This guide provides installation, initial setup, and calibration information for DVC6000 digital valve controllers. For additional
information, refer to the DVC6000 digital valve controllers instruction manual (D102794X012), available from your Emerson
Process Management sales office, or from our website at www.FIELDVUE.com.
The DVC6000 digital valve controller instruction manual (D102794X012) can be found at www.FIELDVUE.com
http://www.documentation.emersonprocess.com/groups/public/documents/instruction_manuals/d102794x012.pdf
Refer to Related Documents on page 37 for other documents containing information related to DVC6000 digital valve controllers
www.Fisher.com
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
Product Description
DVC6000 digital valve controllers (figure 1 and 2) are communicating, microprocessor‐based current‐to‐pneumatic
instruments. In addition to the traditional function of converting an input current signal to a pneumatic output
pressure, the DVC6000 digital valve controller communicate via HARTr protocol.
DVC6000 digital valve controllers are designed to directly replace standard pneumatic and electro‐pneumatic valve
mounted positioners.
Do not install, operate, or maintain a DVC6000 digital valve controller without being fully trained and qualified in
valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage,
it is important to carefully read, understand, and follow all contents of this quick start guide, including all safety
cautions and warnings. If you have any questions about these instructions, contact your Emerson Process
Management sales office before proceeding.
Figure 1. FIELDVUE DVC6010 Digital Valve Controller Figure 2. Fisher Rotary Control Valve with
Mounted on a Fisher Sliding‐Stem Valve Actuator FIELDVUE DVC6020 Digital Valve Controller
W9418
W7957
2
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
This guide describes instrument setup and calibration using a 475 Field Communicator. For information on using the
Field Communicator, see the 475 Field Communicator User's Manual, available from your Emerson Process
Management sales office.
You can also setup and calibrate the instrument using a personal computer and ValveLink software or AMS Suite:
Intelligent Device Manager. For information on using ValveLink software or AMS Device Manager with a FIELDVUE
instrument, refer to the appropriate documentation or online help.
Offline Menu—To see the Field Communicator device description revision number from the Offline menu, select Utility,
Simulation, Fisher Controls, and DVC6000.
Online Menu—To see the Field Communicator device description revision number from the Online menu, connect the
Field Communicator to an instrument connected to a source supplying a 4‐20 mA signal. From the Online menu,
select Overview and DD Information.
3
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
Installation
The DVC6000 can be used with either air or natural gas as the supply medium. If using natural gas as the pneumatic
supply medium, natural gas will be used in the pneumatic output connections of the DVC6000 to any connected
equipment. In normal operation the unit will vent the supply medium into the surrounding atmosphere unless it is
remotely vented. When using natural gas as the supply medium, in a non‐hazardous location in a confined area,
remote venting of the unit is required. Failure to do so could result in personal injury, property damage, and area
re‐classification. For hazardous locations remote venting of the unit may be required, depending upon the area
classification, and as specified by the requirements of local, regional, and federal codes, rules and regulations. Failure
to do so when necessary could result in personal injury, property damage, and area re‐classification.
WARNING
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before proceeding
with any Installation procedures:
D Always wear protective clothing, gloves, and eyewear to prevent personal injury or property damage.
D Do not remove the actuator from the valve while the valve is still pressurized.
D Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and
appropriate preventive measures are not taken. Preventive measures may include, but are not limited to, one or more
of the following: Remote venting of the unit, re‐evaluating the hazardous area classification, ensuring adequate
ventilation, and the removal of any ignition sources. For information on remote venting of this controller, refer to
page 20.
D Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the
actuator cannot suddenly open or close the valve.
D Use bypass valves or completely shut off the process to isolate the valve from process pressure. Relieve process pressure
from both sides of the valve.
D Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
D Vent the pneumatic actuator loading pressure and relieve any actuator spring precompression so the actuator is not
applying force to the valve stem; this will allow for the safe removal of the stem connector.
WARNING
To avoid static discharge from the plastic cover when flammable gases or dust are present, do not rub or clean the cover
with solvents. To do so could result in a spark that may cause the flammable gases or dust to explode, resulting in personal
injury or property damage. Clean with a mild detergent and water only.
WARNING
This unit vents the supply medium into the surrounding atmosphere. When installing this unit in a non‐hazardous
(non‐classified) location in a confined area, with natural gas as the supply medium, you must remotely vent this unit to a
safe location. Failure to do so could result in personal injury or property damage from fire or explosion, and area
re‐classification.
When installing this unit in a hazardous (classified) location remote venting of the unit may be required, depending upon
the area classification, and as specified by the requirements of local, regional, and federal codes, rules and regulations.
4
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
Failure to do so when necessary could result in personal injury or property damage from fire or explosion, and area
re‐classification.
Vent line piping should comply with local and regional codes and should be as short as possible with adequate inside
diameter and few bends to reduce case pressure buildup.
In addition to remote venting of the unit, ensure that all caps and covers are correctly installed. Failure to do so could result
in personal injury or property damage from fire or explosion, and area re‐classification.
Hazardous Area Classifications and Special Instructions for “Safe Use” and
Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring
requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may
override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the nameplate markings affixed to the product.
Always refer to the nameplate itself to identify the appropriate certification. Contact your Emerson Process Management sales
office for approval/certification information not listed here.
Approval information is for both aluminum and stainless steel constructions.
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, or
area re‐classification.
5
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
CSA
No special conditions for safe use.
Refer to table 2 for approval information, figure 24 for the CSA loop schematic, and figure 25 for a typical CSA/FM
nameplate.
FM
Special Conditions of Safe Use
1. When product is used with natural gas as the pneumatic medium, the maximum working pressure of the natural
gas supply shall be limited to 145 psi.
2. When product is used with natural gas as the pneumatic medium the product shall not be permitted in a Class I,
Division 2, Group A, B, C, D location without the proper venting installation as per the manufacturer's instruction
manual.
3. The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or
friction. Care must be taken into account during installation and use to prevent impact or friction.
4. Part of the enclosure is constructed from plastic. To prevent the risk of electrostatic sparking the plastic surface
should only be cleaned with a damp cloth.
Refer to table 3 for approval information, figure 26 for the FM loop schematic, and figure 25 for a typical CSA/FM
nameplate.
