Linear Diffuser
Linear Diffuser
Contents
Page No.
Model
49-240 Model
48LL1
Model
49-280
B Model
48LL2
Model
49-480
LINEAR DIFFUSERS AND BAR GRILLES
Supply Models:
5050 1/2" (13) Slot
5075 3/4" (19) Slot
5010 1" (25) Slot
Return Models:
5050R 1/2" (13) Slot
5075R 3/4" (19) Slot
Model 5075
B
5010R 1" (25) Slot
The Series 5000 Linear Slot Ceiling Diffuser has been specially designed to provide both the unobtrusive appearance
required for architectural excellence, and the full 180° pattern controller adjustment at minimum NC levels required for high
Standard Frame
D
D = Duct Size
S = Slot Width
W = Overall Face Width 1 7/8"
(48)
Standard Frames are the most commonly
specified and readily available from stock.
3/4" S 1 1/8"
(19) (29)
5/32"
W = D + 1 1/8" (29) (4)
Dimensions are in inches (mm). COUNTERSUNK SCREW HOLES FOR #8 SCREWS, 3/8" (10) FROM EDGE
B
Standard Frame Standard Frame
Type C Type D
• Flange Frame • Flange Frame, Narrow Margin
LINEAR DIFFUSERS AND BAR GRILLES
3 1/2" (89)
3/16" (5) 3/16" (5)
TO TO
3/4" (19)
1 7/8" (48)
1 7/8" (48)
3/4" (19)
Type E Type F
• Flush Frame and Sub-Frame • Flange Frame and Sub-Frame
• Concealed Mounting • Concealed Mounting
D D
3 1/4" (83)
3 1/4" (83)
1 7/8" (48)
1 7/8" (48)
Type G Type H
• Flush Frame with Plaster and Tile Sub-Frame • Flange Frame with Plaster and Tile Sub-Frame
• Concealed Mounting • Concealed Mounting
D + 1 1/4" (32) D + 1 1/4" (32)
D + 1/2 " (13) D + 1/2" (13)
D D
3 1/4" (83)
3 1/4" (83)
1 7/8" (48)
1 7/8" (48)
1"
1" (25)
(25)
B
Type M Type N
• Flush Frame • Spline Frame Ceiling
• Duct Mounting • Concealed Mounting
3 1/4" (83)
1 7/8" (48)
1 7/8" (48)
11/32"
1 1/16" (27)
(9)
Frame Sub-frame
Dimensions are in inches (mm).
No. 5050 5075 5010 No. 5050 5075 5010 No. 5050 5075 5010
Frame Frame Frame
of 5050R 5075R 5010R of 5050R 5075R 5010R of 5050R 5075R 5010R
Type Type Type
B Slots S=1/2 S=3/4 S=1 Slots S=1/2 S=3/4 S=1 Slots S=1/2 S=3/4 S=1
1 2 2 1/4 2 1/2 1 2 1/2 2 3/4 3 1 1 3/8 1 5/8 1 7/8
2 3 1/4 3 3/4 4 1/4 2 3 3/4 4 1/4 4 3/4 2 2 5/8 3 1/8 3 5/8
3 4 1/2 5 1/4 6 3 5 5 3/4 6 1/2 3 3 7/8 4 5/8 5 3/8
F 4 5 3/4 6 3/4 7 3/4 4 6 1/4 7 1/4 8 1/4 4 5 1/8 6 1/8 7 1/8
5 7 8 1/4 9 1/2 5 7 1/2 8 3/4 10 5 6 3/8 7 5/8 8 7/8
LINEAR DIFFUSERS AND BAR GRILLES
No. 5050 5075 5010 No. 5050 5075 5010 No. 5050 5075 5010
Frame Frame Frame
of 5050R 5075R 5010R of 5050R 5075R 5010R of 5050R 5075R 5010R
Type Type Type
Slots S=13 S=19 S=25 Slots S=13 S=19 S=25 Slots S=13 S=19 S=25
1 51 57 64 1 64 70 76 1 35 41 48
2 83 95 108 2 95 108 121 2 67 79 92
3 115 133 152 3 127 146 165 3 98 117 137
F 4 146 171 197 4 159 184 210 4 130 156 181
5 178 210 241 5 191 222 254 5 162 194 225
H 6 210 248 286
G 6 222 260 298
M 6 194 232 270
N 7 241 286 330 7 254 298 343 7 225 270 314
8 273 324 375 8 286 337 387 8 257 308 359
9 304 362 419 9 318 375 432 9 289 346 400
10 337 400 464 10 349 413 476 10 321 384 448
Frame types A, B,
C, D, F, G and H only.
Field attachable.
Suitable for stocking representatives.
B
O - OPEN END C - FLAT END CAP
L D
E E
D L
Frame
M M F F M O M C O O O C C C
Type F C
F O
E L E L E L ✝ E L ✝ E L E L E L
A, B D-1/2 (13) D+1 (25) D-1/2 (13) D+1 1/2 (38) D-1/4 (6) D+1/2 (13) D-3/16 (5) D+9/16 (14) D D D-1/16 (2) D-1/16 (2) D-1/8 (3) D-1/8 (3)
C D-1/2 (13) D+1 (25) D-1/2 (13) D+1 1/2 (38) D-1/4 (6) D+1/2 (13) D-3/16 (5) D+9/16 (14) D D D-1/16 (2) D-1/16 (2) D-1/8 (3) D-1/8 (3)
D D-1/2 (13) D+1/2 (13) D-1/2 (13) D+1 (25) D-1/4 (6) D+1/4 (6) D-3/16 (5) D+7/16 11) D D D-1/16 (2) D-1/16 (2) D-1/8 (3) D-1/8 (3)
E D-7/8 (22) D – – D-7/16 (11) D D-3/8 (10) D+1/16 (2) D D D-1/16 (2) D-1/16 (2) D-1/8 (3) D-1/8 (3)
F, H D-3/4 (19) D+3/4 (19) D-3/4 (19) D+3/4 (19) D-3/8 (10) D+3/8 (10) D-5/16 (8) D+7/16 (11) D D D-1/16 (2) D-1/16 (2) D-1/8 (3) D-1/8 (3)
G D-1/8 (3) D D-1/8 (3) D D-9/16 (14) D D-1/2 (13) D+1/16 (2) D D D-1/16 (2) D-1/16 (2) D-1/8 (3) D-1/8 (3)
M*, N* D-1/16 (2) D-1/16 (2) – – D-1/32 (1) D-1/32 (1) D-1/16 (2) D-1/16 (2) D D D-1/16 (2) D-1/16 (2) D-1/8 (3) D-1/8 (3)
✝ Configurations FO and FC: Add 1/4" (6) for frame types A, B, C, D, F, G and H. Dimensions are in inches (mm).
Not available on frame types E, M and N.
* These types have a flangeless mitered end cap which is the same extrusion profile as the frame.
1 3/4" (44)
Also available in custom lengths for special applications and in multiple
section assemblies for continuous paired T-Bar ceilings.
*Type CC Flat Endcaps are not recommended for use with 9/16" (14) flat 15/16" 3/4" 7/8"
S
face T-bar. (24) (19) (22)
CM - 5/8" (16)
B
Plenums W W 1 1/4"
(32)
NOMINAL LENGTH
Uninsulated Models:
5350 • 1/2" (13) Slot
D - 1/8" (3)
5375 • 3/4" (19) Slot
BO Blank-Offs
• Cold-Rolled Steel
• Fits over Neck Shipped in 6' (1829) lengths
• Black Finish to be field-cut.
