0% found this document useful (0 votes)
227 views22 pages

Building Management System-UOM - MSC - Part - 1

BMS means mostly a hudge electronic,Electrical ,communication integrated system, can someone control whole system via a central point.

Uploaded by

Uwan Kivindu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
227 views22 pages

Building Management System-UOM - MSC - Part - 1

BMS means mostly a hudge electronic,Electrical ,communication integrated system, can someone control whole system via a central point.

Uploaded by

Uwan Kivindu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 22

7/25/2015

Building Management Systems


(EE5118)
Part -1
for MSc @ UOM

Jagath Wickramasekara, Bsc

Control Strategies
Why Control Strategies …? à Benefits of BMS

Type -1

• Air Side Controlling Strategies


Control • Chilled water side Controlling Strategies The Building
Services
Strategies Research
and Information
Type -2 Association
- Local Control Strategies AG 7/98
- Supervisory control Strategies

1
7/25/2015

Local Control & Supervisory Control


• Local Control
• AHU Supply Air temperature Control
• Static Pressure Control
• Zone Temperature Control
• Fresh Air Supply Control
• Ect

• Supervisory Control
• Static Pressure Set-point Reset
• AHU Supply Air set-point reset
• Ect..

Terms
• CAV – Constant Air Volume System- constant speed fan
• VAV – Variable Air Volume System
• PAU/FAU – Primary/Fresh Air Handling Unit – provides fresh air to
above systems , Constant Speed fan, no Control of Outdoor Air.
• FCU – Fan Coil Units
• AHU – Air Handling Unit

2
7/25/2015

HVACSystem…
• Chillers
• Chilled ( Primary , secondary) water Pumps/ Condenser water pumps
• Cooling Tower
• AHUs/ FCU/VAV/CAV

How Can we control an AHU…..?

3
7/25/2015

AHU -Constant Air Volume System


• Electrical Controlling (On /OFF, Auto/Manual , Trip , On/Off Status, Flow Status)
• Electrical Single Line Diagram ( DOL / Star – Delta )
• Air Side and Chilled water Controlling

Relays & Contactors – Digital Actuators

4
7/25/2015

Click here for the


Drawings

Mixed Air Control


• Also Known As Economizer Control
• Dry climate and low dew point
• OA , MXA, and RA are measured
• When OA temp goes up it closes the OA damper, more RA is taken
• Minimum OA damper Continues operate to feed minimum OA requirement
Supplied Air Temperature Control
• Areas like Lobby, VAV Supply Air

5
7/25/2015

Enthalpy Controlling
• If the enthalpy of Fresh lower than that of return Air, Fresh air can be directly
used maintain the Supply Air temperature.
• If Fresh Air Damper has reached to its maximum position , mechanical cooling
can be introduced.
• If fresh Air temp/enthalpy is higher than Return Air , damper should remain its
minimum position to introduce minimum fresh requirement, while mechanical
cooling works on return air + Fresh Air Mixture.

Control of VAV Air Handling unit


• Supply Air temp is Constant ( or will be varied by Supervisory strategy)
• Supply Air Volume is changed to satisfy the cooling load
• SO the Air Volume needs to be adjusted ( VSD, Fitch angle , inlet/outlet vanes control)

6
7/25/2015

Controlling……
• Supply air Static Pressure controller (PC-1) controls the Speed of the Motor (M-
1) to keep pressure @ set point
• Return air fan speed is regulated based on difference of flow or flow ration
• In Many cases return Air fan is used to keep space static pressure positive or
negative

VAV Air Handling unit

https://www.youtube.com/watch?v=YCogTVa3XOw

7
7/25/2015

Static Pressure Control


• In VAV system, it maintains the minimum pressure through the Duct
• Methods
• Duct Static Pressure – Pressure Sensor located at the down stream of the Duct
• Building Static Pressure – pressure located at occupied spaces
• Above pressures reported to the DDC and then VSD maintains the
Static pressure
• Controlling Air in SA fan
• Discharge Damper – not energy efficient
• Inlet Vane Damper – less energy but High maintenance and high noise
• VSD
• When critical pressure conditions are to be maintained – volumetric control is
deployed
• Flow meter measures the Air Volume and adjust the speed of the RA fan
• For recommended method
• Both RA and SA volume are measured
• According to the difference, RA fan speed changed

VAV Controlling Terminal Controlling


https://www.youtube.com/watch?v=YCogTVa3XOw
• Pressure dependent
• No measurement of System Pressure
• Depend on Central fan to adjust the flow
• Box near to fan get more air
• Pressure Independent
• If there is change in the pressure in the supply air duct , flow changes
accordingly

