Flexeon 210 LT Series Users Manual
Flexeon 210 LT Series Users Manual
Flexeon 210 LT Series Users Manual
User’s Manual
Model
LT-200, LT-300
LT-300 Pictured
This Page
Left Blank
2
LT – Series User’s Manual
MKTF-210 06/12
Table of Contents
INTRODUCTION....................................................................................................................................... 4
SAFETY .................................................................................................................................................... 4
FEED WATER AND OPERATION SPECIFICATIONS ............................................................................ 5
REJECTION, RECOVERY AND FLOW RATES ...................................................................................... 5
SYSTEM INSTALLATION AND START-UP PROCEDURES .................................................................. 6
MEMBRANE ELEMENTS ......................................................................................................................... 8
LT-200, LT-300 SYSTEM IDENTIFICATION .......................................................................................... 11
LT-200 MEMBRANE FLOW DIAGRAM .................................................................................................. 15
LT-300 MEMBRANE FLOW DIAGRAM .................................................................................................. 16
DESIGN BASIS FOR LT-200, LT 300 .................................................................................................... 17
OPERATING DO’s AND DON’Ts ........................................................................................................... 18
MAINTENANCE PROCEDURES ........................................................................................................... 18
MEMBRANE REMOVAL AND REPLACEMENT .................................................................................... 20
PREPARING UNIT FOR STORAGE OR SHIPMENT ............................................................................ 22
REVERSE OSMOSIS TROUBLESHOOTING ........................................................................................ 23
TEMPERATURE CORRECTION FACTORS FOR MEMBRANE ........................................................... 25
OPERATION ........................................................................................................................................... 27
DRAWINGS............................................................................................................................................. 28
3
LT – Series User’s Manual
MKTF-210 06/12
INTRODUCTION
Your LT-Series system is a durable piece of equipment which, with proper care, will last
for many years. This User’s Manual outlines installation, operation, maintenance and
troubleshooting details vital to the sustained performance of your system.
The test results which are included with this User’s Manual indicate your system’s
permeate (product) and concentrate ((waste) test results.
SAFETY
The Safety section of this User’s Manual outlines the various safety headings used
throughout this manual’s text and are enha
enhanced and defined below:
4
LT – Series User’s Manual
MKTF-210 06/12
DO NOT UNDER ANY CIRCUMSTANCE REMOVE ANY CAUTION,
TION, WARNING,
WARNING
OR OTHER DESCRIPTIVE LABELS FROM THE SYSTEM.
Nothing has a greater effect on a reverse osmosis system than the feed water quality.
quality
OPERATING LIMITS
LT-Series reverse
everse osmosis systems are designed to produce permeate water at the
capacities indicated by the suffix in the system’s name under the conditions listed
above. For example, the LT-3 300 produces 300 gallons per day of permeate water at
the listed operating test conditions.
5
LT – Series User’s Manual
MKTF-210 06/12
The amount of total dissolved solids (TDS) rejected by the membrane is expressed as a
percentage. For example, a 98.5% rejection rate means that 98.5% of total dissolved
solids do not pass through the membrane. To calculate the % rejection, use the
following formula:
Example:
LT-Series reverse osmosis systems are designed to reject up to 98.5% NaCl, unless
computer projections have been provided or stated otherwise.
% Recovery = (Product Water Flow Rate / Feed Water Flow Rate) x 100
Example:
1. Inspect the system for any damage that could have occurred during shipment.
Although our systems have been individually inspected, complete a quick inspection
of the fittings, tubing and other components.
2. Please provide a reasonable amount of space for installation and leave 6 inches of
space below the filter housings for ease of maintenance.
6
LT – Series User’s Manual
MKTF-210 06/12
NOTE: THE REVERSE OSMOSIS SYSTEM SHOULD BE INSTALLED
INDOORS AND IT IS SUGGESTED THAT IT NOT BE IN DIRECT SUNLIGHT OR
EXTREME COLD.
3. Connect the 3/8” or 1/4” tube fitting to an incoming water source. The minimum
water pressure should be at least 30 psi. The system’s minimum operating pressure
is 80 PSI, but the optimum operating pressure is 100 psi.
NOTE: THE TANK PRESSURE SWITCH WILL SHUT THE SYSTEM OFF
AUTOMATICALLY WHEN THE BLADDER TANK IS FULL.
7. The sediment filter and carbon must be serviced regularly for optimal performance.
The filters and water quality should be checked every two weeks minimum.
