Design Guide For Short Circuit Calculation Generation System PDF
Design Guide For Short Circuit Calculation Generation System PDF
Design Guide For Short Circuit Calculation Generation System PDF
DESIGN GUIDE
FOR
FLOPPY NO : TCE.M6-EL-CD-DOC-003
FILE NAME : M6-700-6621.DOC
REV.NO R0 ISSUE
DATE 1992.03.30
REVISION
ISSUE
R0
CONTENT
1.0 SCOPE 1
4.0 DATA 1
5.0 PROCEDURE 2
6.0 DISCUSSION 3
7.0 REFERENCE 3
ISSUE
R0
1.0 SCOPE
1.1 The scope of this design guide is to provide a detailed method to calculate the fault
currents when a 3 phase fault occurs at any point in the following sections of the
power plant electrical network.
b) The unit auxiliary transformer section consisting of tap off section of the
busduct upto the unit auxiliary transformer.
1.2 The fault currents calculated would be required to assign the rating of the
equipment operating in the electrical network indicated above such as Extra High
Voltage Circuit Breaker, Bus Duct and Generator Circuit Breaker (if provided)
GT : Generator Transformer
UAT : Unit Auxiliary Transformer
EHVCB: Extra High Voltage Circuit Breaker
GCB : Generator Circuit Breaker
SEB : State Electricity Board
pu : Per Unit
3.1 A schematic diagram indicating the equipment such as Generator, GT, UAT,
EHVCB and GCB is given in Annexure-1.
4.0 DATA
4.1 GRID : Following details/data of the grid to which the generator is connected are
required.
ISSUE
R0
4.2 Generator
4.2.1 The data required from the generator manufacturer to carryout the fault calculations
are listed in Annexure-2.
4.2.2 Tolerances on the machine parameters shall be specifically confirmed with the
manufacturer, in the absence of this confirmation, tolerances as per IEC-34 or
relevant standards shall be applied.
4.3.1 The following parameters of the GT are required for fault calculation:
The resistance of the transformer shall be found using the full load copper losses in
case the values of the resistances are not directly available.
4.4.1 The values of resistance and reactance of the busduct are very small quantities of
the order of micro ohms. Hence these parameters need not be considered for
calculation.
5.0 PROCEDURE
5.2 The base MVA and base kV shall preferably be taken as the rated MVA and rated
kV of the generator.
5.5 P.U. Impedance on any other MVA and kV can be converted to the P.U. Impedance
on base MVA & base kV as follows:
6.0 DISCUSSION
6.1 A sample calculation to calculate the symmetrical fault current, the DC component,
the asymmetrical fault current and the momentary current has been given in
Annexure-3 for a typical 500 MW plant having a generator circuit breaker. The
calculation steps have been explained in detail and the same procedure shall be
adopted for units of other ratings also.
6.2 While specifying the rating of the equipment operating in the electrical network
considered in this design guide such as GCB and EHVCB, etc., the results obtained
from the calculations shall be indicated in the data sheet-A of the relevant
specification.
7.0 REFERENCES
7.1 The general theory of electrical machines- Adkins B. Chapman & Hall Ltd. 1962.
7.2 ANSI/IEEE Std. C.37.5-1979 IEEE Guide for calculation of fault currents for
application of AC High Voltage Circuit Breakers rated on a total current basis.
7.4 IEEE C37.013-1989 Standard for AC High Voltage Generator Circuit Breakers
rated on a symmetrical current basis.
7.7 Control and Stability of Electric Power Systems – Anderson and Fouad.
ISSUE
R0
ANNEXURE-2
5. Frequency f Hz
12. Direct Axis Short Circuit Transient Time Constant Td’ Sec
ISSUE
R0
ANNEXURE-3
SAMPLE CALCULATION
1.0 This section outlines the detailed procedure for calculation of fault current in the
generator-generator transformer, UAT tap off section. Reference to the figure in
Annexure-1 shall be made.
1.1 Part-1 : Calculates 3 phase fault currents at any point between the generator and
generator transformer when generator alone is contributing to the fault.
1.2 Part-2 : Calculates 3 phase fault current at any point between GT and EHVCB
when grid/generator is contributing to the fault when the value of 3 phase
symmetrical fault current is known.
1.3 Part-3 : Calculates the 3 phase fault currents at the point considered in part 1 when
grid alone is feeding the fault.
1.4 Part-4 : Calculates the 3 phase fault currents on the UAT tap off part of the busduct
when both the grid and generator are feeding the fault.
1.5 Part-5 : Gives a summary of sizing the equipment performing in this section of the
electrical network considered.
2.1 For conservation fault estimation, the saturated value of the reactances are
considered.
2.2 The speed of the machine is assumed to be constant for about 60 to 80 milliseconds
(3 to 4 cycles) even after the instant of short circuit.
2.3 The switching angle A defines the point in the AC cycle at which the short circuit
occurs. The fault current at λ = 00 for unloaded generator case gives the maximum
DC component & λ = 900 gives the zero DC component. Hence λ = 00 is assumed.
The power angle σ is the angle between E the generated voltage and Vt the terminal
voltage of the generator is equal to zero since the value of E and Vt are same for
unloaded generator.
ISSUE
R0
2.4 The fault current fed from generator will be maximum when the value of λ and σ
are nearly equal. This is applicable for loaded as well as unloaded cases prior to
occurrence of the fault. For engineering applications the value of fault current
under generator unloaded conditions is adequate.
