NCMA TEK

National Concrete Masonry Association


an information series from the national authority on concrete masonry technology

EMPIRICAL DESIGN OF TEK 14-8B


Structural (2008)
CONCRETE MASONRY WALLS

Keywords: allowable stress, anchorage, bonding, building


codes, empirical design, height/thickness ratio, intersecting
walls, lateral support, nonbearing wall, parapet, partition
walls, shear wall, unreinforced concrete masonry, vertical
loads, wall ties

INTRODUCTION This TEK is based on the provisions of Section 2109 of


the International Building Code (IBC) (ref. 1). These empiri-
Empirical design is a procedure of proportioning and siz- cal design requirements do not apply to other design methods
ing unreinforced masonry elements based on known historical such as allowable stress or limit states design. For empirical
performance for a given application. Empirical provisions design of foundation walls, see TEK 15-1B, Allowable Stress
preceded the development of engineered masonry design, and Design of Concrete Masonry Foundation Walls (ref. 2)
can be traced back several centuries. This approach to design
is based on historical experience in lieu of analytical methods. APPLICABILITY OF EMPIRICAL DESIGN
It has proven to be an expedient design method for typical
loadbearing structures subjected to relatively small wind loads The IBC allows elements of masonry structures to be de-
and located in areas of low seismic risk. Empirical design has signed by empirical methods when assigned to Seismic Design
also been used extensively for the design of exterior curtain Category (SDC) A, B or C, subject to additional restrictions
walls and interior partitions. described below. When empirically designed elements are part
Using empirical design, vertical and lateral load resistance of the seismic lateral force resisting system, however, their
is governed by prescriptive criteria which include wall height to use is limited to SDC A.
thickness ratios, shear wall length and spacing, minimum wall Empirical design has primarily been used with masonry
thickness, maximum building height, and other criteria, which laid in running bond. When laid in stack bond, the IBC requires
have proven to be effective through years of experience. a minimum amount of horizontal reinforcement (0.003 times

Table 1—2006 IBC Empirical Design Limitations Based on Building Height and Basic Wind SpeedA

Basic wind speed, w, mph (m/s)


Building height, w < 90 90 < w < 100 100 < w < 110 110 < w
Masonry wall type: h, ft (m) (w < 40) (40 < w < 45) (45 < w < 49) (49 < w)
Part of the lateral force-
resisting system h < 35 (11) Allowed Not allowed
Interior, not part of the h > 180 (55) Not allowed
lateral force-resisting 60 (18) < h < 180 (55) Allowed Not allowed
system, in buildings other 35 (11) < h < 60 (18) Allowed Not allowed
than enclosedA h < 35 (11) Allowed Not allowed
Exterior, not part of the h > 180 (55) Not allowed
lateral force-resisting 60 (18) < h < 180 (55) Allowed Not allowed
system 35 (11) < h < 60 (18) Allowed Not allowed
Exterior h < 35 (11) Allowed Not allowed
A
Per Minimum Design Loads for Buildings and Other Structures, ASCE 7 (ref. 4).

TEK 14-8B © 2008 National Concrete Masonry Association (replaces TEK 14-8A)
t

Simple span deflection


l
t
h

t t1
l
t2

Simple span deflection


Single wythe Double wythe
Note: In cases where reinforced masonry pilasters have
(Note: t = t1 + t2 )
control joints on only one side of each pilaster, the clear
span, l, extends from control joint to control joint.
Where:
h = clear span between supports t = nominal wall thickness
l = horizontal span t1, t2 = nominal wythe thicknesses
Figure 1—Lateral Support of Empirically Designed (Unreinforced) Concrete Masonry Walls

Table 2—Wall Lateral Support Requirements (ref. 1) Table 3—Maximum Unreinforced Wall Spans, ft (m)A

