M85005-0131 - VS1 64 Point Intelligent Fire Alarm Control Panel
M85005-0131 - VS1 64 Point Intelligent Fire Alarm Control Panel
M85005-0131 - VS1 64 Point Intelligent Fire Alarm Control Panel
Overview Features
The GE Vigilant VS1 intelligent life safety system offers the speed • Comes standard with one loop that supports up to 64 intelligent
of high-end intelligent processing in a configuration that deliv- devices of any type and two Class B NACs..
ers an uncomplicated solution for small to mid-sized applications. • Form C contacts for alarm and trouble, Form A for supervisory
With intelligent detection, electronic addressing, automatic device
mapping, optional Ethernet® connectivity, and a full line of easily- • Electronic addressing with automatic device mapping
configured option cards and modules, this quick-to-install system • Optional Ethernet port for diagnostics, programming
offers versatile features that benefit building owners and contrac-
• Supports systemwide strobe synchronization
tors alike.
• Two programmable switches with LEDs and custom labeling
The VS1 provides one Class B analog device loop that supports up
to 64 device addresses, and two Class B Notification Applianc e • On board NACs support Genesis horn silence over two wires and
Circuits (NACs). Optional Class A device wiring is available with the UL 1971-compliant strobe synchronization
use of a module. • Optional Class A wiring
This life safety system features an attractive contemporary design • Supports up to eight serial annunciators, (LCD, LED-only, and
that fits with any decor. Its gently curved doorfront offers a distinc- graphic interface).
tive flair with available red or silver finishes. Controls are discreetly • Can use existing wiring for most retrofit applications
inset behind a striking black bezel.
• Supports V-Series single and multisensor detectors
The VS1 supports a wide range of accessories and related equip- • Upload/download remotely or locally
ment, including:
• Two-level maintenance alert reporting
• Intelligent modules, detectors, and bases
• R-Series remote annunciators • Pre-alarm and alarm verification by point
• Option cards that expand system capacity and extend system • Adjustable detector sensitivity
capabilities. • 4 x 20 character backlit LCD display
VS1 Intelligent
Life Safety System
Language English or French Auto signal Off: Allows immediate silencing of signals from an
Marketplace U.S. or Canada silence off-normal condition using the Signal Silence button
AC fail delay Off: Off-premise notification of an AC power failure is 5 to 30 minutes: Delays the silencing of signals from
immediate. an off-normal condition by disabling the Signal
1 to 15 hours: Delays the off-premise notification of Silence button for the time period selected.
an AC power failure by the time period selected. Day start Start time for daytime sensitivity
Zone resound On: NACs resound each time a device in the zone Night start Start time for nighttime sensitivity
goes into alarm even if they were silenced Date U.S.: MM/DD/YYYY
Off: Inhibits the NACs from turning on again (after Canada: DD/MM/YYYY
they were silenced) when a second device in the zone Mapping Disabled: Device mapping is not available
goes into alarm. Enabled: Device mapping is available
Reset inhibit after Off: Panel reset is operational immediately. LCD banner Banner text for line one and line two. Each line is
NACs turn on 1 minute: Panel reset is inhibited for one minute. capable of up to 20 characters.
Event notification Zone: When a device is a member of a zone, only the
zone information is sent to the LCD display, LEDs,
printer, and dialer.
Zone/device: Zone information is sent to the LCD
display and LEDs. Device information is sent to the
printer and dialer.
Device: Only device information is reported.
The VS1 comes equipped with two notification appliance circuits. The trouble relay is normally-open, held closed, and opens on any
Each circuit can be individually configured for continuous, temporal, trouble event or when the panel is de-energized. The supervisory
synchronized, and coded output. relay is normally-open, and closes on any supervisory event. The
alarm relay changes over on any alarm event.
Circuit Specifications
Relay specifications
Circuit Type 2 Class B, Class A optional when Class A card is installed.
Each circuit is 2.5 amps. Alarm Trouble Supervisory
Voltage 24 VFWR Type Form C Form A
Current 3.75A total (115/230 60hz) Voltage 24 VDC at 1 A resistive 24 VDC at 1 A resistive
3.0A total (230v 50hz) Relay circuits can only be connected to power-limited sources.
2.5 A max per circuit
Impedance 26 Ω total, 0.35 µF max
EOLR 15 K Ω, ½ W
Auxiliary & Smoke power outputs (TB3)
The control panel provides two auxiliary power outputs which can
Class B wiring
be used for powering ancillary equipment such as remote an-
nunciators and two wire smoke detectors. Aux 2 can be software
NAC1 -
+ + selected to operate continuous. The circuit is supervised for shorts
NAC1+ and grounds.