6
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
ATEX
Special Conditions for Safe Use
Intrinsically Safe
1. This apparatus can only be connected to an intrinsically safe certified equipment and this combination must be
compatible as regards the intrinsically safe rules.
2. The electrical parameters of this equipment must not exceed any following values:
Uo ≤ 30 V; Io ≤ 226 mA; Po ≤ 1.4 W
3. Operating ambient temperature: -52_C or -40_C to + 80_C
4. For the model with aluminum body: the apparatus must not be submitted to frictions or mechanical impacts.
5. Covered by standards EN 60079‐0 (2009), EN 60079‐11 (2012), EN 60079‐26 (2007).
6. Install per drawing GE60771.
Flameproof
Type n
Refer to table 4 for additional approval information, figure 27 for the ATEX loop schematic and figure 28 for typical
ATEX nameplates.
7
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
IECEx
Conditions of Certification
Ex ia /Ex nC / Ex d
1. Warning: Electrostatic charge hazard. Do not rub or clean with solvents. To do so could result in an explosion.
Ex nC / EX d
2. Do not open while energized.
Refer to table 5 for additional approval information, figure 29 for the IECEx loop schematic and figure 30 for a typical
IECEx nameplate.
Mounting Guidelines
Standard DVC6000 Digital Valve Controllers
If ordered as part of a control valve assembly, the factory mounts the digital valve controller on the actuator, makes
pneumatic connections to the actuator, sets up, and calibrates the instrument. If you purchased the digital valve
controller separately, you will need a mounting kit to mount the digital valve controller on the actuator. See the
instructions that come with the mounting kit for detailed information on mounting the digital valve controller to a
specific actuator model.
8
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
Figure 3. FIELDVUE DVC6010 Digital Valve Controller Mounted on Sliding‐Stem Actuators with up to 2 Inches Travel
MACHINE SCREW
SHIELD
ADJUSTMENT ARM
CONNECTOR ARM
CAP SCREW
PLAIN WASHER
29B1674‐A
Note
Do not use the stainless steel DVC6010S in high vibration service where the mounting bracket uses standoffs (spacers) to mount
to the actuator.
Refer to the following guidelines when mounting on sliding‐stem actuators with up to 4 inches of travel.
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure
that the above measures stay in effect while you work on the equipment.
2. Attach the connector arm to the valve stem connector.
3. Attach the mounting bracket to the digital valve controller housing.
9
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
4. If valve travel exceeds 2 inches, a feedback arm extension is attached to the existing 2‐inch feedback arm. Remove
the existing bias spring from the 2‐inch feedback arm. Attach the feedback arm extension to the feedback arm as
shown in figure 4.
Figure 4. FIELDVUE DVC6010 Digital Valve Controller Mounted on Sliding‐Stem Actuators with 2 to 4 Inches Travel
MACHINE SCREW,
FLAT HEAD
MACHINE SCREW
LOCK WASHER
SHIELD
MACHINE SCREW,
LOCK WASHER, PLAIN WASHER
HEX NUT
CONNECTOR ARM
5. Mount the digital valve controller on the actuator as described in the mounting kit instructions.
6. Set the position of the feedback arm on the digital valve controller to the no air position by inserting the alignment
pin through the hole on the feedback arm as follows:
D For air‐to‐open actuators (i.e., the actuator stem retracts into the actuator casing or cylinder as air pressure to
the casing or lower cylinder increases), insert the alignment pin into the hole marked “A''. For this style actuator,
the feedback arm rotates counterclockwise, from A to B, as air pressure to the casing or lower cylinder increases.
D For air‐to‐close actuators (i.e., the actuator stem extends from the actuator casing or cylinder as air pressure to
the casing or upper cylinder increases), insert the alignment pin into the hole marked “B''. For this style actuator,
the feedback arm rotates clockwise, from B to A, as air pressure to the casing or upper cylinder increases.
Note
When performing the following steps, ensure there is enough clearance between the adjustment arm and the feedback arm to
prevent interference with the bias spring.
10
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
7. Apply anti‐seize to the pin of the adjustment arm. As shown in figure 5, place the pin into the slot of the feedback
arm or feedback arm extension so that the bias spring loads the pin against the side of the arm with the valve travel
markings.
8. Install the external lock washer on the adjustment arm. Position the adjustment arm in the slot of the connector
arm and loosely install the flanged hex nut.
9. Slide the adjustment arm pin in the slot of the connector arm until the pin is in line with the desired valve travel
marking. Tighten the flanged hex nut.
10. Remove the alignment pin and store it in the module base next to the I/P assembly.
11. After calibrating the instrument, attach the shield with two machine screws.
FEEDBACK ARM
BIAS SPRING
ADJUSTMENT
ARM PIN BIAS
SPRING
SPRING UNDER TENSION OF
A7209‐1 SPRING RELAXED ADJUSTMENT ARM PIN
Note
All cams supplied with FIELDVUE mounting kits are characterized to provide a linear response.
Note
Do not use the stainless steel DVC6020S in high vibration service where the mounting bracket uses standoffs (spacers) to mount
to the actuator.
As shown in figure 6, two feedback arms are available for the digital valve controller. Installations on Fisher 1051 size
33 and 1052 size 20 and 33 actuators use the short feedback arm [54 mm (2.13 inches) from roller to pivot point].
Most other use the long feedback arm. Make sure the correct feedback arm is installed on the digital valve controller
before beginning the mounting procedure.
11
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
CAM
29B1672‐A
CAM
29B2094‐A MACHINE SCREW
TYPICAL MOUNTING WITH SHORT FEEDBACK ARM TYPICAL MOUNTING WITH LONG FEEDBACK ARM
(FISHER 1052 SIZE 33 ACTUATOR SHOWN) (FISHER 1061 SIZE 30-68 ACTUATOR SHOWN)
Refer to figure 6 for parts locations. Refer to the following guidelines when mounting on rotary actuators:
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the pneumatic actuator, releasing all pressure from the actuator. Use lock‐out procedures to
be sure that the above measures stay in effect while working on the equipment.
2. If a cam is not already installed on the actuator, install the cam as described in the instructions included with the
mounting kit.
3. If a mounting plate is required, fasten the mounting plate to the actuator.
4. For applications that require remote venting, a pipe‐away bracket kit is available. Follow the instructions included
with the kit to replace the existing mounting bracket on the digital valve controller with the pipe‐away bracket and
to transfer the feedback parts from the existing mounting bracket to the pipe‐away bracket.