FIELD
ASSEMBLED
CORNER
END SUB-FRAME
TEMPORARY
GAUGE
MITERED
B ALIGNMENT
CORNER
SECTION
STRIPS (INACTIVE)
SPRING
CLIP
LINEAR DIFFUSERS AND BAR GRILLES
FACTORY BLANK-OFFS:
INSTALLED OPTIONAL FOR
SPACER INACTIVE SECTIONS.
BLADE ALIGNMENT SUPPLIED AS
TYPE C
TYPE M SUPPORT STRIPS STANDARD ON
FLAT
MITERED END CAP BAR MITERED CORNERS
END (OPTIONAL) WHICH ARE
CAP RENDERED INACTIVE.
(STANDARD)
PATTERN
CONTROLLERS
HEMMED
DUCT
CEILING
• Far and away the most popular type of installation. • Sub-frame should be attached to inside of duct and/or a
Simple and quick. framed ceiling opening as deemed necessary.
• Diffuser simply pushes up into duct until the legs of • Factory supplied mounting straps locate into an extrusion
the factory supplied mounting straps locate into the
hems of the duct.
slot in the sub-frame. Installation of diffuser is similar to
the hemmed duct method shown to the left.
B
• Factory supplied levelling screws then draw the
diffuser up until it is tight and snug with the ceiling.
• Duct should be fabricated with a 1/2" (13) hem on
both long sides and opened approximately 1/8" (3).
L= L=
OVERALL OVERALL
LENGTH PLAN VIEW LENGTH
The above example illustrates a typical 3 slot installation Note: It is extremely difficult to achieve a perfect installation
with two 90° mitered corner sections. where compound miters are involved, such as above, when
➀ Type 'CO' End Cap configuration. all sections are ordered from the factory fabricated to suit
② and ⑥ 'MC' Mitered Corner Section. finished duct dimensions. This is due to field tolerance
③, ④ and ➄ Type 'OO' End Cap configuration. variations which may prevent proper alignment and butting
➆ Type 'MO' End Cap configuration. together of individual sections due to insufficient material.
Each straight section, regardless of total duct length It is recommended that section ③, ④ or ➄ is ordered
may be ordered as a single section. oversize by 3" (76) and field cut to suit field conditions. 'OO'
Example: configuration lengths can be trimmed by up to 6" (152). 3"
(76) from each end.
➀ and ➆ Each section may be ordered as a single
item, regardless of total length.
③, ④ and ➄ One section may be ordered, regardless of
total length.
Multiple sections are sub-divided by the factory into
equal length sections at the factories' discretion.
MODEL ACCESSORIES
- Linear Slot Diffuser 50 - Angle Cut One End AC1
- Angle Cut Both Ends AC2
Notes:
1. Flanged end caps (FF) may be shipped loose upon request for field attachment and are intended for use with field cut
sections or for use by stocking representatives.
2. It is helpful to include a sketch for multiple sectioned units with mitered corners and angle cuts. Specify exact outside
length of duct run and angles.
3. For lay-in T-Bar installations, specify nominal T-Bar opening length.
4.*Blank-offs are supplied in 6' (1829) lengths, therefore, 'No. of Slots' is the only required variant that needs to be specified.
Performance Data
Supply • Continuous Pressurized Plenum.
Model 5050 • 1/2" (13) Slot
No. of Total H .005 .020 .041 .074 .120 .173 .230 .310
Slots Pressure V .003 .014 .027 .051 .083 .116 .158 .215
CFM per Ft. 5 10 15 20 25 30 35 40
H 1-1-6 3-6-12 6-10-14 8-12-18 10-14-18 12-14-20 12-14-20 14-16-24
1 Throw
V 2 6 9 11 12 13 14 15
NC — –– 17 21 26 31 35 38
CFM per Ft. 10 20 30 40 50 60 70 80
H 1-3-9 4-9-16 6-12-20 10-16-22 14-18-24 16-20-28 18-20-30 18-22-32
2 Throw
V 3 7 12 14 15 17 18 20
NC — 15 20 24 28 34 38 41
CFM per Ft. 15 30 45 60 75 90 105 120
H 2-4-10 6-12-20 10-16-24 14-20-28 18-20-30 20-24-38 20-24-40 22-28-44
3 Throw
V 4 10 15 18 21 22 25 23
NC — 16 21 26 31 36 40 43
B CFM per Ft. 20 40 60 80 100 120 140 160
H 3-5-12 8-12-22 12-18-28 16-22-32 20-24-40 22-28-44 24-30-48 26-32-52
4 Throw
V 6 11 16 20 22 24 26 29
NC — 17 22 27 32 37 41 44
CFM per Ft. 25 50 75 100 125 150 175 200
LINEAR DIFFUSERS AND BAR GRILLES
NC Correction Factors for Various Lengths Throw Correction Factors for Various Lengths
Length (ft.) 2 4 6 8 9 10 15 Length (ft.) 2 4 6 8 10 12
Supply -3 0 +2 +3 +4 +5 +8 Multiplier 0.70 1.0 1.25 1.40 1.55 1.70
Return 0 +3 +4 +6 +7 +8 + 10
1. Data is based upon pressurized sections 4 ft. long. For other lengths, 7. Data derived from tests conducted in
plenum application (non ducted) with use the correction factor table above. accordance with ANSI/ASHRAE
no plenum effect for pressure or sound. 5. NC (Noise criteria) values are based Standard 70-2006.
Plenums should be sized to achieve on 10 dB room absorption, re 10-12
equal velocity along the slot length. watts, for a 4 ft. section. For other Number Ak Factor per foot
Keep duct inlet velocities below 700 lengths, use the correction factor table of
fpm in order to maintain cataloged above. Slots Supply Return
performance. 1 .018 .033
6. Throw values are for a 1-way air
2. All pressures are in inches w.g.. pattern. For divided airflow, deduce the 2 .035 .066
3. Horizontal throws are given at airflow in each direction according to 3 .053 .099
150,100 and 50 fpm terminal velocities. the number of slots, with the total 4 .070 .132
Vertical throws are given at 50 fpm airflow apportioned between the slots. 5 .088 .165
terminal velocity. Both under isothermal Look up throw for the airflow in each 6 .105 .198
conditions. direction according to the number of 7 .123 .231
slots in that direction. 8 .140 .264
4. Throw data are based on active
B16 Previous View Home Contents Dimensions Specification Performance
LINEAR SLOT DIFFUSERS
Performance Data
Supply • Continuous Pressurized Plenum.
