The test is performed by a current
Steam Boiler generator (greater than 10 Adc) and a
Storage Tank voltmeter. The acceptance criteria shall be
based on manufacturer approved
Process Heater procedure but usually phase to phase
deviation should not be more than 2%, and
max deviation from theoretical value should
ROTARY not be more than 5%.
EQUIPMENT
Centrifugal Temperature Sensor
Pump Resistance Test
Centrifugal
Compressor This test is done to make sure the
continuity and homogeneity of each
Reciprocating temperature sensor defined at 100 Ohms
Compressor for 0°C. A multimeter or temperature direct
Gas Turbine reading probe is used for measurement.
The acceptance criteria depends on test
Steam Turbine
procedure but normally should not be more
Fan & Blower than +/- 2° celsius
http://www.inspection-for-industry.com/induction-motor-testing.html 2/7
1/30/2018 Induction Motor Testing
Switchgear
We will be updating
and growing this No-Load Curve &
site with more and
more of industrial Losses Characteristics
inspection related @ Induction Motor
articles.
Routine Testing
Please subscribe to
my monthly
newsletter so you
don't miss a thing.
http://www.inspection-for-industry.com/induction-motor-testing.html 3/7
1/30/2018 Induction Motor Testing
Overspeed Test @
Induction Motor Testing
The overspeed test is performed to make
sure that rotor speed can reach to the 1.2
times of the rated speed in 2 minutes. A
speedometer is used to measure the rotor
speed, and no particular noise, excess
vibration and abnormal temperature rise
shall be observed.
http://www.inspection-for-industry.com/induction-motor-testing.html 4/7
1/30/2018 Induction Motor Testing
http://www.inspection-for-industry.com/induction-motor-testing.html 5/7
1/30/2018 Induction Motor Testing
Insulation Resistance
Test
The test is one of important test in the
induction motor routine testing and is done
to measure the winding insulation
resistance of the armature, field poles,
http://www.inspection-for-industry.com/induction-motor-testing.html 6/7
1/30/2018 Induction Motor Testing
New! Comments
Have your say about what you just read!
Leave me a comment in the box below.
inspection-for-industry.com
Copyright © 2012-2013 Inspection-for-Industry.Com
http://www.inspection-for-industry.com/induction-motor-testing.html 7/7