This document provides data on calculating the source impedance for a network feeder with a nominal voltage of 20 kV. It lists the initial symmetrical short circuit current as 10 kA and a voltage factor of 1.1. Using the rated transformation ratio of 48.78 and the given data, it calculates the source impedance ZQt to be 0.053+0.531j mΩ.

Uploaded by

DEADMAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
472 views1 page

Source Impedance Calculation

This document provides data on calculating the source impedance for a network feeder with a nominal voltage of 20 kV. It lists the initial symmetrical short circuit current as 10 kA and a voltage factor of 1.1. Using the rated transformation ratio of 48.78 and the given data, it calculates the source impedance ZQt to be 0.053+0.531j mΩ.

Uploaded by

DEADMAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Network Feeder (Source Impedance)

1 Data Required:

Nominal System Voltage (UnQ) = 20 KV


Initial Symmetrical Short Circuit Current (I''kQ) = 10 kA
Voltage Factor for the Voltage UnQ = 1.10
Rated Transformation Ratio (tr) = 48.78

2 Source (Network) Impedance:

=
x

ZQt = 0.534 mΩ

RQt = 0.053 mΩ

XQt = 0.531 mΩ

ZQt = 0.053+0.531j mΩ