Data sheet Automatic Gen-set Controller

Multi-line 2
4921240295D
SW version 3.20.0 or later

Standard functions

Operation modes Display


• Automatic mains failure • Push-buttons for start and stop
• Island operation • Push-buttons for breaker
• Fixed power/base load operations
• Peak shaving • Status texts
• Load take over • Alarm indication
• Mains power export • Prepared for remote mounting

Engine control M-logic


• Start/stop sequences • Simple logic configuration tool
• Run and stop coil • Selectable input events
• Relay outputs for governor • Selectable output commands
DEIF A/S

control
General
Protection (ANSI) • USB interface to PC
• Overcurrent, 4 levels (51) • Free PC utility software for
• Reverse power, 2 levels (32) commissioning
• Multi inputs, 3 configurable • Additional functions available

© DEIF A/S
Data sheet Automatic Gen-set Controller
Application Test
The Automatic Gen-set Controller is a microprocessor The available gen-set modes except island operation
based control unit containing all necessary functions for include a test mode. The test can be configured in 3
protection and control of a gen-set. It contains all different ways.
necessary 3-phase measuring circuits and all values
and alarms are presented on the LCD display. Simple: Gen-set starting and running for a preset time.
Generator breaker is open during the test.
The AGC is a compact all-in-one unit designed for the
following applications: Load: Gen-set starting, synchronisation of the
generator breaker. The test is carried out for a
• Automatic mains failure preset period of time at a fixed power set point
• Island operation parallel to the mains.
• Fixed power/base load
• Peak shaving Full: Gen-set starting, synchronisation of the
• Load take over generator breaker, de-load and opening of the
• Mains power export (fixed power to mains) mains breaker. The test is carried out for a
preset period of time after which the load is
Optional applications: transferred back to the mains connection.

• Multiple gen-sets, load sharing Setup


• Power management (island operation) Setup is easily done via a menu structure in the display
• Power management (parallel with 1 or 2 mains) (password protected) or via the USB PC connection
and the multi-line 2 Windows® based PC utility
The AGC can operate in automatic mains software. The PC utility software can be downloaded
failure mode as a secondary mode free of charge from www.deif.com. The utility software
regardless of the type of application - except offers additional features such as monitoring of all
the island applications. relevant information during commissioning, saving and
downloading of settings and downloading of software
The display is separate and can be installed directly on updates.
the main unit or in the front of the switchboard door
(requires option J1 - display cable). Options
In order to perfectly match the product solution to
The AGC is supplied with an engine interface I/O card specific applications, the functionality of the AGC can
with separate power supply and processor. The card is be equipped with a number of available options. The
equipped with the following I/Os: options selected by the customer will be integrated in
the standard AGC hereby securing the same user
interface unaffected by whether the application needs a
In-/outputs Available
highly complex or a more basic gen-set controller.
4-20mA
Digital inputs Please refer to page 6 for the options available.
PT100
Multi inputs: 3 (3) Unit definitions
PT1000
AGC: The standard control unit designed for a
VDO number of applications (1-9). An
0-40V DC extensive list of hardware and software
Digital inputs 7 (6) options is available for the AGC.
RPM (MPU) 1
AGC mains: A special power management control unit
Relays 4 used in the parallel with mains power
CANbus comm. 2 management application (9). Several
options are available for the AGC mains.

The number in parenthesis indicates the M-logic


number of user configurable in-/outputs. This configuration tool is part of the PC utility software
which is free of charge. With this tool it is possible to
The two CAN communications are only customise the application to your needs. It is possible to
available, if option G5 or H5 is selected. dedicate specific functions or logical conditions to
different inputs and outputs.

