1 - DV-5 Deluge Valve 7 - Water Supply Pressure Gauge 12 - Waterflow Pressure Alarm Switch
2 - Main Control Valve (N.O.) 8 - Diaphragm Chamber Pressure (Shown at Rear of Valve)
3 - Diaphragm Chamber Supply Gauge 13 - Water Motor Alarm (Optional)
Control Valve (N.O.) 9 - System Drain Valve (N.C.) 14 - Dry Pilot Actuator
4 - Local Manual Control Station 10 - Main Drain Valve (N.C.) 15 - Low Pressure Alarm Switch
5 - Open Nozzles or Sprinklers (Shown at Rear of Valve) 16 - Automatic Air/Nitrogen Supply
6 - Dry Pilot Line Sprinklers 11 - Diaphragm Chamber Automatic
(Fire Detection) Shut-Off Valve
FIGURE 1 (1 OF 2)
SYSTEM SCHEMATIC (FRONT VIEW)
DRY PILOT ACTUATION
TFP1315
Page 3 of 16
15
13
11
14
12
3
16
10
1
1 - DV-5 Deluge Valve 7 - Water Supply Pressure Gauge 13 - Water Motor Alarm (Optional)
2 - Main Control Valve (N.O.) (Shown at Front of Valve) 14 - Dry Pilot Actuator
3 - Diaphragm Chamber Supply 8 - Diaphragm Chamber Pressure 15 - Low Pressure Alarm Switch
Control Valve (N.O.) Gauge (Shown at Front of Valve)
16 - Automatic Air/Nitrogen Supply
4 - Local Manual Control Station 9 - System Drain Valve (N.C.)
(Shown at Front of Valve) 10 - Main Drain Valve (N.C.)
5 - Open Nozzles or Sprinklers 11 - Diaphragm Chamber Automatic
6 - Dry Pilot Line Sprinklers Shut-Off Valve
(Fire Detection) 12 - Waterflow Pressure Alarm Switch
FIGURE 1 (2 OF 2)
SYSTEM SCHEMATIC (REAR VIEW)
DRY PILOT ACTUATION
TFP1315
Page 4 of 16
NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 31 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH D15 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 32 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 3 CH D16 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 33 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 10 CH D17 1/2" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 34 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 35 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 4 CH COMPONENTS INCLUDED ONLY IN
6 Item No. Not Used 36 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH PRE-TRIMMED VALVE ASSEMBLIES:
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 37 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH A1 Waterflow Pressure Alarm Switch,
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 38 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 39 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH A2 Low Air Pressure Alarm Switch,
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 40 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730
11 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 2 46-048-1-005 41 3/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 1 CH A3 Butterfly Valve, Power Ball 300:
12 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 42 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 8 CH 1-1/2" (DN40) . . . . . . . . . . . . . . . . . . . . . . . . 1 51024A
13 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 43 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH 2" (DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 51021A
14 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 44 3/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH A4 Figure 577 Coupling:
15 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 45 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH 1-1/2" (DN40) . . . . . . . . . . . . . . . . . . . . . . . . 1 57715ACP
16 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 2" (DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 57720ACP
17 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH D1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012
18 1/2" x 12" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH D2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002
19 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001 D5
20 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D4 Item No. Not Used
21 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH D5 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004 D15 D6 A2
22 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH D6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020
23 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D7 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
24 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH D8 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH D15 D1
25 3/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D9 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
26 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH D10 1/2" 45° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D13
27 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH D11 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D12
28 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH D12 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
29 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH D13 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH D17 D9
30 3/4" x 3/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH D14 1/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
D13 D15
D12 D2
16 11 D10
41 D14
A1 D8
30
27 42 45 D15
15 D16
29 (GREEN 24 D7 D15 D3
LOCATION 20 TINT) 35
FOR OPTIONAL 4
ELECTRICALLY 35 28 42 33 D11 D15
SUPERVISED 42 22 21
N.O. ALARM 43 36 21 32
CONTROL 42 25 33
VALVE 42
22 26
33 10 26
42 42 24 40
24 42 35 24 24
29 12 1
14 26
38 28 33 32
11 44 33 27
7
13 37
35 1 5 33 3
A4
NOTES:
21 8
1. Dry Pilot Actuation Trim is 19 2 21
comprised of Items 1-45 A3
36 24 32
plus Items D1-D17. Items 34
A1-A4 included only in 39 18
pre-trimmed valve assemblies 9
31 27 33 17
33 24 24
as applicable; otherwise
31 33
ordered separately. 23 2" (DN50)
2. All Fittings and Nipples are GROOVE x GROOVE Nipple
Select Appropriate Nipple Sizes
galvanized (Standard Order). DV-5 DELUGE VALVE 21 Number
per DV-5 Deluge Valve Size
1-1/2" (DN40) 2" (DN50)
3. CH: Common Hardware. SHOWN 38 1/2" x 1-1/2" 1/2" x 2"
4. See Figure 2 of TFP1305 for 33 39 1/2" x 2" 1/2" x 1-1/2"
40 1/2" x 5" 1/2" x 5-1/2"
Valve Port identification.
