7PG11 AR Catalogue Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 48

Reyrolle

Protection
Devices

7PG111 & 7PG112 AR


Auxiliary Relay

Answers for energy


7PG111 & 7PG112 AR
First Digit Second Digit Third Digit Type of
Type of flag contact reset
Auxiliary Relay Number of 0 No flag 1 Self
identical 1 Hand reset 2 Hand
elements 2 Hand reset 3 Electrical &
reverse acting hand
3 Self reset 4 Hand & self
4 Self reset 6 Electrical
reverse acting
Table 1. Relay Features

Suffix letters are used to identify further features:


Suffix D – indicates a relay fitted with a suppression diode
across the coil to reduce the effects of back emf on switch-
off.
Suffix SB – identifies a relay with a series break contact to
cut-off the operating coil, thus the relay burden becomes
zero after operation of this contact. Only available with AR
relays which have hand reset contacts.
Description
Type Number of Flag Contact
Contacts Reset Reset
The 7PG111 & 7PG112 AR range of electromechanical relays AR101 2,4,6 or 8 N.A. Self
are available with up to eight self, hand or electrically reset N.A. Elec & Hand
AR103 4,6 or 8
contacts. They can be supplied in most combinations of
AR106 2, 4, or 6 N.A. Elec
contact, flag and reset arrangements. Fixed time delay
AR111 2,4,6 or 8 Hand Self
models are also available.
AR112 2,4,6 or 8 Hand Hand
AR113 4, 6 or 8 Hand Elec & Hand
AR relays are voltage operated from either AC or DC supplies.
AR114 4 or 6 Hand Hand & Self
Heavy duty contacts are available on most devices.
AR121 2,4,6 or 8 Hand* Self
AR124 4,or 6 Hand* Hand & Self
Features AR131 2,4,or 6 Self Self
AR133 2,4,6 or 8 Self Elec & Hand
AR136 2,4 or 6 Self Elec
• Consistent positive action
AR141 2,4,or 6 Self* Self
• Robust design for a long, reliable, service life
AR101T 2,4,or 6 N.A. Self
AR111T 2,4,or 6 Hand Self
Type AR relays are a range of electro-mechanical relays with
AR112T 2,4,or 6 Hand Hand
up to 8 contacts and complying to BS142. They can be
supplied in most combinations of contact, flag and reset AR121T 2,4,or 6 Hand* Self
arrangements and with a fixed time delay. Heavy duty AR131T 2 or 4 Self Self
contacts are available on most models. AR141T 2 or 4 Self* Self
The relays are identified by a series of numbers and letters * Indicates a reverse acting flag indicating on de-energisation.
which define important relay features. Table 2. Relay Features
The following comments are provided as a guide to the
various features of type AR relays. Suffix T – identifies time delayed relays. The reference is
completed by adding a code number:
AR - 1 Up to 8 self reset contacts, in any combination of
normally open or normally closed as required. Delay on De-energisation
AR - 2 Up to 8 self reset contacts, in any combination of Number of contacts available
normally open or normally closed as required. Suffix Nominal AR101T, AR111T, AR AR
AR - 3 Electrical and hand set contacts supplied with a Time AR112T, AR121T 131T 141
contact reset mechanism in the relay case cover. T
AR - 4 Hand and self reset contacts, can be supplied with 2 T1 Up to 100ms 6 4 4
hand reset contacts and a maximum of 4 self reset contacts. T2 101 to 200ms 6 4 4
All the contacts may be either normally open or normally T3 201 to 300ms 4 2 2
closed. T4 301 to 400ms 2 N.A. N.A
AR - 6 Electrical reset contacts with optional self reset flag. Delay on Energisation
AR – 3 & 6 Reset coils are short time rated, we recommend T6 50ms max. 6 6 4
that reset circuits include a normally open (cut-off) contact Table 3.Summary of Time Delayed Operation

Siemens Protection Devices Limited 2


Transient Overvoltage
Technical Data IEC 60255-5

Between all terminals and


Inputs and Outputs earth or between any two 5 kV
independent circuits 1.2/50 µs
without damage or 0.5 J
Rated Voltage (Vn) flashover
A.C. 63.5, 110, 220, 240V
D.C. 12, 24, 30, 50, 125, 240V
Mechanical
Operating Range
A.C. 80% to 110% of rated
Vibration (Sinusoidal)
voltage
D.C. 70% to 115% of rated
IEC 255-21-1 The relays meet the
voltage
requirements of Class 1
for vibration response and
Burden
endurance
3 to 5W/VA depending upon Dependent on rating.
BS142 section 2.1 relays will withstand a
rating Rectified a.c. relays
category S2 20G shock or impact on
nominal power factor =
the panel without
0.96
operating

