Cummins C33D5 - Data Sheet
Cummins C33D5 - Data Sheet
Standby Prime
Fuel consumption kVA (kW) kVA (kW)
Ratings 33 (26.4) 30 (24)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
gph 0.8 1.2 1.6 2.3 0.8 1.1 1.5 2.0
L/hr 3 4.4 6.1 8.7 2.9 4.1 5.6 7.6
Fuel flow
Maximum fuel flow, L/hr 40
Maximum fuel inlet restriction, mm Hg 73.66
Maximum fuel inlet temperature, °C 60
©2015 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
DS93f-CPGK (1/15)
Air Standby Rating Prime Rating
3
Combustion air, m /min 2.06 2.06
Maximum air cleaner restriction, kPa 2.5
Exhaust
Exhaust gas flow at set rated load, m3/min 2.29 2.29
Exhaust gas temperature, °C 600 550
Maximum exhaust back pressure, kPa 4.75
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
©2015 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
DS93f-CPGK (1/15)
Alternator data
Connection Temp rise ºC Duty Alternator Voltage
Wye, 3-phase 163/125 S/P PI144G 380-416V
Wye, 3-phase 125/105 S/P PI144H 380-440
Wye, 1-phase 163/125 S/P PI144H 220-240
Ratings definitions
Emergency standby power Limited-time running power Base load (continuous)
(ESP): (LTP): Prime power (PRP): power (COP):
Applicable for supplying power to Applicable for supplying power Applicable for supplying power Applicable for supplying
varying electrical load for the to a constant electrical load for to varying electrical load for power continuously to a
duration of power interruption of a limited hours. Limited Time unlimited hours. Prime Power constant electrical load for
reliable utility source. Emergency Running Power (LTP) is in (PRP) is in accordance with ISO unlimited hours. Continuous
Standby Power (ESP) is in accordance with ISO 8528. 8528. Ten percent overload Power (COP) is in accordance
accordance with ISO 8528. Fuel capability is available in with ISO 8528, ISO 3046, AS
Stop power in accordance with accordance with ISO 3046, 2789 and DIN 6271.
ISO 3046, AS 2789 and DIN 6271. AS 2789 and DIN 6271.
©2015 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.