Model 5075 • 3/4" (19) Slot
No. of Total H .004 .017 .030 .055 .089 .123 .176 .256
Slots Pressure V .003 .012 .026 .042 .065 .092 .125 .174
CFM per Ft. 5 10 20 25 30 35 40 50
H 1-1-5 2-5-14 5-9-16 7-14-21 12-16-23 14-16-23 16-18-25 16-21-28
1 Throw
V 2 6 10 12 13 14 15 16
NC — — 16 21 26 30 33 38
CFM per Ft. 10 20 40 50 60 70 80 100
H 1-2-10 4-9-21 7-16-23 14-21-28 16-23-32 21-23-35 21-25-44 23-28-46
2 Throw
V 3 8 11 15 18 20 21 22
NC — — 19 24 29 33 36 41
CFM per Ft. 15 30 60 75 90 105 120 150
H 2-4-12 6-12-23 12-18-30 16-23-35 21-28-46 23-30-48 28-32-53 28-35-55
3 Throw
V 6 10 15 19 20 24 25 27
NC — — 21 26 31 35 38 43
CFM per Ft. 20 40 80 100 120 140 160 200 B
H 2-5-14 8-14-28 16-23-35 21-28-46 23-32-53 28-35-55 32-44-60 32-46-64
4 Throw
V 5 11 18 21 25 27 30 31
NC — — 22 27 32 36 39 44
CFM per Ft. 25 50 100 125 150 175 200 250
NC Correction Factors for Various Lengths Throw Correction Factors for Various Lengths
Length (ft.) 2 4 6 8 9 10 15 Length (ft.) 2 4 6 8 10 12
Supply -3 0 +2 +3 +4 +5 +8 Multiplier 0.70 1.0 1.25 1.40 1.55 1.70
Return 0 +3 +4 +6 +7 +8 + 10
1. Data is based upon pressurized sections 4 ft. long. For other lengths, 7. Data derived from tests conducted in
plenum application (non ducted) with use the correction factor table above. accordance with ANSI/ASHRAE
no plenum effect for pressure or sound. 5. NC (Noise criteria) values are based Standard 70-2006.
Plenums should be sized to achieve on 10 dB room absorption, re 10-12
equal velocity along the slot length. watts, for a 4 ft. section. For other Number Ak Factor per foot
Keep duct inlet velocities below 700 lengths, use the correction factor table of
fpm in order to maintain cataloged above. Slots Supply Return
performance. 1 .024 .039
6. Throw values are for a 1-way air
2. All pressures are in inches w.g.. pattern. For divided airflow, deduce the 2 .049 .078
3. Horizontal throws are given at airflow in each direction according to 3 .073 .117
150,100 and 50 fpm terminal velocities. the number of slots, with the total 4 .098 .156
Vertical throws are given at 50 fpm airflow apportioned between the slots. 5 .122 .195
terminal velocity. Both under isothermal Look up throw for the airflow in each 6 .146 .234
conditions. direction according to the number of 7 .171 .273
slots in that direction. 8 .195 .312
4. Throw data are based on active
Previous View Home Contents Dimensions Specification Performance B17
LINEAR SLOT DIFFUSERS
Performance Data
Supply • Continuous Pressurized Plenum.
Model 5010 • 1" (25) Slot
No. of Total H .004 .016 .036 .065 .098 .138 .192 .245
Slots Pressure V 002 .009 .024 .038 .057 .082 .113 .148
CFM per Ft. 10 15 25 30 40 50 55 65
H 1-4-10 3-6-13 8-13-18 10-16-21 13-16-23 16-18-26 18-18-26 18-21-29
1 Throw
V 2 8 12 13 15 16 17 18
NC — — 18 22 29 34 37 41
CFM per Ft. 20 30 50 60 80 100 110 130
2 H 3-7-18 5-10-21 13-18-26 16-21-31 18-23-39 21-26-42 23-34-44 26-39-47
Throw
V 4 10 16 19 20 21 23 25
NC — 10 21 25 32 37 40 44
CFM per Ft. 30 45 75 90 120 150 165 195
H 5-9-21 8-14-26 16-21-31 18-26-42 23-29-47 26-31-49 29-34-55 31-36-57
3 Throw
V 6 11 18 22 25 27 30 31
B NC
CFM per Ft.
—
40
—
60
23
100
27
120
34
160
39
200
42
220
46
260
H 8-10-26 12-19-31 18-26-42 21-29-47 26-39-55 29-42-57 31-44-62 34-47-68
4 Throw
V 7 13 21 26 29 30 34 36
NC — — 24 28 35 40 43 47
CFM per Ft. 50 75 125 150 200 250 275 325
LINEAR DIFFUSERS AND BAR GRILLES
NC Correction Factors for Various Lengths Throw Correction Factors for Various Lengths
Length (ft.) 2 4 6 8 9 10 15 Length (ft.) 2 4 6 8 10 12
Supply -3 0 +2 +3 +4 +5 +8 Multiplier 0.70 1.0 1.25 1.40 1.55 1.70
Return 0 +3 +4 +6 +7 +8 + 10
1. Data is based upon pressurized sections 4 ft. long. For other lengths, 7. Data derived from tests conducted in
plenum application (non ducted) with use the correction factor table above. accordance with ANSI/ASHRAE
no plenum effect for pressure or sound. 5. NC (Noise criteria) values are based Standard 70-2006.
Plenums should be sized to achieve on 10 dB room absorption, re 10-12
equal velocity along the slot length. watts, for a 4 ft. section. For other Number Ak Factor per foot
Keep duct inlet velocities below 700 lengths, use the correction factor table of
fpm in order to maintain cataloged above. Slots Supply Return
performance. 1 .030 .044
6. Throw values are for a 1-way air
2. All pressures are in inches w.g.. pattern. For divided airflow, deduce the 2 .060 .088
3. Horizontal throws are given at airflow in each direction according to 3 .090 .132
150,100 and 50 fpm terminal velocities. the number of slots, with the total 4 .121 .176
Vertical throws are given at 50 fpm airflow apportioned between the slots. 5 .151 .220
terminal velocity. Both under isothermal Look up throw for the airflow in each 6 .181 .264
conditions. direction according to the number of 7 .211 .308
slots in that direction. 8 .241 .352
4. Throw data are based on active
B18 Previous View Home Contents Dimensions Specification Performance
LINEAR SLOT DIFFUSERS
Performance Data
Model 5050R • 1/2" (13) Slot
Plenum Return
No. of
Slots SP .011 .024 .045 .070 .108 .184 .279 .421
CFM per Ft. 10 15 20 25 30 40 50 60
1
NC — — — 20 26 34 39 45
CFM per Ft. 20 30 40 50 60 80 100 120
2
NC — — — 23 28 37 42 48
CFM per Ft. 30 45 60 75 90 120 150 180
3
NC — — — 25 31 39 44 50
CFM per Ft. 40 60 80 100 120 160 200 240
4
NC — — 20 26 30 38 45 51
CFM per Ft. 50 75 100 125 150 200 250 300
5
NC — — 21 27 32 40 45 53
CFM per Ft. 60 90 120 150 180 240 300 360
6
NC — — 22 29 33 41 46 53
CFM per Ft. 70 105 140 175 210 280 350 420
7
NC — — 23 29 34 42 47 53
CFM per Ft. 80 120 160 200 240 320 400 480
8
NC — — 23 30 34 43 48 54 B
Model 5075R • 3/4" (19) Slot
No. of
Slots SP .006 .028 .065 .110 .170 .250 .350 .465
Standard Models:
5350(I) 1/2" (13) Slot
5375(I) 3/4" (19) Slot
5310(I) 1" (25) Slot
Modified Performance Models:
5350(I)MP 1/2" (13) Slot
5375(I)MP 3/4" (19) Slot
B 5310(I)MP 1" (25) Slot
Model Series 5300
• Suffix 'I' adds internal insulation
The Nailor Series 5300 Diffuser Plenums are designed specifically to fit the Series 5000 'Ice Tong' Linear Slot
LINEAR DIFFUSERS AND BAR GRILLES
Diffusers.
They have been designed for flexible duct connection with a model to suit each of the various frame/sub-frame 5000 Series
combinations available. For drywall ceiling mounted applications the plenums are installed separately. Unless there is
access to the ceiling space, the plenum is intended to be installed during the drywall installation. Most applications of this
type utilize concealed mounting straps on the 5000 Series. The plenums may be supplied with a hemmed leg into which
the mounting straps snap or they locate in extrusion slots on sub-frames as the linear is drawn up to the plenum from below
the ceiling.
