Tool For Compressed Air Calculations
Tool For Compressed Air Calculations
(FAD Test)
Step 1 Isolate the compressor along with its receiver from rest of the system (close outlet valve of air
receiver tank)
Step 2 Shut off the compressor drive motor
Step 3 Drain water completely and remove compressed air from air receiver tank and distribution line till
the isolation valve
Step 4 Close the water drain valve tightly and note down the initial pressure on air receiver tank or on
the control panel
Step 5 Re-start compresor motor
Step 6 Note down the pressure when the motor cuts off
Step 7 Note the time taken for motor to cut off (from initial pressure to final pressure)
Fill only green coloured cells (please ensure figures with correct units when filling the cells. Use conversion
tables provided below if needed)
*Calculations are done considering that compressor is able to achieve atleast 90% of the rated
Leakage Test of Compressor
Step 1 Conduct test when no equipment is consuming compressed air (all the end user points are
closed or user equipment is switched off), but air receiver tank outlet is open
Step 3 Note the subsequent ‘load’ and ‘unload’ time for 3 or 4 continuous cycles and obtain
average values for load and unload times each
Fill only green coloured cells (please ensure figures with correct units when filling the cells. Use
conversion tables provided below if needed)
Fill only green coloured cells (please ensure figures with correct units when filling the cells. Use conversion
tables provided below if needed)