2.5 The calculations are done using general theory of electrical machines which is
based on a general machine concept. This is required to incorporate the finite effect
of saliency present in the turbo-generators which takes into consideration the
differences between the values of direct and quadrature axis reactances and time
constants and thus give accurate results.
2.6 The generator circuit breaker shall be sized such that the maximum values of the
symmetrical short circuit current, DC component shall be taken from part 1 and part
3 of the calculation.
2.7 Equivalent system (grid) X/R ratio at typical locations (for quick approximations)
are given below.
ISSUE
R0
General Calculations
Base kV = 21 kV
Base MVA = 659 MVA
Following table furnish the parameters of generator, generator transformer and grid.
Refer Annexure-2 for details required for generator.
a) GENERATOR
5. Rated frequency 50 Hz - -
6. Xd - 2.16 1.728
7. Xq - 2.16 1.728
ISSUE
R0
b) GENERATOR TRANSFORMER
2. LV Volts 21 kV - -
6. Inductance, Xt - - 0.141
c) GRID
2. Fault current 40 kA - -
4. Grid X/R 40 - -
Notes:
659
Grid fault impedance in pu = ------------ = 0.02378 pu
27712
PART-1
λ = 00 & σ = 00
The steady state value of the voltage before short circuit can be analysed to be made up of
2 components namely Direct and Quadrature axes.
The complete expression for the fault current in each phase consists of 2 components Ia1 &
Ia2 whose equations are given below for phase ‘a’. The value of fault currents in the other
two phases ‘b’ & ‘c’ can be calculated substituting λ by (λ- 2π/3) and (λ - 4π/3)
respectively.
ISSUE
R0
Equation 1 :
Ia1 = [ Vq/xd +(Vq/Xd’ – Vq/Xd”) e- t/Td” + (Vq/Xd” – Vq/Xd’) e –t/Td”] cos (ωt +λ)
Part – a :
Iac1 = [ Vq/xd +(Vq/Xd’ – Vq/Xd”) e- t/Td” + (Vq/Xd” – Vq/Xd’) e –t/Td”] cos (wt +λ)
Part-b :
Part –c :
ISSUE
R0
Iac1 = - 6.8669 pu
Iac2 = 0.3192 pu
Idc = 6.80699 pu
Iac1 + Iac2
Symm Iac rms = --------------------- = 4.6299 pu
√2
Iactual = I base x I pu
123.33 x 100
% DC = ------------------------ = 103.97%
√ 2 x 83.88
A computer package SMS is available which calculates the fault currents which have been
computed above manually.
ISSUE
R0
PART-2
a) Grid Feed
X/R = 2πFL / R
L 40
∴ Time constant , τ = ------ = ----------- = 0.127 sec
R 2π x 50
Idc
= 35.27 kA
Idc x 100 35.27
% DC component = -------------- = -------- x 100 = 62.35%
Iacg (peak) 56.57
½
Total Asymmetrical Current = (Iac2grms +Idc2 ) = 53.33 kA
b) Generator Feed
The generator feed to the fault current when a fault occurs after EHVCB can be
computed by using equation 1 referred in part A of the calculations. However the
value of reactances such as Xd, Xd’, Xd”, Xq, Xq” etc. get modified as Xd + Xt,
Xd’ + Xt, Xd”+Xt, Xq+Xt, Xq”+Xt etc. respectively where Xt is the GT reactance.
The armature time constant Ta which is approximately equal to Ld”/Ra becomes
(Ld” + Lt)/(Ra + Rt)
I
The values on 400 kV side of the GT = ------------
(400 + 21)
4.2325 x 100
% DC component = --------------------- = 64.08%
√ 2 x 4.67
Comparing grid feed and generator feed for the fault considered, we find that the
grid feed is much larger than the generator feed because of the impedance of the
GT. Hence EHVCB should be sized to perform for grid feed.
ISSUE
R0
PART – 3
The fault current fed from grid alone when a 3 phase fault occurs anywhere
between the generator and generator transformer LV bushing is calculated in this
section.
400 kV
The grid impedance = ---------------- = 5.774 ohms
√ 3 x 40
∴ Zg = 5.744 ohms
But Z2 = R2 + X2
(5.774)2
Rg2 = ----------------- = 0.020824 ohms
(1600 + 1)
Assuming 630 MVA and 400 kV the rating of transformer as base MVA and base
kV on EHV side of the transformer, the base impedance.
4002
= ----- = 253.97 ohms
630
ISSUE
R0
3847 .79
∴ Symmetrical fault current Igrms = ------------ = 105.79 kA
on 21 kV side √ 3 x 21
0.02273
Lg = ------------- pu = 0.00007235 pu & Rg = 0.000082 pu
2π x 50
0.1408
Similarly Lt = ------------- = 0.00044 pu & Rt = 0.0075 pu
2 x π x 50
t = 60 x 10-3 sec
ISSUE
R0
61.3
% DC component = ---------- x 100 = 41%
149.605
ISSUE
R0
PART-4
This part calculates the fault currents on the UAT tap off portion of the busduct.
The total fault current will be equal to the sum of the fault currents fed from the
generator and the grid.
Hence the total fault current will be equal to the sum of the fault currents calculated
in Part 1 and Part 3.
ISSUE
R0
PART-5
GCB shall be sized for the above values of the short circuit current. The generator
circuit breaker as per IEEE C 37.013 – 1989 meeting the above rating shall be
specified.
% DC component = 63%
3. BUSDUCT
b) Portion of the busduct from UAT tapoff point till UAT HV terminals.
This portion of the bus duct is susceptible to fault currents fed from both generator
and EHV grid.
ISSUE
R0