DEIF A/S Page 2 of 12


Data sheet Automatic Gen-set Controller
Single line application diagrams

Standard

1. Automatic mains failure and 2. Island 3. Peak shaving, load take over and
fixed power/base load mains power export

37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72

Engine CAN
PMS CAN Service port Display
37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72

Power
Self check ok
Alarm inhibit Engine CAN
PMS CAN Service port Display

73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 Power
Self check ok
Alarm inhibit

73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97

37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72

Engine CAN
PMS CAN Service port Display

Power
Self check ok
Alarm inhibit

73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97

3
3

Optional

4. Multiple gen-sets, load sharing 5-7. Power management

See separate page in this data sheet

37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72

Engine CAN Engine CAN


PMS CAN Service port Display PMS CAN Service port Display

Power Power
Self check ok Self check ok
Alarm inhibit Alarm inhibit

73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97

3 3

DEIF A/S Page 3 of 12


Data sheet Automatic Gen-set Controller
Power management (option G5)

Description Test
The AGC can be equipped with a power management The available gen-set modes except island operation
option (G5). Using this possibility the AGC will be able include a test mode. The test can be configured as
to handle applications with up to 16 gen-sets. described on page 2.

The basic functions are: Priority selection


The priority routines in the AGC can be based on:
• Multi-master system
• Control of up to 16 gen-sets • Manual selection
• Load dependent start/stop operation • Absolute running hours
• Priority selection of gen-sets and mains • Relative running hours
• Ground relay control • Fuel optimising
• Tie breaker control (selectable)
• Mains breaker control Load dependent operation
• 2 mains connections The load dependent starting and stopping of the gen-
sets is based on a power available calculation. The next
In a multi-master system the power management generator will start, when the available power
control is automatically performed by the available gen- decreases below the adjustable set point. It will stop,
set AGC units. This means that the system is not when too much power is available.
dependent on one master unit. If 2 AGC mains units are
available in the power management application, a Load management
similar system is made for the mains control. The If a certain amount of available power on the busbar is
internal communication between the AGC units is
required to connect certain load groups, relays can be
CANbus. configured to activate when the specific amount of
available power is reached and thereby connect a load
Application group.
The power management option supports two basic
configurations only: Ground relay
If configurable relays are available in the specific AGC
• Island operation units (option dependent), it is possible to control the
• Parallel to mains star point ground connection of the generators. This is
in order to have only one ground connection at a time.
The gen-set modes supported by the power
management option are:
Automatic Transfer Switch (ATS)
The AGC supports applications where an ATS is used
• Automatic mains failure
instead of a mains breaker.
• Island operation
• Fixed power/base load
• Peak shaving
Redundant AGC mains and CANbus
In emergency systems where extra operation reliability
• Load take over
is required, redundant AGC mains units and redundant
• Mains power export (fixed power to mains) CANbus communication lines can be used to provide
back-up.
These are the selectable gen-set modes of the entire
plant, and they are adjusted on the AGC mains unit.
Redundant AGC mains units are only
The AGC mains is not required in island operation
supported in the application: Parallel with 2
configuration, since no mains breaker is to be
mains.
controlled.

Start/stop control
Start and stop of the power management can be done
in the following ways:

Local: Start and stop is controlled from the display.

Remote: Start and stop is controlled with a binary


input.

Timer: Start and stop is automatically controlled by


internal command timers programmed
through the PC utility software.

DEIF A/S Page 4 of 12


Data sheet Automatic Gen-set Controller
Optional power management applications
5. Island operation 6. Parallel with mains
The tie breaker can be selected on the AGC mains depending
on applicational needs.

37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72

3 Engine CAN
PMS CAN Service port Display

Power
Self check ok
Alarm inhibit

73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97

37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72

Engine CAN Engine CAN


PMS CAN Service port Display PMS CAN Service port Display

Power Power
Self check ok Self check ok
Alarm inhibit Alarm inhibit

73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97

37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72

Engine CAN Engine CAN


PMS CAN Service port Display PMS CAN Service port Display

3 3 Power Power
Self check ok Self check ok
Alarm inhibit Alarm inhibit

73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97

3 3

7. Parallel with 2 mains


The tie breaker can be selected on the AGC mains depending on applicational needs. Up to 8 gen-sets can be handled
in this application.