Output Contacts
Shock Bump

Make and carry 1250VAa.c. or 1250Wd.c.


continuously IEC 255-21-2 Class 1 severity
within the limits of 660V and
BS142, sub-section 1.5.2. Class 1 severity
5A
(1989)
Make and carry for 3 7500VAa.c. or 7500Wd.c.
seconds within the limits of 660Vand
30A Mechanical Life
Breaking Capacity
( ≤ 5 A and ≤ 250 V): Durability in excess of 10,000
AC Resistive 1250 VA operations with the contact
DC Resistive 100 W rating at a rate of 600
DC Inductive 50 W L/R = 40ms operations per hour
Minimum number of
1000 at maximum load
operations
Minimum recommended
0.5 Watt limits 10mA or 5V
Environmental
load

Temperature
Electrical Tests IEC 68-2-1/2

Operating -10 °C to +55 °C


Insulation
Storage -25 °C to +70 °C
IEC 60255-5 RMS levels for 1 minute
Humidity
Between contacts to earth 2.0 kV IEC 68-2-3
and to the coil
Between any case terminal 2.0 kV Operational test 56 days at 40 °C and 95%
and earth RH
Between case terminals of 2.0 kV
independent circuits
Across normally open 1.0 kV
Performance
contacts
Instantaneous Operating time
Typically 25ms
Range 10ms to 50ms

Siemens Protection Devices Limited 3


Case Dimensions

Fig 1. E2 Case Dimensions

Fig 2. E4 Case Dimensions

Siemens Protection Devices Limited 4


Connection Diagram 7PG11 AR

Fig 3. Connection Diagrams

Siemens Protection Devices Limited 5


Ordering Information – 7PG111 AR
Product description Variants Order No.

Auxiliary relay (AR101, AR103) 7 P G 1 1 □▲ □▲ - □▲ □▲ □▲ □▲ □▲ - □▲ □▲ □▲ □▲


A.C. or D.C. voltage operated | | | | | | | | | | |
relay. | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
No flag 0 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
Hand and electrical reset contacts 3 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
7 NO H | | | | | | |
8 NO J | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
7 NC H | | | | | |
8 NC J | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 1 | | | | |
Six 3 | | | | |
Eight 5 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
(continued on following page)

Siemens Protection Devices Limited 6


Product description Variants Order No.

Auxiliary relay (AR101, AR103) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲
(continued from previous page) | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 7


Product description Variants Order No.

Auxiliary relay (AR101T) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay. | | | | | | | | | | |
| | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
No flag 0 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 3) 1 | | | | |
Six 4) 3 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
T1 (up to 100ms) - Delay on de-energisation 1 | | |
T2 (101 to 200ms) - Delay on de-energisation 2 | | |
T3 (201 to 300ms) - Delay on de-energisation 3 | | |
T4 (301 to 400ms) - Delay on de-energisation 4 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement
3) Four contact arrangements may only have a time delay of T1, T2 or T3
4) Six contact arrangements may only have a time delay of T1 or T2

Siemens Protection Devices Limited 8


Product description Variants Order No.

Auxiliary relay (AR106) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
A.C. or D.C. voltage operated | | | | | | | | | | |
relay. | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
No flag 0 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Electrical reset contacts 6 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 1 | | | | |
Six 3 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
(continued on following page)

Siemens Protection Devices Limited 9


Product description Variants Order No.

Auxiliary relay (AR106) 7 P G 1 1 □□ - □□□□□ - □□□□



(continued from previous page) Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 10


Product description Variants Order No.

Auxiliary relay (AR201) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
A.C. or D.C. voltage operated | | | | | | | | | | |
relay. | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Two element 2 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
No flag 0 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts/element 2) | | | | | |
Two 0 | |A| |
Four 1 | | C | |
Six 3 | | C | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
Case size E4 (4U high) C | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
(continued on following page)

Siemens Protection Devices Limited 11


Product description Variants Order No.

