-5 Assembly with But-
terfly Valve, P/N (specify):
1-1/2 Inch G x G . . . . . . . . . . . P/N 52-912-0-1AP
2 Inch G x G . . . . . . . . . . . . . P/N 52-922-0-1AP
3 Inch G X G . . . . . . . . . . . . . P/N 52-932-0-1AP
4 Inch G x G . . . . . . . . . . . . . P/N 52-942-0-1AP
6 Inch G x G . . . . . . . . . . . . . P/N 52-962-0-1AP
8 Inch G x G . . . . . . . . . . . . . P/N 52-982-0-1AP

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright © 2014 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of the DuPont Corporation.

You might also like