The Series 5300 Plenums save on-site fabrication and field labor. When room lay-out changes occur, the plenums can be
simply relocated to satisfy the re-arrangement of air distribution requirements.
The Series 5300 Plenums maximize the Series 5000's performance. The airflow discharge maintains a horizontal pattern
that is close and tight to the ceiling throughout the full range of cataloged air volumes. Excellent for variable air volume
applications.
The Series 5300MP Modified Performance Plenums are fabricated in a similar manner to the Series 5300 with the addition
of internal sloping baffles for reduced throw and increased spread of the air pattern.
FEATURES:
• Standard nominal lengths are 20", • Easily installed with flexible duct. • ID Inlet dampers are available.
24", 30", 36", 48" and 60" (500, 600, • End caps can be folded up to allow • EX External Foil Back insulation.
750, 900, 1200 and 1500 mm). continuous runs with the plenums. Material: Corrosion-resistant steel.
• Widths available to fit Model Series Options:
5000 and 5000R with 1, 2, 3 or 4 • Optional internal insulation. Model
slots. Series 5300I and 5300IMP.
DIFFUSER
5300MP
INTEGRAL BAFFLES
REDUCE THROW ISOVEL
AND INCREASE Vt = 50 fpm
SPREAD FOR
IMPROVED COMFORT THROW
IN SHORT-THROW
APPLICATIONS.
5300
SPREAD
Dimensional Data
Model Series 5300 and 5300MP Plenums for Series 5000 and 5000R Linear Slot Diffusers
D - 1/8" (3)
11"
(279)
1 1/2" (38)
Frame Types:
1/4" (6)
Frame Types:
OPTIONAL 5300MP OPTIONAL INTERNAL
INSULATION
B
MODIFIED PLENUM
C, D, N A, B, E, F, FL, G, H, M and T
Nominal Length (N) Standard Nominal Inlets (D) NOMINAL LENGTH - 3/8" (10)
inches mm inches mm EXCEPT FRAME T WHICH IS
NOM. - 1" (25)
Plenum Width (W) For Various Frame Types NOMINAL LENGTH - 3/8" (10)
No.
Model of Imperial Units (inches) Metric Units (mm)
Slots A,B,FL,M,T C,D,F,H,N E G A,B,FL,M,T C,D,F,H,N E G
5350 1 1/2 2 2 1/4 2 1/2 38 51 57 64
5375 1 1 3/4 2 1/4 2 1/2 2 3/4 44 57 64 70
5310 2 2 1/2 2 3/4 3 51 64 70 76
5350 2 3/4 3 1/4 3 1/2 3 3/4 70 83 89 95 NOMINAL LENGTH + 1/8" (3)
5375 2 3 1/4 3 3/4 4 4 1/4 83 95 102 108 OPEN END (O)
5310 3 3/4 4 1/4 4 1/2 4 3/4 95 108 114 121
5350 4 4 1/2 4 3/4 5 102 114 114 127
5375 3 4 3/4 5 1/4 5 1/2 5 3/4 121 133 140 146 NOMINAL LENGTH - 3/8" (10)
5310 5 1/2 6 6 1/4 6 1/2 140 152 159 165
5350 5 1/4 5 3/4 6 6 1/4 133 146 152 159
5375 4 6 1/4 6 3/4 7 7 1/4 159 171 178 184
5310 7 1/4 7 3/4 8 8 1/4 184 197 203 210
PLENUM END
CAP CAN BE TURNED UP
CONTINUOUS RUN
Notes:
1. Plenums are shipped loose as standard for field installation.
2. Plenums for frame/sub-frame types A, B, E, F, G, H, M, T and FL are for direct attachment to diffuser neck or sub-frame.
3. Plenums for frame types (C, D and N) are hemmed for field attachment by use of concealed mounting straps.
4. End caps of plenums can be turned up for use on continuous runs.
5. For lay-in T-Bar installations, specify nominal T-Bar opening length.
SUGGESTED SPECIFICATION:
Models 5310, 5375, 5350
Specification Text File
Furnish and install Nailor Model (select one) 5310/5310I (1" (25) slot), 5375/5375I (3/4" (19) slot), or 5350/5350I (1/2" (13)
slot) Plenums for Linear Slot Diffusers of the sizes and capacities as shown on the plans and air distribution schedules. The
plenums shall be manufactured from corrosion-resistant steel and shall include a side inlet for connection to the duct. The width
shall fit a 1, 2, 3, or 4 slot linear as specified and the length shall be in standard nominal lengths of 20", 24", 30", 36", 48" and
60" (508, 610, 762, 914, 1219 and 1524 mm). When continuous sections are required, the end caps shall be folded up for
uninterrupted airflow. Models 5310I, 5375I and 5350I shall have internal insulation.
The manufacturer shall provide published performance data for the linear slot diffuser plenums, which shall be tested in
accordance with ANSI/ASHRAE Standard 70 – 2006.
Specification Text File
Models 5310MP, 5375MP, 5350MP
Furnish and install Nailor Model (select one) 5310MP/5310MPI (1" (25) slot), 5375MP/5375MPI (3/4" (19) slot), or
5350MP/5350MPI (1/2" (13) slot) Modified Performance Plenums for Linear Slot Diffusers of the sizes and capacities as
shown on the plans and air distribution schedules. The plenums shall be manufactured from corrosion-resistant steel and shall
include a side inlet for connection to the duct. The width shall fit a 1, 2, 3, or 4 slot linear as specified and the length shall be
in standard nominal lengths of 20", 24", 30", 36", 48" and 60" (508, 610, 762, 914, 1219 and 1524 mm). When continuous
sections are required, the end caps shall be folded up for uninterrupted airflow. Models 5310MPI, 5375MPI and 5350MPI shall
have internal insulation.
The manufacturer shall provide published performance data for the linear slot diffuser plenums, which shall be tested in
accordance with ANSI/ASHRAE Standard 70 – 2006.
