Alarm and Alert Codes
Alarm and Alert Codes
49
Downloaded from www.Manualslib.com manuals search engine
Table 29 — Alarm and Alert Codes (cont)
ALARM/ ALARM WHY WAS THIS
ALERT OR DESCRIPTION ALARM ACTION TAKEN RESET PROBABLE
BY CONTROL METHOD CAUSE
CODE ALERT GENERATED?
T112 Alert Circuit A High Suction If EXV is greater than Circuit A shutdown after Manual Faulty expansion
Superheat 98%, suction superheat is pumpdown complete. valve or EXV board,
greater than 75 F (41.7 C) low refrigerant
and saturated suction charge, plugged fil-
temperature is less than ter drier, faulty suc-
MOP for 5 minutes tion gas thermistor
(T7) or cooler ther-
mistor (T5).
T113 Alert Circuit B High Suction If EXV is greater than Circuit B shutdown after Manual Faulty expansion
Superheat 98% suction superheat is pumpdown complete. valve or EXV board,
greater than 75 F (41.7 C) low refrigerant
and saturated suction charge, plugged fil-
temperature is less than ter drier, faulty suc-
MOP for 5 minutes tion gas thermistor
(T8) or cooler ther-
mistor (T6).
T114 Alert Circuit A Low Suction If EXV is greater than Circuit A shutdown after Automatic restart Faulty expansion
Superheat 10%, and either suction pumpdown complete. after first daily valve or EXV board,
superheat is less than occurrence. faulty suction gas
superheat set point –10 F Manual restart thermistor (T7) or
(5.6 C) or saturated thereafter. cooler thermistor
suction temperature is (T5).
greater than MOP for
5 minutes
T115 Alert Circuit B Low Suction If EXV is greater than Circuit B shutdown after Automatic restart Faulty expansion
Superheat 10%, and either suction pumpdown complete. after first daily valve or EXV board,
superheat is less than occurrence. faulty suction gas
superheat set point –10 F Manual restart thermistor (T8) or
(5.6 C) or saturated thereafter. cooler thermistor
suction temperature is (T6).
greater than MOP for
5 minutes
T116 Alert Circuit A Low Cooler 1. If the saturated suction 1. Mode 7 initiated. No addi- 1. Automatic reset Faulty expansion
Suction Temperature temperature is 24 to tional capacity increases. if corrected. valve or EXV board,
29° F (13.3 to 16.1° C) Alert not tripped. low refrigerant
below cooler LWT and charge, plugged fil-
is also 2° F (1.1° C) ter drier, faulty suc-
less than freeze* tion gas thermistor
2. If the saturated suction 2. Circuit shutdown without 2. Manual (T7) or cooler ther-
temperature is 30° F going through pumpdown. mistor (T5), low
(16.7° C) below cooler cooler fluid flow.
LWT and is also 2° F
(1.1° C) less than
freeze* for 10 minutes
T117 Alert Circuit B Low Cooler 1. If the saturated suction 1. Mode 8 initiated. No addi- 1. Automatic reset Faulty expansion
Suction Temperature temperature is 24 to tional capacity increases. if corrected. valve or EXV board,
29°F (13.3 to 16.1° C) Alert not tripped. low refrigerant
below cooler LWT and charge, plugged fil-
is also 2°F (1.1° C) ter drier, faulty suc-
less than freeze* tion gas thermistor
2. If the saturated suction 2. Circuit shutdown without 2. Manual (T8) or cooler ther-
temperature is 30° F going through pumpdown. mistor (T6), low
(16.7° C) below cooler cooler fluid flow.
LWT and is also 2° F
(1.1° C) less than
freeze* for 10 minutes
T118 Alert Circuit A Low Oil Oil pressure switch open Circuit shutdown without Manual Oil pump failure, low
Pressure after 1 minute of continu- going through pumpdown. oil level, switch fail-
ous operation ure or compressor
circuit breaker
tripped.
T119 Alert Circuit B Low Oil Oil pressure switch open Circuit shutdown without Manual Oil pump failure, low
Pressure after 1 minute of continu- going through pumpdown. oil level, switch fail-
ous operation ure or compressor
circuit breaker
tripped.
LEGEND *Freeze is defined as 34° F (1.1 C) for water. For brine fluids, freeze
CCN — Carrier Comfort Network is CSP.1 –8° F (4.4 C) for single set point and lower of CSP.1 or
CPCS — Compressor Protection Control System CSP.2 –8° F (4.4 C) for dual set point configuration.