45 3/4" x 1-1/2" 3/4" x 2-1/2"
5. Route all Tubing to Drip Funnel, 7
Item 14.
FIGURE 3A (1 OF 3)
1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 DELUGE VALVES
EXPLODED VIEW OF VERTICAL DRY PILOT ACTUATION TRIM
TFP1315
Page 6 of 16
NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 32 1-1/4" x 3/4" x 1-1/4" Tee. . . . . . . . . . . . . . . 1 CH D14 1/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 33 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH D15 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 34 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH D16 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 35 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 13 CH D17 1/2" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 36 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
6 Item No. Not Used 37 1/2" x 3-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH COMPONENTS INCLUDED ONLY IN
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 38 1/2" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH PRE-TRIMMED VALVE ASSEMBLIES:
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 39 1/2" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH A1 Waterflow Pressure Alarm Switch,
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 40 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 41 1/2" x 5-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH A2 Low Air Pressure Alarm Switch,
11 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-005 42 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730
12 1-1/4" Angle Valve . . . . . . . . . . . . . . . . . . . . 1 46-048-1-007 43 3/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 3 CH A3 Model BFV-N Butterfly Valve, 3" (DN80) . . . 1 59300F030N
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 44 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 5 CH A4 Figure 577 Coupling, 3" (DN80) . . . . . . . . . . 1 57730ACP
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 45 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 46 3/4" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 47 1-1/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
17 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 48 1-1/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH D5
18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
19 1/2" x 12" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH D1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012 D15 D6 A2
20 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002
21 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001
22 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH D4 Item No. Not Used D15 D1
23 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH D5 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004
24 1/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020 D13
25 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 8 CH D7 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
26 3/4" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D8 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH D12
27 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH D9 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D17 D9
28 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH D10 1/2" 45° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
29 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH D11 1/2" 90° Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH D13 D15
30 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH D12 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 2 CH
31 3/4" x 3/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH D13 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
D12 D2
D10
17 11 D14
43 D8
A1
31
D15
28 44 46 D16
16 25
30 D7 D15 D3
(GREEN
LOCATION 21 TINT)
FOR OPTIONAL 36 26 35
D11 D15
ELECTRICALLY 36 29
SUPERVISED 44 22
23 27 4 41 22 35
N.O. ALARM 45 35
CONTROL 44 43
VALVE 44 27
23 38
35 10 25 42
43 13
44 25 25
25 15 1
30 27
35 35 34
32 35 28
7 47 48 14
42
12 5 35 3
40
NOTES: 1
8
1. Dry Pilot Actuation Trim is 22
comprised of Items 1-48 22
20 2 A4
25 34
plus Items D1-D17. Items 37
A1-A4 included only in 19
39 A3 9
pre-trimmed valve assemblies 35 18
35 25 25
as applicable; otherwise 35
33 28 35
ordered separately.
