This document outlines occupancy and occupant load requirements for health care facilities. Some key points:
1. Health care occupancies must be separated from other occupancies by noncombustible walls with a two-hour fire rating. Means of egress from health care spaces through other areas must also meet health care requirements.
2. Occupant loads are based on gross floor area, with at least one person per 11.1 sqm for inpatient areas and 22.3 sqm for other departments.
3. At least two exits must be provided per floor, restricted to doors, stairs, ramps, horizontal exits, or passageways. Exits must be independent and remote from each other.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
133 views47 pages
Occupancy and Occupant Load
This document outlines occupancy and occupant load requirements for health care facilities. Some key points:
1. Health care occupancies must be separated from other occupancies by noncombustible walls with a two-hour fire rating. Means of egress from health care spaces through other areas must also meet health care requirements.
2. Occupant loads are based on gross floor area, with at least one person per 11.1 sqm for inpatient areas and 22.3 sqm for other departments.
3. At least two exits must be provided per floor, restricted to doors, stairs, ramps, horizontal exits, or passageways. Exits must be independent and remote from each other.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 47
Occupancy and Occupant Load square meters (11.
1 m2) gross floor area in
1. Health care occupancies in buildings health care sleeping housing other occupancies shall departments and not less than one (1) be completely separated from them by persons for each twenty two noncombustible construction square meters (22.3 m2) of gross floor area having at least a two (2)-hour fire-resistance of inpatient health care rating. All means of egress treatment departments. Gross floors areas from health care occupancies that traverse shall be measured within non-health care spaces the exterior building walls with no shall conform to requirements of this deductions. standard for health care SECTION 10.2.10.2 EXIT DETAILS occupancies. Any occupancy with a hazard A. Number and Types of contents classified 1. Exits shall be restricted to the following higher than that of the health care and permissible types; located in the same building a. Doors leading directly outside the building as health care occupancies shall be b. Stairs and smoke-proof enclosures protected. Industrial, office, c. Ramps mercantile and storage occupancies d. Horizontal exits categorized as high hazard shall e. Exit Passageways not be permitted in buildings housing health 2. At least two (2) exits of the above types, care occupancies. remote from each other, shall 2. Sections of health care buildings may be be provided for each floor or fire section of classified as other occupancies the building. if they meet at the following conditions: 3. Elevators constitute a supplementary a. They are not intended to serve health facility, but-shall not be counted care occupants for purposes as required exits. of housing, treatment, customary access, or B. Capacity of Exits means of egress. The capacity of means of egress shall be in b. They are adequately separated from areas accordance with Section of health care occupancies 10.2.5.2 para “C” of this IRR. by construction having a two-(2) hour fire C. Access to Exit resistance rating. 1. Every aisle, passageway, corridor, exit 3. Auditoriums, chapels, staff residential discharge, exit location and areas, garages or similar occupancies access shall be in accordance with Section provided in connection with health care 10.2.5.2 of this IRR, except occupancy shall as modified in the succeeding paragraphs of have exits provided in accordance with this subsection. other applicable sections of 2. Travel distance shall comply with the this Chapter. following: 4. The occupant load for which means of a. Between any room door intended as exit egress shall be provided for access and an exit shall any floor shall be the maximum number of not exceed thirty (30) meters; persons intended to b. Between any point in a room and an exit occupy that floor but not less than one (1) shall not exceed forty six persons for each eleven (46) meters; 153 c. Between any point in a health care sleeping room or suite and an exit access door of that room or suite shall 5. Any rooms and any suite or rooms of not exceed fifteen (15) more than ninety three square meters. meters (93 m2) shall have at least two (2) 154 exit access doors remote d. Travel distance shall be measured in from each other. accordance with Section 6. Every exit or exit access shall be so 10.2.5.2 of this IRR. arranged that no corridor or aisle e. The travel distances in para (2) (a) and (b) has a pocket or dead-end exceeding six above may be meters (6 m). increased by fifteen meters (15 m) in 7. Any health care sleeping room which buildings completely complies with the requirements equipped with an automatic fire suppression previously set forth in this section may be system. subdivided with non firerated, 3. Every health care sleeping room, unless it non-combustible partitions, provided, that has a door opening at the arrangement ground level, shall have an exit access door allows for direct and constant visual leading directly to a supervision by nursing personnel. corridor which leads to an exit. One adjacent Rooms which are so subdivided shall not room such as a sitting or exceed four hundred sixty five anteroom may intervene if all doors along square meters (465 m2). the path of exit travel are D. Doors equipped with non-lockable hardware, and 1. Doors shall be in accordance with Section this intervening room is 10.2.5.3, except as modified not intended to serve more than eight (8) in this subsection. For door requirements in health care sleeping beds. horizontal exits and smoke However, special nursing suites or nurseries partitions, see Section 10.2.5.6, Section permitted in this Division 10.2.6.Error! Reference source shall not be limited to eight (8) cribs or not found.9 and this Section. bassinets. 2. Locks shall not be permitted on patient 4. Aisles, corridors and ramps required for sleeping room doors. exit access of exit in hospitals or 155 nursing homes shall be at least two hundred Exception No. 1: Key-locking devices that forty four (244) centimeters restrict access to the room in clear and unobstructed width. Aisles, from the corridor and that are operable only corridors and ramps by staff from the corridor required for exit access or exit in a side shall be permitted. Such devices shall residential-custodial care institution not restrict egress from the shall be at least one hundred eighty three room. centimeters (183 cm) in Exception No. 2: Door-locking arrangements clear and unobstructed width. Corridors and shall be permitted in ramps in adjunct areas health care occupancies, or portions of not intended for the housing, treatment, or health care occupancies, use of inpatients, shall be at where the clinical needs of the patients least one hundred eighty three centimeters require specialized security (183 cm) in clear and measures for their safety, provided that keys unobstructed width. are carried by staff at all times. 3. Exit access doors from hospital and provided on each side of the horizontal exit nursing home sleeping rooms, for the total number of diagnostic and treatment rooms or areas 156 such as X-ray, surgery and occupants in adjoining compartments. physical therapy, all doors between these 2. A single door may be used as a horizontal spaces and the required exit if it serves one direction, exits, and all exit doors serving these spaces only and is at least one hundred twelve shall be at least one centimeters (112 cm) wide for hundred twelve (112) centimeters. Doors to a hospital or nursing home or at least ninety residential-custodial one centimeters (91 cm) sleeping rooms and door to nursery sleeping wide for residential-custodial care rooms and all exit doors institutions. The swing shall be in the serving these spaces shall be at least ninety direction of exit travel. one centimeters (91 cm) 3. A horizontal exit involving a corridor two wide. and four tenths (2.40) meters 4. Any door in a fire separation, horizontal or more in width serving as means of egress exit or a smoke partition may from both sides of the be held open only by an electrical device doorway shall have the opening protected which complies with by a pair of swinging Section 10.2.5.3. Each of the following doors, each door having a clear width of systems shall be so arranged as 1055 mm and swinging in to initiate the self-closing action throughout the opposite direction from the other. the entire health care 4. An approved vision panel is