- -
EOLR
NAC2 -
+ + Note: For a complete list of devices that can be connected to
NAC2+
- - this circuit, refer to the VS1 and VS2 series compatibility list (p/n
TB2 3101065).
Marking indicates output signal polarity when the circuit is active.
Class B reverses
Polarity wiring when the circuit is not active. Wire notification Circuit specifications
appliances accordingly. Notification appliance polarity shown in
NAC1 - Circuit voltage range 21.9 to 28.3 V
active state. + +
NAC1+ Resettable circuit 24 VDC nominal at 500 mA
- - (Aux power 2)
EOLR
NAC2 -
+ + Continuous circuit 24 VDC nominal at 500 mA. Use this circuit for
Device loop
NAC2+
- - (Aux power 1) powering two-wire smoke detectors.
The
TB2 system provides one device loop circuit that can be used with Note: Any current above 0.5 amp connected to both Aux 1 and 2 will reduce the total
any mix of-detectors and
NAC3
+ modules.+ The loop circuit is supervised for available NAC power by that amount.
opens, shorts, and grounds.
NAC3+
- - EOLR
NAC4 -
Circuit Specifications + +
NAC4+ Annunciator loop (TB4)
Device loops - Class B or- Class A supporting up to 64 device
1 Loop
TB6 addresses. The control panel provides a connection for up to eight serially
Communication Maximum 20 V peek-to-peek driven and supervised remote annunciators.
line voltage Channel 1 Channel 2
Class A wiring – –
+
+
Circuit current 0.5 A max Circuit specifications TB4
NAC1 -
Circuit impedance 66Ω + total, 0.5 µF,+max Device loops Class B (Style Y) or Class A* (Style Z)
NAC1+ Annunciator
Isolators 64 -maximum - Circuit voltage 2.55 V
CH1 (+) IN
NAC2 - Circuit current 30 mA max
+ + CH1 (–) IN
NAC2+ Circuit impedance Up to 8 annunciators or 4000 feet, 18AWG wire
Class B wiring - -
TB2 CH2 (+) IN
- Class B Class A CH2 (–) IN
-
+
Loop 1 SEC Data Line
+ Channel 1 Channel 2 Channel 1 Channel 2
- – – – –
+
+
+
- + +
+ 1 PRI
Loop
- -
TB4 TB4
+
TB6 Loop Loop Annunciator Annunciator
- + + TB4
Loop 1 PRI
+ - -
Annunciator
Loop Loop
device device CH1 (+) IN
Loop card Data Line
CH1 (–) IN
CH2 (+) IN
CH2 (–) IN
related equipment that enhance performance and extend system The SA-232 card provides an RS-232 inter- GND (black wire)
TXD (white wire)
capabilities. Option cards are easy to install and set up. They simply face with V-Series panels. It can be used for RXD (red wire)
plug directly into the control panel main circuit board or are con- connecting a printer to the control panel to
nected to it with a ribbon cable. After installation, terminals remain print system events. The card also can be
easily accessible for quick connection of field wiring. The cabinet used for connecting a computer to down-
provides ample room for wire routing, keeping wiring neat and easy load a configuration program from the
to service at all times. VS-CU to the control panel.
The RS-232 card is installed on the plastic assembly and connects
to the main circuit board via a ribbon cable.
SA-CLA Class A Module
SA-232 specifications
The SA-CLA card
SA-CLA wiring Operating voltage Standard EIA-232
provides Class A
TB2 on main NAC1 Terminal rating 12 to18 AWG (0.75 to 2.5 sq mm)
capability for NAC, + +
circuit board NAC1+
loop, and annuncia- Operating environment
NAC2
+ + Temperature 32 to 120°F (0 to 49°C)
tor wiring. Its termi- NAC2+
Humidity 0 to 93% RH, noncondensing at 90°F (32°C)
nal block provides
the wiring connec-
+
tion for NAC return
SMK Smoke Power Converter
wiring. The card is +
The SMK Smoke Power
required for loop 24 VDC
Class A card installed Converter Module provides auxilliary
and annunciator power
+
_
on main circuit board a backup power source for (not resettable)
Class A wiring even
two-wire smoke circuits
though this wiring does not return to the SA-CLA card. The SA-CLA
connected to a Signature
is compatible with VS1 control panels only. VS2 panels are Class A
data circuit. The SMK moni-
ready. The SA-CLA is installed directly to the control panel circuit 8 7 6 5
tors the operating power SMK + +
board using its plastic standoffs and plug connection. Power in
from the power supply. Power out
SA-CLA specifications When power begins to + +
4 3 2 1
Operating voltage 24 VFWR degrade, the SMK provides
Operating current 2.5 A/circuit, 3.75A total (115/230 60hz) the necessary operating
3.0A total (230v 50hz) voltage to the two-wire Two-wire smoke
Circuit impedance 26 Ω, 0.35 µF, max smoke detection circuits. detectors
Data in +
Dimensions
Surface mounting holes Backbox with Backbox with door and
Backbox and backbox with door
D2 D3 door attached trim ring attached D1 [1] D2 D3 D4 D5 [1] D6 D7 D8 D9
D7
21.50 in. 3.85 in. 7.5 in. 15.50 14.25 10.25 3.9 in. 21.7 in. 2.7 in.