2. All Fittings and Nipples are 33
24
galvanized (Standard Order). 3" (DN80) 22
3. CH: Common Hardware. GROOVE x GROOVE
DV-5 DELUGE VALVE 35
4. See Figure 2 of TFP1305 for
SHOWN
Valve Port identification.
5. Route all Tubing to Drip Funnel, 7
Item 15.
FIGURE 3A (2 OF 3)
3 INCH (DN80) DV-5 DELUGE VALVE
EXPLODED VIEW OF VERTICAL DRY PILOT ACTUATION TRIM
TFP1315
Page 7 of 16
NOTES: Nipple Select Appropriate Nipple and Tube Sizes per DV-5 Deluge Valve Size
1. Install subassemblies in alphabetical order. Number 1-1/2" (DN40) 2" (DN50) 3" (DN80) 4" (DN100) 6" (DN150) 8" (DN200)
2. See Figure 2 of TFP1305 for Valve Port 1 1/2" x Close 1/2" x 2" 1/2" x 1-1/2" 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8-1/2"
identification.
2 1/2" x Close 1/2" x Close 1/2" x 1-1/2" 1/2" x 2" 1/2" x 3" 1/2" x 3-1/2"
3. Route all Tubing to Drip Funnel.
3 1/2" x 5" 1/2" x 5-1/2" 1/2" x 7" 1/2" x 6-1/2" 1/2" x 7-1/2" 1/2" x 9"
4. When DV-5 trips, Automatic Shut-Off Valve
4 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
shuts off diaphragm chamber supply.
5 3/4" x 1-1/2" 3/4" x 2-1/2" 3/4" x 4-1/2" 1" x 6" 1" x 9" 1" x 12"
5. Nipples 1-7 and Tube 1 vary in length relative
to DV-5 size. Select per table. All other nipples 6 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 3" 1/2" x 3" 1/2" x 5"
and tubing packed unassembled shall be 7 1/2" x 7" 1/2" x 7" 1/2" x 7" 1/2" x 7" 1/2" x 7" 1/2" x 9"
installed per appropriate trim exploded view, Main Drain
Figure 3A Part 1, 2, or 3. 3/4" NPT 3/4" NPT 1-1/4" NPT 2" NPT 2" NPT 2" NPT
Size
Tube 1 1/4" x 18" 1/4" x 18" 1/4" x 18" 1/4" x 24" 1/4" x 24" 1/4" x 32"
WATERFLOW
PRESSURE ALARM VENT FITTING
(GREEN TINT)
SWITCH, ORDERED
1/2 INCH NPT
SEPARATELY CONNECTION LOW AIR
SYSTEM
TUBE 1 DRAIN VALVE 1/2 INCH NPT FOR "DRY PILOT PRESSURE
3/4 INCH NPT (NORMALLY CONNECTION DETECTION" ALARM SWITCH,
CONNECTION FOR CLOSED) FOR DRY PILOT ORDERED
B SEPARATELY
WATER MOTOR AIR SUPPLY
ALARM NIPPLE
4 DRY
AUTOMATIC PILOT LINE
LOCATION DRY PILOT PRESSURE
DRAIN VALVE
FOR OPTIONAL AIR SUPPLY GAUGE
CONTROL VALVE E
ELECTRICALLY
SUPERVISED NIPPLE (NORMALLY DRY PILOT
N.O. ALARM NIPPLE 5 OPEN) ACTUATOR
CONTROL 6 (NORMALLY
VALVE CLOSED)
4" (DN100)
DRIP
FLANGE x FLANGE
FUNNEL
NIPPLE DV-5 DELUGE NIPPLE
1 VALVE SHOWN 2
1-1/4 INCH NPT
CONNECTION NIPPLE
TO DRAIN 3
MAIN A
DRAIN VALVE DIAPHRAGM
(NORMALLY D CHAMBER
CLOSED) PRESSURE
GAUGE
ALARM MAIN DRAIN NIPPLE
TEST VALVE CONNECTION 7
(NORMALLY (SIZED PER MANUAL
CLOSED) TABLE) CONTROL
STATION
SYSTEM
WATER C AUTOMATIC
SUPPLY DIAPHRAGM
CHAMBER SUPPLY SHUT-OFF VALVE
PRESSURE (NORMALLY
GAUGE CONTROL VALVE
(NORMALLY OPEN)
OPEN) 1/2 INCH NPT
CONNECTION FROM
WATER SUPPLY
FIGURE 3B
1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 DELUGE VALVES
OPERATIONAL COMPONENTS OF VERTICAL DRY PILOT ACTUATION TRIM
EXPLODED ARRANGEMENT OF SEMI-PREASSEMBLED TRIM
TFP1315
Page 9 of 16
* MINIMUM CLEARANCE
A* B C* D*
E*
M
L
N
F
H K
G J
FIGURE 5 (1 OF 3)
1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 DELUGE VALVES
EXPLODED VIEW OF HORIZONTAL DRY PILOT ACTUATION TRIM
TFP1315
Page 12 of 16
FIGURE 5 (2 OF 3)
3 INCH (DN80) DV-5 DELUGE VALVE
EXPLODED VIEW OF HORIZONTAL DRY PILOT ACTUATION TRIM
TFP1315
Page 13 of 16