Maximum wall length-to Wall thickness, in. (mm) 6 (152) 8 (203) 10 (254) 12 (305)
thickness or height-to Bearing walls
Construction (unreinforced) thickness ratioA Solid or solid grouted 10 (3.0)B 13.3 (4.1) 16.6 (5.1) 20 (6.1)
Bearing walls All other 9 (2.7)B 12 (3.7) 15 (4.5) 18 (5.5)
Solid units or solid grouted 20 Nonbearing walls
All others 18 Exterior 9 (2.7) 12 (3.7) 15 (4.5) 18 (5.5)
Nonbearing walls Interior 18 (5.5) 24 (7.3) 30 (9.1) 36 (11)
Exterior 18 Cantilever WallsC
Interior 36 Solid 3 (0.9) 4 (1.2) 5 (1.5) 6 (1.8)
Cantilever wallsB Hollow 2 (0.6) 2.6 (0.8) 3.3 (1.0) 4 (1.2)
Solid 6 Parapets C 1.5 (0.5) 2 (0.6) 2.5 (0.8) 3 (0.9)
Hollow 4 A
Note that Ref. 6 includes modified requirements for walls
Parapets (8-in. (203-mm) thick min.)B 3
with openings.
A
Ratios are determined using nominal dimensions. For multi- B Unreinforced 6-in. (152-mm) thick bearing walls are limited
wythe walls where wythes are bonded by masonry headers, to one story in height.
the thickness is the nominal wall thickness. When multiwythe C For these cases, spans are maximum wall heights.
walls are bonded by metal wall ties, the thickness is taken
as the sum of the wythe thicknesses. Note that Reference 6
includes modified requirements for walls with openings. check the SDC and basic wind speed, with the 2006 IBC, to
B
The ratios are maximum height-to-thickness ratios and do use empirical design the designer must check:
not limit wall length.
• SDC,
the wall's vertical cross-sectional area and spaced not more • basic wind speed,
than 48 in. (1,219 mm) apart). • building height, and
In addition, buildings that rely on empirically designed • location of gravity loads resultant.
masonry walls for lateral load resistance are allowed up to 35 The limitations based on SDC are the same as in the 2003
ft (10.7 m) in height. IBC, described above. Building height and basic wind speed
The 2003 IBC restricts empirical design to locations where conditions where empirical design is permitted under the 2006
the basic wind speed (three-second gust, not fastest mile) is IBC are summarized in Table 1.
less than or equal to 110 mph (79 m/s), as defined in Minimum The 2006 IBC also requires the resultant of gravity loads
Design Loads for Buildings and Other Structures, ASCE 7 to fall within the kern of the masonry element, to avoid im-
(ref. 3). A wind speed of this velocity generally applies along parting tension to the element. This area is defined as: within
the East and Gulf coasts of the United States. the center third of the wall thickness, or, for foundation piers,
The 2006 IBC further refines the empirical design limi- within the central area bounded by lines at one-third of each
tations. Whereas with the 2003 IBC, the designer need only cross-sectional dimension of the pier.
Table 4—Allowable Compressive Stress for DESIGN PROVISIONS
Empirical Design of Masonry
Minimum Wall Thickness
Allowable compressive stresses Empirically designed (unreinforced) bearing walls of
based on gross cross-sectional one story buildings must be at least 6 in. (152 mm) thick. For
area, psi (MPa)A buildings more than one story high, walls must be at least 8
Gross area compressive Type M or S Type N in. (203 mm) thick. The minimum thickness for unreinforced
strength of unit, psi (MPa) mortar mortar masonry shear walls and for masonry foundation walls is also
8 in. (203 mm). Note that the 2003 IBC allows shear walls
