Ventellation Calcualtion

This document provides information for ventilation calculations for a control room at a 30MW/36MWp solar PV power plant being built at Kadiri, Andhra Pradesh, India. It includes inputs such as the site's coordinates and maximum ambient temperature, heat loads from electrical equipment in the control room totaling 5,767 Watts, and air flow calculations to account for the heat gain in the control room.

Uploaded by

Santosh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
264 views6 pages

Ventellation Calcualtion

This document provides information for ventilation calculations for a control room at a 30MW/36MWp solar PV power plant being built at Kadiri, Andhra Pradesh, India. It includes inputs such as the site's coordinates and maximum ambient temperature, heat loads from electrical equipment in the control room totaling 5,767 Watts, and air flow calculations to account for the heat gain in the control room.

Uploaded by

Santosh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

This document is the property of Larsen & Toubro Limited, ECC Division - EDRC and must not be passed

on to any third person or firm not authorised by us,


nor be copied/made use of in full or part by such person or firm without our prior permission writing
SEI DOC. NO : IN-13-0368-EE-41

15.10.2015 A FIRST SUBMISSION SRK VR TRAMS


DATE REV. NO. DESCRIPTION Designed Checked Approved
REVISIONS
L&T Construction
Water & Renewable Energy
Solar Projects
PROJECT : CUSTOMER :

SEI ARUSHI PVT. LTD. SUNEDISON SOLAR POWER INDIA PVT. LTD.

PROJECT :
30MW / 36MWp SOLAR PV POWER PLANT AT KADIRI, ANDHRA PRADESH
SUPPLIER / CONTRACTOR:L & T CONSTRUCTION
Solar Projects
JOB No. O15111-WS-S
TOTAL NO. OF PAGES 5 TITLE :
NAME SIGN DATE
DSGN SRK SRK 15.10.2015

CHKD VR VR 15.10.2015
VENTILATION CALCULATION - CONTROL ROOM
APPD TRAMS TRAMS 15.10.2015
CODE REV.
DOC. No. O 1 5 1 1 1 - W S - S - D C - V F - 0 0 0 1
IS A
Sheet 01A of 04

RELEASED FOR PRELIMINARY TENDER INFORMATION  APPROVAL CONSTRUCTION


L&T Construction
Water & Renewable Energy
Solar Projects
30MW / 36MWp SOLAR PV POWER PLANT AT DOC.NO : DATE
PROJECT:
KADIRI, ANDHRA PRADESH O15111-WS-S 15.10.2015
DESIGNED CHECKED APPROVED
TITLE: SITE DATA & DC/AC INPUT
SRK VR TRAMS

INPUTS & DESIGN CONSIDERATIONS :

14.2 ⁰N [ Approximate location


Co-ordinates of the site/location =
78.1 ⁰E co-ordinates of plant ]

Maximum ambient temperature (in a year ) = 41.2 ⁰C [ From meteonorm]

Wet bulb temperature


= 26.5 ⁰C
@ max ambient temperature point

Specific volume of air @ DBT & WBT ( Sa ) = 0.91 m³ / kg of dry air [ From psychrometric chart]

Heat dissipation from list of equipment : [ Inputs from AC,DC & Scada Electrical ]

Heat load values


S. No Equipment
(W)
33kV HT PANEL 5000.0
ACDB / LT PANEL 75
CONTROL BATTERY CHARGER 602
ROOM LIGHTING DB 75
UPS DB 15
Total heat dissipated 5767.0

NOTE : Heat load of inverter is not considered, only air requirement specified by the inverter manufacturer is considered for
sizing/selection of supply air fan.
L&T Construction
Water & Renewable Energy
Solar Projects
30MW / 36MWp SOLAR PV POWER PLANT AT KADIRI, DOC.NO : DATE
PROJECT:
ANDHRA PRADESH O15111-WS-S 15.10.2015
DESIGNED CHECKED APPROVED
TITLE: CONTROL ROOM - HT PANEL ROOM
SRK VR TRAMS

AIR FLOW CALCULATIONS FOR THE ROOM :

a) Air flow requirement for equipment heat load:

Total thermal heat addition into the room from the eletrical [ Inputs from the electrical DC / AC
= 5.767 kW
equipment ( with out inverter ), q team ]

Since, Heat dissipated from the electrical equipment = Heat gain by the supplied air into the room
[m : Mass of air ;
So, Heat gain is given by, q = m x Cp x ⍙t kW Cp: Specific heat of fluid ;
⍙t : Rise in temperature]

Specific heat of air, Cp = 1.001 kJ / kg - k

Rise in temperature of supplied ambient air, ⍙t = 3 ⁰C

Temperature inside the room (maintained) = DBT + 3 ⁰C [ As per ISHARE ]


[ As per ISHARE, maximum room inside temperature shall be 3⁰C above the ambient temperature for mechanically ventilated areas ]

Rate of air flow into room, m (m³/ hr) = (( q x 3600) x Sa ) / ( Cp x ⍙t ) [ q in KJ / hr; Sa in m³ / Kg ;


Cp in kJ/Kg .k ]
Specific volume of ambient air, Sa = 0.91 m³ / Kg

= (5.767 x 0.91 x 3600) / (1.001 x 3)


Air flow required to remove heat dissipated by the equipment
= 6291 m³ / hr

= 6300 m³ / hr [ Approx. ]

b) Air flow requirement based on air changes in the room:

Dimensions of the room = 13.415 * 8.64 * 3.7 ( L x B x H )m

Number of Air changes considered inside the room = 15 Nos.

