This document summarizes the design of reinforced concrete beam C50x100 that requires strengthening. It provides details on the geometry, materials, reinforcement, loads, and checks the capacity before and after strengthening with fiber reinforced polymer. The beam was found to be insufficient before strengthening but adequate after strengthening when the compressive concrete strength was increased and higher axial and moment capacities were achieved.

Uploaded by

Gabriel Rojas
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
85 views

C50X100

This document summarizes the design of reinforced concrete beam C50x100 that requires strengthening. It provides details on the geometry, materials, reinforcement, loads, and checks the capacity before and after strengthening with fiber reinforced polymer. The beam was found to be insufficient before strengthening but adequate after strengthening when the compressive concrete strength was increased and higher axial and moment capacities were achieved.

Uploaded by

Gabriel Rojas
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

PROJECT Reforzamiento La Hacienda DATE Marzo-2018

SUBJECT C50x100 CALCU. By EM Ingenieros

1. Geometry and Materials


Design Code : ACI318-05, ACI 440.2R
Design Concept : ISIS CANADA - Design Manual No.4
Material Data : fck = 210 kgf/cm2 (1=0.850)
: fy = 4200 kgf/cm2

100.0
: fys = 4200 kgf/cm2
Section Dim. : 100 x 50 cm
Effective Len. : KLu = 490 cm

6.0
Steel Distribut : 20 - 8 - c = 6 cm) 50.0
Total Steel Area : Ast = 101.9 cm2 (st=0.0204)

2. Reinforcing Materials
Position Wfrp (cm) Tfrp (cm) ffrp (kgf/cm2) frp,Allow frp Product
Horizontal 50.00 0.0337 2447318.91 0.0155 0.7000

3. Magnified Moment
KLu/rx = 490/29 = 17 < 34-12(M1/M2) = 22.00
x = 1.000

KLu/ry = 490/14 = 34 > 34-12(M1/M2) = 22.00


y = MAX[1.00/(1-Pu/0.75/6205), 1.0] = 1.041

4. Member Force and Moment


Pu = 181.86 tonf
x Mux = x  MAX[Mux, Puemin] = 0.12 tonf-m
y Muy = x  MAX[Muy, Puemin] = 140.4 tonf-m

5. Check Axial and Moment Capacity - Before Strengthening


Rotation Angle  = 89.95 
Depth to the Neutral Axis c = 41.78 cm
Strength Reduction Factor  = 0.65
Maximum Axial Load Pn(max) = 677.27 tonf
Design Axial Load Strength Pn = 121.29 tonf
Design Moment Strength Mnx = 0.08 tonf-m
Mny = 93.68 tonf-m
Strength Ratio : Applied/Design = 1.499 > 1.000 ........ Reinforcement

P (tonf) My (tonf-m)
1400 175
 = 89.95  Pn = 121.29 tonf
1200 140 (0.12, 140.4)

1000 105
(0.08, 93.68)
800 70
fs=0
677.27
600 35

400 fs=0.5fy 0
Mx (tonf-m)
200 eb=87cm -35
(181.86, 140.4)
(121.29, 93.68)
0 -70
M (tonf-m)
-200 -105

-400 -140

-600 -175
0

15

30

45

60

75

90

105

120

135

150

-70

-35

35

70

105

140

175
-175

-140

-105

Page 1
PROJECT Reforzamiento La Hacienda DATE Marzo-2018

SUBJECT C50x100 CALCU. By EM Ingenieros

6. Check Shear Capacity - Before Strengthening


Strength Reduction Factor  = 0.75
Y-Y Direction
Design Force Vuy = 68.58 tonf (Pu = 181.86 tonf)
Required Tie Spacing : 3 - 
Provided Tie Spacing : 3 - 
Vcy + Vsy = 34.1 + 76.41 = 110.51 tonf > Vuy = 68.58 tonf ....... O.K.

X-X Direction
Design Force Vux = 0.01 tonf (Pu = 181.86 tonf)
Required Tie Spacing : 5 - 
Provided Tie Spacing : 5 - 
Vcx + Vsx = 31.92 + 59.61 = 91.53 tonf > Vux = 0.01 tonf ....... O.K.

7. Calculate Concrete Strength - After Strengthening


Ultimate Confinement Pressure due to FRP Strengthening
'frp = 0.0020
f'frp = ffrp  'frp / frp.Allow = 315783.09 kgf/cm2
flfrp = 2 frp  f'frp  tfrp  (B+D) / (B  D) = 446.96 kgf/cm2
Volumetric Ratio of FRP Strength to Concrete Strength
 = flfrp / (c  fck) = 3.274
Compressive Strength of Confined Concrete
f'cc = fck  (1 + pr  ) = 897.63 kgf/cm2
pr = 1.000

8. Check Axial and Moment Capacity - After Strengthening


Rotation Angle  = 89.95 
Depth to the Neutral Axis c = 27.55 cm
Strength Reduction Factor  = 0.677
Maximum Axial Load Pn(max) = 2165.95 tonf
Design Axial Load Strength Pn = 271.01 tonf
Design Moment Strength Mnx = 0.18 tonf-m
Mny = 207.92 tonf-m
Strength Ratio : Applied/Design = 0.671 < 1.000 ........ O.K.

P (tonf) My (tonf-m)
4500 300
 = 89.95  Pn = 271.01 tonf
4000 240

(0.18, 207.92)
3500 180

3000 120 (0.12, 139.52)

2500 60

2000 2165.95 0
fs=0 Mx (tonf-m)
1500 -60
fs=0.5fy
1000 -120
eb=48cm

500 -180
(271.01, 207.92)
(181.86, 139.52)
0 -240
M (tonf-m)
-500 -300
0

49

99

149

198

248

297

346

396

446

495

-300

-240

-180

-120

-60

60

120

180

240

300

Page 2
PROJECT Reforzamiento La Hacienda DATE Marzo-2018

SUBJECT C50x100 CALCU. By EM Ingenieros

9. Check Shear Capacity - After Strengthening


Strength Reduction Factor : Concrete c = 0.750
Strength Reduction Factor : Hoof s = 0.750
Strength Reduction Factor : FRP frp = 0.700

Vcy = 2  (1+Pu/Ag/2000)  fck  B  dc = 93.99 tonf


Vsy = Avy  fy  dc / s = 101.88 tonf
Vfrpy = Tfrp  0.002  Efrp  dc = 0.63 tonf ( Efrp = 1679532.41 kgf/cm2 )
Vny = cVcy + sVsy + frpVfrpy = 147.35 tonf  Vuy = 68.58 tonf ....... O.K

Vcx = 2  (1+Pu/Ag/2000)  fck  D  bc = 87.99 tonf


Vsx = Avx  fy  bc / s = 79.48 tonf
Vfrpx = Tfrp  0.002  Efrp  bc = 0.30 tonf ( Efrp = 1679532.41 kgf/cm2 )
Vnx = cVcx + sVsx + frpVfrpx = 125.81 tonf  Vux = 0.01 tonf ....... O.K