Solid and Solidly Grouted Masonry (refs. 1, 6): of one-story buildings to have a minimum thickness of 6 in.
Solid concrete brick:
(152 mm).
8,000 (55) or greater 350 (2.41) 300 (2.07)
4,500 (31) 225 (1.55) 200 (1.38)
2,500 (17) 160 (1.10) 140 (0.97) Lateral Support
1,500 (10) 115 (0.79) 100 (0.69) Lateral support for walls can be provided in the horizontal
Grouted concrete masonry: direction by cross walls, pilasters, buttresses and structural
4,500 (31) or greater 225 (1.55) 200 (1.38) frame members, or in the vertical direction by floor diaphragms,
2,500 (17) 160 (1.10) 140 (0.97) roof diaphragms and structural frame members, as illustrated
1,500 (10) 115 (0.79) 100 (0.69) in Figure 1. For empirically designed walls, such support must
Solid concrete masonry units: be provided at the maximum intervals given in Tables 2 and 3.
3,000 (21) or greater 225 (1.55) 200 (1.38) Note that the span limitations apply to only one direction; that
2,000 (14) 160 (1.10) 140 (0.97) is, the span in one direction may be unlimited as long as the
1,200 (8.3) 115 (0.79) 100 (0.69) span in the other direction meets the requirements of Tables
Hollow walls (noncomposite masonry bondedB):
2 or 3.
Solid units:
2,500 (17) or greater 160 (1.10) 140 (0.97)
1,500 (10) 115 (0.79) 100 (0.69) Allowable Stresses
Allowable stresses in empirically designed masonry due
to building code prescribed vertical (gravity) dead and live
Hollow Unit Masonry (Units Complying With ASTM loads (excluding wind or seismic) are given in Table 4.
C 90-06 or Later) (ref. 6)C: Table 4 includes two sets of compressive stresses for
Hollow loadbearing CMU, t < 8 in. (203 mm)D: hollow concrete masonry units (CMU). The first set, titled
2,000 (14) or greater 140 (0.97) 120 (0.83) "Hollow Unit Masonry (Units Complying With ASTM C 90-
1,500 (10) 115 (0.79) 100 (0.69) 06 or Later)" apply to most CMU currently available. The
1,000 (6.9) 75 (0.52) 70 (0.48) 2006 edition of the CMU specification, Standard Specification
700 (4.8) 60 (0.41) 55 (0.38)
for Loadbearing Concrete Masonry Units, ASTM C 90 (ref.
Hollow loadbearing CMU, 8 in. < t < 12 in. (203 to 305 mm)D:
7), included slightly reduced minimum face shell thickness
2,000 (14) or greater 125 (0.86) 110 (0.76)
1,500 (10) 105 (0.72) 90 (0.62) requirements for CMU 10 in. (254 mm) and greater in width.
1,000 (6.9) 65 (0.49) 60 (0.41) These smaller face shells require a corresponding adjustment
700 (4.8) 55 (0.38) 50 (0.35) to the allowable compressive stresses. The values currently
Hollow loadbearing CMU, t > 12 in (305 mm)D: published in the 2006 IBC ("Hollow Unit Masonry (Units
2,000 (14) or greater 115 (0.79) 100 (0.69) Complying With Previous Editions of ASTM C 90)" in Table
1,500 (10) 95 (0.66) 85 (0.59) 4), apply to the previous face shell thicknesses, and should
1,000 (6.9) 60 (0.41) 55 (0.38) only be used if the CMU to be used have the thicker face shells
700 (4.8) 50 (0.35) 45 (0.31)
Hollow walls (noncomposite masonry bondedB):
t < 8 in. (203 mm)D 75 (0.52) 70 (0.48)
A
8 < t < 12 in (203 to 305 mm)D 70 (0.48) 65 (0.45) Linear interpolation for intermediate values of compressive
t > 12 in (305 m.m)D 60 (0.41) 55 (0.38) strength is permitted.
B
Where floor and roof loads are carried on one wythe, the gross
cross-sectional area is that of the wythe under load; if both
wythes are loaded, the gross cross-sectional area is that of the
Hollow Unit Masonry (Units Complying With Previous
wall minus the area of the cavity between the wythes. Walls