5. Apply anti‐seize to the arm assembly pin, as shown in figure 7.
12
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
Figure 7. Locating Adjustment Arm Pin in Feedback Arm of a FIELDVUE DVC6020 Digital Valve Controller
MOUNTING
ADAPTER
MOUNTING
BRACKET
BIAS SPRING
ARM ASSEMBLY
FEEDBACK
ARM ASSEMBLY
D If no mounting adaptor is required, attach the digital valve controller assembly to the actuator or mounting
plate. The roller on the digital valve controller feedback arm will contact the actuator cam as it is being attached.
13
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
Note
Due to NAMUR mounting limitations, do not use the stainless steel DVC6030S in high vibration service.
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the pneumatic actuator, releasing all pressure from the actuator. Use lock‐out procedures to
be sure that the above measures stay in effect while working on the equipment.
2. If necessary, remove the existing hub from the actuator shaft.
3. If a positioner plate is required, attach the positioner plate to the actuator as described in the mounting kit
instructions.
Figure 8. Mounting a FIELDVUE DVC6030 Digital Valve Controller on a Rotary Actuator (Fisher 1032 Size 425A
Shown)
MOUNTING
BRACKET FEEDBACK ARM
TRAVEL INDICATOR
PIN
29B1703‐A
SPACER
TRAVEL INDICATOR
19B3879-A
14
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
Refer to figures 9 and 10. The travel indicator assembly can have a starting position of 7:30 or 10:30. Determine the
desired starting position then proceed with the next step. Considering the top of the digital valve controller as the 12
o'clock position, in the next step attach the travel indicator, so that the pin is positioned as follows:
D If increasing pressure from the digital valve controller output A rotates the potentiometer shaft clockwise (as
viewed from the back of the instrument), mount the travel indicator assembly so that the arrow is in the 10:30
position, as shown in figure 9.
D If increasing pressure from the digital valve controller output A rotates the potentiometer shaft counterclockwise
(as viewed from the back of the instrument), mount the travel indicator assembly so that the arrow is in the 7:30
position, as shown in figure 10.
Note
ValveLink software and the Field Communicator use the convention of clockwise (figure 9) and counterclockwise (figure 10) when
viewing the potentiometer shaft from the back of the FIELDVUE instrument.
5. Attach the travel indicator to the shaft connector or spacer as described in the mounting kit instructions.
6. Attach the mounting bracket to the digital valve controller.
Figure 9. Explanation of FIELDVUE DVC6030 Travel Indicator Starting Position and Movement, if Clockwise
Orientation is Selected for “Travel Sensor Motion” in ValveLink Software or the Field Communicator
E0989
MOVEMENT OF TRAVEL
DVC6030 FEEDBACK ARM MOVEMENT INDICATOR ASSEMBLY WITH
INCREASING PRESSURE
FROM OUTPUT A.
15
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
Figure 10. Explanation of FIELDVUE DVC6030 Travel Indicator Starting Position and Movement if Counterclockwise
Orientation is Selected for “Travel Sensor Motion” in ValveLink Software or the Field Communicator
MOVEMENT OF E0989
TRAVEL INDICATOR
ASSEMBLY WITH
INCREASING
PRESSURE FROM DVC6030 FEEDBACK
OUTPUT A. ARM MOVEMENT
19B3879‐A
7. Position the digital valve controller so that the pin on the travel indicator, engages the slot in the feedback arm and
that the bias spring loads the pin as shown in figure 11. Attach the digital valve controller to the actuator or
positioner plate.
8. If a travel indicator scale is included in the mounting kit, attach the scale as described in the mounting kit
instructions.
Figure 11. Positioning Travel Indicator Pin in the Feedback Arm (Viewed as if Looking from the FIELDVUE DVC6030
toward the Actuator)
HOLE A
HOLE B
TRAVEL
INDICATOR PIN
FEEDBACK ARM
48B4164‐B BIAS SPRING
16
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
Integral‐Mounted Regulator
Refer to figure 12. Lubricate an O‐ring and insert it in the recess around the SUPPLY connection on the digital valve
controller. Attach the 67CFR filter regulator to the side of the digital valve controller. Thread a 1/4‐inch socket‐head
pipe plug into the unused outlet on the filter regulator. This is the standard method of mounting the filter regulator.
Figure 12. Mounting the Fisher 67CFR Regulator on a FIELDVUE DVC6000 Digital Valve Controller
FISHER 67CFR
CAP SCREWS
NOTE: O‐RING 1
1 APPLY LUBRICANT
W8077‐1 SUPPLY CONNECTION
Yoke‐Mounted Regulator
Mount the filter regulator with 2 cap screws to the pre‐drilled and tapped holes in the actuator yoke. Thread a 1/4‐inch
socket‐head pipe plug into the unused outlet on the filter regulator. No O‐ring is required.
Casing‐Mounted Regulator
Use the separate 67CFR filter regulator casing mounting bracket provided with the filter regulator. Attach the
mounting bracket to the 67CFR and then attach this assembly to the actuator casing. Thread a 1/4‐inch socket‐head
pipe plug into the unused outlet on the filter regulator. No O‐ring is required.
17
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
Pressure Connections
Pressure connections are shown in figure 13. All pressure connections on the digital valve controller are 1/4 NPT
internal connections. Use at least 10 mm (3/8‐inch) tubing for all pressure connections. If remote venting is required,
refer to the vent subsection.
OUTPUT A CONNECTION
SUPPLY CONNECTION
OUTPUT B CONNECTION
W7963‐1
Supply Connections
WARNING
To avoid personal injury and property damage resulting from bursting of parts, do not exceed maximum supply pressure.
Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and
appropriate preventive measures are not taken. Preventive measures may include, but are not limited to, one or more of
the following: Remote venting of the unit, re‐evaluating the hazardous area classification, ensuring adequate ventilation,
and the removal of any ignition sources. For information on remote venting of this controller, refer to page 20.
Severe personal injury or property damage may occur from an uncontrolled process if the instrument supply medium is not
clean, dry, oil‐free, and noncorrosive. While use and regular maintenance of a filter that removes particles larger than 40
micrometers in diameter will suffice in most applications, check with an Emerson Process Management field office and
industry instrument air quality standards for use with corrosive air or if you are unsure about the amount of air filtration or
filter maintenance.