37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72

3 Engine CAN Engine CAN


3 E ngine CAN Engine CAN
PMS CA N Ser vice port Display PMS CAN S ervice port Display P MS CAN Service port Display PMS CAN Service port Dis play

Power Power P ower Power


Self check ok Self check ok S elf check ok Self check ok
Alarm inhibit Alarm inhibit A larm inhibit Alarm inhibit

73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97

37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72

Engine CAN Engine CAN


PMS CAN S ervice port Dis play PMS CA N Service port Display

Power Power
Self check ok Self check ok
Alarm inhibit Alarm inhibit

73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97

3 3

DEIF A/S Page 5 of 12


Data sheet Automatic Gen-set Controller
Available options
Option Description Slot Option Note
no. type
A Loss of mains protection package
A1 Over- and undervoltage (generator and busbar/mains) (27/59) Software
Over- and underfrequency (generator and busbar/mains) (81)
Voltage unbalance (busbar) (60)
Vector jump (78)
df/dt (ROCOF) (81)
A2 Over- and undervoltage (generator and busbar/mains) (27/59) Software
Over- and underfrequency (generator and busbar/mains) (81)
Voltage unbalance (busbar) (60)
df/dt (ROCOF) (81)
A3 Over- and undervoltage (generator and busbar/mains) (27/59) Software
Over- and underfrequency (generator and busbar/mains) (81)
Voltage unbalance (busbar) (60)
Vector jump (78)
A4 Positive sequence (mains voltage low) (27) Software
A5 Directional overcurrent (67) Software Only available in AGC mains
B Generator/busbar/mains protection package
B1 Over- and undervoltage (generator and busbar/mains) (27/59) Software
Over- and underfrequency (generator and busbar/mains) (81)
Voltage unbalance (busbar) (60)
C Generator add-on protection package
C1 Over- and undervoltage (27/59) Software
Over- and underfrequency (81)
Overload (32)
Peak current (50)
Current unbalance (46)
Voltage unbalance (60)
Reactive power import (excitation loss) (40)
Reactive power export (overexcitation) (40)
C2 Negative sequence voltage high (47) Software
Negative sequence current high (46)
Zero sequence voltage high (59)
Zero sequence current high (50)
D Voltage/VAr/PF control Not available for AGC mains
D1 Constant voltage control (stand-alone) Software Not with EF2
Constant reactive power control (parallel with mains)
Constant power factor control (parallel with mains)
Reactive load sharing (island paralleling with other generators)
E and F Analogue controller and transducer outputs
E1 2 x +/-25mA (GOV/AVR or transducer) 4 Hardware Not with E2, EF2 or EF4
AVR output requires D1
E2 2 x 0(4)...20mA (GOV/AVR or transducer) 4 Hardware Not with E1, EF2 or EF4
AVR output requires D1
EF2 1 x +/-25mA (GOV/AVR or transducer) 4 Hardware Not with E1, E2 or EF4
1 x 0(4)...20mA (GOV/AVR or transducer) AVR output requires D1
EF4 1 x +/-25mA (GOV/AVR or transducer) 4 Hardware Not with E1, E2 or EF2
2 x relay outputs (GOV/AVR or configurable) AVR output requires D1
F1 2 x 0(4)...20mA (transducer) 6 Hardware Not with M13.6, M14.6 or M15
G Load sharing/power management
G3 Load sharing with analogue lines 3 Hardware/ If M12 is present, G3 is a software
software option
Not available for AGC mains
G5 Power management, 16 gen-sets 7 Software Not with H7

Options E1, E2, EF2 and EF4 are used for GOV/AVR control. 4 relays are used as standard in the AGC for
GOV/AVR control. If selected, these options will replace the 4 relays.

