Description
Application
H07V-K cores are principally used for panels and cabinets stranding.
Installation
Open air, or in conduits, or trunking.
Marking
• For section between 0,75 and 4 mm² : S.Y + USE <HAR>N° Plant
• For section above 4 mm² : S.Y + USE <HAR>H07VK - N° Plant
Standards
International HD 21.3; IEC
60227-2
National NF C 32-201/3
Contact
Nexans - Building activity
4-10 rue Mozart
92587 Clichy Cedex
France
[email protected]
Lead free Mechanical resistance to Cable flexibility Operating temperature, Weather resistance Flame retardant
Yes impacts Flexible range Good C2, NF C 32-070
Low -5 .. 60 °C
Technical data
Cross Conductor Nom. outer Permissible current rating Permissible current Approx.
section diam. diam. (3 conductors) (one phase) weight
mm² mm mm A A kg/km
1.5 1.55 3.5 15.5 17.5 20
2.5 2.0 4.2 21.0 24.0 30
4 2.5 4.8 28.0 32.0 45
6 3.0 6.3 36.0 41.0 65
10 4.0 7.6 50.0 57.0 110
16 5.45 8.8 68.0 76.0 170
25 6.6 11.0 89.0 96.0 255
.
Cross Conductor Nom. outer Permissible current rating Permissible current Approx.
section diam. diam. (3 conductors) (one phase) weight
mm² mm mm A A kg/km
25 6.6 11.0 89.0 96.0 270
35 8.0 12.5 110.0 119.0 370
50 9.5 14.5 134.0 144.0 495
70 11.3 17.0 171.0 184.0 700
95 13.6 19.0 207.0 223.0 920
120 15.2 21.0 239.0 259.0 1130
150 16.7 23.5 275.0 299.0 1425
185 18.7 26.0 315.0 341.0 1740
240 21.2 29.5 371.0 403.0 2240