ASHRAE62.1 and FAQs
ASHRAE62.1 and FAQs
1: Ventilation for
Acceptable Indoor Air Quality
Ventilation refers to the introduction of an adequate amount of fresh
outdoor air to dilute contaminants that are generated inside the building
(by people, equipment, processes, or furnishings). This requires the
removal of an equal quantity of air from the building.
Applying ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality 1
These values are calculated
for each room in TRACE when
the Apply ASHRAE Std62-1-
2004/2007 field is set to
“Yes” on the Create Rooms -
Airflows tab.
For this example, the required ventilation airflow has been calculated for
each zone to be:
2 Applying ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality
Calculate the zone outdoor airflow
The next step is to calculate the zone outdoor airflow (Voz), which is the
outdoor airflow rate that must be provided to the ventilation zone by the
supply air distribution system. The zone outdoor airflow accounts for the
zone air distribution effectiveness (Ez) found in Table 6-2.
Voz = Vbz / Ez
where
In this example, a VAV system supplies cool air to each zone from the
ceiling, so the zone air distribution effectiveness is 1.0. As a result,
Voz = Vbz.
Applying ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality 3
2 In the System Ventilation
field, select either ASHRAE
Std 62.1 2004/2007 or
ASHRAE Std 62.1 2004/
2007 w/Vent Reset.
Begin by determining the uncorrected outdoor air intake flow (Vou) for the
system by totaling the breathing zone outdoor airflow requirements from
all of the spaces served by a common system using Equation 6-6.
4 Applying ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality
For this example, a diversity ratio of 1.0 is assumed and the uncorrected
outdoor air intake (Vou) is calculated as follows:
To determine what that percentage needs to be, the primary outdoor air
fraction (Zp) must be calculated for each zone.
Applying ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality 5
In TRACE 700, Vpz - min is set in
the VAV Minimum Rate field
on the Create Rooms –
Airflows tab. For most
systems the default value is
30%.
Note: In TRACE 700, Vpz - min is
also equal to the VAV minimum
heating airflow.
In the figure below, the minimum zone primary airflows have been added
to the example and the primary outdoor air fraction has been calculated for
each breathing zone:
6 Applying ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality
In this example, 50% of the system primary air must be outdoor air to
properly ventilate the critical zone. This means that all of the zones will
receive 50% outdoor air and any zone with a lower primary outdoor air
fraction than the critical zone will be overventilated. This overventilation
results in “unused” outdoor air that is recirculated in the return air coming
from these zones and can be used to offset the ventilation requirements
of the system.
TRACE 700 determines the system ventilation efficiency using both methods
and then selects the higher of the two efficiencies.
Note: For values of Max (Zp) between 0.15 and 0.55, the corresponding
value of Ev may be determined by interpolating the values in Table 6-3.
For the VAV system in this example, the Ev for a primary outdoor air
fraction of 50% would be 0.65 (65%).
Table 6-3 may result in unrealistically low values of Ev for systems with
higher average outdoor air fraction values, and the use of Appendix A may
yield more practical results.
Applying ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality 7
Method 2: Appendix A
Section A1.2.1 from Appendix A states:
“For ‘single supply’ systems, wherein all of the air supplied to each
ventilation zone is a mixture of outdoor air and system-level recirculated
air, zone ventilation efficiency (Evz) shall be determined in accordance with
Equation A-2.”
Evz = 1 + Xs – Zd
where
Evz = efficiency with which a system distributes outdoor air from the
intake to an individual breathing zone
Xs = average outdoor air fraction for the ventilation system
Zd = the percentage of outdoor air in the air discharged to the zone
The discharge outdoor air fraction (Zd) is calculated for each zone using the
equation:
Zd = Voz / Vdz
where
where
Vdz = the primary zone airflow (Vpz) + any locally recirculated airflow
For this example, it is assumed that all of the VAV boxes are shutoff boxes
and as a result: Vdz = Vpz and Zd = Zp for all of the zones.
In TRACE 700,
8 Applying ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality
Applying the default VAV Minimum Rate of 30% to all three zones, the
resulting primary zone airflows will be:
Xs = Vou/Vps
After the ventilation efficiency (Evz) has been calculated for all of the zones,
the system ventilation efficiency (Ev) is determined to be the smallest zone
ventilation efficiency per Equation A-3:
Ev = minimum (Evz)
For this example, Ev = 0.5913.
Applying ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality 9
Find outdoor-air intake flow Vot
The final step is to calculate the outdoor air intake flow (Vot) by dividing the
uncorrected outdoor air intake (Vou) by the highest system ventilation
efficiency (Ev):
10 Applying ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality
Applying ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality 11
Frequently Asked Questions
What’s the difference between ASHRAE Std 62.1 2004/2007
and ASHRAE Std 62.1 2004/2007 w/Vent Reset?
These two options are available from the System Ventilation Flag field
on the Create Systems - Advanced screen (accessed from the Create
Systems screen by clicking the Advanced button).
When ASHRAE Std 62.1 2004/2007 is selected, the outdoor air intake
flow (Vot) is maintained at a constant flow rate established at design
conditions while TRACE™ 700 performs the building simulation
calculations.
The graph below shows the difference in the ventilation airflow (cfm) for a
typical weekday in January without ventilation reset (alt 1) and with
ventilation reset (alt 2).
3
No vent reset
2.5
Vent reset
ventilation airflow, cfm
1.5
0.5
0
2 4 6 8 10 12 14 16 18 20 22 24
time of day
This condition occurs if at any time the zone outdoor airflow (Voz) is equal
to the lowest zone primary airflow value expected at the design condition
analyzed (Vpz). The System Checksums report below shows an example of
this.
Under these conditions, the resultant primary outdoor air fraction is now
equal to 1.0 (i.e., the critical zone requires 100% outdoor air). This excerpt
from a TRACE 700 ASHRAE Standard 62.1 report shows a room in this
condition.
To prevent this situation from occurring, you can set a maximum outdoor
air fraction limit in TRACE. This value can be entered in the ASHRAE
Std62 Max Vent (Z) Ratio Allowed field on the Create Systems-
Advanced screen.
In the following example, the ASHRAE Std62 Max Vent (Z) Ratio
Allowed value has been set to 60%. Zones 1 and 3 are unaffected
because their respective calculated Z ratios are both less than 60%. Zone
2, however, is affected because its calculated Z ratio of 1.0 (100%) is
greater than the imposed limit of 0.60 (60%). As a result, the zone primary
airflow (Vpz) for Zone 2 must now be calculated.
The remaining calculations for determining the outdoor air intake flow (Vot)
are unchanged by the limited ventilation ratio.
For this example, it is assumed that all of the VAV boxes are shutoff boxes.
As a result, Vdz = Vpz and Zd = Zp for all of the zones.
Xs = Vou/Vps
Ev = minimum (Evz)
For this example, Ev = 0.4737.
Because the maximum ventilation ratio Zp (0.60) is greater than 0.55, Table
6-3 cannot be used to determine the system ventilation efficiency for this
example so: Ev = 0.4737.
The final step is to calculate the outdoor air intake flow (Vot) by dividing the
uncorrected outdoor air intake (Vou) by the highest system ventilation
efficiency (Ev):
What is the “right” value for the Maximum Vent (Z) Ratio
Allowed field?
It is left to your discretion to define the Max Vent (Z) Ratio Allowed
value. While reducing the ventilation fraction decreases the outdoor air
intake flow, it increases the fan energy because of the higher system
airflow. It also increases the amount of VAV reheat required (if present) to
temper the air delivered to the affected zones, or it may lead to
overcooling in the affected zones without reheat.