CXB — Compressor Expansion Board
EMM — Energy Management Module
EWT — Entering Fluid Temperature
EXV — Electronic Expansion Valve
FSM — Flotronic™ System Manager
LCW — Leaving Chilled Water
LWT — Leaving Fluid Temperature
MBB — Main Base Board
MOP — Maximum Operating Pressure
WSM — Water System Manager
50
Downloaded from www.Manualslib.com manuals search engine
Table 29 — Alarm and Alert Codes (cont)
ALARM/ ALARM WHY WAS THIS
ALERT OR DESCRIPTION ALARM ACTION TAKEN RESET PROBABLE
BY CONTROL METHOD CAUSE
CODE ALERT GENERATED?
A150 Alarm Emergency Stop CCN emergency stop Chiller shutdown Automatic once CCN Network
command received without going CCN command for command.
through pumpdown. EMSTOP returns
to normal
A151 Alarm Illegal Configuration One or more of the ille- Chiller is not Manual once con- Configuration
gal configurations allowed to start. figuration errors error. See Note on
exists. are corrected page 52.
A152 Alarm Unit Down Due to Both circuits are down Chiller is unable Automatic once Alarm notifies user
Failure due to alarms/alerts. to run. alarms/alerts are that chiller is100%
cleared that pre- down.
vent the chiller
from starting.
T153 Alert Real Time Clock Internal clock on MBB Occupancy sched- Automatic when Time/Date/Month/
Hardware Failure fails ule will not be used. correct clock con- Day/Year not prop-
Chiller defaults to trol restarts. erly set.
Local On mode.
A154 Alarm Serial EEPROM Hardware failure with Chiller is unable Manual Main Base Board
Hardware Failure MBB to run. failure.
T155 Alert Serial EEPROM Configuration/storage No Action Manual Potential failure of
Storage Failure failure with MBB MBB. Download
current operating
software. Replace
MBB if error
occurs again.
A156 Alarm Critical Serial Configuration/storage Chiller is not Manual Main Base Board
EEPROM Storage failure with MBB allowed to run. failure.
Failure
A157 Alarm A/D Hardware Hardware failure with Chiller is not Manual Main Base Board
Failure peripheral device allowed to run. failure.
T170 Alert Loss of Communica- MBB loses communica- Compressors A3, Automatic Wiring error, faulty
tion with CXB tion with CXB A4 and B3 and wiring or failed
unloaders A2/B2 CXB module.
unable to operate.
A172 Alarm Loss of Communica- MBB loses communica- Chiller shutdown Automatic Wiring error, faulty
tion with EXV tion with EXV without going wiring or failed
through pumpdown. EXV module.
T173 Alert Loss of Communica- MBB loses communica- 4 to 20 mA tempera- Automatic Wiring error, faulty
tion with EMM tion with EMM ture reset disabled. wiring or failed
Demand Limit set to Energy Manage-
100%. 4 to 20 mA ment Module
set point disabled. (EMM).
T174 Alert 4 to 20 mA Cooling If configured with EMM Set point function Automatic Faulty signal gen-
Set Point Input Fail- and input less than disabled. Chiller erator, wiring
ure 2 mA or greater than controls to CSP.1. error, or faulty
22 mA EMM.
T176 Alert 4 to 20 mA Tempera- If configured with EMM Reset function dis- Automatic Faulty signal gen-
ture Reset Input and input less than abled. Chiller erator, wiring
Failure 2 mA or greater than returns to normal error, or faulty
22 mA set point control. EMM.
T177 Alert 4 to 20 mA Demand If configured with EMM Demand limit func- Automatic Faulty signal gen-
Limit Input Failure and input less than tion disabled. Chiller erator, wiring
2 mA or greater than returns to 100% error, or faulty
22 mA demand limit EMM.
control.
A200 Alarm Cooler Pump Inter- Interlock not closed Cooler pump shut Manual Failure of cooler
lock Failure to Close within 5 minutes after off. Chiller shutdown pump, flow switch,
at Start-Up unit is started without going or interlock.
through pumpdown.
A201 Alarm Cooler Pump Inter- Interlock opens during Cooler pump shut Manual Failure of cooler
lock Opened During operation off. Chiller shutdown pump, flow switch,
Normal Operation without going or interlock.
through pumpdown.
A202 Alarm Cooler Pump Inter- If configured for cooler Chiller is not Manual Failure of cooler
lock Closed When pump control and inter- allowed to start. pump relay or
Pump is Off lock closes while cooler interlock, welded
pump relay is off contacts.
