AC Transducer 1

Masibus manufactures high quality power transducers for measuring electrical parameters such as current, voltage, power, frequency and power factor. The transducers provide accurate measurements and transmit linearized signals for applications like SCADA, energy monitoring, and remote indication. They are available in single or three phase versions with accuracy up to 0.25% and offer economical and accurate current and voltage measurement for systems with pure sine waves. Masibus transducers have excellent long-term stability, fast response, and high accuracy for industrial and commercial customers worldwide.

Uploaded by

partha maji
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
200 views4 pages

AC Transducer 1

Masibus manufactures high quality power transducers for measuring electrical parameters such as current, voltage, power, frequency and power factor. The transducers provide accurate measurements and transmit linearized signals for applications like SCADA, energy monitoring, and remote indication. They are available in single or three phase versions with accuracy up to 0.25% and offer economical and accurate current and voltage measurement for systems with pure sine waves. Masibus transducers have excellent long-term stability, fast response, and high accuracy for industrial and commercial customers worldwide.

Uploaded by

partha maji
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

DA/DV/DW/DVA/DH/DPF

Y
AC Line Transducer
K

Features
High accuracy class
0.25%

Confirms to IEC
60688

Power transducers
for all requirements

Excellent long term


stability

A dvanced A utomation - S ure S olutions


Low burden
Masibus manufactures high quality power transducers of various types to help
you manage and conserve electricity. All electrical parameters such as current, Transient protected
voltage, active power, reactive power, energy, frequency and power factor can
be accurately measured. A corresponding linearized signal is then transmitted Both 1-ph & 3-ph
for various applications such as SCADA, S/S automation, energy measurement,
remote indication, check metering etc. versions available
Power transducer series offers an economical and accurate means of current &
voltage measurement on systems where the waveform is a pure sine wave. Good isolation &
Transducers are calibrated to true RMS value of the sine wave. They can also be impulse resistance
used with distorted waveforms where high accuracy is not required.
AC line transducers are having its application to interface with RTUs. Masibus
make current & voltage transducers are also available with dual output.
Minimum ripple at
Transducers are available in 1Ø / 3Ø versions. It provides accuracy up to 0.25% the output
FS with up to 2 KV isolation. Hardware calibration is done through trim-pot.
Since 1994 Masibus has supplied power transducers to hundreds of utilities, Fast response
industrial plants and commercial establishments all over the world. All
transducers perform with exceptional accuracy, repeatability and reliability. In
addition to being most accurate, our transducers are equally preferred by OEMs/ Full power factor
end users to other makes for their excellent stability over a long period of range operation 65
operation. This world class technology now comes to you at a very competitive
price.
ABS DIN rail
AC line transducers are available as current, voltage, frequency, power, power C