Editions of ASTM C 90) (ref. 1)C: bonded with metal ties shall be considered as noncomposite
Hollow concrete masonry units: walls unless collar joints are filled with mortar or grout.
2,000 (14) or greater 140 (0.97) 120 (0.83) C
Minimum unit face shell thicknesses, for units 10 in. (254 mm)
1,500 (10) 115 (0.79) 100 (0.69) and greater in width, were reduced beginning with ASTM C
1,000 (6.9) 75 (0.52) 70 (0.48) 90-06. Hence, minimum allowable compressive stresses should
700 (4.8) 60 (0.41) 55 (0.38) be reduced accordingly when using these units. See text for
Hollow walls (noncomposite masonry bondedB): further information.
D
Hollow units 75 (0.52) 70 (0.48) t = nominal unit thickness.
listed in previous editions of ASTM C 90. This distinction is erly anchored so that the imposed loads can be transmitted
not applicable to masonry that will be solidly grouted. from the wall to the supporting element. Minimum anchor-
Calculated compressive stresses for both single and mul- age requirements for intersecting walls and for floor and roof
tiwythe walls are determined by dividing the design load by diaphragms are shown in Figures 2 and 3, respectively.
the gross cross-sectional area of the wall, excluding areas of Masonry walls are required to be anchored to structural
openings, chases or recesses. The area is based on the specified frames that provide lateral support by 1/2 in. (13 mm) diameter
dimensions of masonry, rather than on nominal dimensions. bolts spaced at a maximum of 4 ft (1.2 m), or with other bolts
In multiwythe walls, the allowable stress is determined by the and spacings that provide equivalent anchorage. The bolts
weakest combination of units and mortar shown in Table 4. must be embedded a minimum of 4 in. (102 mm) into the
In addition, the commentary to Building Code Require- masonry.
ments for Masonry Structures (refs. 6, 8) contains additional In addition, the 2006 IBC requires the designer to check
guidance for concentrated loads. According to the commentary, the roof loading for net uplift and, where net uplift occurs, to
when concentrated loads act on empirically designed masonry, design the anchorage system to entirely resist the uplift.
the course immediately under the point of bearing should be
a solid unit or be filled solid with mortar or grout. Further, Shear Walls
when the concentrated load acts on the full wall thickness, Where the structure depends on masonry walls for lateral
the allowable stresses under the load may be increased by stability against wind or earthquake forces, shear walls must
25 percent. The allowable stresses may be increased by 50 be provided parallel to the direction of the lateral forces as
percent when concentrated loads act on concentrically placed well as in a perpendicular plane, for stability.
bearing plates that are greater than one-half but less than the Requirements for empirically designed masonry shear
full area. walls are shown in Figure 4.
Shear wall spacing is determined empirically by the
Anchorage for Lateral Support length-to-width aspect ratio of the diaphragms that transfer
Where empirically designed masonry walls depend on lateral forces to the shear walls, as listed in Table 5. In addition,
cross walls, roof diaphragms, floor diaphragms or structural roofs must be designed and constructed in a manner such that
frames for lateral support, it is essential that the walls be prop- they will not impose thrust perpendicular to the shear walls

