Power System Analysis Complex Engineering Problem

This project report describes the load flow and fault analysis of an extended 13-bus power system using ETAP software. The system includes 4 generators, 4 transformers, 13 buses, 9 transmission lines, and 5 loads. Load flow analysis was performed and fault currents and short circuit capacities were calculated for faults at each bus. In conclusion, the objectives of designing a power system and performing load flow and fault analysis using a modern tool were achieved.

Uploaded by

mhrs11
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
763 views

Power System Analysis Complex Engineering Problem

This project report describes the load flow and fault analysis of an extended 13-bus power system using ETAP software. The system includes 4 generators, 4 transformers, 13 buses, 9 transmission lines, and 5 loads. Load flow analysis was performed and fault currents and short circuit capacities were calculated for faults at each bus. In conclusion, the objectives of designing a power system and performing load flow and fault analysis using a modern tool were achieved.

Uploaded by

mhrs11
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 13

POWER SYSTEM ANALYSIS LAB

PROJECT REPORT

Engineering Attributes
PLO-3: Design and Development
PLO-5: Modern tool usage

Submitted by: Muhammad Haris


Registration Number: 13R/14-EE-179
Group: C2

JANUARY 19, 2018


UNIVERSITY OF ENGINEERING & TECHNOLOGY TAXILA
Electrical Engineering department
Power system Analysis | Project report

Objective:
To Design a power system for the given requirements on any modern tool and
to perform load flow and short circuit analysis of that system.

Chosen Power system:


The standard IEEE 9-Bus system has been chosen as the base of this system
having an extension of 4 more buses. Following are the main components of
the Power system:
1. 4 Generators
2. 4 Transformers
3. 13 Buses
4. 9 Transmission Lines
5. 5 Loads

Extension of IEEE- 9 Bus System

1
Power system Analysis | Project report

Load Flow Analysis:

2
Power system Analysis | Project report

General Info:

Transformer information:

Loads:

Sources:

3
Power system Analysis | Project report

Fault Analysis
Fault at Bus 1:

Fault Current= 63.51kA


Pre-fault Voltage= 17.16 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1887.6 MVA

Fault at Bus 2:

Fault Current= 53.96kA


Pre-fault Voltage= 18.45 kV

4
Power system Analysis | Project report

Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent


= 1724.4 MVA

Fault at Bus 3:

Fault Current= 59.09kA


Pre-fault Voltage= 14.145 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1447.7 MVA

Fault at Bus 4:

5
Power system Analysis | Project report

Fault Current= 4.82kA


Pre-fault Voltage= 229.7 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1917.6 MVA

Fault at Bus 5:

Fault Current= 4.82kA


Pre-fault Voltage= 229.6 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1916.8 MVA

Fault at Bus 6:

6
Power system Analysis | Project report

Fault Current= 4.81kA


Pre-fault Voltage= 229.6 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1912.8 MVA

Fault at Bus 7:

Fault Current= 4.82kA

7
Power system Analysis | Project report

Pre-fault Voltage= 229.7 kV


Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1917.6 MVA
Fault at Bus 8:

Fault Current= 4.78kA


Pre-fault Voltage= 229.7 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1901.7 MVA

Fault at Bus 9:

8
Power system Analysis | Project report

Fault Current= 34.65kA


Pre-fault Voltage= 18 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 10803 MVA

Fault at Bus 10:

Fault Current= 4.82kA

9
Power system Analysis | Project report

Pre-fault Voltage= 229.6 kV


Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1917.6 MVA

Fault at Bus 11:

Fault Current= 4.8kA


Pre-fault Voltage= 229.6 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1909.8 MVA

Fault at Bus 12:

10
Power system Analysis | Project report

Fault Current= 4.8kA


Pre-fault Voltage= 229.6 kV
Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1909.9 MVA

Fault at Bus 13:

Fault Current= 4.8kA

11
Power system Analysis | Project report

Pre-fault Voltage= 229.6 kV


Short circuit Capacity=sqrt(3)*V(loadflow)*FaultCurrrent
= 1909.8 MVA

Conclusion:
Hence Load flow Analysis and Fault Analysis has been done under given
constraints on ETAP.