WARNING
When using natural gas as the supply medium, or for explosion proof applications, the following warnings also apply:
D Remove electrical power before removing the housing cap. Personal injury or property damage from fire or explosion
may result if power is not disconnected before removing the cap.
18
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
The DVC6000 can be used with air or natural gas as the supply medium. If using natural gas as the pneumatic supply
medium, natural gas will be used in the pneumatic output connections of the DVC6000 to any connected equipment.
In normal operation the unit will vent the supply medium into the surrounding atmosphere unless it is remotely
vented.
Natural Gas Certified, Single Seal instruments can be identified by the natural gas approval label shown in figure 14.
The Natural Gas Certified, Single Seal device option simplifies conduit sealing requirements. Read and follow all local,
regional, and federal wiring requirements for natural gas installations. Contact your Emerson Process Management
sales office for information on obtaining a Natural Gas Certified, Single Seal DVC6000 digital valve controller.
LABEL LOCATED
ON TOP OF
TERMINAL BOX
Supply pressure must be clean, dry air that meets the requirements of ISA Standard 7.0.01.
Alternatively, natural gas must be clean, dry, oil‐free, and noncorrosive. H2S content should not exceed 20 ppm.
A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer
particle size is recommended. Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis.
Condensation in the air supply should be minimized.
If you are using a 67CFR filter regulator with standard 5 micrometer filter, connect the supply line to the 1/4 NPT IN
connection and attach tubing from the output connection on the filter regulator to the SUPPLY connection on the
instrument. If you are using an integral mounted 67CFR filter regulator, connect the supply to the IN connection on
the regulator.
Output Connection
A factory mounted digital valve controller has its output piped to the supply connection on the actuator. If mounting
the digital valve controller in the field, connect the 1/4 NPT digital valve controller output connection to the
pneumatic actuator input connection.
19
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
Single‐Acting Actuators
When using a single‐acting direct digital valve controller (relay A or C) on a single‐acting actuator, connect OUTPUT A
to the actuator pneumatic input.
When using a single‐acting reverse digital valve controller (relay B) on a single‐acting actuator, connect OUTPUT B to
the actuator diaphragm casing.
Double‐Acting Actuators
DVC6000 digital valve controllers on double‐acting actuators always use relay A. With no input current, OUTPUT A is at
0 pressure and OUTPUT B is at full supply pressure when the relay is properly adjusted.
To have the actuator stem extend from the cylinder with increasing input signal, connect OUTPUT A to the upper
actuator cylinder connection. Connect OUTPUT B to the lower cylinder connection. Figure 15 shows the digital valve
controller connected to a double‐acting piston actuator.
To have the actuator stem retract into the cylinder with increasing input signal, connect OUTPUT A to the lower
actuator cylinder connection. Connect OUTPUT B to the upper cylinder connection.
Figure 15. FIELDVUE DVC6010 Digital Valve Controller Mounted on Fisher 585C Piston Actuator
W9131‐1
Vent
WARNING
Personal injury or property damage can occur from cover failure due to overpressure. Ensure that the housing vent
opening is open and free of debris to prevent pressure buildup under the cover.
This unit vents the supply medium into the surrounding atmosphere. When installing this unit in a non‐hazardous
(non‐classified) location in a confined area, with natural gas as the supply medium, you must remotely vent this unit to a
safe location. Failure to do so could result in personal injury or property damage from fire or explosion, and area
re‐classification.
20
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
When installing this unit in a hazardous (classified) location remote venting of the unit may be required, depending upon
the area classification, and as specified by the requirements of local, regional, and federal codes, rules and regulations.
Failure to do so when necessary could result in personal injury or property damage from fire or explosion, and area
re‐classification.
Vent line piping should comply with local and regional codes and should be as short as possible with adequate inside
diameter and few bends to reduce case pressure buildup.
In addition to remote venting of the unit, ensure that all caps and covers are correctly installed. Failure to do so could result
in personal injury or property damage from fire or explosion, and area re‐classification.
The relay output constantly bleeds a small amount of supply medium into the area under the cover. The vent openings
at the back of the housing should be left open to prevent pressure buildup under the cover. If a remote vent is
required, the vent lines must be as short as possible with a minimum number of bends and elbows.
Note
Connect the digital valve controller to a 4‐20 mA current source for operation in the point‐to‐point wiring mode. In the
point‐to‐point wiring mode, the digital valve controller will not operate when connected to a voltage source.
21
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
WARNING
Personal injury or property damage, caused by fire or explosion, can result from the discharge of static electricity. Connect
a 14 AWG (2.08 mm2) ground strap between the digital valve controller and earth ground when flammable or hazardous
gases are present. Refer to national and local codes and standards for grounding requirements.
To avoid static discharge from the plastic cover when flammable gases or dust are present, do not rub or clean the cover
with solvents. To do so could result in a spark that may cause the flammable gases or dust to explode, resulting in personal
injury or property damage. Clean with a mild detergent and water only.
EARTH GROUND
LOOP+
39B3399‐B Sheet 2
LOOP-
22
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
HART Filter
Depending on the control system you are using, a HART filter may be needed to allow HART communication. The
HART filter is a passive device that is inserted in field wiring from the HART loop. The filter is normally installed near the
field wiring terminals of the control system I/O (see figure 17). Its purpose is to effectively isolate the control system
output from modulated HART communication signals and raise the impedance of the control system to allow HART
communication. For more information on the description and use of the HART filter, refer to the appropriate separate
HART filter instruction manual.
To determine if your system requires a filter contact your Emerson Process Management sales office.
I/O I/O
HART
FILTER
4‐20 mA
DIGITAL VALVE
CONTROLLER
Tx Tx VALVE
A6188‐1
23
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
j Is the instrument output connected to the actuator? If not, connect instrument output as
described on page 19.
j Is the loop wiring properly connected to the LOOP + and - terminals in the terminal box? If not,
connect loop wiring as described on page 21.
j If necessary, is the HART filter installed on your system? To determine if a HART filter is necessary,
contact your Emerson Process Management sales office. For HART filter installation information,
refer to the appropriate HART instruction manual.
You are ready to perform Basic Setup and Calibration in the next section.
