0% found this document useful (0 votes)
112 views2 pages

Acme f12ndf50

Acme F range of front access VRLA batteries has been specifically designed for applications using 19" and 23" cabinets, especially telecoms. Patented post seal and state-of-the-art AGM design developed to comply with the latest IEC, British and Telcordia standards. A 12+ years design life and centralised venting system add to the suitability and flexibility of this superior range.

Uploaded by

kylegaze
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
112 views2 pages

Acme f12ndf50

Acme F range of front access VRLA batteries has been specifically designed for applications using 19" and 23" cabinets, especially telecoms. Patented post seal and state-of-the-art AGM design developed to comply with the latest IEC, British and Telcordia standards. A 12+ years design life and centralised venting system add to the suitability and flexibility of this superior range.

Uploaded by

kylegaze
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

stored energy solutions for a demanding world

Model: 12NDF50
The Acme F range of front access VRLA batteries has been specifically
designed for applications using 19" and 23" cabinets, especially telecoms .
Reliability is assured with the patented post seal and a state-of-the-art AGM
design developed to comply with the latest IEC, British and Telcordia
standards. A 12+ years design life and centralised venting system
add to the suitability and flexibility of this superior range.
Dimensions-mm[inch]

Specifications
Battery Model 12NDF50

Nominal Voltage 12V


Rated Capacity 50Ah (10 hour rate) to 1.80V/cell @25 OC (77 OF )
Typical Weight 21kg

Internal Resistance Approx 8.87mΩ


O O O O
Operation ( maximum ): -40 C to 5 5 C( -40 F to 1 31 F)
O O O O
Temperature Ranges Operation ( recommended ): 15 C to 25 C( 59 F to 77 F)
O O O O
Storage: -20 C to 40 C( -4 F to 104 F)
Float Voltage 2.25V/cell@25 OC (77 OF )
Recommended Maximum
Charging Current Limit 12.5A

Equalize and Cycle Service 2.35V~ 2.40V/cell@25 OC (77 OF )


Self Discharge The residual capacity is above 90% after 90 days storage(25 OC /77 OF )

Terminal M6 Female

Terminal Hardware Torque 10 ± 1. 0Nm


Container Material ABS ( V0 optional)
O O
Constant Current Discharge Characteristics Units: Amperes (25 C, 77 F)
End voltage
per cell 5MIN 15MIN 30MIN 45MIN 1HR 2HR 3HR 4HR 5HR 6HR 8HR 10HR 12HR 20HR 24HR
1.60V 188 101 61.2 44.3 35.8 20.6 14.9 11.7 9.88 8.49 6.51 5.36 4.52 2.83 2.36
1.67V 176 97.4 60.1 44.0 35.6 20.4 14.6 11.6 9.83 8.41 6.47 5.28 4.51 2.80 2.34
1.70V 175 95.7 59.3 43.7 35.4 20.3 14.6 11.6 9.67 8.35 6.44 5.28 4.46 2.80 2.34
1.75V 160 92.7 58.7 43.4 34.8 19.8 14.4 11.4 9.62 8.28 6.37 5.25 4.46 2.79 2.34
1.80V 144 86.4 56.2 41.6 33.9 19.6 14.3 11.4 9.42 8.11 6.33 5.20 4.43 2.76 2.33
1.83V 137 79.2 55.2 40.2 32.5 19.4 13.8 10.9 9.11 7.83 6.18 5.01 4.21 2.76 2.30
1.85V 129 76.7 51.3 38.6 31.5 18.6 13.4 10.7 8.89 7.66 5.98 4.97 4.16 2.70 2.28
O O
Discharge Data with Constant Power Units:Watts per cell (25 C, 77 F)
End voltage
per cell 5MIN 15MIN 30MIN 45MIN 1HR 2HR 3HR 4HR 5HR 6HR 8HR 10HR 12HR 20HR 24HR
1.60V 314 177 111 83.2 67.4 38.8 28.3 22.5 18.9 16.3 12.6 10.4 8.74 5.60 4.69
1.67V 302 174 110 82.7 67.0 38.7 28.0 22.4 18.9 16.2 12.6 10.3 8.74 5.58 4.69
1.70V 301 172 110 82.6 66.8 38.5 28.0 22.3 18.7 16.1 12.5 10.2 8.66 5.57 4.68
1.75V 280 171 109 82.4 65.8 38.3 27.7 22.3 18.7 16.1 12.4 10.2 8.66 5.55 4.68
1.80V 257 162 107 80.4 65.7 38.2 27.6 22.2 18.3 15.9 12.3 10.2 8.63 5.55 4.67
1.83V 246 148 105 78.0 63.0 37.7 27.0 21.4 17.9 15.4 12.2 9.91 8.37 5.54 4.64
1.85V 230 144 97.9 74.9 61.0 36.5 26.2 21.1 17.5 15.1 11.8 9.83 8.28 5.44 4.60

Copyright Narada Power Source Co.,Ltd. www.naradabattery.com


stored energy solutions for a demanding world
Model: 12NDF50

Terminal Voltage(V) Vs. Discharge Time (25OC, 77OF) Battery Voltage Vs. Charge Time

Capacity

Current

Voltage
Charge

Charge
Charge
13
Charge Characteristic
Discharge Voltage(V)

12
(%) (CA) (V) Constant Charge At 0.20CA-14.1V(25℃)
120
11 Charge Charge
0.05CA 14 Voltage Capacity
0. 1CA 100
10 0. 25CA
0. 6CA
1CA 80 0.20 13
9 100%Charge
60 0.15
12 50%Charge
8
40 0.10
11
20 0.05
0 2 6 12 30 60 3 10 20 Charge
Current
Min h 0 0 0 2 4 6 8 10 12
Time(hour)

Relationship of OCV Vs. State of Charge Capacity Retention Characteristic


13.5

13.0
100
Capacity(%)
OCV (V)

12.5 75 O O
10 C(50 F)

12.0 50
40 OC (104 OF) 30 OC (86 OF) O
20 C(68 F)
O

25
11.5

11.0 3 6 9 12 15 18 21 24 27
0 10 20 30 40 50 60 70 80 90 100
Storage Time(month)
Remained Capacity(%)

Charging Procedures Discharge Current VS. Discharge Voltage

Charge Voltage (V/Cell)

Final E. & O. E.
Max. Discharge
Set Allowable 1.80 1.70 1.55 1.30
Application Temperature Charge Voltage
Point Range Current V/Cell
2008

Cycle 25 OC 2.40 2.35~2.45 Discharge


0.25C Current (A) 0.2C≥(A) 0.2C<(A)<0.5C 0.5C<(A)<1.0C (A)>1.0C
Standby 25 OC 2.25 2.23~2.27
12NDF50- 02- EN January

NARADA POWER SOURCE CO., LTD. NARADA EUROPE (UK) LTD. NARADA ASIA PACIFIC PTE.LTD.
No.459 Wensan Road, Hangzhou, Zhejiang, P.R.China Spectrum House, Dunstable Road, Redbourn, 65 Ubi Cresent Hola centre #08-02 Singapore
St.Albans, Herts AL3 7PR, UK
Tel:+86-571-28827013 Fax:+86-571-85126942 Tel: +44 (0)845 371 7095 Fax:+44 (0)845 612 2031 Tel:+65-68481191/+65-67421208 Fax:+65-67493498
Website:www.naradabattery.com E-mail: [email protected] E-mail: [email protected] E-mail: [email protected]