Auxiliary relay (AR201) 7 P G 1 1 □ □ - □ □ □ □ □ - □ □ □ □▲


(continued from previous page) Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 12


Product description Variants Order No.

Auxiliary relay (AR201T) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay. | | | | | | | | | | |
| | | | | | | | | | |
Number of elements | | | | | | | | | | |
Two element 2 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
No flag 0 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts/element 2) | | | | | |
Two 0 | |A| |
Four 3) 1 | | C | |
Six 4) 3 | | C | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
T1 (up to 100ms) - Delay on de-energisation 1 | | |
T2 (101 to 200ms) - Delay on de-energisation 2 | | |
T3 (201 to 300ms) - Delay on de-energisation 3 | | |
T4 (301 to 400ms) - Delay on de-energisation 4 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
Case size E4 (4U high) C | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement
3) Four contact arrangements may only have a time delay of T1, T2 or T3
4) Six contact arrangements may only have a time delay of T1 or T2

Siemens Protection Devices Limited 13


Product description Variants Order No.

Auxiliary relay (AR111, AR112) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
A.C. or D.C. voltage operated. | | | | | | | | | | |
relay | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset flag 1 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
Hand reset contacts 2 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
7 NO H | | | | | | |
8 NO J | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
7 NC H | | | | | |
8 NC J | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 1 | | | | |
Six 3 | | | | |
Eight 5 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
(continued on following page )

Siemens Protection Devices Limited 14


Product description Variants Order No.

Auxiliary relay (AR111, AR112) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲
(continued from previous page) | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 15


Product description Variants Order No.

Auxiliary relay (AR111T) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay. | | | | | | | | | | |
| | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset flag 1 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 3) 1 | | | | |
Six 4) 3 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
T1 (up to 100ms) - Delay on de-energisation 1 | | |
T2 (101 to 200ms) - Delay on de-energisation 2 | | |
T3 (201 to 300ms) - Delay on de-energisation 3 | | |
T4 (301 to 400ms) - Delay on de-energisation 4 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement
3) Four contact arrangements may only have a time delay of T1, T2 or T3
4) Six contact arrangements may only have a time delay of T1 or T2

Siemens Protection Devices Limited 16


Product description Variants Order No.

Auxiliary relay (AR112T) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay. | | | | | | | | | | |
| | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset flag 1 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Hand reset contacts 2 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 1 | | | | |
Six 3 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
T6 (50ms max) - Delay on energisation 6 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 17


Product description Variants Order No.

Auxiliary relay (AR112SB) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay with | | | | | | | | | | |
series break contact to reduce | | | | | | | | | | |
relay burden to zero after Number of elements | | | | | | | | | | |
operation. Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset flag 1 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Hand reset contacts 2 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
7 NO H | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
7 NC H | | | | | |
8 NC J | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 1 | | | | |
Six 3 | | | | |
Eight 5 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard / 1 SB) 4 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
(continued on following page )

Siemens Protection Devices Limited 18


Product description Variants Order No.

Auxiliary relay (AR112SB) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲
(continued from previous page) | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) One NO contact allocated for series break


2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 19


Product description Variants Order No.

Auxiliary relay (AR113) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
A.C. or D.C. voltage operated. | | | | | | | | | | |
relay | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset flag 1 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Hand and electrical reset contacts 3 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
7 NO H | | | | | | |
8 NO J | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
7 NC H | | | | | |
8 NC J | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Four 1 | | | | |
Six 3 | | | | |
Eight 5 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
(continued on following page )

Siemens Protection Devices Limited 20


Product description Variants Order No.

Auxiliary relay (AR113) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲
(continued from previous page) | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 21


Product description Variants Order No.

Auxiliary relay (AR114) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
A.C. or D.C. voltage operated. | | | | | | | | | | |
relay | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset flag 1 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Hand and self reset contacts 4 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Four 1 | | | | |
Six 3 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Self Reset) / NC (Self Reset / 2 Hand Reset) 1 | | | |
NO (Self Reset / 2 Hand Reset) / NC (Self Reset) 2 | | | |
NO (Self Reset / 1 Hand Reset) / NC (Self Reset / 1 Hand Reset) 3 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
(continued on following page )

Siemens Protection Devices Limited 22


Product description Variants Order No.

Auxiliary relay (AR114) 7 P G 1 1 □□ - □□□□□ - □□□□



(continued from previous page) Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Hand reset contacts are fitted as 2NO, 2NC or 1NO/1NC, remaining contacts are self reset in any combination
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 23


Product description Variants Order No.

