3H Expansion Design
3H Expansion Design
FW-D-0042
XHBN.FW-D-0042
Joint Systems
Page Bottom
Assembly Rating — 3 Hr
1. Wall Assembly — Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400
kg/m3) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of
manufacturers.
2. Floor Assembly — Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400
kg/m3) structural concrete.
3. Joint System — Max width of joint (at time of installation of joint system) is 2 in. (51 mm). The joint
system is designed to accommodate a max 6 percent compression or extension from its installed width. The
joint system shall consist of the following:
A. Forming Material — Min 4 pcf (64 kg/m3) mineral wool batt insulation installed in joint
opening as a permanent form. Pieces of batt cut to min width of 5 in. (127 mm) and installed
edge-first into joint opening, parallel with joint direction, such that batt sections are compressed
min 50 percent in thickness and such that the compressed batt sections are recessed from the
top surface of the floor as required to accommodate the required thickness of fill material.
Adjoining lengths of batt to be tightly-butted with butted seams spaced min 24 in. (610 mm)
apart along the length of the joint.
B. Fill, Void or Cavity Material* — Sealant — Min 1/2 in. (13 mm) thickness of fill material
applied within the joint, flush with top surface of the floor.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP606 Flexible Firestop Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL
Certification (such as Canada), respectively.
© 2017 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2017 UL LLC".