required in facility. each horizontal exit door. a. The required alarm system Center mullions are prohibited. b. The required automatic fire detection G. Ramps system Ramps in accordance with Section 10.2.5.7 c. An approved automatic fire suppression shall be permitted. system, H. Emergency Lighting, Exit Markings, Alarms 5. Doors in stair enclosures and in walls and Communication Systems surrounding hazardous areas shall 1. Each hospital shall be provided with not be equipped with hold-open devices. emergency lighting as described E. Stairs and Smokeproof Enclosures in Section 10.2.5.11 and exit markings as Every stair and smokeproof enclosure shall described in Section 10.2.5.12 be in accordance with Section of this IRR. Such emergency lighting and the 10.2.5.4. illumination of required F. Horizontal Exits exits and directional signs shall be supplied A horizontal exit shall be in conformance by the Life Safety Branch of with Section 10.2.5.6and/or as the hospital electrical system as described in modified in this subsection. NFPA 99, Standard for 1. At least two and eight-tenths (2.80) Health Care Facilities. The Life Safety Branch square meter per occupant in a shall also serve alarms, hospital or nursing home or one and four- emergency communication systems and the tenths (1.40) square meter illumination of generator per occupant in a residential-custodial care set locations as described in paragraph (c), institution shall be (d) and (e), Section 312 of the same reference. 2. Each nursing home and residential- least one half square meter (0.5 m2) per custodial care facility shall have occupant shall be provided emergency lighting in accordance with on each side of the smoke partition for the Section 10.2.5.11 of this IRR. total number of occupants Emergency lighting with at least 1 ½ hour in adjoining compartments. duration shall be provided. 5. Corridor openings in smoke partitions 3. Exit signs shall be provided in each shall be protected by a pair of hospital, nursing home, and swinging doors, door to swing in a direction residential custodial care facility in opposite from the other. accordance with Section 10.2.5.12 The minimum width of each door for of this IRR. hospitals and nursing homes shall SECTION 10.2.10.3 PROTECTION be one hundred twelve centimeters (112 A. Subdivision of Building Spaces cm), while that for residentialcustodial 1. Smoke Partitions Required - Smoke care institutions shall be eighty one partitions shall be provided, centimeters (81 cm). regardless of building construction type, as 6. Doors in smoke partitions shall comply follows: with Section 10.2.6.9 of this IRR a. To divide into at least two (2) and shall be self-closing and held open only compartments every storey used by if they meet the 157 requirements of this section. inpatients for sleeping or treatment and any 7. Vision panels of approved transparent storey having an wired glass not exceeding forty occupant load of fifty (50) or more persons. six-hundredth square meter (0.46 m2) in b. To limit on any storey the maximum area steel frames shall be provided of each smoke compartment in all doors in smoke partitions. to no more than two thousand one hundred 8. Stops are required on the head and sides square meters of door frames in smoke partitions (2,100 m2), of which both length and width and center mullions are prohibited. shall be no more than B. Minimum Construction Standards forty six meters (46 m). 1. Health care buildings of one (1) storey Note: Protection may be accomplished in only may be constructed of conjunction with the protected non-combustible construction, provisions of horizontal exits. fire-resistive construction, 2. Smoke partitions shall be provided on protected ordinary construction, protected storeys which are usable but wood frame construction, unoccupied. heavy timber construction or unprotected 3. Any smoke partition shall be constructed noncombustible in accordance with Section construction. For the purpose of this 10.2.6.9 of this IRR and shall have a fire subsection, storeys shall be resistance rating of at least one 158 (1) hour. counted starting at the lowest floor of exit 4. At least two and eight-tenths square discharge. All levels below meters (2.8 m2) per occupant for the floor of exit discharge shall be separated the total of bed or litter patients shall be from the floor of exit provided on each side of the discharge by at least protected non- smoke partition. On other storeys not combustible construction. housing bed or litter patients at 2. Health care buildings two (2) storeys or be provided with latches of a type suitable more shall be at least fireresistive for keeping the door tightly construction. closed. 3. Health care occupancies two (2) or more 4. Transfer grills, whether protected by storeys shall have enclosure fusible link-operated dampers or walls of non-combustible materials having a not, shall not be used in these walls or fire resistance rating of at doors. least two (2) hours around stairways, 5. Fixed wired glass vision panels may be elevators, chutes, and other placed in corridor walls, vertical openings between floors. provided they do not exceed eighty four- 4. All interior walls and partitions in hundredth square meters buildings of fire-resistive and (0.84 m2) in size and are installed in noncombustible approved steel frames. Fixed wired construction shall be composed on non- glass vision panels may be installed in combustible wooden doors, provided they materials. do not exceed forty six-hundredth square 5. Every health care sleeping room shall meters (0.46 m2) size and have an outside window or are installed in approved steel frames. outside door arranged and located so that it 159 can be opened from the 6. Waiting areas of twenty three square inside without the use of tools or keys to meters (23 m2) or less on an permit the products of institutional sleeping floor of fifty six square combustion and to permit any occupant to meters (56 m2) or less on have direct access to other floors may be open to the corridor, fresh air in case of emergency. The provided that they are maximum allowable sill height shall located to permit direct supervision by the not exceed ninety one centimeters (91 cm) institutional staff so above the floor except arranged as not to obstruct any access to that in special nursing care areas the required exits. Such areas window sill may be one and a shall be equipped with an electrically half meters (1.5 m) above the floor. supervised automatic smoke C. Construction of Corridor Walls detection system installed in accordance 1. Corridors shall be separated from use with this Section. Not more areas by partitions having a fireresistance than one such waiting area is permitted in rating of at least one (1) hour. each smoke compartment. 2. These walls shall be continuous from the D. Protection of Vertical Openings and Fire- floor slab to the underside of stopping the floor or rood slab above, through any 1. Any stairway, ramp, elevator shaft, light concealed spaces such as and ventilation shaft, chute those above the, suspended ceilings and and other openings between storeys shall be through interstitial structural enclosed with and mechanical spaces. noncombustible materials in accordance 3. Doors with a twenty (20) minute fire with Section 10.2.5.2., protection rating shall be used on Section 10.2.6.2 of this IRR and this Section. openings other than those serving exits or 2. A door in a stairway enclosure shall be hazardous areas. Doors shall self-closing, shall normally be kept in closed position and shall be marked 3. Approved, supervised sprinkler system in accordance with shall be provided throughout all Section 10.2.5.3 of this IRR. hospitals, nursing homes, and residential- 3. Fire-stopping shall be provided in custodial care facilities. accordance with Section 10.2.6.5 of Replenishment of water supplies shall be this IRR. strictly considered in the E. Interior Finish design. Quick-response sprinklers shall be Interior finish of walls and ceilings in means required in smoke of egress and of any room shall compartments containing patient sleeping be Class A in accordance with Section rooms. 10.2.6.3 of this IRR, while floor finish 4. Approved, supervised sprinkler system material shall be Class A or B throughout all shall be in accordance with the hospitals, nursing homes and requirements of Section 10.2.6.5 of this IRR. residential-custodial care facilities. 