Performance Data
Model 5350(I) • 1/2" (13) Slot Width
1 Slot • 24" (610) Long
Airflow, CFM 20 30 40 50 60 70 80 90
6" TP .017 .038 .068 .107 .154 .209 .273 .346
Round NC — 17 23 29 33 37 41 43
Inlet T 1-1-6 1-3-7 3-6-9 4-7-9 5-7-10 6-7-10 7-8-12 7-9-13
Performance Data
Model 5350(I) • 1/2" (13) Slot Width
2 Slot • 24" (610) Long
Airflow, CFM 35 50 65 80 95 110 125 140
6" TP .021 .042 .072 .108 .153 .205 .265 .332
Round NC — 18 24 29 34 37 40 43
Inlet T 1-3-7 2-5-8 3-7-9 5-8-11 6-8-12 7-9-13 8-10-14 8-10-15
Airflow, CFM 100 120 140 160 180 200 220 240
10" TP .054 .077 .105 .137 .174 .214 .259 .309
Oval NC 18 22 26 29 32 35 37 39
Inlet T 3-6-12 4-8-13 5-9-14 6-10-15 7-11-16 8-13-17 9-13-19 10-14-20
LINEAR DIFFUSERS AND BAR GRILLES
Airflow, CFM 140 160 180 200 220 240 260 280
10" TP .065 .085 .107 .133 .161 .191 .224 .260
Oval NC 22 25 28 31 33 35 37 39
Inlet T 4-7-12 4-8-13 5-9-14 6-10-15 7-11-16 7-12-16 8-13-17 8-13-19
Performance Data
Model 5375(I) • 3/4" (19) Slot Width
1 Slot • 24" (610) Long
Airflow, CFM 20 30 40 50 60 70 80 90
6" TP .014 .031 .055 .085 .123 .168 .219 .277
Round NC — 15 21 27 31 35 38 41
Inlet T 1-2-4 1-3-6 2-4-7 3-6-9 5-7-10 6-7-10 7-8-11 7-9-12
Airflow, CFM 110 125 140 155 170 185 200 215
12" TP .077 .100 .125 .153 .184 .218 .255 .295
Oval NC 22 25 27 30 32 34 37 38
Inlet T 5-7-11 5-8-12 6-9-14 7-10-15 7-11-16 8-12-17 8-13-18 9-14-19
Performance Data
Model 5375(I) • 3/4" (19) Slot Width
2 Slot • 24" (610) Long
Airflow, CFM 50 65 80 95 110 125 140 155
6" TP .027 .045 .068 .096 .129 .167 .209 .257
Round NC 17 22 27 31 35 38 41 44
Inlet T 1-3-8 2-5-9 3-7-10 5-9-12 6-9-13 7-10-14 8-10-15 8-11-17
Round NC — 18 22 26 30 33 36 39
Inlet T 2-5-12 2-6-13 3-6-13 4-7-14 4-10-14 5-11-16 6-12-17 7-13-18
Airflow, CFM 100 120 140 160 180 200 220 240
10" TP .025 .036 .049 .064 .082 .101 .122 .145
Oval NC 16 20 24 27 30 33 36 38
Inlet T 2-6-13 3-6-13 4-7-14 4-10-14 5-11-16 6-12-17 7-13-18 8-14-20
Airflow, CFM 120 140 160 180 200 220 240 260
12" TP .038 .052 .068 .087 .107 .129 .154 .180
Oval NC 16 19 22 27 30 33 36 38
Inlet T 3-6-13 4-7-14 4-10-14 5-11-16 6-12-17 7-13-18 8-14-20 9-15-21
Airflow, CFM 160 180 200 220 240 260 280 300
10" TP .049 .063 .077 .093 .111 .130 .151 .174
Oval NC 23 26 28 31 33 35 37 39
Inlet T 3-7-14 5-8-15 5-8-16 6-9-17 6-10-18 7-11-19 8-13-20 8-15-21
Airflow, CFM 180 200 220 240 260 280 300 320
12" TP .044 .055 .066 .079 .092 .107 .123 .140
Oval NC 22 25 27 29 31 33 35 37
Inlet T 5-8-15 5-8-16 6-9-17 6-10-18 7-11-19 8-13-20 8-15-21 9-16-22
Performance Data
Model 5375(I) • 3/4" (19) Slot Width
3 Slot • 24" (610) Long
Airflow, CFM 60 80 100 120 140 160 180 200
6" TP .026 .047 .073 .106 .144 .188 .238 .294
Round NC 15 21 27 31 35 38 41 44
Inlet T 2-5-10 3-6-11 4-7-12 5-8-13 6-9-16 7-10-18 9-12-20 10-13-21
Airflow, CFM 100 120 140 160 180 200 220 240
10" TP .049 .071 .097 .126 .160 .198 .239 .284
Oval NC 20 24 28 31 34 36 38 40
Inlet T 4-7-12 5-8-13 6-9-16 7-10-18 9-12-20 10-13-21 10-14-22 11-14-23
Airflow, CFM 150 175 200 225 250 275 300 325
8" TP .057 .077 .101 .128 .157 .191 .227 .266
Airflow, CFM 175 200 225 250 275 300 325 350
10" TP .051 .067 .085 .104 .126 .150 .176 .204
Oval NC 23 26 28 31 33 35 37 39
Inlet T 5-9-16 6-10-17 6-11-18 7-12-19 7-13-20 8-14-21 9-15-23 10-16-25
Airflow, CFM 200 225 250 275 300 325 350 375
12" TP .041 .052 .064 .077 .092 .108 .125 .143
Oval NC 21 24 27 29 31 33 35 39
Inlet T 6-10-17 6-11-18 7-12-19 7-13-20 8-14-21 9-15-23 10-16-25 11-17-27
Airflow, CFM 210 240 270 300 330 360 390 420
10" TP .064 .084 .106 .131 .159 .189 .222 .257
Oval NC 24 27 29 32 34 36 38 40
Inlet T 5-10-16 6-11-18 7-12-19 7-13-20 8-14-21 8-15-22 9-16-23 9-17-24
Airflow, CFM 240 270 300 330 360 390 420 450
12" TP .049 .063 .077 .093 .111 .130 .151 .174
Oval NC 23 25 28 30 32 34 36 38
Inlet T 6-11-18 7-12-19 7-13-20 8-14-21 8-15-22 9-16-23 9-17-24 10-17-25
Performance Data
Model 5375(I) • 3/4" (19) Slot Width
4 Slot • 24" (610) Long
Airflow, CFM 75 100 125 150 175 200 225 250
6" TP .033 .058 .091 .131 .179 .233 .295 .365
Round NC 17 22 28 32 36 39 42 45
Inlet T 2-6-11 3-7-13 5-8-14 7-10-15 8-11-17 9-12-20 9-13-21 10-14-23
Airflow, CFM 100 125 150 175 200 225 250 275
8" TP .031 .049 .070 .095 .124 .157 .194 .235
Round NC 18 23 27 32 35 38 40 42
Inlet T 3-7-13 5-8-14 7-10-15 8-11-17 9-12-20 9-13-21 10-14-23 11-16-24
Airflow, CFM 125 150 175 200 225 250 275 300
10" TP .042 .060 .082 .107 .135 .167 .202 .240
Oval NC 22 25 28 32 35 37 39 41
Inlet T 5-8-14 7-10-15 8-11-17 9-12-20 9-13-21 10-14-23 11-16-24 13-19-26
Airflow, CFM 190 220 250 280 310 340 370 400
8" TP .071 .096 .124 .155 .190 .229 .271 .317
LINEAR DIFFUSERS AND BAR GRILLES
Round NC 23 26 29 32 34 37 39 41
Inlet T 4-10-16 5-12-18 6-13-20 7-14-21 9-15-22 10-16-24 11-17-26 12-17-28
Airflow, CFM 220 250 280 310 340 370 400 430
10" TP .064 .082 .103 .126 .152 .180 .210 .243
Oval NC 23 26 29 32 34 36 38 40
Inlet T 5-12-18 6-13-20 7-14-21 9-15-22 10-16-24 11-17-26 12-17-28 12-18-29
Airflow, CFM 250 280 310 340 370 400 430 460
12" TP .046 .057 .070 .084 .100 .117 .135 .155
Oval NC 22 25 28 30 32 34 36 38
Inlet T 6-13-20 7-14-21 9-15-22 10-16-24 11-17-26 12-17-28 12-18-29 13-19-30
Airflow, CFM 260 300 340 380 420 460 500 540
10" TP .077 .103 .132 .165 .201 .242 .285 .333
Oval NC 24 27 30 33 36 38 40 42
Inlet T 4-11-18 6-12-20 8-13-22 10-15-24 11-16-26 12-17-28 13-19-31 14-20-32
Airflow, CFM 300 340 380 420 460 500 540 580
12" TP .053 .068 .085 .104 .124 .147 .171 .198
Oval NC 23 26 29 31 34 36 38 40
Inlet T 6-12-20 8-13-22 10-15-24 11-16-26 12-17-28 13-19-31 14-20-32 14-21-34
CFM -cubic feet per minute airflow, deduce the airflow in each 4. Dash ( — ) in space indicates an NC
TP -total pressure - inches w.g. direction according to the number of level of less than 15.
slots, with the total airflow apportioned 5. Data derived from tests conducted in
T -throw in feet between the slots. Look up throw for the accordance with ANSI/ASHRAE
NC -Noise Criteria (values) based on airflow in each direction according to the Standard 70 – 2006.