of approximately 45 psi (3,1 bar), which Step 4. Depress the plunger of the Au- Step 11. Slowly open the Main Con-
can typically be used for a maximum tomatic Drain Valve to verify that it is trol Valve. Close the Main Drain Valve
dry pilot actuation system pressure of open and that the DV-5 Valve is com- as soon as water discharges from the
40 psi (2,8 bar). The Pressure Relief pletely drained. drain connection. Observe the Auto-
Valve may be reset; however, it must Step 5. Clean the Strainer in the Dia- matic Drain Valve for leaks. If there are
be reset to relieve at a pressure which phragm Chamber Supply connection leaks, determine/correct the cause of
is in accordance with the requirements by removing the clean-out plug and the leakage problem. If there are no
of the authority having jurisdiction. strainer basket. The Strainer may be leaks, the DV-5 Valve is ready to be
placed in service and the Main Control
To reset the Pressure Relief Valve, first flushed out by momentarily opening
Valve must then be fully opened.
loosen the jam nut and then adjust the the Diaphragm Chamber Supply Con-
cap accordingly, clockwise for a high- trol Valve. NOTE: When the Main Control Valve
er pressure setting or counter-clock- is opened, the pressure on the Dia-
Step 6. Reset the actuation system.
wise for a lower pressure setting. After phragm Chamber may increase. This
verifying the desired pressure setting, Manual Actuation — Push the operat- increase in pressure is normal, and if
tighten the jam nut. ing lever up; however, do not close the the pressure is greater than 250 psi
hinged cover at this time. (17,2 bar), the pressure is to be relieved
Step 14. Conduit and electrical con-
Dry Pilot Actuation — Replace oper- by partially and temporarily opening
nections are to be made in accordance
ated pilot sprinklers and/or reset the the Manual Control Station; however,
with the requirements of the authority
manual control stations. Re-establish do not allow the pressure as indicated
having jurisdiction and/or the National
dry pilot pneumatic pressure. on the Diaphragm Chamber Pressure
Electric Code.
Gauge to drop below the supply pres-
Step 15. Before a system hydrostatic NOTE: In order to prevent the possi- sure shown on the Water Supply Pres-
test is performed in accordance with bility of a subsequent operation of an sure Gauge, since this action may re-
NFPA 13 system acceptance test re- over-heated solder type pilot sprinkler, sult in tripping of the DV-5 Valve.
quirements, the DV-5 Diaphragm any solder type pilot sprinklers that
were possibly exposed to a tempera- After setting a fire protection system,
Chamber is to be depressurized, the
ture greater than their maximum rated notify the proper authorities and advise
Automatic Drain Valve (Item 4, Fig. 3A
ambient must be replaced. those responsible for monitoring pro-
and 5) is to be temporarily replaced
prietary and/or central station alarms.
with a 1/2 inch NPT plug, the 3/32 Step 7. Open the Diaphragm Chamber
inch Vent Fitting (16 - Fig. 3A and 5)
is to be temporarily replaced with a
1/4 inch NPT plug, and the Diaphragm
Supply Control Valve and allow time
for full pressure to build up in the Dia- Care and
Cover Bolts must be uniformly and se-
curely tightened using a cross-draw
phragm Chamber.