5. In light hazard occupancies, required F. Alarm, Detection and Extinguishment automatic fire suppression Systems systems shall be in accordance with Section 1. Every building shall have an electrically 10.2.6.5 of this IRR for supervised automatic fire systems and shall be electrically alarm system capable of being manually interconnected with the fire alarm operated in accordance system. The main automatic fire suppression with Section 10.2.6.4 of this IRR. The fire control valve shall be alarm system shall be installed electrically monitored so that at least a local with provisions for future connection to the alarm will sound when nearest BFP station in the the valve is closed. locality. Internal audible alarm devices shall 6. If the fire suppression system is an be provided in automatic sprinkler, its piping serving accordance with Section 10.2.6.4 of this IRR. no more than six (6) sprinklers for any Pre-signal systems shall not isolated hazardous area, may be be permitted in healthcare occupancies. connected directly to a domestic water 2. An approved automatic heat and/or supply system having a smoke detection system shall be capacity sufficient to provide six (6) liters per installed in all corridors of hospitals, nursing minute per square meters homes, and residentialcustodial of floor area throughout the entire enclosed care facilities, such systems shall be installed area. As outside-screwand- in accordance yoke shutoff valve shall be installed in an with the applicable standards of the NFPA accessible location 72, but in no case shall between the sprinklers and the connection smoke detectors be spaced further apart to the domestic water than nine (9) meters on centers supply. or more than four and six-tenths meters 7. Portable fire extinguishers shall be (4.60 m) from any wall all provided in all institutional occupancies automatic heat and/or smoke detection in accordance with Section 10.2.6.5 of this systems required by this IRR. section shall be electrically inter-connected G. Hazardous Areas to the fire alarm system. Any hazardous area shall be segregated and 160 protected in accordance with Section 10.2.6.8 of this IRR. Hazardous case of either excessive temperatures or areas include, but are not ignition failure. Fire-places limited to the following: may be installed and used only in areas Boiler and heater rooms other than patient sleeping Laundries areas, provided that these areas are Kitchens separated from patient sleeping Repair shops spaces by construction having a one-hour Handicraft shops fire resistance rating. In Employee locker rooms addition thereto, the fireplace shall be *Soiled linen rooms equipped with a hearth that *Paint shops shall be raised at least ten centimeters (10 *Rooms or spaces, including shops, used for cm), and a heat tempered the storage of combustible supplies and glass fireplace enclosure guaranteed against equipment in quantities deemed breakage up to a hazardous by the Chief, BFP or his duly temperature of three hundred forty three authorized representative. (343°C) degrees Celsius. If Trash collection rooms special hazards are present, a lock on the Gift shops enclosure and other safety Those areas marked by asterisk (*) shall be precautions may be required. both separated and provided 3. Combustion and ventilation air for Boiler, with automatic fire suppression system. incinerator or heater rooms SECTION 10.2.10.4 BUILDING SERVICE shall be taken directly from and discharged EQUIPMENT directly to the outside air. A. Air Conditioning, Ventilating, Heating, 4. Any rubbish chute and linen chute Cooking and Other Service including pneumatic systems shall 161 be safeguarded in accordance with Section Equipment 10.2.6.2and 10.2.7.4 of 1. Air-conditioning, ventilating, heating, this IRR. An incinerator shall not be directly cooking and other service flue-fed nor shall any floor equipment shall be in accordance with charging chute directly connect with the Division 7 of this Chapter. combustion chamber. Any 2. Any heating device other than a central rubbish chute shall discharge into a rubbish heating plant shall be so collecting room used for designed and installed that combustible no other purpose and protected in material will not be ignited by accordance with Section 10.2.6.8 it or its appurtenances. If fuel fired, such of this IRR heating devices shall be DIVISION 11. DETENTION AND chimney or vent connected, shall take air for CORRECTIONAL OCCUPANCIES combustion directly from SECTION 10.2.11.1 GENERAL REQUIREMENTS outside, and shall be so designed and A. Definition installed to provide for Detention and correctional occupancies complete separation of the combustion shall include those used for system from the atmosphere purposes such as correctional institutions, of the occupied area. The heating system detention facilities, community shall have safety devices to residential centers and substance abuse or immediately stop the flow of fuel and shut rehabilitation centers where down the equipment in occupants are confined or housed under spaces, and other occupied areas within the some degree of restraint or smoke compartment security. to another smoke compartment. B. Occupancy 2. To be classified as Use Condition III or Use 162 Condition IV, the 1. For the application of the life safety arrangement, accessibility, and security of requirements of this Division, the the release mechanism(s) resident user category shall be divided into used for emergency egress shall be such the following five groups. that the minimum available a. Use Condition I — Free Egress. Free staff, at any time, can promptly release the movement is allowed from locks. sleeping areas and other spaces where 3. Areas housing occupancies corresponding access or occupancy is to Use Condition I shall permitted to the exterior via means of conform to the requirements of residential egress that meet the occupancies under this requirements of this IRR. Chapter. b. Use Condition II — Zoned Egress. Free Exception: Use Condition I facilities shall be movement is allowed from permitted to conform to sleeping areas and any other occupied the requirements of this Division for Use smoke compartment to Condition II facilities, provided one or more other smoke compartments. that said facilities is provided with a 24-hour c. Use Condition III — Zoned Impeded Egress. on-duty staff. Free movement is C. Occupant Load allowed within individual smoke The occupant load for which means of compartments, such as within a egress shall be provided for any residential unit comprised of individual floor shall be the maximum number of sleeping rooms and a group persons intended to occupy that activity space, with egress impeded by 163 remote-controlled release floor but not less than one (1) person for of means of egress from such a smoke each eleven and one-tenth compartment to another square meters (11.1 m2) gross floor area. smoke compartment. SECTION 10.2.11.2 EXIT DETAILS d. Use Condition IV — Impeded Egress. Free A. Types movement is restricted 1. Exits shall be restricted to the following from an occupied space. Remote-controlled permissible types; release is provided to a. Doors allow movement from all sleeping rooms, b. Stairs and smoke-proof enclosures activity spaces, and other c. Horizontal exits occupied areas within the smoke d. Exit passageways compartment to another smoke B. Capacity of Exits compartment. The capacity of means of egress shall be e. Use Condition V — Contained. Free calculated in accordance with movement is restricted from an Section 10.2.5.2 para “C” of this IRR. occupied space. Staff-controlled manual C. Number of Exits release at each door is 1. At least two (2) exits of the above types, provided to allow movement from all remote from each other, shall sleeping rooms, activity be provided for each floor or fire section of meters (46 m); and the building. 3. Any point in a sleeping room to the door 2. Exit access travel shall be permitted to be in that room shall have a common path not maximum travel distance of ten meters (10 exceeding thirty meters (30 m). m). D. Access to Exit G. Discharge from Exits Every aisle, passageway, corridor, exit 1. Exits shall be permitted to discharge into discharge, exit location and access a fenced or walled courtyard, shall be in accordance with Section 10.2.5.2 provided that not more than two walls of of this IRR. the courtyard are the E. Arrangement of Means of Egress building walls from which egress is being 1. Every sleeping room shall have a door made. Enclosed yards or leading directly to an exit courts shall be of sufficient size to access corridor, unless otherwise permitted accommodate all occupants at a by the following: distance of not less than fifteen meters (15 a. If there is an exit door opening directly to m) from the building while the outside from the room providing a net area of one and four-tenths at the ground level. square meters (1.4 m2) b. One adjacent room, such as a day room, per person. group activity space, or 2. All exits shall be permitted to discharge other common space shall be permitted to through the level of exit intervene. Where discharge. This requirement shall be waived, sleeping rooms directly adjoin a day room or provided that not more group activity space than 50 percent of the exits discharge into a that is used for access to an exit, such single fire compartment sleeping rooms shall be separated from other compartments by permitted to open directly to the day room construction having not less or space and shall be than a 1-hour fire resistance rating. 