DEIF A/S Page 6 of 12


Data sheet Automatic Gen-set Controller
Option Description Slot Option Note
no. type
H Serial communication
H2 Modbus RTU (RS485) 2 Hardware Not with H3
H3 Profibus DP 2 Hardware Not with H2
H5 CANbus: 8 Hardware Not with H6, H7, M13.8 or M14.8
MTU (MDEC) and all J1939 engine comm. Not available for AGC mains
included in option H7
H6 Cummins GCS 8 Hardware Not with H5, H7, M13.8 or M14.8
Not available for AGC mains
H7 CANbus (J1939): 7 Software Not with H5, H6 or G5
Not available for AGC mains
Caterpillar Perkins
Detroit Diesel (DDEC) Scania (EMS)
Deutz (EMR) Scania (EMS S6)
Iveco (NEF/CURSOR) Volvo Penta (EMS)
John Deere (JDEC) Volvo (EMS2)
H11 LED I/F card w/RS232 service port Hardware Not with N
Class 1.0 measurements
J Cables
J1 Display cable with plugs, 3 m. UL94 (V1) approved Other
J2 Display cable with plugs, 6 m. UL94 (V1) approved Other
J3 PC cable for utility software (RS232) 3 m. UL94 (V1) approved Other Only with H11
J6 Display cable with plugs, 1 m. UL94 (V1) approved Other
J7 PC cable for utility software (USB) 3 m. UL94 (V1) approved Other Not with H11
K Designer’s Reference Handbook (hard copy) Other
L Display gasket for IP54 Other Standard is IP52
M Binary and analogue I/Os
M12 13 binary inputs, 4 relay outputs, configurable 3 Hardware/ If G3 is present, M12 is a software
software option
M13.X 7 binary inputs, configurable 6, 8 Hardware M13.6: Not with F1, M14.6 or M15
M13.8: Not with H5, H6 or M14.8
M14.X 4 relay outputs, configurable 6, 8 Hardware M14.6: Not with F1, M13.6 or M15
M14.8: Not with H5, H6 or M13.8
M15 4 analogue inputs, configurable, 4...20mA 6 Hardware Not with F1, M13.6 or M14.6
N Ethernet TCP/IP communication
N5 Ethernet TCP/IP Modbus comm. and alarms via SMS or e-mail Hardware/ If N6 is present, this is a software
software option
Not with H11
N6 Advanced logging and alarms via SMS or e-mail Hardware/ If N5 is present, this is a software
software option
Not with H11
P Printer
P1 Event and alarm printer software Software Only with H11
Q Measurement accuracy
Q1 Verified class 0.5 Other Not with H11
X Display
X2 Additional standard display. CANbus comm. Other Two X2 options can be ordered for
each AGC unit.
Only available if the AGC unit is
ordered with a display
X3 Additional operator panel (AOP-1): 16 configurable LEDs and Other
8 configurable push-buttons
X4 Additional operator panel (AOP-2): 16 configurable LEDs, 8 Other Five X4 options can be ordered for
configurable buttons and 1 status relay. CANbus comm. each AGC unit.
Only available if the AGC unit is
ordered with a display
Y Display layout
Y1 AGC display for island operation (no mains breaker) Other

(ANSI# as per IEEE Std C37.2-1996 (R2001) in parenthesis).

Please notice that not all options can be selected for the same unit. Please refer to page 9 in this data
sheet for further information about the location of the options in the unit.

DEIF A/S Page 7 of 12


Data sheet Automatic Gen-set Controller
Principle diagrams

AGC

Hz 65

50

45

+ -

AGC mains

Hz 65

50

45

+ -

DEIF supplies a complete range of current transformers (MAK range of CTs), power supplies (DCP
range), meters (DQ range) and transducers (TAS range) that are suitable for use with our range of
generator controls and protection relays - please see www.deif.com for full details.

DEIF A/S Page 8 of 12


Data sheet Automatic Gen-set Controller
Hardware overview

Slot #4, term. 65-72 Ethernet Slot #6, term. 90-97


Governor, AVR, in-/outputs N5: TCP/IP Modbus comm.
In-/outputs

M14.4: 4 x relay (standard) N6: Advanced logging F1: 2 x 0(4)…20mA out, transducer

E1: 2 x +/-20mA out M13.6: 7 x digital inputs

E2: 2 x 0(4)…20mA out M14.6: 4 x relay outputs

EF2: 1 x +/-20mA out M15: 4 x 4…20mA inputs


1 x 0(4)…20mA out

EF4: 1 x +/-20mA out


2 x relay

Slot #8, term. 126-133


Slot #2, term. 29-36 Engine comm., in-/outputs

90 91 92 93 94 95 96 97
Communication
65 66 67 68 69 70 71 72

H6: Cummins GCS

H2: Modbus RTU (RS485) H5: MTU (MDEC) + J1939 (option H7)

H3: Profibus DP M13.8: 7 x digital inputs


51 52 53 54 55 56 57 58 59 60 61 62 63 64

M14.8: 4 x relay outputs


Display

85 86 87 88 89
Service port
USB Memory

Slot #7, term. 98-125


79 80 81 82 83 84

Engine I/F (std.)