3 in. (76 mm) min. At corners, overlap


or use prefabricated
extension into the wall sections
Joint reinforcement
at 8 in. (203 mm) 30 in. (762 mm) min.
max. vertical extension in each
Alternate courses spacing - W 1.7 direction
intersect as shown
(MW 11) min.
longitudial wire size

Loadbearing walls Loadbearing walls

Metal lath below or wide Control joint


screen over cores to rake and caulk
support grout fill

Embed bent ends in grout,


2 in. (51 mm) min., or use
cross pins to form anchorage

Galvanized mesh joint


reinforcement or 1/4 in.
Grouted cores (6.4 mm) hardware cloth,
Steel connectors at 48 in. 16 in. (406 mm) max.
(1.2 m) o.c. max. vertically. vertical spcacing
24 in. (610 mm) min. length
and min. section 1/4 x 1 1/2 in.
(6.4 x 38 mm)
Loadbearing walls Interior nonloadbearing walls
Note: Other metal ties, joint reinforcement or anchors may be used, provided they are spaced to provide an equivalent area of anchorage.

Figure 2—Empirical Anchorage Requirements for Lateral Support of Intersecting Masonry Walls
to which they are attached. each face must be composed of headers, which must extend
The height of empirically designed shear walls is not at least 3 in. (76 mm) into the backing. The distance between
permitted to exceed 35 ft (10.7 m). The minimum nominal adjacent full-length headers may not exceed 24 in. (610 mm)
thickness of shear walls is 8 in. (203 mm), except under the in either the horizontal or vertical direction. In walls where
2003 IBC, which allows shear walls of one-story buildings a single header does not extend through the wall, headers
to have a minimum thickness of 6 in. (152 mm). from opposite sides must overlap at least 3 in. (76 mm), or
headers from opposite sides must be covered with another
Bonding of Multiwythe Walls header course which overlaps the header below by at least
Wythes of multiwythe masonry walls are required to 3 in. (76 mm).
be bonded together. Bonding can be achieved using masonry
headers, metal wall ties, or prefabricated joint reinforcement, Bonding of hollow unit walls with masonry headers.
as illustrated in Figure 5. Various empirical requirements for Where two or more hollow units are used to make up the thick-
each of these bonding methods are given below. ness of a wall, the stretcher courses must be bonded at vertical
intervals not exceeding 34 in. (864 mm) by lapping at least
Bonding of solid unit walls with masonry headers. 3 in. (76 mm) over the unit below, or by lapping at vertical
Where masonry headers are used to bond wythes of solid intervals not exceeding 17 in. (432 mm) with units that are at
masonry construction, at least 4 percent of the wall surface of least 50 percent greater in thickness than the units below.

Unit notched at
joist, solid or
filled at joist
location

Fill with concrete Solid or filled


masonry units concrete masonry
between joists unit, notched at
joist

1
2 in. (13 mm)
diameter anchor
at 6 ft (1.8 m)
max., or
equivalent,
embedded at least
Strap anchors at 6 ft. 15 in. (381 mm) A
(1.8 m) o.c. max. Weld or other approved
connection
Mesh or other
CMU with grout grout stop device
filled cores