8
7/25/2015

VAV Terminal Control


• To supply the Minimum Cooling air of the space
• As per the Space temperature set point, damper regulated
• Pressure Dependent terminals – modulate the air volume in response to the
changes in space temperature irrespective of upstream static pressure
• Pressure Independent type terminals – minimum quantity of supply air must
be provided

Demand Ventilation Controlling


• Conventional ventilation control (economizer with lower limit fresh air enthalpy
control) do not support
• ASHRAE – Standards 62-2004 requires that minimum outdoor fresh air
ventilation based on occupancy
• CO2 is measured as occupancy indicator , Non occupancy based pollutants cant
be detected ( Furniture , building materials)
• CO2 <1000 ppm, CO, VOC , NO

9
7/25/2015

FCU Controlling

Thermostats
• Sensor & Controller combined
• Used for FCU controlling
• Comfort, Economy and Protection mode operation
• Coil Protection
• Very important items in the hotel Industry

10
7/25/2015

Types/Features
• Day/Night Function/ Night Setback- One set point day
time, lower set point night time ( to prevent too cold),
Automatic or Manual changeover
• Combination Heat / Cool thermostats
• Dead band Thermostat

• Output Can be Modulating or On/OFF type

11
7/25/2015

Topologies

VAV Controlling Will be discussed separately..

Supervisory Control – Supply Air temp Set-point Controlling


• Air flow rate to zone is reduced by closing down the VAV damper when the load is low
• Under partial load, the total flow rate of a zone may be reduced to be very low in order
to meet the reduced load
• Reduction is flow rate reduce power of the fan
• However low ventilation flow rate causes dumping , poor air circulation in the room
• When minimum flow rate is introduced space may be over cooled under low partial load
if supply air temperature is low
• Proper resetting of supply air temperature avoid poor ventilation & save energy from the
fan.

Heat Wheel Controlling

12
7/25/2015

Chilling System has 3 subsystems


• Chillers – ( Reciprocating , Rotary screw , Centrifugal)
• Heat Rejection System
• Chilled water Distribution System

Chillers & Cooling Towers


• COP = Coefficient of Performance = Amount of heat Ejected / amount of work
• Normally COP >100% ( 2.5 ~ 7 Range )
• Chiller optimization by increasing evaporating temperature or decreasing condensing
temperature
• Chiller Internal Capacity Controlling , safety interlocks , special parameters monitoring
• Water Cooling , Air Cooled , Cooling Tower
• Cooling Towers cool water 2.5 to 5.5 k above the ambient is cooled down

Cooling Circuits types


The goal of the chilled water system is to produce and
distribute chilled water reliably , low cost and high
flexibility
• Constant Primary only Pumping System
• Constant Primary & Variable Secondary System
• Variable Primary Only System

The distribution system à variable flow with two


way valves or Constant flow with three way
valves

• Primary System – Production system


• Secondary system – Distribution System

13
7/25/2015

Constant Primary Only


• Pumps at a constant speed
• DPV help s maintain the constant chilled water
flow through chillers
• DP is monitored and controlled
• MV is controlled based on DP
• Waste of energy at Chiller part loads
• Two way valves and bypass line w/o VSD
• Energy saving by chiller loading and unloading
• Not savings by Pumps as they are running
@100% speed
• At part load , waste by pump power

Constant Primary / Variable Secondary


• Less power for primary pumps , balance for design flow rate
• Higher power for secondary pumps – can be either constant speed or variable
Speed

• Instead of check valve a flow meter can be installed to measure flow


through by pass line , accordingly chiller selection can be done

14
7/25/2015

Variable Primary Only System


• Its not possible to get proper saving by only controlling the secondary pumps
• Controller maintains DP ( differential pressure) at the most critical path
• Flow meter ensures minimum flow through the chillers
• Complex in bypass valve operation and sequencing

Chiller energy performance


• Condenser temperature as low as possible / evaporator temperature as high as
possible
• Increase of 1K of evaporator / condenser temp increase COP by 3% ( practically
1.5 ~2.5 %)
• Lower load lower efficiency / higher load higher efficiency , however centrifugal
as per the graph

15
7/25/2015

Optimal Set-point reset of chilled water supply temperature


• Variable water volume system -When return
temp is constant, each I K increase of supply
temp , reduces compressor operating cost by
2 ~ 3 % , but chilled water distribution cost by
10%.
• Constant water volume system – set point is
kept as high as possible , since no savings
from pumps, savings from chillers
• If all water valves are unsaturated or the
discharge air temperatures of all AHUs with
saturated valves are lower than the set- point,
increase the chilled water supply temperature set-
point.
• If more than one valve is saturated at 100 per
cent open and their corresponding discharge air
temperatures are greater than their set- points,
decrease the chilled water supply temperature set-
point.