Total rate of air flow as per air changes = (13.415 * 8.64 * 3.7 ) x ( 15 )
= 6433 m³ / hr

Since, the amount of air flow calculated as per air changes in the room is higher than the equipment heat load requirement - Air flow requirement
based on air changes in the room shall be considered for ventilation design.
L&T Construction
Water & Renewable Energy
Solar Projects
30MW / 36MWp SOLAR PV POWER PLANT AT KADIRI, DOC.NO : DATE
PROJECT:
ANDHRA PRADESH O15111-WS-S 15.10.2015
DESIGNED CHECKED APPROVED
TITLE: CONTROL ROOM - HT PANEL ROOM
SRK VR TRAMS

MECHANICAL VENTILATION - FORCED AIR INLET DESIGN:

a) Total Air Inlet & Exhaust :


Number of air supply / exhaust fans will be estimated & sized as per the vendor catalogue for tube axial fans & propeller fans.

Amount of forced air to be supplied into the room = 6433 m³ / hr

[ Sum of air flow required for inverter &


With 20% approx margin = 7720 m³ / hr
heat removal in the room]
[Remaining air will be exhausted
Minimum amount of air to be exhausted from the room = 6400 m³ / hr
through the inverter exhaust duct]

b) Sizing of air filters @ supply fan:

Number of supply air fans considered to meet the minimum air


= 1 Nos'
requirement of 7720 m³ / hr

Flow rate of each supply air fan ( Q ) = 8000 m³ / hr

Maximum allowable velocity of air flow through the Air filter = 2.5 m / sec

Velocity of air flow through the Air-Filter ( V ) = 2.2 m / sec [ Design consideration ]

Flow rate (Q) = Area (A) x Velocity (V)


8000 = A x 2.2
So, cross-section area of air filter required, A = 1.0 m²

Standard size of air filter = 610 x 610 mm [ As per availability]

Minimum number of air filters/each inlet fan = 1 / (610 x 610 )


= 2.7 Nos.

Specification for Fans :

Purpose Type of fan Capacity ( m³ / hr) Quantity Remarks

Supply / Inlet Air fans Tube Axial fans 8000 1


HT panel room
Exhaust fans Heavy Duty propeller fans 3250 2
L&T Construction
Water & Renewable Energy
Solar Projects
30MW / 36MWp SOLAR PV POWER PLANT AT KADIRI, DOC.NO : DATE
PROJECT:
ANDHRA PRADESH O15111-WS-S 15.10.2015
DESIGNED CHECKED APPROVED
TITLE: CONTROL ROOM - INVERTER ROOM
SRK VR TRAMS

AIR FLOW CALCULATIONS :

a) Air flow requirement based on air changes in the room:

Dimensions of the room = 14.1 x 3.375 x 3.7 ( L x B x H )m

Number of Air changes considered inside the room = 15 Nos.

Total rate of air flow as per air changes = (14.1 x 3.375 x 3.7 ) x ( 15 )
= 2641 m³ / hr

b) Air flow requirement for inverters':

[ As per 'TMEIC' inverter manufacturer


Rate of air flow required for each inverter in the room = 2400 m³ / hr
specification ]

Total number of inverters in the room = 4 No's

Rate of air flow required for inverters in to the room = ( 2400 x 4 )

= 9600 m³ / hr

MECHANICAL VENTILATION - FORCED AIR INLET DESIGN:

a) Sizing of air supply fans / exhaust fans :

Number of air supply / exhaust fans will be estimated & sized as per the vendor catalogue for tube axial fans & propeller fans.

Amount of forced air to be supplied into the room = (2641) + ( 2400 * 4 )


= 12241 m³ / hr [ Sum of air flow required for inverter &
air changes in the room]
With 20% approx margin = 14689 m³ / hr
[Remaining air will be exhausted
Minimum amount of air to be exhausted from the room = 2641 m³ / hr
through the inverter exhaust duct]

b) Sizing of air filter & numbers / each supply fan:

Number of supply air fans considered to meet the minimum air


= 3 Nos'
requirement of 14689 m³ / hr

Flow rate of each supply air fan ( Q ) = 5000 m³ / hr [ From product catalogue ]

Maximum allowable velocity of air flow through the Air filter = 2.5 m / sec
L&T Construction
Water & Renewable Energy
Solar Projects
30MW / 36MWp SOLAR PV POWER PLANT AT KADIRI, DOC.NO : DATE
PROJECT:
ANDHRA PRADESH O15111-WS-S 15.10.2015
DESIGNED CHECKED APPROVED
TITLE: CONTROL ROOM - INVERTER ROOM
SRK VR TRAMS

Velocity of air flow through the Air-Filter ( V ) = 2.2 m / sec [ Design consideration ]

Flow rate (Q) = Area (A) x Velocity (V)


5000 = A x 2.2

So, Cross-section area of air filter required, A = 0.6 m²


Standard size of air filter = 610 x 610 mm [ As per availability]

Minimum number of air filters/each inlet fan = 0.6 / (610 x 610 )


= 2

Specification for Fans:

Purpose Type of fan Capacity ( m³ / hr) Quantity Remarks

Supply/Inlet Air fans Tube Axial 5000 3


Inverter room
Exhaust fans Heavy Duty - propeller 2850 1