Step 8. Operate (open) the Manu-
Maintenance
sequence. After tightening, double- al Control Station to vent trapped air The following procedures and inspec-
check to make certain that all of the from the Diaphragm Chamber. If nec- tions must be performed as indicated,
Diaphragm Cover Bolts are securely essary, first open the hinged cover, and in addition to any specific requirements
tightened. then fully pull down on the operating of the NFPA, and any impairment must
lever. Slowly close the operating lever, be immediately corrected.
Valve Setting by pushing it up, after aerated water
ceases to discharge from the Manual Before closing a fire protection system
main control valve for maintenance
Procedure Control Station drain tubing. Close the
hinged cover and insert a new break work on the fire protection system that
it controls, permission to shut down the
rod in the small hole through the top of
Steps 1 through 11 are to be performed the enclosing box. affected fire protection systems must
when initially setting the DV-5 Deluge first be obtained from the proper au-
Valve, after an operational test of the Step 9. Inspect the drain connections thorities and all personnel who may be
fire protection system, or after system from the Manual Control Station and affected by this action must be notified.
operation due to a fire. the Dry Pilot Actuator. Any leaks must Reset the DV-5 Deluge Valve in accor-
be corrected before proceeding to the dance with the Valve Setting Procedure
NOTE: When the system is using ei- next step. section.
ther a seawater or brackish water sup-
ply, it is recommended that the system Step 10. Verify the ability of the DV-5 The owner is responsible for the in-
be thoroughly flushed with clean fresh Diaphragm to hold pressure as follows: spection, testing, and maintenance of
water. Following this recommendation • With the Diaphragm Chamber pres- their fire protection system and devices
will increase the service life of the DV-5 surized per Step 8, temporarily in compliance with this document, as
Valve and Trim. close the Diaphragm Chamber Sup- well as with the applicable standards
ply Control Valve, and then observe of the National Fire Protection Associa-
Step 1. Close the Main Control Valve.
the Diaphragm Chamber Pressure tion (e.g., NFPA 25), in addition to the
Step 2. Close the Diaphragm Chamber Gauge for a drop in pressure. standards of any authority having juris-
Supply Control Valve, and close the Air diction. Contact the installing contrac-
Supply Control Valve (Ref. Fig. 3B). • If a drop in pressure is noted, the tor or product manufacturer with any
DV-5 Diaphragm is to be replaced questions.
Step 3. Open the Main Drain Valve, and/or any leaks must be corrected
System Drain Valve, and all auxiliary before proceeding to the next step. It is recommended that automatic
drains in the system. Close the System sprinkler systems be inspected, tested,
Drain Valve and auxiliary drain valves • If the Diaphragm Chamber Pressure and maintained by a qualified Inspec-
after water ceases to discharge. Leave Gauge indicates no drop in pressure, tion Service in accordance with local
the Main Drain Valve open. re-open the Diaphragm Chamber requirements and/or national codes.
Supply Control Valve and proceed
to the next step.
TFP1315
Page 15 of 16
NOTICE Step 3. Open the Inspector’s Test Con- Step 6. Close the Inspector’s Test Con-
Some of the procedures outlined in nection on the Dry Pilot Line. nection, and allow the Dry Pilot Line to
this section will result in operation of automatically repressurize.