Ethernet

Slot #1, term. 1-28


37 38 39 40 41 42 43 44 45 46 47 48 49 50

Power supply (std.) 8-36V DC supply, 5W


1 x magnetic pick-up (MPU)
Self check ok
Engine CAN

Alarm inhibit
PMS CAN

3 x multi inputs
Ethernet

Power

8-36V DC supply, 11W


USB

7 x digital inputs
73 74 75 76 77 78

1 x status output relay


5 x relay outputs 4 x relay outputs
2 x pulse outputs (kWh, kvarh)
5 x digital inputs G5: Power management

H7: J1939

Slot #3, term. 37-64 Slot #5, term. 73-89


In-/outputs/load sharing AC measuring (std.)

M12: 13 x digital inputs 3 x generator voltage


4 x relay outputs 3 x generator current
LED I/F 3 x busbar/mains voltage
G3: Active power load sharing
Reactive power load sharing H11: RS232 service port
(requires D1)

There can only be one hardware option in each slot. It is e.g. not possible to select option H2 and option
H3 at the same time, because both options require a PCB in slot #2.

Besides the hardware options shown on this page it is possible to select the software options
mentioned in the chapter ‘Available options’.

DEIF A/S Page 9 of 12


Data sheet Automatic Gen-set Controller
Technical specifications
Accuracy: Class 1.0 0(4)…20mA:
Class 0.5 with option Q1 Impedance: 50Ω
Not galvanically separated
Positive, negative and zero
sequence alarms: Class 1 within RPM (MPU): 2…70V AC,
5% voltage unbalance 10…10000Hz, 250…3000Ω
Class 1.0 for neg. seq. current
Multi inputs: 0(4)…20mA:
Fast overcurrent: 0-20mA, +/-1%
3% of 350%*In Not galvanically separated
Analogue outputs: Binary:
Class 1.0 according to total Max. resistance for ON
range detection: 100Ω
Not galvanically separated
To EN60688/IEC 688
PT100/1000:
Operating temp.: -25…70οC (-13...158ο F) -40…250οC, +/-1%
(UL/cUL: Max. surrounding air Not galvanically separated
temp.: 55οC/131οF) To IEC 751 and EN60751

Storage temp.: -40…70οC (-40...158ο F) VDO:


0…1700Ω, +/-2%
Climate: Class HSE, to DIN 40040 Not galvanically separated
V DC:
Meas. voltage: 100-690V AC +/-20%
0…40V DC, +/-1%
(UL/cUL: 480V AC phase-
Not galvanically separated
phase)
Consumption: Max. 0.25VA/phase Relay outputs: Electrical rating:
250V AC/30V DC, 5A
Meas. current: -/1 or -/5A AC (UL/cUL: 250V AC/24V DC, 2A
(UL/cUL: From CTs 1-5A) resistive load)
Consumption: Max. 0.3VA/phase Thermal rating @ 50οC:
2A: Continuously
Current overload: 4 x In continuously 4A: tON = 5 sec., tOFF = 15 sec.
20 x In, 10 sec. (max. 75A)
80 x In, 1 sec. (max. 300A) (Unit status output: 1A)

Meas. frequency: 30…70Hz Open collector


outputs: Supply: 8…36V DC, max. 10mA
Aux. supply: Terminals 1 and 2:
12/24V DC (8...36V Analogue outputs: 0(4)...20mA and +/-25mA
continuously, 6V 1 sec.) Galvanically separated
Max. 11W consumption Active output (internal supply)
Load max. 500Ω
Terminals 98 and 99: (UL/cUL: Max. 20mA output)
12/24V DC (8...36V
continuously, 6V 1 sec.) Update rate:
Max. 5W consumption Transducer output: 250 ms
Regulator output: 100 ms
The aux. supply inputs are to
be protected by a 2A slow blow Load sharing lines: -5…0…+5V DC,
fuse Impedance: 23.5 kΩ
(UL/cUL: AWG 24)
Galv. separation: Between AC voltage, AC current
Binary inputs: Optocoupler, bi-directional and other I/Os:
ON: 8…36V DC 3250V AC, 50Hz, 1 min.
Impedance: 4.7kΩ
OFF: <2V DC Between analogue outputs and
other I/Os:
Analogue inputs: -10…+10V DC: 500V DC, 1 min.
Not galvanically separated Between binary input groups
Impedance: 100kΩ and other I/Os:
500V DC, 1 min.