factor and energy in 1Ø / 3Ø configuration. mounting M

K
E-mail: [email protected] | Web: www.masibus.com
DA/DV/DW/DVA/DH/DPF

Y
AC Line Current/Voltage
K

TECHNICAL SPECIFICATIONS CURRENT/VOLTAGE TRANSDUCER TECHNICAL SPECIFICATIONS CURRENT/VOLTAGE TRANSDUCER


General specification Enclosure ABS DIN, Rail Mount
Temperature 0 to 55°C AC Current Transducer DA
Humidity 40-90% RH (non condensing) AC Voltage Transducer DV
Terminations Metal Screw can accept up to 2.5 square mm wire Configuration
Mounting DIN rail mounting Single Phase 1
Case material ABS, Light gray. (RAL 7035) with fireproofing finish Three Phase* 3
Case Size Width-55 mm, Height-75 mm, Depth-110 mm (1Ø) Input
Circuit boards Copper cladded laminate FR-4 Grade epoxy glass Current Voltage
Connection Power/ Input/ Output 1/ Output 2 0-5A 0-150V 0
AC Current Transducers Specifications 0-1A 0-90V 1
Input Signal 0-5A, 0-1A, 0-2A. 0-2A 0-300V 2
Output Signal 0-1mA, 0-3mA, 0-5mA, 0-10mA, 4-20mA, 0-450V 3
0-1V, 0-5V, 0-10V, 1-5V
Output
Calibration Zero & Span of output can be adjusted by Trim pots
0-1mA (0-10,000 Ohms) 0
at the front
0-3mA (0-3,300 Ohms) 1
Loading
0-5mA (0-2,000 Ohms) 2
For Current See OUTPUT in Model Identification
0-10mA (0-1,000 Ohms) 3
For Voltage See OUTPUT in Model Identification
4-20mA (0-750 Ohms) 4
Output Accuracy ±0.25% of full scale Output Ripple < 75mV Peak
0-1V (180 Ohms minimum) 6
Response Time < 400 ms
0-5V (500 Ohms minimum) 7
Temp. Effect Less than ±0.01% per ºC
0-10V (1000 Ohms minimum) 8
Isolation 2.0KV AC for one minute Input/Output/Power/Case
1-5V (500 Ohms minimum) 9
Input Burden Input burden is 0.2 VA at full scale regardless of option
Special X
Weight 400 gms
Aux power
AC Voltage Transducers Specifications
110 VAC Aux Power EC
Input Signal 0-150V, 0-90V, 0-300V, 0-450V
230 VAC Aux Power FC
Output Signal 0-1mA, 0-3mA, 0-5mA, 0-10mA, 4-20mA, 0-100mV
0-1V, 0-5V, 0-10V, 1-5V DC Aux Power 24VDC K1
Calibration Zero & Span of output can be adjusted by Trim pots DC Aux Power 48VDC K2
at the front
DC Aux Power 125VDC K3
Loading
DC Aux Power 220VDC K4
For Current See OUTPUT in Model Identification
Special X
For Voltage See OUTPUT in Model Identification
* Self power only.
Output Accuracy ±0.25% of full scale Output Ripple < 75mV Peak
NO. of Outputs
Response Time < 400 ms
Single Keep Blank
Temp. Effect Less than ±0.01% per ºC
Dual D
Isolation 2.0KV AC for one minute Input/Output/Power/Case
Input Burden Input burden is 0.6 VA at full scale regardless of option For Example: DA-104-FC-D is the ordering code for 1-phase AC current
transducer in a DIN rail, with a 0-5A input, a 4-20mA dual output &
Weight 400 gms 230 VAC aux power.
NOTE: 1. Output code 4 & 9 and dual output is available only with 1-phase
configuration.
2. Output code 4 & 9 is & dual output available only with Aux supply
option.

66

K
DA/DV/DW/DVA/DH/DPF
C

Y
Power Transducer
K

TECHNICAL SPECIFICATIONS POWER TRANSDUCER Input 0-1A


Type Watt,VA,VAR Over range with accuracy 2A
Configuration Three phase, 3 wire, 2 element Maximum burden 0.5 VA
3 phase, 4 wire, 3 element Overload continuous 3A
Input Voltage 208 to 240 V, 63 to 69 V Overload 10 s/h 6A
100 to 120 V, 460 to 480 V Overload 1 s/h 100A
Input Current 0 to 5 Amp OUTPUT TABLE
0 to 1 Amp Range full Scale Output loading Compliance or
Accuracy Watt:0.19% of Rdg/Cosf ±0.01% of FS maximum current
VAR:0.19% of Rdg/sinf ±0.01% of FS 0 to ±1 mA 0-10000 Ohms ± 11 V
VA:0.19% of Rdg ±0.01% of FS 0 to ±3 mA 0-3000 Ohms ± 11 V
Output 0 to ± 1mA (0-10000 Ohms) 0 to ±5 mA 0-2000 Ohms ± 11 V
0 to ± 3 mA (0-3000 Ohms) 0 to ±10 mA 0-1000 Ohms ± 11 V
0 to ± 5 mA (0-2000 Ohms) 4 to 20 mA Unidirectional 0-750 Ohms 15 V
0 to ± 10 mA (0-1000 Ohms) 0 to ±100 mV 20 Ohms - 8 5 mA
4 to 20 mA (0-750 Ohms)* 0 to ±1 V 200 Ohms - 8 5 mA
0 to ± 100 mV (20 Ohms - 8 ) 0 to ±5 V 1000 Ohms - 8 5 mA
0 to ± 1 V (200 Ohms - 8 ) 0 to ±10 V 2000 Ohms - 8 5 mA
0 to ± 5 V (1000 Ohms - 8 ) 1 to 5 V 1000 Ohms - 8 1000 Ohms - 8
0 to ± 10 V (2000 Ohms - 8 ) Standard Calibration of watts.VAR,VA per element
1 to 5 V (1000 Ohms - 8 )* A\V 100-120V 208-240V
*Auxiliary power required for these outputs 0-5A 500 1000
Calibration Hardware - through Trim Pot 0-1A 100 200
Stability 0.2% per year
Auxiliary Power Supply 230VAC / 110VAC, 50Hz