24
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
If the Field Communicator is connected directly to the digital valve controller, attach the clip‐on wires provided with
the Field Communicator to the TALK terminals, or the LOOP + and - terminals, in the digital valve controller terminal
box. The TALK terminals are the same as the LOOP + and - terminals (see figure 16).
FIELD
INSTRUMENT
HF340 HART CONNECTION 4‐20 MA LOOP
FILTER CONNECTIONS
OR 0‐24VDC
CONTROLLER
I/O - -
+ +
1
HART
COMMUNICATION
CONNECTION
2
NOTE:
1 NOT ALL CONTROL SYSTEMS REQUIRE A HART FILTER. IF NO HART FILTER IS PRESENT,
CONNECT FIELD COMMUNICATOR TO CONTROL SYSTEM OUTPUT TERMINALS.
2 SEE FIGURE 16 FOR TERMINAL BOX DETAILS.
38B6470‐A
A6194-4
Basic Setup
WARNING
Changes to the instrument setup may cause changes in the output pressure or valve travel. Depending on the application,
these changes may upset process control, which may result in personal injury or property damage.
25
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
Before beginning Basic Setup, be sure the instrument is correctly mounted. Refer to the installation instructions
supplied with the mounting kit.
Connect a 4‐20 mA current source to the instrument. Connect the Field Communicator to the instrument and turn it
on. For information on connecting the Field Communicator, see Connecting the Field Communicator to the Digital
Valve Controller.
Typical Actuators
The Setup Wizard determines the required setup information based upon the actuator manufacturer and model
specified. Turn on the Field Communicator and start the Setup Wizard by proceeding through the menu sequence
shown in figure 19 or enter the fast‐key sequence 1‐1‐1 on the keypad. Follow the prompts on the Field Communicator
display to setup the instrument. If the actuator on which the instrument is mounted is not listed by the Setup Wizard,
specify OTHER as the actuator manufacturer or actuator type and refer to Non‐Typical Actuators.
Figure 19. Accessing Setup Wizard on the Field Communicator (Instrument Level HC, AD, and PD)
HOME HOME
From the DVC6000 Online menu, From the Configure menu, From the Guided Setup menu,
select Configure select Guided Setup. select Setup Wizard and
follow the on‐line instructions
WARNING
During calibration the valve will move full stroke. To avoid personal injury and property damage caused by the release of
process fluid or pressure, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the
process fluid.
After completing the setup information, travel is automatically calibrated. Follow the prompts on the Field
Communicator display. The calibration procedure uses the valve and actuator stops as the 0% and 100% calibration
points. For additional information, refer to Auto Calibrate Travel in this section.
When travel calibration is complete, you are asked if you wish to adjust the relay (double‐acting only). Select yes to
adjust the relay. For additional information, refer to Relay Adjustment in this section.
Non‐Typical Actuators
If the actuator on which the instrument is mounted is not listed during the Setup Wizard, specify OTHER as the
actuator manufacturer or actuator type. You are then prompted for setup parameters such as:
D Actuator Style (spring & diaphragm, piston double‐acting without spring, piston single‐acting with spring, piston
double‐acting with spring)
26
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
D On Loss of Instrument Signal, Valve (opens or closes) This identifies whether the valve is fully open or fully closed
when the input is 0%. If you are unsure how to set this parameter, disconnect the current source to the instrument.
(With double‐acting and single‐acting direct digital valve controllers, disconnecting the current source is the same
as setting the output A pressure to zero. For single‐acting reverse digital valve controllers, disconnecting the
current source is the same as setting the output B pressure to supply.)
D Feedback Connection (Rotary ‐ All, SStem ‐ Standard, SStem ‐ Roller). For rotary valves, enter Rotary ‐ All. For
sliding‐stem valves, if the feedback linkage consists of a connector arm, adjustment arm, and feedback arm (similar
to figure 22), enter SStem ‐ Standard. If the feedback linkage consists of a roller that follows a cam (similar to figure
20), enter SStem ‐ Roller.
Figure 20. Feedback Connection for Typical Long‐Stroke Sliding‐Stem Actuator (4 to 24 inches travel)
ROLLER
29B1665‐A
WARNING
If you answer YES to the prompt for permission to move the valve when determining travel sensor motion, the instrument
will move the valve through a significant portion of its travel range. To avoid personal injury and property damage caused
by the release of pressure or process fluid, provide some temporary means of control for the process.
D Travel Sensor Motion The Setup Wizard asks if it can move the valve to determine travel sensor motion. If you
answer Yes, the instrument will stroke the valve the full travel span to determine travel sensor motion. If you answer
No, then you must specify the rotation for increasing air pressure: clockwise or counterclockwise. Determine
rotation by viewing the end of the travel sensor shaft.
For instruments with relay A or C. If increasing air pressure at output A causes the shaft to turn clockwise, enter
Clockwise. If it causes the shaft to turn counterclockwise, enter Cntrclockwise.
27
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
For instruments with relay B. If decreasing air pressure at output B causes the shaft to turn clockwise, enter
Clockwise. If it causes the shaft to turn counterclockwise, enter Cntrclockwise.
Note
Relay adjustment may be required before the Setup Wizard can determine travel sensor motion. Follow the prompts on the Field
Communicator display if relay adjustment is necessary.
D Volume Booster The Setup Wizard asks if a volume booster or quick release is present.
WARNING
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury and property damage
caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.
D Tuning Set There are twelve tuning sets from which to choose. Each tuning set provides preselected values for the
digital valve controller gain and rate settings. Typically, tuning set B provides the slowest response and M provides
the fastest response. For smaller actuators, use tuning set C or D. For larger actuators, use tuning set F or G.
Note
Tuning set B is only available in Pressure Control Mode.
In addition, you can select User Adjusted or Expert, which allows you to modify tuning of the digital valve controller.
With User Adjusted you can specify the proportional gain. An algorithm in the Field Communicator calculates the
other gains. With Expert you can specify not only the proportional gain but the velocity and minor loop feedback gain
as well.
Note
Use Expert tuning only if standard tuning has not achieved the desired results.
Stabilize/Optimize or Performance Tuner may be used to achieve the desired results more rapidly than Expert tuning.
The tuning sets suggested by the Setup Wizard are only recommended starting points. After you finish setting up and
calibrating the instrument, run the Performance Tuner or use Stabilize/Optimize Tuning to obtain optimum tuning.