10 dB room absorption, re 10 -12 number of slots in that direction.
watts. 3. Performance data is based upon the Ak Factor
Number per foot
Performance Notes: standard 5300 Series Model.
of Slots
The 5300MP Modified Performance Supply Return
1. Throws are given at 150, 100 and 50 Series reduces the tabulated throw 1 .024 .039
fpm terminal velocities under isothermal values by approximately 25%. 2 .049 .078
conditions. Horizontal spread values are 3 .073 .117
2. Cataloged throws are for a one-way approximately 150% of the horizontal 4 .098 .156
horizontal air pattern. For divided throw (T) projection values.
Performance Data
Model 5310(I) • 1" (25) Slot Width
1 Slot • 24" (610) Long
Airflow, CFM 20 30 40 50 60 70 80 90
6" TP .008 .018 .032 .049 .071 .097 .126 .160
Round NC — — 19 25 29 33 36 39
Inlet T 1-2-4 2-3-5 2-4-6 3-5-7 4-6-8 4-6-9 5-6-9 5-7-10
Airflow, CFM 110 125 140 155 170 185 200 215
12" TP .040 .052 .065 .080 .096 .114 .133 .153
Oval NC 19 22 24 28 30 32 34 36
Inlet T 2-4-9 3-5-10 3-5-11 4-6-11 5-7-12 6-8-13 6-9-14 7-10-15
Performance Data
Model 5310(I) • 1" (25) Slot Width
2 Slot • 24" (610) Long
Airflow, CFM 50 65 80 95 110 125 140 155
6" TP .020 .034 .052 .073 .098 .127 .159 .195
Round NC — 19 25 29 33 36 39 42
Inlet T 2-4-7 2-5-8 4-6-9 5-6-10 6-7-10 6-8-12 7-8-14 7-9-15
Airflow, CFM 120 140 160 180 200 220 240 260
8" TP .041 .056 .073 .092 .113 .137 .163 .192
LINEAR DIFFUSERS AND BAR GRILLES
Round NC 20 24 27 30 33 35 37 39
Inlet T 2-6-9 4-7-12 5-8-13 6-9-14 6-10-14 7-11-15 8-12-17 8-12-17
Airflow, CFM 140 160 180 200 220 240 260 280
10" TP .038 .049 .063 .077 .093 .111 .130 .151
Oval NC 21 24 27 30 32 34 36 38
Inlet T 4-7-12 5-8-13 6-9-14 6-10-14 7-11-15 8-12-17 8-12-17 9-13-19
Airflow, CFM 160 180 200 220 240 260 280 300
12" TP .032 .040 .049 .060 .071 .083 .097 .111
Oval NC 20 24 26 28 30 32 34 36
Inlet T 5-8-13 6-9-14 6-10-14 7-11-15 8-12-17 8-12-17 9-13-19 9-13-21
Airflow, CFM 180 200 220 240 260 280 300 320
10" TP .052 .064 .077 .092 .108 .125 .143 .163
Oval NC 24 26 28 31 33 35 37 39
Inlet T 4-7-12 6-9-14 7-9-15 7-10-16 8-11-17 8-12-18 9-13-19 9-14-21
Airflow, CFM 200 220 240 260 280 300 320 340
12" TP .045 .054 .064 .076 .088 .101 .115 .129
Oval NC 23 26 28 30 32 34 36 38
Inlet T 6-9-14 7-9-15 7-10-16 8-11-17 8-12-18 9-13-19 9-14-21 10-15-22
Performance Data
Model 5310(I) • 1" (25) Slot Width
3 Slot • 24" (610) Long
Airflow, CFM 60 80 100 120 140 160 180 200
6" TP .024 .043 .067 .096 .131 .171 .216 .267
Round NC — 19 24 28 32 35 38 41
Inlet T 2-4-8 3-5-9 4-6-10 5-7-11 6-8-12 7-9-14 7-10-15 8-10-16
Airflow, CFM 100 120 140 160 180 200 220 240
10" TP .029 .042 .057 .075 .095 .117 .141 .168
Oval NC 18 22 25 28 31 34 36 38
Inlet T 4-6-10 5-7-11 6-8-12 7-9-14 7-10-15 8-10-16 8-11-17 9-11-18
Airflow, CFM 150 175 200 225 250 275 300 325
8" TP .048 .065 .085 .108 .134 .162 .192 .226
Airflow, CFM 175 200 225 250 275 300 325 350
10" TP .045 .058 .074 .091 .110 .131 .154 .179
Oval NC 20 23 26 28 30 32 34 36
Inlet T 5-7-14 5-8-15 6-8-16 7-9-17 7-10-18 7-11-18 8-12-20 8-13-22
Airflow, CFM 200 225 250 275 300 325 350 375
12" TP .032 .040 .049 .060 .071 .083 .097 .111
Oval NC 19 22 25 27 29 31 33 35
Inlet T 5-8-15 6-8-16 7-9-17 7-10-18 7-11-18 8-12-20 8-13-22 9-14-23
Airflow, CFM 210 240 270 300 330 360 390 420
10" TP .054 .071 .090 .111 .134 .160 .188 .218
Oval NC 22 24 27 29 32 34 36 38
Inlet T 4-8-15 6-9-17 6-10-18 7-11-19 7-12-20 8-13-22 8-14-23 9-15-24
Airflow, CFM 240 270 300 330 360 390 420 450
12" TP .036 .046 .057 .069 .082 .096 .111 .128
Oval NC 21 23 25 28 30 32 34 36
Inlet T 6-9-17 6-10-18 7-11-19 7-12-20 8-13-22 8-14-23 9-15-24 10-16-26
Performance Data
Model 5310(I) • 1" (25) Slot Width
4 Slot • 24" (610) Long
Airflow, CFM 75 100 125 150 175 200 225 250
6" TP .030 .054 .084 .121 .164 .214 .271 .335
Round NC 16 20 25 29 33 36 39 41
Inlet T 3-5-10 4-7-11 6-8-12 6-8-13 7-9-15 7-10-16 8-11-18 8-11-19
Airflow, CFM 100 125 150 175 200 225 250 275
8" TP .027 .042 .060 .082 .107 .135 .167 .202
Round NC 17 21 25 29 33 35 37 40
Inlet T 4-7-11 6-8-12 6-8-13 7-9-15 7-10-16 8-11-18 8-11-19 9-13-21
Airflow, CFM 125 150 175 200 225 250 275 300
10" TP .029 .041 .056 .073 .093 .115 .139 .165
Oval NC 19 23 26 30 32 35 37 39
Inlet T 6-8-12 6-8-13 7-9-15 7-10-16 8-11-18 8-11-19 9-13-21 9-14-22
Airflow, CFM 190 220 250 280 310 340 370 400
8" TP .065 .087 .112 .140 .172 .207 .245 .287
LINEAR DIFFUSERS AND BAR GRILLES
Round NC 21 24 27 30 32 34 36 38
Inlet T 5-7-15 6-8-16 7-10-17 7-11-18 8-12-19 8-13-20 9-14-21 9-14-22
Airflow, CFM 220 250 280 310 340 370 400 430
10" TP .054 .070 .088 .108 .129 .153 .179 .207
Oval NC 21 24 27 29 31 33 35 37
Inlet T 6-8-16 7-10-17 7-11-18 8-12-19 8-13-20 9-14-21 9-14-22 10-15-24
Airflow, CFM 250 280 310 340 370 400 430 460
12" TP .039 .049 .061 .073 .086 .101 .116 .133
Oval NC 20 23 26 28 30 32 34 36
Inlet T 7-10-17 7-11-18 8-12-19 8-13-20 9-14-21 9-14-22 10-15-24 10-16-26
Airflow, CFM 260 300 340 380 420 460 500 540
10" TP .072 .095 .122 .153 .187 .224 .265 .309
Oval NC 22 25 28 31 33 35 37 39
Inlet T 6-8-15 7-10-17 8-12-19 9-13-21 9-14-22 10-15-23 10-16-24 11-18-26
Airflow, CFM 300 340 380 420 460 500 540 580
12" TP .043 .056 .070 .085 .102 .121 .141 .162
Oval NC 21 24 27 29 31 33 35 37
Inlet T 7-10-17 8-12-19 9-13-21 9-14-22 10-15-23 10-16-24 11-18-26 12-19-28
CFM -cubic feet per minute airflow, deduce the airflow in each throw (T) projection values.