A dvanced A utomation - S ure S olutions


Environmental Conditions 0 to 55°C, 0 to 95% non-condensing
Temperature Co-effcient ± 0.005% per °C
Case ABS Din Rail Mount
ORDERING INFORMATION
Power factor range any Enclosure ABS DIN rail mount D
Model Watt W
Operating frequency 50Hz/60Hz
VA VA
Dielectric Test 2 KV AC for 1 minute VAR R
Surge Withstand EN61000-4-5 Configuration 3-element (3-ph, 4 wire) 30
Response Time To 90% : 200 ms maximum 2 element ( 3ph, 3 wire) 20
To 99% : 400 ms maximum Input nominal voltage 100 to 120 V 0
63 to 69 V 1
Calibration Adjustment Full scale ±10%, Zero ±2%
208 to 240 V 2
Operating frequency Nominal ± 10% in accordance with IEC 688 415 to 480 V 3
Dimension 106W X 70H X 110D mm Input current 0 to 5 A 0
Different model Self powered /externally powered 0 to 1 A 1
POTENTIAL TABLE Output 0 to ±1 mA 0
0 to ±3 mA 1
Nominal input 100-120v 63-69V
0 to ±5 mA 2
Potential range with accuracy(self-powered) 85-150V 50-90 V
0 to ±10 mA 3
Potential range with accuracy(external-powered) 10-150V 10-90 V 4 to 20 mA Unidirectional 4
Maximum burden at nominal input 0.1 VA* 0.1 VA* 0 to ±100 mV 5
Potential overload continuous 180V 100V 0 to ±1 V 6
Nominal input 208-240v 460-480V 0 to ±5 V 7
0 to ±10 V 8
Potential range with accuracy(self-powered) 170-300V 325-575 V
1 to 5 V 9
Potential range with accuracy(external-powered) 20-300V 30-575 V Special X
Maximum burden at nominal input 0.1 VA* 0.1 VA* Auxilary Power Supply 120VAC EC
Potential overload continuous 350V 700V 230VAC FC
* self powered units have a burden of < 3 VA across either ÔA-N,or ÔA- ÔB DC Aux 24VDC K1
CURRENT TABLE DC Aux Power 48VDC K2
DC Aux Power 125VDC K3
Input 0-5A
DC Aux Power 220VDC K4
67
Over range with accuracy 10A Special X
Maximum burden 0.5 VA No. of output single Keep blank
Overload continuous 15A Dual D
Overload 10 s/h 30A C
Overload 1 s/h 200A M
SPECIAL CALIBRATION INSTRUCTIONS
Y
Please specify: 1. CT Ratio 2. PT Ratio 3. Desired Full Scale Calibration in kW, kVAR, kVA
K
E-mail: [email protected] | Web: www.masibus.com
DA/DV/DW/DVA/DH/DPF