DEIF A/S Page 10 of 12


Data sheet Automatic Gen-set Controller
Response times: Terminals 98-116:
(Delay set to min.) 0.2-1.5 mm2 stranded wire
(UL/cUL: AWG 24)
Busbar:
Over-/undervoltage: < 50 ms Other:
2
Over-/underfrequency: < 50 ms 0.2-2.5 mm stranded wire
Voltage unbalance: < 200 ms (UL/cUL: AWG 24)
Generator: Display:
Reverse power: <200 ms 9-pole Sub-D female
Overcurrent: <200 ms
Fast overcurrent: < 40 ms Service port:
Directional overcurrent <100 ms USB A-B
Over-/undervoltage: <200 ms
Over-/underfrequency: <300 ms Protection: Unit: IP20
Overload: <200 ms Display: IP52 (IP54 with gasket:
Current unbalance: <200 ms Option L)
Voltage unbalance: <200 ms (UL/cUL: Type Complete Device,
React. power import: <200 ms Open Type)
React. power export: <200 ms To IEC 529 and EN 60529
Negative sequence I: <400 ms
Negative sequence U: <400 ms Governors: Multi-line 2 interfaces to all governors,
Zero sequence I: <400 ms including GAC, Barber-Colman,
Zero sequence U: <400 ms Woodward and Cummins
Overspeed: <400 ms
Digital inputs: <250 ms See interfacing guide at
Emergency stop: <200 ms www.deif.com
Multi inputs: <800 ms
Wire failure: <600 ms Approvals: UL and cUL

Mains: UL markings: Wiring:


df/dt (ROCOF): <130 ms (4 periods) Use 60/75οC copper conductors only
Vector jump: < 40 ms
Positive sequence: < 60 ms Mounting:
For use on a flat surface of type 1
Mounting: DIN-rail mount or base mount enclosure
with 6 screws Installation:
To be installed in accordance with the
Safety: To EN 61010-1, installation NEC (US) or the CEC (Canada)
category (overvoltage
category) III, 600V, pollution AOP-2: Maximum ambient temperature:
degree 2 60οC
To UL 508 and CSA 22.2 no.
14-05, overvoltage category Wiring:
III, 300V, pollution degree 2 Use 60/75οC copper conductors only
Mounting:
EMC/CE: To EN 61000-6-1/2/3/4 For use on a flat surface of type 3
SS4631503 (PL4) and (IP54) enclosure
IEC 255-3 Main disconnect must be provided by
installer
Material: All plastic materials are self-
extinguishing according to Installation:
UL94 (V1) To be installed in accordance with the
NEC (US) or the CEC (Canada)
Plug connec- DC/DC converter
tions: AC current: for AOP-2: Tightening torque: 0.5Nm (4.4lb-in)
2
0.2-4.0 mm stranded wire
(UL/cUL: AWG 18) Wire size: AWG 22-14
AC voltage: Weight: Base unit: 1.6 kg (3.5 lbs.)
2
0.2-2.5 mm stranded wire Option J1/J3/J6: 0.2 kg (0.4 lbs.)
(UL/cUL: AWG 20) Option J2: 0.4 kg (0.9 lbs.)
Relays: Display: 0.4 kg (0.9 lbs.)
(UL/cUL: AWG 22)

DEIF A/S Page 11 of 12


Data sheet Automatic Gen-set Controller
Unit dimensions in mm (inches)

115.0 (4.528)

165.0 (6.496)

144.0 (5.669)
230.0 (9.055) 120.0 ( 4.724)
115.0 (4.528)
20.0 (0.787)

220.0 (9.055)

Order specifications

As the AGC mains unit is only usable


with option G5, this option is already
included when ordered.