(54.6 (9.8 (19 cm) in. (39.4 in. (36.2 in. (26 (9.9 (55.1 (6.8
cm) cm) cm) cm) cm) cm) cm) cm)
Semiflush mounting holes
D6
D9 D9
D5
Option Cards
SA-DACT Dual Line Dialer/Modem, supports Contact ID, mounts in cabinet on base plate.
SA-232 Serial Port (RS-232), for connection to printers & computers, mounts in cabinet to base plate
SA-ETH Ethernet Port, Slave, mounts in cabinet on base plate
SA-CLA Class A adapter module. Provides Class A capacity on NACs. Mounts in cabinet on main board.
Programming Tools
VS-CU Vigilant Series configuration and diagnostics utility.
Continued...
Latin America
T 305 593 4301 System Accessories
F 305 593 4300 CTM City Tie Module. Mounts in 2-gang electric box. 0.6 (0.3)
Provides connection to a local energy fire alarm box.
www.gesecurity.com
BC-1 Battery Cabinet. 14.0" x 18.25" x 7.25" Free-standing cabinet with key 50.0 (22.7)
Windows is a registered trademark lock. Supports up to 40 Ah batteries. Holds up to 2 12V24A batteries.
of Microsoft Corporation. BC-1R Battery Cabinet - Red. 14.0" x 18.25" x 7.25" Free standing cabinet with 50.0 (22.7)
Ethernet is a registered trademark of Xerox. key lock. Supports up to 40 Ah batteries. Holds up to 2 12V24A batteries.
IOP3A Isolator Module - RS232. For use with short haul modems. 1.61 (0.7)
© 2008 General Electric Company
All Rights Reserved RPM Reverse Polarity Module 3.0 (1.36)
MFC-A Multifunction Fire Cabinet, 8" x 14" x 3.5" - RED. 20.6 (9.4)
MIR-PRT/S System Printer - Desktop style. 36.6 (16.6)
GSA-CC1 Single Input Signal Module (Standard Mount) 0.5 (0.23)
GSA-MCC1 Single Input Signal Module (UIO Mount) 0.18 (0.08)
GSA-CC1S Synchronization Output Module (Standard Mount) 0.5 (0.23)
GSA-MCC1S Synchronization Output Module (UIO Mount) 0.18 (0.08)
GSA-CC2 Dual Input Signal Module (Standard Mount) 0.5 (0.23)
GSA-MCC2 Dual Input Signal Module (UIO Mount) 0.18 (0.08)
GSA-CR Control Relay Module (Standard Mount) 0.4 (0.15)
GSA-MCR Control Relay Module (UIO Mount) 0.18 (0.08)
GSA-CRR Polarity Reversal Relay Module (Standard Mount) 0.4 (0.15)
GSA-MCRR Polarity Reversal Relay Module (UIO Mount) 0.18 (0.08)
GSA-RM1 Riser Monitor Module (Standard Mount) 0.5 (0.23)
GSA-MRM1 Riser Monitor Module (Plug-in) 0.18 (0.08)
GSA-IO Input/Output Module (Standard Mount) 0.34 (0.15)
GSA-MIO Input/Output Module (Plug-in) 0.22 (0.10)
GSA-CT1 Single Input Module 0.4 (0.15)
GSA-CT2 Dual Input Module 0.4 (0.15)
GSA-MCT2 Dual Input Plug-in (UIO) Module 0.1 (0.05)
GSA-IM Fault Isolator Module .5 (.23)
GSA-MM1 Monitor Module 0.4 (.15)
GSA-WTM Waterflow/Tamper Module 0.4 (.15)
GSA-UIO2R Universal Module Board w/Riser Inputs - Two Module Positions 0.32 (0.15)
GSA-UIO6R Universal Module Board w/Riser Inputs - Six Module Positions 0.62 (0.28)
GSA-UIO6 Universal Module Board - Six Module Positions 0.56 (0.25)
SMK Smoke Power Converter Module 0.4 (0.15)
imagination at work
Data Sheet M85005-0131 Issue 1