Data Sheet 630kva 33kv Cu F 90 Ip23

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Enquiry No.

: STD-630KVA-11KV-CU-F-90
Revision : A
Date : 20-12-2016

Technical Particulars of Vacuum Cast Coil (VCC)


Dry type Transformers ABB
S. No. Description UNIT Parameter
1 Name of Manufacturer ABB India Ltd.
2 General Description Dry Type Transformer
3 Reference Standard IS 11171 & IEC 60076-11
4 Installation Indoor
5 Duty Continuous
6 Application Distribution Transformer
7 Altitude m Less than / equal to 1000 m
8 Rated Power (based on AN Cooling) kVA 630
9 Rated No-Load Voltage Ratio (HV / LV) kV 11 / 0.433
10 Rated Frequency Hz 50
11 Number of Phases Nos. 3
12 Material of Winding (HV / LV) CU / CU
13 Vector Group Dyn11
14 Connection (HV / LV) Delta / Star
15 Tapping Off Circuit
16 Type of Tap Changer Off Circuit Bolted Links
17 Tapping Range/Tap step +5% to -5% in steps of 2.5%
18 No. of Steps Nos. +2 / -2
19 For HV Variation / LV Variation HV Variation
20 Class of Insulation (HV / LV) Class F/F
21 Method of Cooling AN
22 Avg. Temp. Rise of Winding Deg.C 90 / 90
23 Ambient Temp. (Max. / Mini. / Year / Day) Deg.C 50 / -5 / 32 / 40
No-Load Loss at Rated Voltage & Frequency (+15%
24 kW 2.50
of IS Tol.)
Full-Load Loss at Rated Current, at 75 Deg. C & at Principal
25 kW 5.50
Tap (+15% of IS Tol.)
Total Loss at Rated Voltage at Principal Tapping, Rated
26 kW 8.00
Frequency, at 75 Deg. C & at 100% load (+10% of IS Tol.)
% Impedance at Rated Current, at 75 Deg. C & at Principal
% 4.00
Tap (±10% of IS Tol.)
27
A. Reactance % 3.90
B.Resistance % 0.87
No-Load Current at Rated Voltage & Frequency
28 % 2.00
(as % of F.L.R.C.)(+30% IS Tol.)
Efficiencies at 75 Deg. C at Unity Power Factor (Reference
vaule)
29 a) At Full Load % 98.75
b) At 3/4 Full Load % 98.83
c) At 1/2 Full Load % 98.78
Regulation at Full Load at 75 Deg. C
30 a) At Unity Power Factor % 0.95
b) At 0.8 Power Factor (Lagging) % 3.05
31 BIL (Insulation Level) :
32 Full Wave Lightning Impulse Withstand Voltage (HV / LV) kV peak 170 / -
Separate Source Power-Frequency Voltage Withstand (HV
33 kV rms 70 / 03
/ LV)
34 Enclosure
35 Degree of protection of Enclosure IP IP23
36 Termination Arrangements
37 HV Cable box
38 LV Bus duct
Enquiry No. : STD-630KVA-11KV-CU-F-90
Revision : A
Date : 20-12-2016

Technical Particulars of Vacuum Cast Coil (VCC)


Dry type Transformers ABB
S. No. Description UNIT Parameter
39 Orientation between HV & LV Deg. 180
Weights (Approx.)
Core & Winding Kg. 2700
40
Enclosure & Fittings Kg. 850
Total Weight Kg. 3550
Over-all Dimensions (Approx)
Length mm 2200
41
Breadth mm 2550
Height (With base channel) mm 2250
Rating & Diagram plate, Base Channel,
Earthing terminals, Lifting lugs &
42 Fittings / Accessories WTI Scanner with 3 PT-100 Sensors

43 List of Tests to be conducted at Manufacturer's Works Routine Test According to IS 11171


Noise level values shall be as per
44 Noise Level when measured at 1 Meter Distance dB
NEMA TR-1

Note:
1)Efficiency and regulation values are calculated based on nominal values of NLL,LL & %Z.
2)Weights & dimensions are subject to ±10% Tolerance.
3)Terminal arrangement will be done with suitable size of support insulators & busbars; No bushing shall be provided.
4)Cable termination kits, lugs, glands etc. are not in our scope of supply.
5)Enclosure manufacturing & painting shall be done as per ABB standrad practice;