Chilled Water Reset


§ Establish chiller plant leaving chilled water
temperature based on AHU requirements

§ Identify zone requiring most cooling and do


water balancing to save even more energy

§ Note that this strategy may increase space


humidity levels (okay in office)

§ For primary-secondary systems, use valve


position to reset secondary flow

§ Use similar strategy to reset static pressure


setpoint of VAV system

16
7/25/2015

Chiller sequencing
Multiple Chillers , why – chillers can be fully loaded, life time is increased, easy
maintenance
Economical loading and unloading of chiller is called chiller sequencing ( high
overall COP)
Typical sequencing method
• Temperature Based – Monitor the return chilled water temperature
• Bypass flow based – Difference in Primary circuit & Secondary circuit
• Total Cooling Load based
Temperature Based -
• Return temp is measured
• Chillers with pumps operated - interlock
• Dead Band to prevent cycling

By pass flow based sequencing


• Strategy attempts to keep secondary flow
larger than the primary flow
• Flow in secondary increases , another
chiller starts
• When the flow in by pass line (sup to
return) exceeds design flow of a chiller ,
chillers is OFF
Cooling load based sequencing
• Direct load is calculated
• Best method
• High accurate sensors needed

17
7/25/2015

Pumps sequencing & speed


• Interlocking with lag and lead time for
operation
• Secondary pumps
• Pumps in operation should meet demand
• Controlled variable can be à flow rate or
differential pressure of chilled water
supplied to the load side

Cooling tower
• Cooling tower Fan Speed control
• Modulating cooling tower fan speed
• Usually runs @ 100% speed
• Modulate the fan to meet condenser water set point
• Measuring Wet bulb temperature and chiller load
• Running at 24 C is more energy efficient ( usually 30 ~ 32 C)
• Low cooling tower supply water increase chiller efficiency , but more work on Cooling
tower fans
• Each 1K reduction in Cooling tower supply temperature can reduce 2.5% compressor
operating cost

18
7/25/2015

Multiple Chiller configuration


• Option -1
• Multiple Chillers and bypass loop with differential pressure regulator
• Option -2
• Chiller in constant flow circuits
• Distribution system variable flow
• By pass line with Flow meter
• If the flow meter flow is equal to the flow a chiller pump, one chiller can be
turned off
• Flow switch is needed to detect the direction
• Reverse direction of flow needs additional chiller to operate

Monitoring Strategies
• Power Consumption Metering
• Water/ Gas consumption
• Strange operation – Jokey pumps
• Critical Area Temp/RH monitoring - Freezers
• Trend Log
• Operation report
• Maintenance Time Reminder ( MTR)
• Energy Management Reports

19
7/25/2015

Supervisory Controlling
• Independent from Local and system control
• It has the capability to override local programmed control when it is needed to
achieve the overall objectives
• Example – PID adjustment, Supply Air set point of AHU, emergency stop of
system under smoke condition
• Anticipate problem based on historical data

Supervisory Control Strategies


• Turn it OFF when not needed
• Time Scheduled Control – in rush current reduction by staggering start time of fans
and lights
• Optimal Start/Stop – based on previous data system predicts time to start
• Duty Cycle Control – turning OFF the devices for short period of time , speed change
is more effective à leads to complains
• Load Shedding – based on the electricity demand ON/OFF is done, Bulk of load
should be sheddable for reasonable result ( Lights Elevator )
• Temperature Setback – based on outdoor condition temperature set point is adjusted
• Optimization Control Routines

20
7/25/2015

BMS Design
Air Handling unit ( AHU) of a conference hall area should be controlled as per the
following strategies
• Motorized valve modulation as per the return air temperature ( Set-point 25 C –
adjustable)
• ON/OFF operation and Status monitoring by the BMS
• Auto/Manual Status Monitoring by the BMS
• Trip Alarm Status monitoring by the BMS
• RH level of Return Air and temperature of supply Air should also be monitored
• When the Air Filter is Clogged, an alarm must appear at the BMS
• Fresh Air supply to the Building must be regulated as per the prevailing CO2 level ( Set-
point 1000 ppm – adjustable)
• BTU Consumption by the AHU must also be monitored
• If the Duct Smoke Is Presented , FAN should go off, OA damper must be closed

Approach
• Draw the sketch
• Write all the control Strategies
Consultants
• Prepare point list
• Prepare the specifications for every item

• Configure DDCs as per the Point List


• Select Sensors and Actuators – as per the specifications
• DDC panel Sizing and cabling
Contractors
• Software sizing
• Third-party integration
• Pricing & Estimation

21
7/25/2015

End

Jagath Wickramasekara,( Bsc, PGD-Industrial Automation)

Direct : 0094 011 460 7141


General : 0094 011 460 7100
0094 011 460 7140
Fax : 0094 011 460 7101
0094 011 460 7136
Mobile : 0094 0778 47 98 58
E-mail : [email protected]

22

You might also like