TP -total pressure - inches w.g. direction according to the number of 4. Dash ( — ) in space indicates an NC
slots, with the total airflow apportioned level of less than 15.
T -throw in feet between the slots. Look up throw for the
5. Data derived from tests conducted in
NC -Noise Criteria (values) based on airflow in each direction according to the accordance with ANSI/ASHRAE
10 dB room absorption, re 10 -12 number of slots in that direction. Standard 70 – 2006.
watts. 3. Performance data is based upon the
Ak Factor
Performance Notes: standard 5300 Series Model. Number per foot
1. Throws are given at 150, 100 and 50 The 5300MP Modified Performance of Slots Supply Return
fpm terminal velocities under isothermal Series reduces the tabulated throw
1 .030 .051
conditions. values by approximately 25%.
2 .060 .104
Horizontal spread values are
2. Cataloged throws are for a one-way 3 .090 .155
approximately 150% of the horizontal
horizontal air pattern. For divided 4 .120 .206
Models:
1/2" (13) Bar Spacing
49-240 • 1/4" (6) Bars • 0° Deflection • Pencil-Proof
49-241 • 1/4" (6) Bars • 15° Deflection • Pencil-Proof
49-243 • 1/4" (6) Bars • 30° Deflection • Pencil-Proof
49-280 • 1/8" (3) Bars • 0° Deflection
49-281 • 1/8" (3) Bars • 15° Deflection
1/4" (6) Bar Spacing
49-480 • 1/8" (3) Bars • 0° Deflection
B
49-481 • 1/8" (3) Bars • 15° Deflection
• Suffix '- O' adds a steel damper
The Model Series 4900 Linear Bar Grilles have been specially designed to provide the precision quality appearance
required for architectural excellence with crisply sculptured styling, careful workmanship and effective air distribution.
The Series 4900 Linear Bar Grilles are designed for heating and cooling applications, supply and return.
The grilles are manufactured with precision mitered corners to maximize quality.
FEATURES: Options:
• Deflection bars are fixed and are • Ideal for continuous length • Heavy gauge steel opposed blade
parallel to the long dimension. applications. damper (add suffix '-O').
• Available in 7 core styles and a • Multiple sections are provided with • DV Rear directional control vanes.
variety of frame and sub-frame alignment strips on the frame and • MC Mitered Corner Sections.
options. sub-frame to provide superior,
• AD Access Doors.
• Diffusers are supplied in lengths of positive field alignment.
• BO Blank-offs.
up to 6 ft. (1829) in a single section. • End caps are staked and mitered for
a superior quality appearance. Material: Extruded Aluminum.
• Standard incremental units of length
are 1, 2, 3, 4, 5 and 6 ft. (305, 610, • Standard duty models are available Finish: Standard finish is AW
914, 1219, 1524 and 1829 mm). for ceiling, wall or sill installations. Appliance White baked enamel.
However, the 4900 Series is Heavy duty models are designed Optional finish is AL Aluminum baked
available in any nominal length to specifically for use in floor enamel.
suit engineering and architectural installations. Premium finishes are SA Satin (clear)
requirements. Anodized or BC Brushed and Clear
Coat lacquer.
Other finishes are available.
1 1/4" (32)
1 3/8" (35)
1 1/4" (32)
1 1/4" (32)
Standard
1 3/16" (30)
Frame
B
Type D Type E
• 1" (25) Border • 1/2" (13) Narrow Border
• Deep Stack (permits DV option)
OVERALL = D + 1 1/2" (38) OVERALL = D + 1/2" (13)
LINEAR DIFFUSERS AND BAR GRILLES
D = DUCT SIZE
D = DUCT SIZE
1/8"
1" (25)
(3) 1/8"
(3)
1 3/4" (44)
2" (51)
2" (51)
5/32"
(4)
5/32" 1/4" D = DUCT SIZE
(4) (6)
D = DUCT SIZE DUCT = DUCT SIZE
3/4" 3/4"
5/8" (19) 5/8" (19)
(16) (16)
SUPPORT BAR SUPPORT BAR
PENCIL PROOF
3/4" 3/4"
5/8" (19) 5/8" (19)
(16) (16)
SUPPORT BAR SUPPORT BAR
3/4" 3/4"
5/8" (19) 5/8" (19)
(16) (16)
SUPPORT BAR SUPPORT BAR
Dimensional Data
Overall Length and Width
CORE
CORE
N = NECK LENGTH
D = DUCT LENGTH N = NECK LENGTH
O = 0VERALL LENGTH D - 1/4" (6)
D = DUCT LENGTH
O = 0VERALL LENGTH
Type N O
A D - 1/2" (13) D + 1 1/2" (38)
B D - 1/2" (13) D + 1" (25)
B D D - 1/2" (13) D + 1 1/2" (38) Type N O
E D - 1/2" (13) D + 1/2" (13) C D - 1/2" (13) D + 2 1/8" (54)
F D D + 1 5/8" (41)
G D D Dimensions are for length or width.
H D D + 1 1/8" (29)
LINEAR DIFFUSERS AND BAR GRILLES
Cross-Bar Spacing
S S
Standard Core: S = 12" (305) maximum support bar spacing. Frame Types A, B, C, D and E.
Optional HC Heavy Duty Core: S = 8" (203) maximum.
Standard for floor models with frame types F, G, and H which also include secondary reinforcing support bars.
Dimensional Data
Typical Frame/Core Assemblies
Core with Frame Core with Frame & Sub-Frame
Fastenings
Type A • Countersunk Screw Holes Type B • Friction Spring Clip Type C • Concealed Mounting
For ceiling, side wall, sill or floor. For sill installations. For ceiling, side wall, sill or floor.
Frame Types Frame Types Frame Types
A, B, C, D, F. A, B, D, E, F, G, H. A, B, C, D, E.
Not recommended for use with
cores with 1/4" (6) bar spacing.