164 H. Emergency Lighting and Exit Markings permitted to be separated in elevation by a 1. Means of egress shall be illuminated in one-half or full storey accordance with Section height. 10.2.5.11 of this IRR. 2. No exit or exit access shall contain a 2. Emergency lighting shall be provided in corridor, hallway, or aisle having a accordance with Section pocket or dead end exceeding six meters (6 10.2.5.11 of this IRR. m). 3. Exit signs shall be provided in areas 3. A sally port shall be permitted in a means accessible to the public. of egress where there are 165 provisions for continuous and unobstructed SECTION 10.2.11.3 PROTECTION travel through the sally port A. Protection of Vertical Opening during an emergency egress condition. 1. Any vertical opening shall be enclosed or F. Travel Distance to Exits protected. 1. Between any room door intended as exit Exception no. 1: Unprotected vertical access and an exit shall not openings in accordance with exceed thirty meters (30 m); Section 10.2.6.2 of this IRR shall be 2. Between any point in a room and an exit permitted. shall not exceed forty six Exception no. 2: In sleeping quarters smoke accordance with Section 10.2.6.4 of this IRR, compartments, a positive alarm unprotected vertical openings shall be sequence shall be permitted. permitted in accordance with Exception: any smoke detectors required by the conditions of 10.2.6.2of this IRR, this chapter shall be provided that the height between permitted to be arranged to alarm at a the lowest and highest finished floor levels constantly attended location does not exceed seven only and shall not be required to accomplish meters (7 m). The number of levels shall not general occupant be restricted. Sleeping 166 quarters subdivided in accordance with this notification. section shall be permitted 4. Fire department notification shall be to be considered as part of the accomplished in accordance communicating space. The separation with section 10.2.6.4 of this IRR, a positive shall not be required to have a fire alarm sequence shall be resistance rating. permitted . B. Interior Finish Exception no. 1: Any smoke detectors Interior finish shall be Class A or Class B required by this chapter shall C. Detection, Alarm and Communication not be required to transmit an alarm to the Systems fire department. 1. Detention and correctional occupancies Exception no. 2: This requirement shall not shall be provided with a fire apply where staff is alarm system in accordance with Section provided at a constantly attended location 10.2.6.4 of this IRR, except as that has the capability to modified by the succeeding paragraphs. promptly notify the fire department or has 2. Initiation of the required fire alarm direct communication with system shall be by manual means in a control room having direct access to the accordance with Section 10.2.6.4 of this IRR, fire department. by means of any required 5. An approved automatic smoke detection detection devices or detection systems, and system shall be in by means of waterflow accordance with Section 10.2.6.4 of this IRR, alarm in the sprinkler system. as modified by the para 6 Exception No. 1: Manual fire alarm boxes through 8 hereof throughout all resident shall be permitted to be sleeping areas and adjacent locked, provided that staff is present within day rooms, activity rooms, or contiguous the area when it is common spaces. occupied and staff has keys readily available 6. Smoke detectors shall not be required in to unlock the boxes. sleeping rooms with four or Exception No. 2: Manual fire alarm boxes fewer occupants. shall be permitted to be 7. Other arrangements and positioning of located in a staff location, provided that the smoke detectors shall be staff location is attended permitted to prevent damage or tampering, when the building is occupied and that the or for other purposes. staff attendant has direct Such arrangements shall be capable of supervision of the sleeping area. detecting any fire, and the 3. Occupant notification shall be placement of detectors shall be such that accomplished automatically in the speed of detection is equivalent to that provided by the spacing b. Class III standpipe and hose systems shall and arrangements be provided for all required by the installation standards nonsprinklered buildings over two storeys in referenced in Section 10.2.6.4of height. this IRR. Detectors shall be permitted to be Exception No. 1: Separate Class I and Class II located in exhaust ducts systems shall be from cells, behind grilles, or in other permitted in lieu of a Class III system. locations. E. Subdivision of Building Spaces 8. Smoke detectors shall not be required in 1. Every storey used for sleeping by Use Condition II open residents, or any other storey with an dormitories where staff is present within the occupant load of fifty (50) or more persons, dormitory whenever the shall be subdivided into dormitory is occupied. compartments by means of smoke barrier. D. Extinguishment Requirements 2. The requirement for subdivision of 1. All buildings classified as Use Condition II, building space shall be permitted as Use Condition III, Use follows: Condition IV, or Use Condition V shall be a. By smoke compartments having exit to protected throughout by an the public way, provided approved, supervised automatic sprinkler that such exit serves only one area and has system in accordance with no opening to other Section 10.2.6.5 of this IRR. areas; 2. The automatic sprinkler system required b. A building separated from the resident by the preceding paragraph housing area by 2 – hour fire shall be fully supervised and electrically resistance rating or 14 meters of open area ; connected to the fire alarm and system. c. Secured open area holding a space 3. Portable fire extinguishers shall be located 15 meters from the provided in accordance with housing area that provides 1.4 m2 or more Section 10.2.6.5 para “C” of this IRR. of refuge area for each 167 person. Exception No. 1: Access to portable fire F. Hazardous Areas extinguishers shall be 1. Any hazardous area shall be protected in permitted to be locked, provided that accordance with Section personnel are on duty on a 24- 10.2.6.8 The areas described in Table 13 hour basis and keys are readily available to shall be protected as unlock access to the indicated. extinguishers. 168 Exception No. 2: Portable fire extinguishers Table 13: HAZARDOUS AREA OPERATION shall be permitted to be HAZARDOUS AREA DESCRIPTION located at staff locations only. SEPARATION/PROTECTION 4. Standpipe and hose systems shall be Areas not incidental to resident housing 2 provided in accordance with hours Section 10.2.6.5 “C” of this IRR as follows: Boiler and fuel-fired heater rooms 1 hour a. Class I standpipe systems shall be Central or bulk laundries > 9.3 m2 1 hour provided for any building over Commercial cooking equipment In two storeys in height. accordance with 3.601 Commissaries Smoke resistant Employee locker rooms Smoke resistant per occupant shall be provided on each side Hobby/handicraft shops Smoke resistant of the smoke barrier for Maintenance shops Smoke resistant 169 Padded cells 1 hour the total number of occupants in adjoining Soiled linen rooms 1 hour compartments. This space Storage rooms >4.6 m2 in area but 9.3 m2 in shall be readily available wherever area storing combustible material Smoke occupants are moved across the resistant smoke barrier in a fire emergency. Storage rooms >9.3 m2 storing combustible 6. Doors shall provide resistance to the materials 1 hour passage of smoke. Swinging doors Trash collection rooms 1 hour shall be self-latching, or the opening Doors used to access the areas specified resistance of the door shall be not above shall meet the less than 22 N. requirements for doors at smoke barriers for 7. Doors in smoke barriers shall conform to the applicable use the requirements for doors in condition. means of egress and shall have locking and 2. Where smoke barriers are required, they release arrangements shall limit the occupant load according to the applicable use condition. to not more than 200 residents in any 8. Vision panels shall be provided in smoke smoke compartment and limit barriers at points where the the travel distance to a door in a smoke barrier crosses an exit access corridor. barrier as follows: 9. Smoke dampers shall be provided. a. The distance from any room door SECTION 10.2.11.4 