Factory Defaults
During basic setup, the Setup Wizard will ask you if you want to use factory defaults. If you select YES, the Setup
Wizard sets the setup parameters to the values listed in table 6. (Yes is recommended for initial setup). If you select
NO, the setup parameters listed in the table remain at their previous settings.
28
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
Relay Adjustment
The double‐acting relay can be adjusted as part of the Setup Wizard. The following is a brief description of relay
adjustment. For additional information, see the Calibration section in the DVC6000 instruction manual.
Note
Relay B and C are not user‐adjustable.
CAUTION
Care should be taken during relay adjustment as the adjustment disc may disengage if rotated too far.
29
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
ADJUSTMENT DISC
FOR DOUBLE‐ACTING RELAYS: ROTATE
ADJUSTMENT DISC IN THIS DIRECTION TO
INCREASE OUTPUT PRESSURE
W9034
The instrument is calibrated during the Setup Wizard. Follow the prompts on the Field Communicator display to
automatically calibrate instrument travel. The calibration procedure uses the valve and actuator stops as the 0% and
100% calibration points.
For additional calibration information, refer to the DVC6000 instruction manual.
1. If the Feedback Connection is Sliding‐Stem Standard, the Field Communicator prompts you to select the method of
crossover adjustment: manual, last value, or default. Manual adjustment is recommended for initial travel
calibration.
30
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
2. When prompted by the Field Communicator, make the crossover adjustment by adjusting the current source until
the feedback arm is 90° to the actuator stem, as shown in figure 22.
ACTUATOR STEM
TRAVEL SENSOR SHAFT
FEEDBACK ARM
ADJUSTMENT ARM
CONNECTOR ARM
A6536‐1
3. The remainder of the auto‐calibration procedure is automatic. After completing auto travel calibration, the Field
Communicator prompts you to place the instrument In Service and verify that the travel properly tracks the current
source.
If the unit does not calibrate, refer to table 7 for error messages and possible remedies.
If after completing setup and calibration the valve cycles or overshoots (unstable), or is unresponsive (sluggish), you
can improve operation by selecting either Performance Tuner or Stabilize/Optimize from the Guided Setup menu.
31
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
Note
The Performance Tuner is not available for instrument level AC or HC.
WARNING
During performance tuning the valve may move, causing process fluid or pressure to be released. To avoid personal injury
and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize
pressure on both sides of the valve or bleed off the process fluid.
The Performance Tuner is used to optimize digital valve controller tuning. It can be used on most sliding‐stem and
rotary designs, including Fisher and other manufacturers' products. Moreover, because the Performance Tuner can
detect internal instabilities before they become apparent in the travel response, it can generally optimize tuning more
effectively than manual tuning. Typically, the Performance Tuner takes 3 to 5 minutes to tune an instrument, although
tuning instruments mounted on larger actuators may take longer.
Access the Performance Tuner by selecting Performance Tuner from the Guided Setup menu. Follow the prompts on the
Field Communicator display to optimize digital valve controller tuning.
Note
Stabilize/Optimize is only available through the Guided Setup menu for instrument level HC.
WARNING
During Stabilize/Optimize the valve may move, causing process fluid or pressure to be released. To avoid personal injury
and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize
pressure on both sides of the valve or bleed off the process fluid.
If after completing setup and calibration the valve seems slightly unstable or unresponsive, you can improve operation
by pressing the Hot Key and selecting Stabilize/Optimize, or select Stabilize/Optimize from the Guided Setup menu.
Stabilize/Optimize permits you to adjust valve response by changing the digital valve controller tuning.
If the valve is unstable, select Decrease Response to stabilize valve operation. This selects the next lower tuning set
(e.g., F to E). If the valve response is sluggish, select Increase Response to make the valve more responsive. This selects
the next higher tuning set (e.g., F to G).
If after selecting Decrease Response or Increase Response the valve travel overshoot is excessive you can adjust the
damping by selecting Decrease Damping or Increase Damping. By selecting Decrease Damping or Increase Damping the
32
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
tuning set will become Expert, and allow you to select a damping value that is not represented in a predefined tuning
set. Select Decrease Damping to select a damping value that allows more overshoot. Select Increase Damping to select a
damping value that will decrease the overshoot.
j Is basic setup complete? If not, perform Basic Setup procedure on page 25.
j Does the final control element correctly respond to a setpoint change and is it
stable? If not, perform Stabilizing or Optimizing Valve Response on page 32.
33
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
Table 8. Specifications
Available Configurations Maximum: 10.0 bar (145 psig) or maximum pressure
Valve‐Mounted Instrument rating of the actuator, whichever is lower
DVC6010: Sliding‐stem applications Medium: Air or Natural Gas
DVC6020: Rotary and long‐stroke sliding‐stem Air: Supply pressure must be clean, dry air that meets
applications the requirements of ISA Standard 7.0.01.
DVC6030: Quarter‐turn rotary applications
Natural Gas: Natural gas must be clean, dry, oil‐free,
Remote‐Mounted Instrument(1)
and noncorrosive. H2S content should not exceed 20
DVC6005: Base unit for 2 inch pipestand or wall
ppm.
mounting
DVC6015: Feedback unit for sliding‐stem applications A maximum 40 micrometer particle size in the air
DVC6025: Feedback unit for rotary or long‐stroke system is acceptable. Further filtration down to 5
sliding‐stem applications micrometer particle size is recommended. Lubricant
DVC6035: Feedback unit for quarter‐turn rotary content is not to exceed 1 ppm weight (w/w) or
applications volume (v/v) basis. Condensation in the air supply
should be minimized
DVC6000 digital valve controllers can be mounted on
Fisher and other manufacturers rotary and
sliding‐stem actuators. Steady‐State Air Consumption(3)
Standard Relay
Input Signal At 1.4 bar (20 psig) supply pressure:
Point‐to‐Point: Less than 0.38 normal m3/hr (14 scfh)
Analog Input Signal: 4‐20 mA DC, nominal At 5.5 bar (80 psig) supply pressure:
Minimum Voltage Available at instrument terminals Less than 1.3 normal m3/hr (49 scfh)
must be 10.5 volts DC for analog control, 11 volts DC Low Bleed Relay(4)
for HART communication (see instrument instruction At 1.4 bar (20 psig) supply pressure:
manual for details) Average value 0.056 normal m3/hr (2.1 scfh)
Minimum Control Current: 4.0 mA At 5.5 bar (80 psig) supply pressure:
Minimum Current w/o Microprocessor Restart: 3.5 mA Average value 0.184 normal m3/hr (6.9 scfh)
Maximum Voltage: 30 volts DC
Overcurrent Protection: Input circuitry limits current to Maximum Output Capacity(3)
prevent internal damage. At 1.4 bar (20 psig) supply pressure:
Reverse Polarity Protection: No damage occurs from 10.0 normal m3/hr (375 scfh)
reversal of loop current. At 5.5 bar (80 psig) supply pressure:
Multi‐drop: 29.5 normal m3/hr (1100 scfh)
Instrument Power: 11‐30 VDC at approximately 8 mA
Reverse Polarity Protection: No damage occurs from Failure Modes
reversal of loop current.
