0% found this document useful (0 votes)
177 views3 pages

Condensing Unit - Chiller 1.01

This document provides specifications for a BITZER LH64E/2EES-3Y condensing unit. It lists the unit's input values, resulting capacity and performance values, dimensions, connections, technical data, and application limits. Key details include a cooling capacity of 3.91 kW, power input of 2.03 kW, operating mode of standard, total width of 1000mm, and refrigerants supported including R134a, R407C, R404A. The document also provides dimensions, connection sizes, weight, coil volume, and receiver options.

Uploaded by

Harsha Vardhan B
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
177 views3 pages

Condensing Unit - Chiller 1.01

This document provides specifications for a BITZER LH64E/2EES-3Y condensing unit. It lists the unit's input values, resulting capacity and performance values, dimensions, connections, technical data, and application limits. Key details include a cooling capacity of 3.91 kW, power input of 2.03 kW, operating mode of standard, total width of 1000mm, and refrigerants supported including R134a, R407C, R404A. The document also provides dimensions, connection sizes, weight, coil volume, and receiver options.

Uploaded by

Harsha Vardhan B
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

BITZER Software v6.7.0 rev1849 03-Oct-17 / All data subject to change.

1/3

Selection: Condensing Units


Input Values
Unit type LH64E/2EES-3Y
Series Standard
Refrigerant R134a
Reference temperature Dew point temp.
Evaporating SST -4.00 °C
Ambient temp. 46.0 °C
Suct. gas superheat 10.00 K
Useful superheat 100%
Operating mode Auto
Power supply 400V-3-50Hz
Capacity Control 100%

Result
Unit type LH64E/2EES-3Y-40S
Capacity steps 100%
Cooling capacity 3.91 kW
Evaporator capacity 3.91 kW
Power input * 2.03 kW
Current (400V) 4.18 A
Voltage range 380-420V
Mass flow 105.8 kg/h
Condensing SDT 52.5 °C
Liquid subcooling 2.93 K
Operating mode Standard

Tentative Data.
*Power input including fan power absorbtion
Performance data certified by ASERCOM (see T.Data/ Notes)

Application Limits

Legend
additional cooling

suction gas superheat >10K

M1: motor 1

M2: motor 2
BITZER Software v6.7.0 rev1849 03-Oct-17 / All data subject to change. 2/3

Technical Data: LH64E/2EES-3Y


Dimensions and Connections

Technical Data
Technical Data
Weight 130 kg
Total width 1000 mm
Total depth 672 mm
Total height 687 mm
Connection suction line 22 mm - 7/8''
Connection liquid line 12 mm - 1/2''
Fans: Number 1xEC
Voltage (more on request) 230V-1-50Hz (Standard)
Current / Power consumption of each fan 1,8 A / 330 W
Air flow condenser 50Hz 4300 m³/h
Voltage (more on request) 230V-1-60Hz (Standard)
Current / Power consumption of each fan 1,8 A / 330 W
Air flow condenser 60Hz 3100 m³/h
Coil Volume 1,05 dm3
Receiver type (Standard) FS076
Max. refrigerant charge 90% at 20°C
R22 8,5 kg
R134a 8,6 kg
R407C 8,1 kg
R404A/R507A 7,5 kg
R407A
R407F
Receiver type (Option) FS125
R22 14,2 kg
R134a 14,3 kg
R407C 13,6 kg
R404A/R507A 12,5 kg
Extent of delivery (Standard)
Discharge line Standard
Protective charge Standard
Available Options
Oil separator Option
Check valve Option
High & low pressure switch Option
Dressed unit Option
Weather protective housing Option
Fans: elect. Speed control Option
Sound measurement
Data of compressors: see compressor program
BITZER Software v6.7.0 rev1849 03-Oct-17 / All data subject to change. 3/3
Condensing Units

Condensing Units
Motor 1 = e.g. LH..E/4TES-12 with 12 "HP", primary for air-conditioning (e.g. R22,R407C) and medium temperature application
(e.g. R134a, R407F, R407A, R404A, R507A, R22) and air-conditioning with R134a at high ambient temperatures.
Motor 2 = e.g. LH..E/4TES-9 with 8 "HP", for medium and low temperature application (e.g. R134a, R407F, R407A, R404A,
R507A, R22) and air-conditioning with R134a.
For more information concerning the application range use the "limits" button.

Operation modes for LH..E/4VES-7 to LH../6HE-28 with R22


CIC = liquid injection with low temperature application, suction gas cooled motor

Specifications for sound emission Ecostar


The data are based on 50 Hz operation with R404A.
Soundpressure: Data are valid for free field conditions according to EN13487 with a block-shaped reference area in a distance
of 10m.
For further informations see technical information for sound data.
Legend of connection positions according to "Dimensions":
1 Suction valve
2 Discharge gas line
3 Condensate line
4 Refrigerant outlet
5 Pressure relief valve connection
Dimensions can show tolerances according to EN ISO 13920-B.