Mesh or other Roof diaphragmsC


grout stop device
Wood floor joistsB

Notes:
A
As an alternative, the bolts can be hooked or welded to at least 0.2 in.2 (No. 4, M#13) of bond beam reinforcement placed
at least 6 in. (152 mm) from the top of the wall.
B
Wood joists anchored parallel to masonry walls require metal straps which extend over or under the joists and which are
secured to at least three joists. Anchors must be spaced at a maximum of 6 ft (1.8 m). Blocking is required between joists
at each strap anchor.
C
Steel floor joists which bear on and are anchored to masonry walls require 3/8 in. (9.5 mm) reinforcing bars spaced a maxi-
mum of 6 ft (1.8 m) on center, or equivalent anchorage. Where joists are parallel to the wall, anchors must be located at
joist cross bridging.
D
Refer to TEK 5-7A, Floor and Roof Connections to Concrete Masonry Walls (ref. 10) for other types of connections. Note
that elements such as flashing, weeps, insulation, etc. are not shown for clarity.
Figure 3—Empirical Anchorage Requirements for Floor and Roof DiaphragmsD
Bonding with metal wall ties (other than adjustable ties).
Lx Wire size W2.8 (MW18) wall ties, or metal wire of equivalent
x1 x2 x3 stiffness, may be used to bond wythes. Each 41/2 ft2 (0.42 m2)
of wall surface must have at least one tie. Ties must be spaced
y1 y3 a maximum of 24 in. (610 mm) vertically and 36 in. (914 mm)
8 in. (203 mm) min.
masonry thickness A horizontally. Hollow masonry walls must use rectangular wall
ties for bonding. In other walls, ends of ties must be bent to
90o angles to provide hooks no less than 2 in. (51 mm) long.
Ly Additional bonding ties are required at all openings, and must
Do not include wall sections
with openings or any element be spaced a maximum of 3 ft (914 mm) apart around the
whose length is less than one- perimeter and located within 12 in. (305 mm) of the opening.
y2 half its height. y4
Note that wall ties may not include drips, and that corrugated
ties may not be used.
x4 x5 x6
Bonding with adjustable ties.
In x-direction, Adjustable ties must be spaced such that there is one tie for
cumulative shear wall length = lx1 + lx2 + ... + lxn each 1.77 ft2 (0.164 m2) of wall area, with maximum horizontal
In y-direction, and vertical spacings of 16 in. (406 mm). The ties must have a
cumulative shear wall length = ly1 + ly2 + ... + lyn maximum clearance between connecting parts of 1/16 in. (1.6
In each direction, cumulative shear wall length must exceed mm), and, when pintle legs are used, at least two legs with a
the larger of 0.4Lx and 0.4Ly B minimum wire size of W2.8 (MW18). The bed joints of the
A
Note that the 2003 IBC allows shear walls of one-story two wythes may have a maximum vertical offset of no more
buildings to have a minimum thickness of 6 in. (152 mm). than 11/4 in. (32 mm). (See Reference 9 for an illustration of
B
Note that in the 2008 Building Code Requirements for Ma- these requirements.)
sonry Structures, this criteria is: In each direction, cumulative
shear wall length must exceed the larger of 0.2Lx and 0.2Ly Bonding with prefabricated joint reinforcement.
Where adjacent wythes of masonry are bonded with
Figure 4—Empirically Designed Shear Wall
prefabricated joint reinforcement, there must be at least one cross
Requirements
wire serving as a tie for each 22/3 ft2 (0.25 m2) of wall area. The
joint reinforcement must be spaced 24 in. (610 mm) or closer
Table 5—Shear Wall Diaphragm Length-to-Width
vertically. Cross wires on prefabricated joint reinforcement must
Ratios (ref. 1)
be at least wire size W1.7 (MW11) and shall be without drips.
The longitudinal wires must be embedded in the mortar.
Floor or roof Maximum length-to-width
diaphragm construction ratio of diaphragm panel Change in Wall Thickness
Cast-in-place concrete 5:1 Whenever wall thickness is decreased, at least one course of
Precast concrete 4:1 solid masonry, or special units or other construction, must be
Metal deck with concrete fill 3:1 placed under the thinner section to ensure load transfer to the
Metal deck with no fill 2:1 thicker section below.
Wood diaphragm 2:1
Miscellaneous Empirical Requirements
Following are additional empirical requirements in Build-
Header ing Code Requirements for Masonry Structures. Although not
Bonding with
masonry header included explicitly in IBC Section 2109, the IBC includes a
direct reference to Building Code Requirements for Masonry
Structures.

Chases and Recesses


Masonry directly above chases or recesses wider than 12 in.
(305 mm) must be supported on lintels.

Lintels
Lintels are designed as reinforced beams, using either the
allowable stress design or the strength design provisions of
Examples of bonding with metal wall ties
Building Code Requirements for Masonry Structures. End
Figure 5—Types of Bonding bearing must be at least 4 in. (102 mm), although 8 in. (203
mm) is typical.
d
a + 1 in. (25 mm), max. Where:
a = air space thickness
d = nominal unit thick-
Pc ≤ t 2 Pc ≤ d 2 ness (specified
p ≤ the lesser of h 2 and d 3 p ≤ the lesser of h 2 and d 3
thickness plus the
thickness of one
mortar joint)
h p
h = nominal unit height
Pc
(specified height
plus the thickness
h
of one mortar joint)
p
Pc = allowable total hor-
p izontal projection
Pc of corbelling
p = allowable projec-
tion of each unit
t a
Pc t = nominal wall thick-
ness
Solid walls Walls with air space

Note: Ties and/or headers not shown for clarity.