BUILDING SERVICE required as exit access shall not EQUIPMENT exceed forty five meters (45 m). A. Air-conditioning, ventilating, heating, b. The distance from any point in a room cooking and other service shall not exceed sixty meters equipment shall be in accordance with (60 m). Division 7 of this Chapter, and 3. Any required smoke barrier shall be shall be installed in accordance with the constructed in accordance with manufacturer's specifications, Section 10.2.6.9. Barriers shall be of except as modified in the following substantial construction and shall paragraphs. have structural fire resistance. B. Combustion and ventilation air for boiler 4. Openings in smoke barriers shall be or incinerator shall be taken protected in accordance with directly from and discharged directly to the Section 10.2.6.9 of this IRR, provided, that, outside air. there shall be no restriction C. Any rubbish chute and linen chute on the total number of vision panels in any including pneumatic systems shall be barrier. Provided, further, safeguarded in accordance with Sections that sliding doors in smoke barriers that are 10.2.6.2 and 10.2.7.4 of this IRR. designed to normally be An incinerator shall not be directly flue-fed kept closed and are remotely operated from nor shall any floor charging a continuously attended chute directly connect with the combustion location shall not be required to be self- chamber. Any trash chute closing. shall discharge into a trash collecting room 5. Not less than fifty six hundredths square used for no other purpose and meters (0.56 m2) of net area protected in accordance with Section without meals, but without separate cooking 10.2.6.8 of this IRR. facilities for individual occupants. DIVISION 12. RESIDENTIAL OCCUPANCIES E. Single-and-Two Family Dwellings – SECTION 10.2.12.1 CLASSIFICATION includes detached dwellings in which Residential occupancies shall include all each living unit is occupied by members of a occupancies so classified in Division 3 of single family. this IRR. They shall be classified in the SECTION 10.2.12.2 REQUIREMENTS following groups, subject to determination A. Occupant Load by the Chief, BFP or his duly authorized The occupant load of residential representative. occupancies in number of persons for A. Hotels – includes buildings or groups of whom exits are to be provided except in building under the same detached single-and-two-family management in which there are more than dwellings shall be determined on the basis fifteen (15) sleeping of one (1) person per eighteen accommodations for hire, primarily used by and six-tenths square meters (18.6 m2) transients who are lodged gross floor area, or the maximum with or without meals, whether designated probable population of any room or section as a hotel, inn, motel, or by under consideration, any other name. So-called appartelle, whichever is greater. The occupant load of condotel or pension houses shall any open mezzanine or be classified as hotels, because they are balcony shall be added to the occupant load potentially subject to transient of the floor below for the 170 purpose of determining exit capacity. occupancy like that of hotels. B. Capacity of Exits B. Dormitories – includes buildings where Capacity of means of egress shall be in group sleeping accommodation accordance with Section 10.2.5.2 are provided for persons, not members of paragraph “C” of this IRR. the same family group in one C. Maintenance of Exits room or in series of closely associated room 1. No door in any means of egress shall be under joint occupancy and locked against egress when single management, as in college the building is occupied. dormitories, convents, fraternity houses, 2. No residential occupancy shall have its military barracks, and the like. means of egress pass through C. Apartment Buildings – includes buildings any nonresidential occupancy in the same containing three (3) or more living building, except in units independent cooking and bathroom buildings provided with approved, facilities, whether designated supervised sprinkler system provided as condominium, row house, apartment that the means of egress shall not pass house, tenement, garden through a high hazard content apartment, or by any other name. 171 D. Lodging or Rooming Houses – includes area as determined by the City/Municipal building in which separate sleeping Fire Marshal having rooms are rented providing sleeping jurisdiction and the means of egress shall be accommodations for a total of separated by a fifteen (15) or less persons, on either a construction of not less than 1 hour. transient or permanent basis; with or 3. No guest room or guest suite shall be permitted to be located above a nonresidential occupancy except when the and used only for mechanical equipment, guest room or guest suite storage, and service and its exits are separated from the operations (other than kitchens which are nonresidential occupancy by considered part of the construction having a fire resistance rating hotel occupancy) shall have exits of not less than 1 hour or appropriate to its actual when the nonresidential occupancy is occupancy in accordance with applicable protected throughout by sections of this approved, supervised sprinkler system. Chapter. SECTION 10.2.12.3 HOTELS AND 172 DORMITORIES d. The same stairway or other exit required A. Requirements to serve any one upper 1. Any ballroom assembly or exhibition hall, floor may also serve other upper floor, and other space used for except that no inside open purposes of public assembly shall be in stairway, escalator, or ramp may serve as a accordance, with Division 7 of required egress from this Chapter. Restaurant having a capacity of more than one floor. fifty (50) or more persons 2. Types of Exits shall be treated as places of assembly. Exits, arranged in accordance with Division 5 2. Any dormitory divided into suites of of this Chapter, shall be rooms, with one or more bedrooms one or more of the following types: opening into a living room or study that has a. Doors, provided that doors in any means a door opening into a of egress shall not be common corridor serving number of suites, locked against egress when the building is shall be classified as an occupied. Delayed apartment building. egress locks may be permitted, provided B. Exit Details that not more than one 1. Requirements such is located in any one egress path. a. Any room having a capacity of less than b. Stairs and smokeproof enclosures. fifty (50) persons with an c. Ramps. outside door at street or ground level may d. Horizontal exits. have such outside door 3. Minimum Corridor Width as a single exit provided that no part of the Corridors, other than those in within room or area is more individual guest rooms or individual than fifteen and one-fourth meters (15.25 guest suites, shall be of sufficient width to m) from the door accommodate the required measured along the natural path of travel. occupant load and shall not be less than one b. Any floor below the floor of exit discharge hundred twelve occupied for public centimeters (112 cm). purposes shall have exits arranged in 4. Number of Exits accordance with the Not less than two (2) exits shall be accessible subsequent paragraph of this Section, with from every floor, access thereto in including floors below the floor of exit accordance with Section 10.2.5.2 of this IRR. discharge and occupied for c. Any floor below the floor of exit discharge public purposes. not open to the public 5. Travel Distance to Exits a. Any exit shall be such that it will not be through areas on the floor of exit discharge necessary to travel more provided: than thirty meters (30 m) from the door of i. Such exits discharge to a free and any room to reach the unobstructed way to the nearest exit. exterior of the building, which way is readily b. Travel distance within a guest room or visible and guest suite to a corridor door identifiable from the point of discharge from shall not exceed twenty three meters (23 m) the exit. in buildings not ii. The floor of discharge into which the exit protected by an approved, supervised discharge is provided automatic sprinkler system. with automatic fire suppression system and c. Travel distance within a guest room or any other portion of guest suite to a corridor door the level of discharge with access to the shall not exceed thirty eight meters (38 m) discharge area is in buildings protected by provided with automatic fire suppression an approved, supervised sprinkler system. system or separated 173 from it in accordance with the requirements 6. Access to and Arrangement of Exits for the enclosure of a. Access to all required exits shall be in exit. (See Section 10.2.5.2 of this IRR), accordance with Section iii. The entire area on the floor of discharge 10.2.5.2 of this IRR, shall