Refer to figure 23
Output Signal
Independent Linearity(5)
Pneumatic signal as required by the actuator, up to
full supply pressure. ±0.50% of output span
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig) Electromagnetic Compatibility
Action: Double, Single direct, and Single reverse Meets EN 61326‐1 (First Edition)
Immunity—Industrial locations per Table 2 of the
Supply Pressure(2) EN 61326‐1 standard. Performance is shown
Recommended: 0.3 bar (5 psig) higher than in table 9 below
maximum actuator requirements, up to maximum Emissions—Class A
supply pressure ISM equipment rating: Group 1, Class A
-continued-
34
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
35
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
NOTE: Specialized instrument terms are defined in ISA Standard 51.1 - Process Instrument Terminology.
1. 3‐conductor shielded cable, 22 AWG minimum wire size, is required for connection between base unit and feedback unit. Pneumatic tubing between base unit output connection and actuator
has been tested to 91 meters (300 feet). At 15 meters (50 feet) there was no performance degradation. At 91 meters there was minimal pneumatic lag.
2. The pressure/temperature limits in this quick start guide and any applicable code or standard should not be exceeded.
3. Values at 1.4 bar (20 psig) based on a single‐acting direct relay; values at 5.5 bar (80 psig) based on double‐acting relay.
4. The low bleed relay is offered as standard relay for DVC6000 SIS tier, used for On/Off applications.
5. Typical value. Not applicable for travels less than 19 mm (0.75 inch) or for shaft rotation less than 60 degrees. Also not applicable for DVC6020 digital valve controllers in long‐stroke applications.
6. Temperature limits vary based on hazardous area approval.
7. Do not use the DVC6010S or DVC6020S in high vibration service where the mounting bracket uses standoffs (spacers) to mount to the actuator. Due to NAMUR mounting limitations, do not use
the DVC6030S in high vibration service.
36
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
W7963‐1
Related Documents
This section lists other documents containing information related to DVC6000 digital valve controllers. These
documents include:
D Remote Mount Installation Guidelines— Supplement to Fisher FIELDVUE DVC6000 Digital Valve Controller Quick
Start Guide (D103421X012)
D FIELDVUE Digital Valve Controller Split Ranging— Supplement to HART Communicating Fisher FIELDVUE Digital
Valve Controller Instruction Manuals (D103262X012)
D Using FIELDVUE Instruments with the Smart HART Loop Interface and Monitor (HIM)— Supplement to HART
Communicating Fisher FIELDVUE Instrument Instruction Manuals (D103263X012)
D Using FIELDVUE Instruments with the Smart Wireless THUMt Adapter and a HART Interface Module (HIM) -
Supplement to HART Communicating Fisher FIELDVUE Instrument Instruction Manuals (D103469X012)
D Audio Monitor for HART Communications— Supplement to HART Communicating Fisher FIELDVUE Instrument
Instruction Manuals (D103265X012)
D HART Field Device Specification— Supplement to Fisher FIELDVUE DVC6000 Digital Valve Controller Instruction
Manual (D103649X012)
D Using the HART Tri‐Loopt HART‐to‐Analog Signal Converter with FIELDVUE Digital Valve Controllers— Supplement
to HART Communicating Fisher FIELDVUE Instrument Instruction Manuals (D103267X012)
D Hot Swap Procedure— Supplement to Fisher FIELDVUE DVC5000 (obsolete product) and DVC6000 Digital Valve
Controller Instruction Manuals (D103264X012)
37
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
D Lock‐in‐Last Strategy—Supplement to Fisher FIELDVUE DVC6000 Digital Valve Controllers Instruction Manual
(D103261X012)
All documents are available from your Emerson Process Management sales office. Also visit our website at
www.FIELDVUE.com.
Educational Services
For information on available courses for DVC6000 digital valve controllers, as well as a variety of other products,
contact:
38
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
1 NOTE 1, 3, 4, 5, 6
T CODE T (amb)
T5 ≤ 80_C 1 NOTE 7
T6 ≤ 75_C
THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY
EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Vmax or Ui), THE CURRENT (Imax or Ii), AND THE
POWER (Pmax or Pi) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc or Uo), AND THE CURRENT
(Isc or Io), AND THE POWER (Po) DEFINED BY THE ASSOCIATED APPARATUS. IN ADDITION, THE SUM OF THE MAX UNPROTECTED CAPACITANCE (Ci)
AND MAX UNPROTECTED INDUCTANCE (Li), INCLUDING THE INTERCONNECTING CABLING CAPACITANCE (Ccable) AND CABLING INDUCTANCE
(Lcable) MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Ca) AND INDUCTANCE (La) DEFINED BY THE ASSOCIATED APPARATUS. IF THE ABOVE
CRITERIA IS MET, THEN THE COMBINATION MAY BE CONNECTED.
Vmax or Ui . Voc or Uo Imax or Ii . Isc or Io Pmax or Pi . Po Ci + Ccable ≤ Ca Li + Lcable ≤ La
INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC) NFPA70 AND ANSI/ISA RP12.6.01
MAXIMUM SAFE AREA VOLTAGE SHOULD NOT EXCEED 250 Vrms
RESISTANCE BETWEEN INTRINSICALLY SAFE GROUND AND EARTH GROUND MUST BE LESS THAN ONE OHM
LOOPS MUST BE CONNECTED ACCORDING TO THE BARRIER MANUFACTURER'S INSTRUCTIONS.