8. Dispose of the product water until the conductivity of the product water reaches your
desired level. Use any TDS or Conductivity meter to monitor the product water
quality. A minimum quality of 96% NaCl rejection is recommended.
7
LT – Series User’s Manual
MKTF-210 06/12
NOTE: ANY CHLORINE EXPOSURE WILL DAMAGE THE MEMBRANE
PERMANENTLY.
9. This system has been factory wired and preset with a pressure switch at 20 - 40 psi,
which is only to be used with a pressurized bladder tank. If using an atmospheric
storage tank, a float switch will be required to turn the system on and off.
MEMBRANE ELEMENTS
LT-Series reverse osmosis systems come pre-loaded with Thin Film Composite (TFC)
HF4 High Flow Low Energy membranes, unless otherwise specified. General
membrane element performance characteristics are listed on the next page.
8
LT – Series User’s Manual
MKTF-210 06/12
HF4-STANDARD
9
LT – Series User’s Manual
MKTF-210 06/12
NF3-OPTIONAL
10
LT – Series User’s Manual
MKTF-210 06/12
NF4-OPTIONAL
11
LT – Series User’s Manual
MKTF-210 06/12
LT-200, LT-300 SYSTEM IDENTIFICATION
FIGURE 1A
NUMBER IDENTIFICATION
12
LT – Series User’s Manual
MKTF-210 06/12
FIGURE 1B
FIGURE 1C
13
LT – Series User’s Manual
MKTF-210 06/12
FIGURE 1D
14
LT – Series User’s Manual
MKTF-210 06/12
LT-200 MEMBRANE FLOW DIAGRAM
FIGURE 1E
Note: Black arrows represent concentrate water and white arrows represent permeate
water.
15
LT – Series User’s Manual
MKTF-210 06/12
LT-300 MEMBRANE FLOW DIAGRAM
FIGURE 1F
Note: Black arrows represent concentrate water and white arrows represent permeate
water.
16
LT – Series User’s Manual
MKTF-210 06/12
DESIGN BASIS FOR LT-200, LT 300
17
LT – Series User’s Manual
MKTF-210 06/12
OPERATING DO’s AND DON’Ts
DO:
• Change the cartridge filters regularly
DON’T
• Permit chlorine to enter or be present in the feed water.
MAINTENANCE PROCEDURES
1. Periodically observe the quality and quantity of product water from the system.
18
LT – Series User’s Manual
MKTF-210 06/12
NOTE: IF THE TDS OF THE FEED WATER EXCEEDS 1000 PPM OF
NACL, A LARGER FLOW RESTRICTOR SHOULD BE USED TO EXTEND THE
MEMBRANE LIFE.
4. It is important to maintain and/or replace the carbon block regularly since the Thin
Film Composite membranes are chlorine sensitive. Irreversible damage will occur
with any chlorine present in the feed water. For additional information, please
review the manufacturer’s membrane specification sheets.
5. The product line has a one way check valve installed. The check valve should be
checked regularly and replaced if it is not properly sealing.
6. Keep the feed water temperature above 4°C (36°F).
19
LT – Series User’s Manual
MKTF-210 06/12
MEMBRANE
BRANE REMOVAL AND REPLACEMENT
Replacing membranes in the pressure vessels is an easy process if you have the
proper information and tools at hand. Please refer to the following instructions when
removing and replacing membrane elements:
1. Remove the end caps from the top of the membrane housings. This is done by
removing the white snap ring of the membrane housing.
2. Remove the membrane bag containing the membrane element from the shipping
box.
3. Cut the bag open as close as possible to the seal at the end of the bag, so the
bag may be re-used
used if necessary.
5. Flow directions should be observed for installation of each element into each
housing.
As time progresses,
ogresses, the efficiency of the membrane will be reduced. In general, the salt
rejection does not change significantly until two or three years after installation when
operated on properly pretreated feed water. The permeate flow rate will begin to decline
slightly after one year of operation, but can be extended with diligent flushing and
cleaning of the system. A high pH and/or precipitation of hardness can cause
premature loss in rejection.
20
LT – Series User’s Manual
MKTF-210 06/12
THAT PROTRUDES ON ONE SIDE OF THE MEMBRANE AND IS ALWAYS ON THE
FEED SIDE OF THE MEMBRANE ELEMENT.