be unobstructed, is separated from and shall not be veiled areas below by construction having a from open view by ornamentation, curtain, minimum fire-resistance or other appurtenance. rating of two (2) hours. b. Means of egress shall be so arranged that, 8. Lighting and Signs from every point in any a. Each public space, hallway, stairway, or open area or from any room door, exits will other means of egress be accessible in at least shall have illumination in accordance with two (2) different directions. Section 10.2.5.11 of this c. Doors between guest rooms and corridors IRR. Access to exit shall be continuously shall be self-closing. illuminated at all times. Any d. Common path of travel shall not exceed hotel and dormitory shall have emergency ten meters (10 m). lighting installed in e. Dead end corridors shall not exceed six individual guest rooms or guest suites, meters (6 m). hallways, landings of 7. Discharge from Exits stairways and other appropriate areas as a. At least half of the required number of determined by the units of exit from upper C/MFM having jurisdiction. floors, exclusive of horizontal exits, shall 174 load directly to the street or b. Every exit access door from public through a yard, court, or passageway with hallways or from corridors on protected openings floors with sleeping accommodations shall and separated from all parts of the interior have an illuminated sign of the buildings. in accordance with Section 10.2.5.12 of this b. A maximum of fifty percent (50%) of the IRR. Where exits are not exits may discharge visible in a hallway or corridor, illuminated directional signs shall be provided to indicate the direction of exit. iii. Places of assembly – See Section 10.2.8.1 C. Protection of this IRR; 1. Protection of Vertical Openings iv. Individual guest rooms – B, or C; and a. Every stairway, elevator shaft and other b. Existing Interior Finish vertical openings shall be i. Exits – Class A or B; enclosed or protected in accordance with ii. Lobbies and Corridors; Section 10.2.6.2 of this ii.a. Used as exit access – Class A or B IRR. ii.b. Not used as required exit access – Class b. Any required exit stair which is so located A, B or C that it is necessary to pass iii. Places of Assembly – See Section through the lobby or other open space to 10.2.8.16 of this IRR; reach the outside of the iv. Individual guest rooms – Class A, B or C; building shall be continuously enclosed and down to the lobby level. v. Other rooms – Class A, B or C. c. No floor below the floor of exit discharge, 4. Fire Detection and Alarm System used only for storage, a. An automatic fire detection and alarm heating requirements, or other than hotel system, in accordance with occupancy open to Section 10.2.6.4 of this IRR, shall be guest or the public, shall have unprotected provided for any hotel or openings to floors used dormitory having accommodations for for hotel purposes. fifteen (15) or more guests. 2. Protection of Guest Rooms For less than 15 guests, a manual fire alarm a. In any new hotel building every corridor system shall be installed. shall be separated from b. Every sounding device shall be of such guest rooms by partitions having at least a character and so located one (1) hour fire as to arouse all occupants of the building or resistance rating. section thereof b. Each guest room shall be provided with a endangered by fire. door having a fire c. An alarm-sending station and manual fire protection rating at least twenty (20) alarm box shall be minutes. provided at the hotel desk or other c. Openings in corridor partitions other than convenient central control door openings shall be point under continuous supervision of prohibited. responsible employees. d. Doors that open directly onto exit access d. Suitable facilities shall be provided for corridors shall be selfclosing immediate notification of the and self-latching. BFP. 3. Interior Finish e. Positive fire alarm sequence may be Interior finish, in accordance with Section permitted. 10.2.6.3 of this IRR and f. Hotels and dormitories including its guest subject to the limitations and modifications rooms and guests suites therein specified, shall be shall be required to be equipped with both as follows: audible and visible a. For new construction or new Interior Finish notification appliance. i. Exits – Class A or Class B; g. In hotels and dormitories not equipped ii. Lobbies, corridors – Class A or Class B; with automatic fire 175 detection and alarm system, guest rooms, a. Any room containing high pressure living area and sleeping boilers, refrigerating machinery, rooms within a guest suite shall be installed transformers, or other service equipment to with single-station possible explosion shall smoke detectors. not be located directly under or directly 176 adjacent to exits. All such 5. Extinguishing Requirements rooms shall be effectively cut off from other a. All buildings shall be protected parts of the building as throughout by an approve, specified in Section 10.2.6.8 of this IRR. supervised sprinkler system except in b. Every hazardous area shall be separated buildings where all guest from other parts of the sleeping rooms or guest suites have a door building by construction having a fire- opening directly resistance rating of at least outside at the street or grade level or one (1) hour and communicating openings exterior exit access arranged shall be protected by in accordance with Section 10.2.5.2 of this approved automatic or self-closing fire IRR in buildings up to doors, or such area shall be and including three (3) storeys in height. equipped with automatic fire suppression b. Listed quick response or listed residential system. Where a hazard sprinklers shall be used is high as determined by the City/Municipal throughout guest rooms and guest room Fire Marshal having suites. jurisdiction, both fire-resistive construction c. Portable fire extinguishers shall be and automatic fire installed in accordance with suppression system shall be used. Hazardous Section 10.2.6.7 of this IRR. areas include, but are 6. Subdivision of Building Spaces not limited to: a. In buildings not protected by an 177 approved, supervised automatic i. Boiler and heater rooms sprinkler system, each hotel guest room, ii. Laundries including guest suites, and iii. Repair shops dormitory rooms shall be separated from iv. Rooms or spaces used storage of other guest rooms or combustible supplies and dormitory rooms by walls and floors having equipment in quantified deemed hazardous fire resistance ratings of by the not less than one (1) hour. City/Municipal Fire Marshal having b. In buildings protected throughout by an jurisdiction. approved, supervised D. Building Service Equipment automatic sprinkler system, each hotel guest 1. Air-Conditioning and Ventilation room, including guest a. Every air conditioning installation shall suites, and dormitory room shall be comply with Division 7 of this separated from other guest Chapter. rooms or dormitory rooms by walls and b. No transom/windowpane shall be floors constructed a fire installed in partition of sleeping barriers having fire resistance ratings of not rooms in new buildings. In existing buildings less than one half (½) transoms shall be fixed hour. in the closed position and shall be covered 7. Hazardous Areas or otherwise protected to provide a fire-resistance rating at least other area not a part of the apartment equivalent to that of the served, may have a single wall in which they are installed. exit. 2. All other building services equipment Exception 2: Apartment buildings of not installed or used in hotels and more than three storeys in dormitories shall comply with Division 7 of height with not more than six (6) living units this Chapter. per floor, with a smokeproof SECTION 10.2.12.4 APARTMENT BUILDINGS enclosure or an outside stairway as the exit, A. General Requirements immediately 1. Any apartment building which complied accessible to all apartments served thereby, with all of the preceding may have a single requirements of this Section for hotels may exit. be considered as a hotel Exception 3: Any building not more than and as such, the following requirements for three (3) storeys in height apartment buildings will with no floor below the floor of exit not be applicable. discharge or, in case there is 2. Every individual unit covered by this such a floor, with the street floor Section shall at least comply with construction of at least one-hour the minimum provisions of Section 10.2.12.6 fire resistance, may have a single exit, under of this IRR entitled Single the following and Two-Family Dwellings. conditions: B. Exit Details i. The stairway is completely enclosed with a 1. General Types and Capacities of Exits partition having a a. Exits of the same arrangement, types and fire resistance rating of at least one (1) hour capacities, as required with self-closing fire by Section 10.2.12.3 of this IRR shall be doors protecting all openings between the provided. stairway enclosed b. Street floor exits shall be sufficient for the and the building. occupant load of the ii. The stairway does not serve any floor street floor plus the required capacity of below the floor of exit discharge, stairs and ramps iii. All corridors serving as access to exits at discharging onto the street floor. least a one (1) hour fireresistance 178 rating. 