Auxiliary relay (AR211, AR212) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
A.C. or D.C. voltage operated. | | | | | | | | | | |
relay | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Two element 2 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset flag 1 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
Hand reset contacts 2 | | | | | C | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts/element 2) | | | | | |
Two 0 | |A| |
Four 1 | | C | |
Six 3 | | C | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
Case size E4 (4U high) C | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
(continued on following page )

Siemens Protection Devices Limited 24


Product description Variants Order No.

Auxiliary relay (AR211, AR212) 7 P G 1 1 □□ - □□□□□ - □□□□



(continued from previous page) Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 25


Product description Variants Order No.

Auxiliary relay (AR211T) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay. | | | | | | | | | | |
| | | | | | | | | | |
Number of elements | | | | | | | | | | |
Two element 2 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset flag 1 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
| | | | | |
Number of contacts/element 2) | | | | | |
Two 0 | | | | |
Four 3) 1 | | C | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
T1 (up to 100ms) - Delay on de-energisation 1 | | |
T2 (101 to 200ms) - Delay on de-energisation 2 | | |
T3 (201 to 300ms) - Delay on de-energisation 3 | | |
T4 (301 to 400ms) - Delay on de-energisation 4 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
Case size E4 (4U high) C | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement
3) Four contact arrangements may only have a time delay of T1, T2 or T3

Siemens Protection Devices Limited 26


Product description Variants Order No.

Auxiliary relay (AR212T) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay. | | | | | | | | | | |
| | | | | | | | | | |
Number of elements | | | | | | | | | | |
Two element 2 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset flag 1 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Hand reset contacts 2 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
| | | | | |
Number of contacts/element 2) | | | | | |
Two 0 | | | | |
Four 1 | | C | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
T6 (50ms max) - Delay on energisation 6 | | |
| | |
Housing size | | |
Case size E4 (4U high) C | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Refer Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not
listed there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 27


Product description Variants Order No.

Auxiliary relay (AR212SB) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay with | | | | | | | | | | |
series break contact to reduce | | | | | | | | | | |
relay burden to zero after. Number of elements | | | | | | | | | | |
operation Two element 2 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset flag 1 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Hand reset contacts 2 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts/element 2) | | | | | |
Two 0 | | | | |
Four 1 | | | | |
Six 3 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard / 1 SB) 4 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E4 (4U high) C | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) One NO contact allocated for series break


2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 28


Product description Variants Order No.

Auxiliary relay (AR121) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
A.C. or D.C. voltage operated. | | | | | | | | | | |
relay | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset reverse acting flag 2 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
7 NO H | | | | | | |
8 NO J | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
7 NC H | | | | | |
8 NC J | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 1 | | | | |
Six 3 | | | | |
Eight 5 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
(continued on following page)

Siemens Protection Devices Limited 29


Product description Variants Order No.

Auxiliary relay (AR121) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲
(continued from previous page) | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 30


Product description Variants Order No.

Auxiliary relay (AR121T) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay. | | | | | | | | | | |
| | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset reverse acting flag 2 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 3) 1 | | | | |
Six 4) 3 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
T1 (up to 100ms) - Delay on de-energisation 1 | | |
T2 (101 to 200ms) - Delay on de-energisation 2 | | |
T3 (201 to 300ms) - Delay on de-energisation 3 | | |
T4 (301 to 400ms) - Delay on de-energisation 4 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement
3) Four contact arrangements may only have a time delay of T1, T2 or T3
4) Six contact arrangements may only have a time delay of T1 or T2

Siemens Protection Devices Limited 31


Product description Variants Order No.

Auxiliary relay (AR124) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
A.C. or D.C. voltage operated. | | | | | | | | | | |
relay | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset reverse acting flag 2 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Hand and self reset contacts 4 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Four 1 | | | | |
Six 3 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Self Reset) / NC (Self Reset / 2 Hand Reset) 1 | | | |
NO (Self Reset / 2 Hand Reset) / NC (Self Reset) 2 | | | |
NO (Self Reset / 1 Hand Reset) / NC (Self Reset / 1 Hand Reset) 3 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
(Continued on following page)

Siemens Protection Devices Limited 32


Product description Variants Order No.