Figure 6—Prescriptive Requirements for Corbelling

Support on Wood
Empirically designed masonry is not permitted to
be supported by wood girders or other forms of
wood construction, due to expected deformations
in wood from deflection and moisture, causing
Compressible filler
distress in the masonry, and due to potential safety
in open joint, 1 2 to
implications in the event of fire. 1 in. (13 to 25 mm)

Corbelling Clip angles at 4


When corbels are not designed using allowable ft (1.2 m) o.c.,
attached to
stress design or strength design, they may be
concrete deck,
detailed using the empirical requirements shown but not to wall
in Figure 6. Only solid or solidly grouted masonry
units may be used for corbelling.

EMPIRICALLY DESIGNED
PARTITION WALLS Figure 7—Example of Support for Empirically
Designed Masonry Partition Wall
In many cases, the building structure is de-
signed using traditional engineered methods, such
as strength design or allowable stress design, but the interior adequate load transfer between the building structure and the
nonloadbearing masonry walls are empirically designed. In loadbearing masonry wall.
these cases, the partition walls are supported according to the Figure 7 shows an example of such a support, using clip
provisions listed in Tables 2 and 3, but it is important that the angles. C channels or adjustable anchors could be used as well.
support conditions provide isolation between the partition walls The gap at the top of the wall should be between 1/2 and 1 in.
and the building's structural elements to prevent the building (13 and 25 mm), or as required to accommodate the anticipated
loads from being transferred into the partition. The anchor, or deflection. The gap is filled with compressible filler, mineral
other support, must provide the required lateral support for the wool or a fire-rated material, if required. Fire walls may also
partition wall while also allowing for differential movement. require a sealant to be applied at the bottom of the clip angles.
This is in contrast to the "Anchorage for Lateral Support" This joint should not be filled with mortar, as it may allow load
section, which details anchorage requirements to help ensure transfer between the structure and the partition wall.
REFERENCES
1. International Building Code. International Code Council, 2003 and 2006.
2. Allowable Stress Design of Concrete Masonry Foundation Walls, TEK 15-1B. National Concrete Masonry Association,
2001.
3. Minimum Design Loads for Buildings and Other Structures, ASCE 7-02. New York, NY: American Society of Civil Engineers,
2002.
4. Minimum Design Loads for Buildings and Other Structures, ASCE 7-05. New York, NY: American Society of Civil Engineers,
2005.
5. Masonry Designer's Guide, 5th Edition. Council for Masonry Research and The Masonry Society, 2007.
6. Building Code Requirements for Masonry Structures, ACI 530-08/ASCE 5-08/TMS 402-08. Reported by the Masonry Stan-
dards Joint Committee, 2008.
7. Standard Specification for Loadbearing Concrete Masonry Units, ASTM C 90-06. ASTM International, Inc., 2006.
8. Building Code Requirements for Masonry Structures, ACI 530/ASCE 5/TMS 402. Reported by the Masonry Standards Joint
Committee, 2002 and 2005.
9. Anchors and Ties for Masonry, TEK 12-1A. National Concrete Masonry Association, 2008.
10. Floor and Roof Connections to Concrete Masonry Walls, TEK 5-7A. National Concrete Masonry Association, 2001.

NCMA and the companies disseminating this technical information disclaim any and all responsibility and liability for the
accuracy and the application of the information contained in this publication.

NATIONAL CONCRETE MASONRY ASSOCIATION To order a complete TEK Manual or TEK Index,
13750 Sunrise Valley Drive, Herndon, Virginia 20171 contact NCMA Publications (703) 713-1900
www.ncma.org