2. Number of Exits iv. There is not more than six and one-tenth a. Every living unit shall have access to at meters (6.10 m) of least two (2) separate exits. travel distance to reach an exit from Exception 1: Any living unit, which has an exit entrance door of any living directly to the street unit. or yard at ground level or by way of an 3. Minimum Corridor Width outside stairway that serve a. Corridors with a required capacity of more a maximum of two units or an enclosed than 50 persons shall be stairway with fire-resistance of sufficient width to accommodate the rating of one (1) hour or more serving that required occupant load apartment only and not but have a width of not less than one communicating with any floor below the hundred twelve centimeters floor of exit discharge or (112 cm). b. Corridors with a required capacity of not IRR. All apartment buildings shall have more than 50 persons shall emergency lighting. not be less than ninety one centimeters (91 b. Signs in accordance with Section cm). 10.2.5.12 of this IRR shall be 179 provided in all apartment buildings . 4. Access to Exits C. Protection a. Exits shall be remote from each other, as 1. Segregation of Dwelling Units required by Section Dwelling units in row apartments shall be 10.2.5.2 of this IRR. separated from each other b. Exits shall be so arranged that there are by partition walls having a fire resistance no dead-end pockets, rating of four (4) hours. Such hallways, corridors, passageways or courts. walls shall be constructed solidly and c. Exits and exit access shall be so located continuously from the ground to that: level one (1) meter above the ridge line of i. It will not be necessary to travel more than the roof. fifteen and one-half 180 meters (15.50 m) within any individual living 2. Protection of Vertical Openings unit to reach the Protection of vertical openings shall be the nearest exit, or to reach an entrance door of same as required for hotels. the apartment (See Section 10.2.12.3 of this IRR) There which provides access through a public shall be no unprotected corridor to an exit on vertical opening in any building or fire the same floor level. section with only one exit. ii. Within any individual living unit it will not 3. Interior Finish be necessary to a. For new construction and new interior traverse stairs more than one (1) storey finish above or below the floor i. Exits - Class A or Class B; level of the apartment to the nearest exit or ii. Lobbies, corridors and public spaces - entrance door. Class A or B; and iii. The entrance door to any apartment is iii. Individual living units - Class A or B or C within thirty one meters b. Existing Interior Finish (31 m) of an exit of within forty six and a half i. Exits - Class A or B meters (46.50 m) in ii. Other spaces - Class A or B or C. a building protected by approved, 4. Alarm Systems supervised sprinkler system in a. Every apartment building of four (4) accordance with Section 10.2.6.5 of this IRR. storeys or more in height, or d. Doors between apartments and corridors more than twelve (12) apartment units shall shall be self-closing. have an automatic fire 5. Discharge from Exits detection and alarm system in accordance Discharge from exits shall be the same as with Section 10.2.6.4 of required for hotels. (See this IRR, except buildings provided with Section 10.2.12.3 of this IRR) approved, supervised 6. Lighting and Signs sprinkler protection in accordance with a. Every public space, hallway, stairway, and Section 10.2.6.5 of this IRR. other means of egress b. Apartment buildings of not more than shall have illumination in accordance with three (3) storeys in height Section 10.2.5.11 of this shall be provided with manual fire alarm suppression system shall be provided. system, provided that D. Building Service Equipment dwelling units shall be installed with single – 1. Air-Conditioning and Ventilation – Air station or multi –station conditioning and ventilation, smoke detectors. when provided, shall be in accordance with 5. Extinguishing Requirements Division 7 of this Chapter. a. All buildings shall be protected 2. All other building services equipment throughout by an approve, installed or used in hotels and supervised sprinkler system except in dormitories shall comply with Division 7 of buildings where all guest this Chapter. sleeping rooms or guest suites have a door SECTION 10.2.12.5 LODGING OR ROOMING opening directly HOUSES outside at the street or grade level or A. General exterior exit access arranged 1. This Section applies only to lodging or in accordance with Section 10.2.5.2 of this rooming houses providing IRR in buildings up to sleeping accommodations for less than and including three (3) storeys in height. fifteen (15) persons, as b. Listed quick response or listed residential specified in Section 10.2.12.1 of this IRR. sprinklers shall be used 2. In addition to the following provisions, throughout all dwelling units. every lodging or rooming house c. Portable fire extinguishers shall be shall comply with the minimum installed in accordance with requirements for detached single and Section 10.2.6.5 of this IRR. two family dwellings. 181 B. Means of Escape Requirement 6. Hazardous Areas 1. Every sleeping room and living area shall a. Every hazardous area shall be separated have access to two means of from other parts of the escape complying with that of single or two building construction having a fire-resistance family dwelling. rating of at least one 2. Every sleeping room above or below the (1) hour. Communicating openings shall be street floor shall have access protected by to two (2) separate means of exit, at least approved automatic or self-closing fire one (1) of which shall consist doors. Hazardous areas of an enclosed interior stairway, an exterior include, but shall not be limited to: stairway, a fire escape or a • Boiler and heater horizontal exit. rooms 182 • Rooms or spaces used for 3. All exits shall be arranged to provide a storage of combustible supplies safe path of travel to the and equipment in quantities outside of the building without traversing deemed hazardous by the any corridor or space C/MFM having jurisdiction. exposed to an unprotected vertical opening. • Laundries 4. Any sleeping room below the street floor • Repair Shops shall have direct access to b. Where the hazard is high as determined the outside or the building. by the C/MFM having C. Alarm System jurisdiction, both fire-resistant construction A manual fire alarm system shall be and automatic fire provided in accordance with Section 10.2.6.4 of this IRR. through another room or apartment not SECTION 10.2.12.6 SINGLE AND TWO FAMILY under the immediate DWELLINGS control of the occupant of the first room or A. General his family, not through a This Section covers detached single and two bathroom or other space subject to locking. family dwellings as specified d. No exit access from sleeping rooms to in Section 10.2.12.1 of this IRR. Where the outside shall be less than occupancy is so limited, the only ninety centimeters (90 cm) wide. requirements applicable are those in this 183 Section. 