Dimensional Data
Mitered Corner Sections
49-240MC 49-281MC Factory welded with precision to match and align with the associated straight leg.
49-241MC 49-480MC Standard mitered corner section for floor, ceiling or wall is 90°. Other angles are
49-243MC 49-481MC available.
OUTSIDE
49-280MC
O
90° D'
Application Pattern
D
O
D'
INSIDE
B W
OVERALL LENGTH
DUCT LENGTH
D' D'
DUCT DUCT
LENGTH MULTIPLE UNITS SHOULD HAVE A PLAN VIEW SKETCH WITH ORDER. LENGTH
OVERALL OVERALL
LENGTH LENGTH
END SECTION (TYPICAL) END SECTION
ONE END CAP ONLY* ONE END CAP ONLY*
*End sections with single end caps and deflecting cores must be specified and ordered with the desired core deflection direction.
End cap configurations (mitered end cap one end and open opposite end):
1-5/16"
(33)
Type AD1R (right side)
NOMINAL WIDTH - 1/4" (6)
Alignment Strips
Supplied as standard on multiple section assemblies to
provide positive and accurate field alignment, except
frame G which uses alignment pins. X
CENTER SECTION:
Type AD3L Type AD3R (not shown)
Specify `X´ dim. (distance from end of grille frame)
Access door is a 6" (152) core section hinged on one side.
When selected with a deflected core, specify deflection:
Sill/Floor - To the front Wall - Up
- To the rear - Down
PLASTER STOP
DUCT
CORE SUPPORT
DUCT
FINISHED
WOOD PANELING
DUCT
DUCT
Performance Data
Model 49-240 • 1/2" Spacing • 1/4" Bars • 0° Deflection
Free Area Nominal
Square Feet Duct
TP .010 .022 .039 .062 .087 .119 .156 .198 .245
Per Lineal Width
Foot (Inches)
Performance Data
Model 49-241 • 1/2" Spacing • 1/4" Bars • 15° Deflection
Free Area Nominal
Square Feet Duct
TP .012 .025 .047 .074 .105 .142 .187 .237 .294
Per Lineal Width
Foot (Inches)
Performance Data
Model 49-243 • 1/2" Spacing • 1/4" Bars • 30° Deflection
Free Area Nominal
Square Feet Duct
Per Lineal Width TP .012 .025 .047 .074 .105 .142 .187 .237 .294
Foot (Inches)
Performance Data
Model 49-280 • 1/2" Spacing • 1/8" Bars • 0° Deflection
Free Area Nominal
Square Feet Duct
Per Lineal Width TP .009 .020 .035 .056 .078 .107 .140 .178 .220
Foot (Inches)
Performance Data
Model 49-281 • 1/2" Spacing • 1/8" Bars • 15° Deflection
Free Area Nominal
Square Feet Duct
Per Lineal Width TP .009 .020 .035 .056 .078 .107 .140 .178 .220
Foot (Inches)
Performance Data
Model 49-480 • 1/4" Spacing • 1/8" Bars • 0° Deflection
Free Area Nominal
Square Feet Duct
Per Lineal Width TP .011 .024 .043 .068 .096 .130 .171 .218 .269
Foot (Inches)
Performance Data
Model 49-481 • 1/4" Spacing • 1/8" Bars • 15° Deflection
Free Area Nominal
Square Feet Duct
Per Lineal Width TP .012 .026 .049 .077 .109 .148 .195 .247 .304
Foot (Inches)
LINEAR LOUVER
DIFFUSERS
• EXTRUDED ALUMINUM
• ARCHITECTURAL
• HIGH CAPACITY
• SQUARE OR RECTANGULAR
NECKS
Models:
48LL1 One-way Pattern
48LL2 Two-way Pattern
• Suffix '- O' adds a steel OBD
• Suffix '- OA' adds an aluminum
OBD
Models 48LL1 and 48LL2 B
The Nailor 48LL Series Linear Louver (Vane) Diffusers feature architectural linear styling for high capacity supply and
return air applications in hard ceilings or sidewalls. They are designed for duct mounted installation. Standard finish is a
high quality, baked enamel for long life and easy cleaning. Designed for use in discrete lengths, the fixed louvers provide
DAMPER
1/4"
2 1/2" (38)
(6)
L + 4 3/4" (121)
Dimensional Data
Linear Louver Diffusers
AVAILABLE SIZES:
Unit Size is determined by duct width W.
Diffuser necks are undersized.
Model 48LL1:
Available widths are 3", 4 1/2", 6", 7 1/2",
NOMINAL DUCT SIZE W
9", 10 1/2", 12" (76, 114, 152, 191, 229,
267, 305). W – 1/4" (6)
Available Widths
Nominal
Duct inches 3 4 1/2 6 7 1/2 9 10 1/2 12
Width mm 76 114 152 191 229 267 305
W
Model 48LL2:
Available widths are 3", 6", 9", 12" (76,
152, 229, 305). NOMINAL DUCT SIZE W
W + 4 3/4" (121)
Available Widths
Nominal
Duct inches 3 6 9 12
Width mm 76 152 229 305
W
MODEL ACCESSORIES
- One-Way Pattern 48LL1 - None (default) —
- Two-Way Pattern 48LL2 - Directional Vanes DV
LENGTH (inches)
- Mitered Open MU B
(for 48LL1)
WIDTH
Model 48LL1
(inches) or
FINISH
- Appliance White (default) AW
- Aluminum AL
Notes:
- Mill Finish MI
1. Currently only available in discrete lengths of up to 72" (1829).
2. Contact factory regarding availability of continuous lengths. - Special SP
3. Consult Dimensional Data page for available length dimensions.
Performance Data
Model: 48LL-1 • One-Way Pattern
Nominal Neck Velocity 300 400 500 600 700 800 900
Duct Width, Velocity Pressure .006 .010 .016 .022 .031 .040 .050
inches Total Pressure .037 .064 .101 .145 .197 .258 .326
CFM per ft. 75 100 125 150 175 200 225
3" NC — — 20 24 28 32 35
Throw 14-17-24 16-20-28 16-22-31 20-24-34 21-26-38 20-28-39 24-30-42
CFM per ft. 113 150 188 225 263 300 338
4 1/2" NC — 16 22 26 30 34 37
Throw 18-22-32 21-26-37 23-29-41 28-32-44 28-34-48 30-37-51 32-39-55
CFM per ft. 150 200 250 300 350 400 450
6" NC — 17 23 27 31 35 38
Throw 21-25-36 24-29-31 27-33-46 29-36-51 32-39-55 34-41-59 36-44-63
CFM per ft. 187 150 312 375 437 500 563
7 1/2" NC — 17 23 27 31 35 38
Throw 23-29-41 27-33-47 29-37-52 33-41-56 36-43-61 38-47-65 41-49-70
B CFM per ft. 225 300 375 450 525 600 675
9" NC — 18 24 28 32 36 39
Throw 25-31-44 30-36-52 33-40-58 35-45-63 39-48-67 42-52-73 45-56-77
CFM per ft. 263 350 438 525 613 700 788
10 1/2" NC — 18 25 28 33 37 40
LINEAR DIFFUSERS AND BAR GRILLES
Throw Correction Factors for Various Lengths NC Correction Factors for Various Lengths
Length (ft.) 2 3 4 5 6 8 10 12 Length (ft.) 2 3 4 5 6 8 10
Throw Correction .70 .86 1.0 1.1 1.25 1.4 1.55 1.7 NC Correction -3 -1 0 +1 +2 +3 +5