51
Downloaded from www.Manualslib.com manuals search engine
Table 29 — Alarm and Alert Codes (cont)
ALARM/ ALARM WHY WAS THIS
ALERT OR DESCRIPTION ALARM ACTION TAKEN RES PROBABLE
BY CONTROL METHOD CAUSE
CODE ALERT GENERATED?
T203 Alert Loss of Communica- Master MBB loses Dual chiller control dis- Automatic Wiring error, faulty wir-
tion with Slave Chiller communication with abled. Chiller runs as a ing, failed Slave MBB
Slave MBB stand-alone machine. module, power loss at
Slave chiller, wrong
slave address.
T204 Alert Loss of Communica- Slave MBB loses com- Dual chiller control dis- Automatic Wiring error, faulty wir-
tion with Master Chiller munication with Master abled. Chiller runs as a ing, failed Master MBB
MBB stand-alone machine module, power loss at
Master chiller.
T205 Alert Master and Slave Master and slave chiller Dual chiller routine dis- Automatic CCN Address for both-
Chiller with Same have the same CCN abled. Master/slave run chillers is the same.
Address address (CCN.A) as stand-alone chillers. Must be different.
Check CCN.A under
the OPT2 sub-mode in
configuration at both
chillers.
T206 Alert High Leaving Chilled LWT read is greater Alert only. No action Automatic Building load greater
Water Temperature than LCW Alert Limit, taken. than unit capacity, low
plus control point and water/brine flow or
Total capacity is 100% compressor fault.
and LWT is greater Check for other
than LWT reading one alarms/alerts.
minute ago
A207 Alarm Cooler Freeze Cooler EWT or LWT is Chiller shutdown with- Automatic for Faulty thermistor (T1/
Protection less than freeze* out going through first occurrence T2), low water flow.
pumpdown. Cooler of day. Manual
pump continues to run reset thereafter.
(if control enabled).
A208 Alarm Low Cooler Fluid Flow Cooler EWT is less Chiller shutdown with- Manual Faulty cooler pump,
than LWT by 3° F out going through low water flow, plugged
(1.7° C) for 1 minute pumpdown. Cooler fluid strainer.
after a circuit is started pump shut off (if control
enabled).
T950 Alert Loss of Communica- No communications WSM forces removed. Automatic Failed module, wiring
tion with WSM have been received by Chiller runs under own error, failed trans-
MBB within 5 minutes control. former, loose connec-
of last transmission tion plug, wrong
address.
T951 Alert Loss of Communica- No communications FSM forces removed. Automatic Failed module, wiring
tion with FSM have been received by Chiller runs under own error, failed trans-
MBB within 5 minutes control. former, loose connec-
of last transmission tion plug, wrong
address.
LEGEND NOTE: The following table shows illegal configurations:
CCN — Carrier Comfort Network
CPCS — Compressor Protection Control System 1 Unit type = 0.
CXB — Compressor Expansion Board 2 4 Compressors in a circuit with 2 unloaders.
EMM — Energy Management Module 4 Compressors in a circuit with 1 unloader and hot gas
EXV — Electronic Expansion Valve 3 bypass.
FSM — Flotronic™ System Manager 4 2 Unloaders and hot gas bypass in a circuit.
LCW — Leaving Chilled Water
LWT — Leaving Fluid Temperature More than one compressor difference between circuits (e.g., 4
5 compressors in Ckt A, 2 in Ckt B).
MBB — Main Base Board
MOP — Maximum Operating Pressure Water cooled units with optional thermistors and configured
6 for head pressure control.
WSM — Water System Manager
Split system chillers with optional thermistors and configured
7 for head pressure control.
*Freeze is defined as 34° F (1.1 C) for water. For brine fluids, freeze Low temperature brine selected for air cooled chillers or split
8 systems with air cooled head pressure control.
is CSP.1 –8° F (4.4 C) for single set point and lower of CSP.1 or
CSP.2 –8° F (4.4 C) for dual set point configuration. Water cooled unit configured for air cooled head pressure
9 control.
Air cooled head pressure control with common fan staging
10 and different head pressure control methods for each circuit
(EXV controlled vs. set point controlled).
Lead/lag enabled, Master selected and Cooling Set Point
11 select is LWT POT.
Water cooled or split units (units types 2, 3, 4) with more than
12 one compressor on a circuit.
13 Condenser pump interlock enabled on air cooled unit.
14 Unit type changed.
15 Low pressure set points out of range.
16 Cooler fluid type is water and ice mode is enabled.