IF HAND‐HELD COMMUNICATOR OR MULTIPLEXER IS USED IT MUST BE CSA APPROVED WITH ENTITY PARAMETERS AND INSTALLED PER THE
MANUFACTURER'S CONTROL DRAWING
GE42818
Sheet 2 Rev. E
Sheet 8 Rev. D
39
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY
EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Vmax or Ui), THE CURRENT (Imax or Ii), AND
THE POWER (Pmax or Pi) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc or Uo), AND THE
CURRENT (Isc or Io), AND THE POWER (Po) DEFINED BY THE ASSOCIATED APPARATUS. IN ADDITION, THE SUM OF THE MAX UNPROTECTED
CAPACITANCE (Ci) AND MAX UNPROTECTED INDUCTANCE (Li), INCLUDING THE INTERCONNECTING CABLING CAPACITANCE (Ccable) AND
CABLING INDUCTANCE (Lcable) MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Ca) AND INDUCTANCE (La) DEFINED BY THE ASSOCIATED
APPARATUS. IF THE ABOVE CRITERIA IS MET, THEN THE COMBINATION MAY BE CONNECTED.
Vmax or Ui . Voc or Uo Imax or Ii . Isc or Io Pmax or Pi . Po Ci + Ccable ≤ Ca Li + Lcable ≤ La
INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC) NFPA70 AND ANSI/ISA RP12.6.01
MAXIMUM SAFE AREA VOLTAGE SHOULD NOT EXCEED 250 Vrms.
RESISTANCE BETWEEN INTRINSICALLY SAFE GROUND AND EARTH GROUND MUST BE LESS THAN ONE OHM
LOOPS MUST BE CONNECTED ACCORDING TO THE BARRIER MANUFACTURER'S INSTRUCTION
IF HAND‐HELD COMMUNICATOR OR MULTIPLEXER IS USED IT MUST BE FM APPROVED WITH ENTITY PARAMETERS AND INSTALLED PER THE
MANUFACTURER'S CONTROL DRAWING
WARNING
THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS CONSIDERED
TO CONSTITUTE A POTENTIAL RISK OF IGNTION BY IMPACT AND FRICTION.
AVOID IMPACT AND FRICTION DURING INSTALLATION AND USE TO
PREVENT RISK OF IGNTION.
GE42819
sheet 2, Rev. D
Sheet 8, Rev. E
40
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
ZONE 0, Ex ia IIC
ZONE 20, Ex ia IIIC
Ui = 30 VDC
Ii = 226 mA
Ci = 5 nF ATEX APPROVED BARRIER
Li = 0.55 mH
Pi = 1.4 W
1 NOTE 1, 3, 4
1 NOTE 5
ZONE 0 ZONE 20
Ex ia IIC Ex ia IIIC
MAX
T CODE T AMB SURFACE T AMB
TEMP
THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED
IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Vmax or Ui), THE CURRENT (Imax or Ii), AND THE POWER (Pmax
or Pi) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc or Uo), AND THE CURRENT (Isc or Io), AND
THE POWER(Po) DEFINED BY THE ASSOCIATED APPARATUS. IN ADDITION, THE SUM OF THE MAX UNPROTECTED CAPACITANCE (Ci) AND MAX
UNPROTECTED INDUCTANCE (Li), INCLUDING THE INTERCONNECTING CABLING CAPACITANCE (Ccable) AND CABLING INDUCTANCE (Lcable) MUST BE
LESS THAN THE ALLOWABLE CAPACITANCE (Ca) AND INDUCTANCE (La) DEFINED BY THE ASSOCIATED APPARATUS. IF THE ABOVE CRITERIA IS MET,
THEN THE COMBINATION MAY BE CONNECTED.
Vmax or Ui . Voc or Uo Imax or Ii . Isc or Io Pmax or Pi . Po Ci + Ccable ≤ Ca Li + Lcable ≤ La
INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL WIRING PRACTICES OF THE COUNTRY IN USE.
LOOPS MUST BE CONNECTED ACCORDING TO THE BARRIER MANUFACTURER'S INSTRUCTIONS.
IF HAND‐HELD COMMUNICATOR OR MULTIPLEXER IS USED, IT MUST BE ATEX APPROVED WITH ENTITY PARAMETERS AND INSTALLED PER THE
MANUFACTURER'S CONTROL DRAWINGS.
41
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
INTRINSICALLY SAFE
FLAMEPROOF
TYPE n
42
Quick Start Guide DVC6000 Digital Valve Controller
D102762X012 July 2013
ZONE 0, Ex ia IIC
T5 ≤ 80_C
T6 ≤ 75_C
THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY
EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Vmax or Ui), THE CURRENT (Imax or Ii), AND THE
POWER (Pmax or Pi) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc OR Uo), AND THE CURRENT
(Isc or Io), AND THE POWER (Po) DEFINED BY THE ASSOCIATED APPARATUS. IN ADDITION, THE SUM OF THE MAX UNPROTECTED CAPACITANCE (Ci)
AND MAX UNPROTECTED INDUCTANCE (Li), INCLUDING THE INTERCONNECTING CABLING CAPACITANCE (Ccable) AND CABLING INDUCTANCE
(Lcable) MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Ca) AND INDUCTANCE (La) DEFINED BY THE ASSOCIATED APPARATUS. IF THE ABOVE
CRITERIA IS MET, THEN THE COMBINATION MAY BE CONNECTED.
Vmax or Ui . Voc or Uo Imax or Ii . Isc or Io Pmax or Pi . Po Ci + Ccable 3 Ca Li + Lcable 3 La
INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL WIRING PRACTICES OF THE COUNTRY IN USE
LOOPS MUST BE CONNECTED ACCORDING TO THE BARRIER MANUFACTURER'S INSTRUCTIONS
IF HAND‐HELD COMMUNICATOR OR MULTIPLEXER IS USED IT MUST BE IECEx APPROVED WITH ENTITY PARAMETERS AND INSTALLED PER THE
MANUFACTURERS CONTROL DRAWING
GE42990
Sheet 2, Rev. E
Sheet 8, Rev. D
43
DVC6000 Digital Valve Controller Quick Start Guide
July 2013 D102762X012
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, ValveLink, PlantWeb, THUM, and Tri‐loop are marks owned by one of the companies in the Emerson Process Management business
division of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co.
All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are