Auxiliary relay (AR124) 7 P G 1 1 □□ - □□□□□ - □□□□



(continued from previous page) Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Hand reset contacts are fitted as 2NO, 2NC or 1NO/1NC, remaining contacts are self reset in any combination
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 33


Product description Variants Order No.

Auxiliary relay (AR221) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
A.C. or D.C. voltage operated. | | | | | | | | | | |
relay Number of elements | | | | | | | | | | |
Two element 2 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset reverse acting flag 2 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts/element 2) | | | | | |
Two 0 | |A| |
Four 1 | | C | |
Six 3 | | C | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
Case size E4 (4U high) C | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 34


Product description Variants Order No.

Auxiliary relay (AR221T) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay. | | | | | | | | | | |
| | | | | | | | | | |
Number of elements | | | | | | | | | | |
Two element 2 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Hand reset reverse acting flag 2 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts/element 2) | | | | | |
Two 0 | | | | |
Four 3) 1 | | C | |
Six 4) 3 | | C | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
T1 (up to 100ms) - Delay on de-energisation 1 | | |
T2 (101 to 200ms) - Delay on de-energisation 2 | | |
T3 (201 to 300ms) - Delay on de-energisation 3 | | |
T4 (301 to 400ms) - Delay on de-energisation 4 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
Case size E4 (4U high) C | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement
3) Four contact arrangements may only have a time delay of T1, T2 or T3
4) Six contact arrangements may only have a time delay of T1 or T2

Siemens Protection Devices Limited 35


Product description Variants Order No.

Auxiliary relay (AR131, AR136) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
A.C. or D.C. voltage operated | | | | | | | | | | |
relay. | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Self reset flag 3 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
Electrical reset contacts 6 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 1 | | | | |
Six 3 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
(Continued on following page)

Siemens Protection Devices Limited 36


Product description Variants Order No.

Auxiliary relay (AR131, AR136) 7 P G 1 1 □□ - □□□□□ - □□□□



(continued from previous page) Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 37


Product description Variants Order No.

Auxiliary relay (AR131T) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay. | | | | | | | | | | |
| | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Self reset flag 3 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 3) 1 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
T1 (up to 100ms) - Delay on de-energisation 1 | | |
T2 (101 to 200ms) - Delay on de-energisation 2 | | |
T3 (201 to 300ms) - Delay on de-energisation 3 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement
3) Four contact arrangements may only have a time delay of T1 or T 2

Siemens Protection Devices Limited 38


Product description Variants Order No.

Auxiliary relay (AR133) 7 P G 1 1 □□ - □□□□□ - □□□□


A.C. or D.C. voltage operated. | | | | | | | | | | |
relay | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Self reset flag 3 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Hand and electrical reset contacts 3 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
7 NO H | | | | | | |
8 NO J | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
7 NC H | | | | | |
8 NC J | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 1 | | | | |
Six 3 | | | | |
Eight 5 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
(continued on following page)

Siemens Protection Devices Limited 39


Product description Variants Order No.

Auxiliary relay (AR133) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲
(continued from previous page) | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 40


Product description Variants Order No.

Auxiliary relay (AR231) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
A.C. or D.C. voltage operated. | | | | | | | | | | |
relay | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Two element 2 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Self reset flag 3 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
| | | | | |
Number of contacts/element 2) | | | | | |
Two 0 | |A| |
Four 1 | | C | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
Case size E4 (4U high) C | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 41


Product description Variants Order No.

Auxiliary relay (AR231T) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay. | | | | | | | | | | |
| | | | | | | | | | |
Number of elements | | | | | | | | | | |
Two element 2 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Self reset flag 3 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
| | | | | |
Number of contacts/element 2) | | | | | |
Two 0 | | | | |
Four 3) 1 | | C | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
T1 (up to 100ms) - Delay on de-energisation 1 | | |
T2 (101 to 200ms) - Delay on de-energisation 2 | | |
T3 (201 to 300ms) - Delay on de-energisation 3 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
Case size E4 (4U high) C | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement
3) Four contact arrangements may only have a time delay of T1 or T2

Siemens Protection Devices Limited 42


Product description Variants Order No.

Auxiliary relay (AR141) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
A.C. or D.C. voltage operated | | | | | | | | | | |
relay | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Self reset reverse acting flag 4 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
5 NO F | | | | | | |
6 NO G | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
5 NC F | | | | | |
6 NC G | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 1 | | | | |
Six 3 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 43


Product description Variants Order No.