2. Lubricate the brine seal with non petroleum based lubricant, Silicone DC 111.
3. Install the brine seal side of the membrane element first. When the housings
have a direction of flow from bottom to top, the brine seal should be located at
the bottom of the housing.
4. At a slight angle, insert the membrane while slightly rotating the element being
careful not to tear or flip the brine seal. A slow twisting motion should be used to
insert the membrane element, to ensure the brine seal stays in place. Re-lube
the brine seal if necessary.
5. With a smooth and constant motion, push the membrane element into the
housing so the brine seal enters the housing without coming out of the brine seal
groove.
6. Re-install the end caps by gently twisting the end cap while pushing it onto the
housing. Ensure that you do not pinch or fatigue any O-rings while re-installing
the end plug. Push the end plug on until the outer diameter of the plug is flush
with the outer diameter of the membrane housing.
7. Insert the snap ring until it is fully seated. Install the locking clip if available.
8. Reconnect any fittings that may have been disconnected when the membrane
element housings were disassembled.
9. To start-up the system, please refer to the Start-Up section of this manual. (See
Page 6)
21
LT – Series User’s Manual
MKTF-210 06/12
PREPARING UNIT FOR STORAGE OR SHIPMENT
Prior to shipping or storing your system, the system should be cleaned with an
appropriate cleaner, flushed with water and protected from biological attack with an
appropriate solution for membrane elements. The membrane housing(s) and plumbing
lines of the system must be completely drained. Any water remaining in the plumbing of
a system may freeze, causing serious damage.
2. Separate the preservation solution from the air outside. Any contact with oxygen
will oxidize the Memstor.
3. Check the pH once a week. When the pH becomes 3 or lower, change the
preservation solution.
During the shutdown period, the plant must be kept frost-free, or the temperature must
not exceed 113°F (45°C).
6. Drain all water from the pre-filter cartridge housings by unscrewing the housings,
removing the pre-filter cartridges, and drain the water from the housings.
7. Disconnect the tubing from the connectors on the permeate and concentrate
inlets and outlets.
8. Allow the system to drain for a minimum of eight hours or until the opened ports
quit dripping.
22
LT – Series User’s Manual
MKTF-210 06/12
REVERSE OSMOSIS TROUBLESHOOTING
23
LT – Series User’s Manual
MKTF-210 06/12
ABNORMAL PERMEATE FLOW
Permeate flow should be within 20% of the rated production, after correcting the feed
water temperatures above or below 77°F. Check your permeate flow meter to
determine the permeate flow rate.
24
LT – Series User’s Manual
MKTF-210 06/12
TEMPERATURE CORRECTION FACTORS FOR MEMBRANE
Find the temperature correction factor (TCF) from the table below. Divide the rated
permeate flow at 77°F by the temperature correction factor. The result is the permeate
flow at the desired temperature. (See example on the next page)
25
LT – Series User’s Manual
MKTF-210 06/12
If a system is rated to produce 5 gpm of permeate water @ 77˚ F, the same system will
produce more water at a higher temperature. It will also produce less water at a lower
temperature. Use the temperature correction table to obtain the correct flow.
Example:
SERVICE ASSISTANCE
If service assistance is required, please complete the following process:
Contact your local dealer or distributor. Prior to making the call, have the following
information available: system installation date, serial number, daily log sheets, current
operating parameters (e.g. flow, operating pressures, pH, etc.) and a detailed
description of the problem.
26
LT – Series User’s Manual
MKTF-210 06/12
OPERATION
Date of Start-
Company:
____________________ Up: ___________________
Date
Time
Hour of Operation
Recovery %
Feed Temperature
Rejection %
Feed PH
Permeate PH
Iron (mg/L)
27
LT – Series User’s Manual
MKTF-210 06/12
DRAWINGS
FIGURE 2
28
LT – Series User’s Manual
MKTF-210 06/12
FIGURE 3
29
LT – Series User’s Manual
MKTF-210 06/12
FIGURE 4
30
LT – Series User’s Manual
MKTF-210 06/12
LT-200 SYSTEM PART LIST
31
LT – Series User’s Manual
MKTF-210 06/12
LT-300 SYSTEM PART LIST
32
LT – Series User’s Manual
MKTF-210 06/12
LT-200 FLOW DIAGRAM
33
LT – Series User’s Manual
MKTF-210 06/12
LT-300 FLOW DIAGRAM
34
LT – Series User’s Manual
MKTF-210 06/12
35
LT – Series User’s Manual
MKTF-210 06/12