Step 4. Verify that the flow of water
the associated alarms. Consequently, from the Dry Pilot Actuator drain con- Step 7. Open the Diaphragm Chamber
notification must first be given to the nection increases to a full flow. Supply Control Valve.
owner and the fire department, central
station, or other signal station to which Step 5. Verify that the Diaphragm Step 8. Slowly open the Main Con-
the alarms are connected. Chamber pressure has decreased trol Valve. Close the Main Drain Valve
to below 25% of the water supply as soon as water discharges from the
When the system is using either a sea- pressure. drain connection. Observe the Au-
water or brackish water supply, inter- tomatic Drain Valve for leaks. If there
nal and external inspection of the DV-5 Step 6. Close the Inspector’s Test
are leaks, determine/correct the cause
Valve and Trim is essential. Parts show- Connection and allow the dry pilot line
of the leakage problem. If there are
ing any signs of corrosion must be re- pressure to re-establish. Check the Dry
no leaks, fully open the Main Control
placed to ensure the integrity of the Pilot Actuator drain for leaks. Any leaks
Valve.
system. must be corrected before proceeding
to the next step.
Annual Operation Test Procedure Step 7. Slowly open the Main Con-
Proper operation of the DV-5 Valve (i.e., trol Valve. Close the Main Drain Valve
opening of the DV-5 Valve as during a as soon as water discharges from the
fire condition) must be verified at least drain connection. Observe the Auto-
once a year as follows: matic Drain Valve for leaks. If there are
Step 1. If water must be prevented leaks, determine/correct the cause of
from flowing beyond the riser, perform the leakage problem. If there are no
the following steps: leaks, the DV-5 Valve is ready to be
placed in service and the Main Control
• Close the Main Control Valve. Valve must then be fully opened.
• Open the Main Drain Valve.
Quarterly Low Pressure Alarm Test
• Open the Main Control Valve one turn Procedure and Condensate Drain
beyond the position at which water Procedure for Dry Pilot Actuation
just begins to flow from the Main For Dry Pilot Actuation, testing of the
Drain Valve. Low Pressure Alarm Switch and drain-
• Close the Main Drain Valve. age of the pilot line condensate must
be performed quarterly as follows.
Step 2. Open the Inspector’s Test
Connection. Step 1. Close the Main Control Valve.
NOTE: Be prepared to quickly perform Step 2. Close the Diaphragm Chamber
Steps 3, 4, and 5 if water must be pre- Supply Control Valve.
vented from flowing beyond the riser. Step 3. Open the Main Drain Valve.
Step 3. Verify that the DV-5 Valve has Step 4. Drain the dry pilot line conden-
tripped, as indicated by the flow of wa- sate as follows:
ter into the system.
• Close the Gauge Test Valve locat-
Step 4. Close the Diaphragm Chamber ed below the Dry Pilot Line Pressure
Supply Control Valve. Gauge.
Step 5. Close the system’s Main Con- • Remove the 1/4 inch Plug from the
trol Valve. Gauge Test Valve.
Step 6. Reset the DV-5 Deluge Valve • Crack Open the Gauge Test Valve
in accordance with the Valve Setting and allow all condensate, if any, to
Procedure. drain out.
Quarterly Waterflow Alarm Test • Close the Gauge Test Valve, replace
Procedure the Plug, and then open the Gauge
Testing of the system waterflow alarms Test Valve.
must be performed quarterly. To test Step 5. Open the Inspector’s Test Con-
the waterflow alarm, open the Alarm nection, and slowly relieve pneumatic
Test Valve, which will allow a flow of pressure. Verify that the Low pres-
water to the Pressure Alarm Switch sure Alarm Switch is operational and
and/or Water Motor Alarm. Upon sat- that the low pressure set points are as
isfactory completion of the test, close follows:
the Alarm Test Valve.
• Low pressure alarm setting at ap-
Quarterly Dry Pilot Actuator Test proximately 6 psi (0,4 bar) below the
Procedure for Dry Pilot Actuation minimum pilot line service pressure
Proper operation of the Dry Pilot Ac- requirement shown in Graph A.
tuator for dry pilot actuation must be
verified at least quarterly as follows: • Fire alarm setting at approximately
15 psi (1,0 bar) below the minimum
Step 1. Close the Main Control Valve. pilot line service pressure require-
Step 2. Open the Main Drain Valve. ment shown in Graph A.