Auxiliary relay (AR141T) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay. | | | | | | | | | | |
| | | | | | | | | | |
Number of elements | | | | | | | | | | |
Single element 1 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Self reset reverse acting flag 4 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
| | | | | |
Number of contacts 2) | | | | | |
Two 0 | | | | |
Four 3) 1 | | | | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
T1 (up to 100ms) - Delay on de-energisation 1 | | |
T2 (101 to 200ms) - Delay on de-energisation 2 | | |
T3 (201 to 300ms) - Delay on de-energisation 3 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement
3) Four contact arrangements may only have a time delay of T1 or T 2

Siemens Protection Devices Limited 44


Product description Variants Order No.

Auxiliary relay (AR241) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
A.C. or D.C. voltage operated | | | | | | | | | | |
relay. | | | | | | | | | | |
Number of elements | | | | | | | | | | |
Two element 2 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Self reset reverse acting flag 4 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
| | | | | |
Number of contacts/element 2) | | | | | |
Two 0 | |A| |
Four 1 | | C | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
No additional time delay 0 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
Case size E4 (4U high) C | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
63.5V AC J 0
110V AC K 0
220V AC L 0
240V AC M 0
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement

Siemens Protection Devices Limited 45


Product description Variants Order No.

Auxiliary relay (AR241T) 7 P G 1 1 □□ - □□□□□ - □□□□


▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
D.C. voltage operated relay. | | | | | | | | | | |
| | | | | | | | | | |
Number of elements | | | | | | | | | | |
Two element 2 | | | | | | | | | |
| | | | | | | | | |
Type of flag | | | | | | | | | |
Self reset reverse acting flag 4 | | | | | | | | |
| | | | | | | | |
Contact operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Contact arrangement – NO | | | | | | | |
0 NO A | | | | | | |
1 NO B | | | | | | |
2 NO C | | | | | | |
3 NO D | | | | | | |
4 NO E | | | | | | |
| | | | | | |
Contact arrangement NC | | | | | | |
0 NC A | | | | | |
1 NC B | | | | | |
2 NC C | | | | | |
3 NC D | | | | | |
4 NC E | | | | | |
| | | | | |
Number of contacts/element 2) | | | | | |
Two 0 | | | | |
Four 3) 1 | | C | |
| | | | |
Contact type 1) | | | | |
NO (Standard) / NC (Standard) 0 | | | |
| | | |
Time delay | | | |
T1 (up to 100ms) - Delay on de-energisation 1 | | |
T2 (101 to 200ms) - Delay on de-energisation 2 | | |
T3 (201 to 300ms) - Delay on de-energisation 3 | | |
| | |
Housing size | | |
Case size E2 (4U high) A | |
Case size E4 (4U high) C | |
| |
Voltage rating | |
12V DC A |
24V DC B |
30V DC C |
50V DC D |
60V DC E |
125V DC F |
220V DC G |
240V DC H |
|
Back emf suppression diode |
Not Fitted 0
Fitted 1

1) Heavy duty contact arrangements available at extra cost. Please see separate non-MLFB list for already defined heavy duty contact arrangements. For arrangements not listed
there please contact the factory.
2) Number of contacts must match selected contact arrangement
3) Four contact arrangements may only have a time delay of T1 or T2

Siemens Protection Devices Limited 46


Siemens Protection Devices Limited 47
Published by and copyright © 2010:
Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany

Siemens Protection Devices Limited


P.O. Box 8
North Farm Road
Hebburn
Tyne & Wear
NE31 1TZ
United Kingdom
Phone: +44 (0)191 401 7901
Fax: +44 (0)191 401 5575
www.siemens.com/energy

For more information, please contact our


Customer Support Center.
Phone: +49 180/524 70 00
Fax: +49 180/524 24 71(Charges depending on provider)
E-mail: [email protected]

Power Distribution Division Order No. E53000-K7076-C44-1


Printed in Fürth

Printed on elementary chlorine-free bleached paper.

All rights reserved.


Trademarks mentioned in this document are the property of Siemens AG, its affili-
ates, or their respective owners.

Subject to change without prior notice.


The information in this document contains general
descriptions of the technical options available, which
may not apply in all cases. The required technical
options should therefore be specified in the contract.

www. siemens.com/energy
Siemens Protection Devices Limited 48