Y
AC Line Frequency & Power Factor Transducer
K

Specifications Specifications
Accuracy 0.05% of Center Frequency Accuracy 0.25% of FS ( @25°C + 2 °C)
Temperature Range -20 °C to +70 °C Temperature Range -20 °C to +70 °C
Temp. Co-efficient ± 0.001% per°C,10ppm typical Temp. Co-efficient ± 0.001% per°C,10ppm typical
Operating Humidity 0-95% non-condensing Operating Humidity 0-95% non-condensing
Power factor range Any Power factor range Any,PF as selected by part no.
operating Voltage Range -30% +25% of Nominal Output ripple peak <0.5% of full scale
Dielectric Test 2kv for 1 minute Burden current :0.5 VA(most options)
Burden 1.5 VA(most options) Voltage:3.5 VA nominal
Surge Withstand ANSI C37.90a(IEEE 472); Overload current:3xF.S cont.,250 A for 1 s/hr.
BEAMA 219;special 5 KV Voltage:1.2 x F.S cont
Response Time 200 ms to 90% Surge Withstand ANSI C37.90a(IEEE 472);
400 ms to 99% BEAMA 219;special 5 KV
Calibration Adjustment ± 10% standard Response Time 200 ms to 90%
Zero Adjustment ± 2% standard 400 ms to 99%
Calibration Adjustment ± 10% standard
Zero Adjustment ± 2% standard

ORDERING CODE ORDERING CODE


Enclosure ABS ,Din Rail mount D Enclosure ABS, Din Rail mount D
Model Frequency H Model Power factor PF

Center frequency 50 Hz 5 Nominal Input volatge 120V 0


60 Hz 6 240V 2
Special X Special X

Frequency Span 50/60Hz Nominal Input Current 1-5A 0


± 1 Hz 1 0.2-1A 1
± 2 Hz 2 Special X
± 3 Hz 3
± 4 Hz 4 Power factor code ± 1.0 0
± 5 Hz 5 ± 0.7 1
± 6 Hz 6 ± 0.5 2
± 7 Hz 7 ± 0.3 3
± 8 Hz 8 ± 0.2 4
± 9 Hz 9 Special x
± 10 Hz 0
special X Output 0 to 1 mA(0-10000 Ohms) 0
0 to ±1 mA(0-10000 Ohms) 1
Nominal Input volatge 120 VAC 0 0 to ±0.5 mA(0-20000 Ohms) 2
69 VAC 1 0 to ±50 mV(10 Ohms min.) 3
240 VAC 2 0 to ±100 mV(20 Ohms min) 4
Special X 0 to ±1 V(200 Ohms min.) 5
0 to ±10 V(2000 Ohms min.) 6
Output 0 to 1 mA(0-10000 Ohms) 0 1 to 5 V(1000 Ohms min)* 7
0 to ±1 mA(0-10000 Ohms) 1 4 to 20 mA(0-750 Ohms)* 8
0 to ±0.5 mA(0-20000 Ohms) 2 0 to ±10 mA(0-1000 Ohms) 9
0 to ±50 mV(10 Ohms min.) 3 special X
0 to ±100 mV(20 Ohms min) 4 *with aux power only
0 to ±1 V(200 Ohms min.) 5
0 to ±10 V(2000 Ohms min.) 6 Auxilary Power Supply Self power keep blank
1 to 5 V(1000 Ohms min)* 7 120VAC E
4 to 20 mA(0-750 Ohms)* 8 230VAC F
0 to ±10 mA(0-1000 Ohms) 9 Dc Aux Power 24 VDC K1
special X Dc Aux Power 48 VDC K2
*with aux power only Dc Aux Power 125 VDC K3
Dc Aux Power 220 VDC K4
Auxilary Power Supply Self power keep blank
120VAC E No of Output Single keep blank
68 230VAC F Dual D
Dc Aux Power 24 VDC K1
Dc Aux Power 48 VDC K2 Note: When you select PF + 0.3,output 4 mA comes at PF -0.7,12mA comes at
Dc Aux Power 125 VDC K3 PF 1 & 20 mA comes at PF +0.7
Dc Aux Power 220 VDC K4
When you select PF + 0.7,output 4 mA comes at PF -0.3,12mA comes at C
No of output PF 1 & 20 mA comes at PF +0.3
Single keep blank M

Dual D Y

All specifications are subject to change without notice due technology reasons.
Doc.ref.CB-2/DA/DV/DW/DVA/DH/DPF/R3/0110