TFP1315
Page 16 of 16
Procedure
3 Inch F x F . . . . . . . . . . . . . . . P/N 52-932-1-1AP
3 Inch F x G . . . . . . . . . . . . . . . P/N 52-932-2-1AP
4 Inch F x F . . . . . . . . . . . . . . . P/N 52-942-1-1AP
NOTE: Part Numbers for factory pre- 4 Inch F x G . . . . . . . . . . . . . . . P/N 52-942-2-1AP
trimmed DV-5 Valves are provided in 6 Inch F x F . . . . . . . . . . . . . . . P/N 52-962-1-1AP
6 Inch F x G . . . . . . . . . . . . . . . P/N 52-962-2-1AP
the Price Book. 8 Inch F x F . . . . . . . . . . . . . . . P/N 52-982-1-1AP
8 Inch F x G . . . . . . . . . . . . . . . P/N 52-982-2-1AP
DV-5 Semi-Pre-assembled Vertical
Dry Pilot Actuation Trim Accessories
Specify: (specify size and finish — gal- Refer to the Technical Data Sheets for
vanized is standard) Semi-Preassem- the following, as applicable, for details
bled Vertical Dry Pilot Actuation Trim and additional accessories:
for DV-5 Deluge Valves, P/N (specify): 600 psi Water
Pressure Gauge . . . . . . . . . . . P/N 92-343-1-004
1-1/2 & 2 Inch Galvanized . . . . P/N 52-477-2-308 Model PS10-2
1-1/2 & 2 Inch Black . . . . . . . . P/N 52-477-1-308 Potter Electric
1-1/2 & 2 Inch Brass . . . . . . . . P/N 52-477-3-308 Waterflow
Pressure
3 Inch Galvanized . . . . . . . . . . P/N 52-477-2-105 Alarm Switch . . . . . . . . . . . . . . . . . . . . P/N 25710
3 Inch Black . . . . . . . . . . . . . . P/N 52-477-1-105 Model PS40-2
3 Inch Brass . . . . . . . . . . . . . . P/N 52-477-3-105 Potter Electric
Dry Pilot Low Air
Pressure
4, 6 & 8 Inch Galvanized . . . . . P/N 52-477-2-302 Alarm Switch . . . . . . . . . . . . . . . . . . . . P/N 25730
4, 6 & 8 Inch Black . . . . . . . . . P/N 52-477-1-302 Model WMA-1 Water
4, 6 & 8 Inch Brass . . . . . . . . . P/N 52-477-3-302 Motor Alarm . . . . . . . . . . . . . P/N 52-630-1-001P
Model AMD-1
DV-5 Unassembled Dry Pilot Air Maint. Device . . . . . . . . . . . P/N 52-324-2-002
Actuation Trim for Vertical or Model AMD-2
Air Maint. Device . . . . . . . . . . . P/N 52-326-2-001
Horizontal Installation Model AMD-3
Specify: (specify size and finish — gal- Nitrogen
vanized is standard) Unassembled Maint. Device. . . . . . . . . . . . . . P/N 52-328-2-001
Dry Pilot Actuation Trim for vertical or Model MC-1
horizontal installation of DV-5 Deluge Manual Control
Stations with
Valves, P/N (specify): galvanized
1-1/2 & 2 Inch Galvanized . . . . P/N 52-477-2-208 connections for
1-1/2 & 2 Inch Black . . . . . . . . P/N 52-477-1-208 remote dry pilot
1-1/2 & 2 Inch Brass . . . . . . . . P/N 52-477-3-208 actuation . . . . . . . . . . . . . . . . . P/N 52-289-2-001
Replacement Trim Parts
3 Inch Galvanized . . . . . . . . . . P/N 52-477-2-205 Specify: (description) for use with DV-5
3 Inch Black . . . . . . . . . . . . . . P/N 52-477-1-205 Deluge Valve, P/N (see Figure 3A or 5).
3 Inch Brass . . . . . . . . . . . . . . P/N 52-477-3-205