Product Data Sheet: Circuit Breaker Compact NSX100F - TMD - 16 A - 3 Poles 2d

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Product data sheet LV429627

Characteristics circuit breaker Compact NSX100F - TMD - 16 A -


3 poles 2d

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range Compact
Product name Compact NSX
Product or component type Circuit breaker
Device short name Compact NSX100F
Device application Distribution
Poles description 3P
Protected poles description 2t
Network type AC
Network frequency 50/60 Hz
[In] rated current 100 A ( 40 °C )
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ue] rated operational voltage 690 V AC 50/60 Hz
Breaking capacity code F
Breaking capacity 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 600 V AC 50/60 Hz conforming to UL 508
25 kA at 480 V AC 50/60 Hz conforming to UL 508
85 kA at 240 V AC 50/60 Hz conforming to UL 508
[Ics] rated service breaking capacity Ics 11 kA 525 V AC 50/60 Hz conforming to IEC 60947-2
Ics 35 kA 440 V AC 50/60 Hz conforming to IEC 60947-2
Ics 36 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Ics 4 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Ics 85 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Ics 12.5 kA 500 V AC 50/60 Hz conforming to IEC 60947-2
Suitability for isolation Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
Utilisation category Category A

Aug 24, 2017


1
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
Trip unit rating 16 A ( 40 °C )
Protection type Short-circuit protection (magnetic)
Overload protection (thermal)
Pollution degree 3 conforming to IEC 60664-1

Complementary
Control type Toggle
Mounting mode Fixed
Mounting support Backplate
Upside connection Front
Downside connection Front
Auxiliary contact composition Without
Mechanical durability 50000 cycles
Electrical durability 10000 cycles 690 V In conforming to IEC 60947-2
20000 cycles 690 V In/2 conforming to IEC 60947-2
30000 cycles 440 V In conforming to IEC 60947-2
50000 cycles 440 V In/2 conforming to IEC 60947-2
Connection pitch 35 mm
Local signalling Positive contact indication
Long time pick-up adjstment type Ir Adjustable
Long time pick-up adjustment range 0.7...1 x In
Long time delay adjustment type Fixed
[Tr] long-time delay adjustment range 15 s 6 x Ir
120...400 s 1.5 x In
Short-time pick-up adjustment type Isd Fixed
[Isd] short-time pick-up adjustment 190 A
range
Short-time delay adjustment type Fixed
Height 161 mm
Width 105 mm
Depth 86 mm
Product weight 2.05 kg

Environment
Electrical shock protection class Class II
Standards UL 508
IEC 60947-2
EN 60947-2
Product certifications CSA
UL
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -35...70 °C
Ambient air temperature for storage -55...85 °C

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  0819  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold

2
Product environmental profile Available

Contractual warranty
Warranty period 18 months