2. Doors B. Means of Escape Requirements a. No doors in the path of travel providing 1. Number, Type and Access to Means of means of escape shall be Escape less than seventy centimeters (70 cm) of a. In any dwelling of more than two (2) clear width. rooms, every room used for b. Every closet door latch shall be such that sleeping, living or dining purposes shall have children can open the at least two (2) means door from inside the closet. of escape at least one (1) of which shall be a c. Every bathroom door lock shall be door or stairway designed to permit the opening providing a means of unobstructed travel to of the locked door from the outside in an the outside of the emergency. building at street or ground level. No room 3. Stairs or space shall be The width, risers, and treads of every stair occupied for living or sleeping purposes shall comply at least with the which is accessible only by minimum requirements for stairs, as a ladder, folding stairs or through a trap described in Section 10.2.5.4 of this door. IRR. b. Every sleeping room shall have at least C. Interior Finish one (1) outside window. Interior finish of occupied spaces of new Such window could be opened from the buildings shall be Class A, B or C inside, without the use of as defined in Section 10.2.6.3 of this IRR and tools, keys or special effort or knowledge to in existing buildings the interior provide a clear finish shall be Class A, B, C or D. opening of not less than five hundred sixty D. Building Service Equipment millimeters (560 mm) in No heating equipment such as stove or width and eight hundred millimeters (800 combustion heater shall be so mm) in height. The located as to block escape in case of fire bottom of the opening shall be not more arising from malfunctioning of than one hundred twenty the stove or heater. two centimeters (122 cm) above the floor, DIVISION 13. MERCANTILE OCCUPANClES except if the room has SECTION 10.2.13.1 GENERAL REQUIREMENTS two (2) doors providing separate ways of A. Classification of Occupancy escape or has a door 1. Mercantile occupancies shall include all leading directly outside of the building. buildings and structures or c. No required path of travel to the outside parts thereof with occupancy as described in from any room shall be Division 3 of this Chapter. 2. Sub-classification of Occupancy c. A balcony or mezzanine floor having an a. Mercantile occupancies shall be classified area less than one-half as follows: (1/2) of the floor below shall not be counted i. Class A. AII stores having aggregate gross as a floor level for the area of two thousand purpose of applying the classification, but if seven hundred eighty seven square meters there are two (2) (2,787 m2) or more, balconies or mezzanine floors, one (1) shall or utilizing more than three (3) floor levels be counted. for sales purposes. d. Storeys not used for sales above or below ii. Class B. All stores of less than two sales floor are not thousand seven hundred counted in the height classification. eighty seven square meters (2,787 m2) e. A mezzanine less than or equal to 1/3 the aggregate area, but area (new) or less than or 184 equal to ½ the area (existing) of the floor over two hundred eighty seven square below is permitted. meters (287 m2), or f. Where a number of stores under different utilizing any balcony, mezzanine or floor management are above or below the located in the same building or in adjoining street floor level for sales purposes except buildings with no fire that if more than wall or other standard fire separations in three (3) floors are utilized, the store shall between, the aggregate be considered Class A, gross of all such stores shall be used in regardless of area. determining classification. iii. Class C. All stores of two hundred seventy B. Classification of Hazard eight square meters The contents of mercantile occupancies (278 m2) or less gross area used for sales shall be classified in accordance purposes on the street with Division 4 of this Chapter. floor only. Exception: Mercantile occupancies classified b. For the purpose of Class A and Class B, C, as high hazard in the aggregate gross accordance with Division 4 of this Chapter area shall be the total area of all floors used shall meet the following for mercantile additional requirements: purposes and, where a store is divided into 1. Exits shall be located not more than sections by fire walls twenty three (23) meters of travel shall include the area of all sections used for from any point is needed to reach the sales purposes. Areas nearest exit. of floors not used for sales purposes, such as 2. From every point there shall be at least a floor below the street two (2) exits accessible by floor used only for storage and not open to 185 the public, shall not be travel in different directions (no common counted for the purpose of the above path of travel). classifications, but exits shall 3. All vertical opening shall be enclosed. be provided for such non-sales area in C. Occupant Load accordance with their 1. For purposes of determining required occupancy, as specified by other Divisions of exits, the occupant load of this Chapter. mercantile buildings or parts of building used for mercantile purposes shall not be less than the following: g. Covered Walls: one (1) person for each a. Street floor, one (I) person for each two two and eight-tenths and eight-tenths square square meters (2.8 m2) gross floor area. meters (2.8 m2) gross floor area. In stores 2. Where any required egress capacity from with no street floor as a balcony or mezzanine defined in Division 2 of this Chapter, but passes through the room below, that with access directly from required capacity shall be the street by stairs or escalators, the added to the required egress capacity of the principal floor at the point of room below. entrance to the store shall be considered 186 the street floor. In stores SECTION 10.2.13.2 EXIT DETAILS where due to difference in grade of streets A. General on different sides, there 1. All exit facilities shall be in accordance are two (2) or more floors directly accessible with Division 5 of this Chapter from the street (not and this Division. Only types of exits including alleys or similar back streets), each specified in this Section shall be such floor shall be used as required exit facilities in any considered a street floor for the purpose of mercantile occupancy. determining occupant 2. Where a stairway, escalator, outside stair, load. or ramp serves two (2) or b. Due to differences in grade of streets on more upper floors, the same stairway or different sides, two or other exit required to serve more floors directly accessible from streets anyone (1) upper floor may also serve other (not including alleys or upper floors. similar back streets) exist; each such floor is Exception: No inside open stairway, permitted to be escalator, or ramp may serve as considered a street floor. The occupant load required egress facility from more than one factor is one person (1) floor. for each 3.7 square meters of gross floor 3. Where there are two (2) or more floors area of sales space. below the street floor, the same c. Sales floors below the street floor: same stairway or other exit may serve all floors, as street floor. but all required exits from d. Upper floors, used for sale: one (1) person such areas shall be independent of any open for each five and six stairways between street tenths square meters (5.6 m2) gross floor and the floor below it. area. 4. Where a level outside exit from upper e. Floor or sections used only for offices, floors is possible owing to hills, storage, shipping and not such outside exits may serve instead of open to the general public: one (1) person horizontal exits. If, however, for each nine and such outside exits from the upper floor also three-tenths (9.3) square meters gross floor serve as an entrance from area. a principal street, the upper floor shall be f. Floors or sections used for assembly classified as a street, and is purposes: occupant load subject to the requirements of this Section determined in accordance with Division 8 of for street floors. this Chapter. B. Types of Exits 1. Exits shall be restricted to the following occupancy, provided that the travel distance permissible types: to the exit or to a mall a. Doors; does not exceed thirty meters (30 m), and b. Stairs and Smokeproof Enclosures; the storey on which the c. Horizontal exits; and occupancy is located, and all communicating d. Ramps. levels that are 2. In existing interior stair or fire escape not traversed to reach the exit or mall, are complying with Section protected throughout by an 10.2.5.4 or Section 10.2.5.10 of this IRR may approved, supervised automatic sprinkler be continued in use, subject system in accordance with to the approval of the City/Municipal Fire Section 10.2.6.5 of this IRR. Marshal having jurisdiction. 5. A single means of egress to an exit or to a C. Capacity of Means of Egress mall shall be permitted from 1. The capacity of means of egress shall be a mezzanine within any Class A, Class B, or in accordance with Section Class C mercantile 10.2.5.2 of this IRR. occupancy, provided that the common path 2. In Class A and Class B mercantile of travel does not occupancies, street floor exits shall exceed thirty meters (30 m) if protected be sufficient for the occupant load of the throughout by an approved, street floor plus the required supervised automatic sprinkler system in 187 accordance with Section capacity of stairs and ramps discharging 10.2.6.5 of this IRR. through the street floor. E. Arrangement and Access of Exits D. Number of Exits 1. Exits shall be remote from each other and 1. Exits shall comply with the following, shall be arranged to except as otherwise permitted by minimize the possibility that both may be paragraphs (2) through (5) below: blocked by an emergency. a. The number of means of egress shall be in Exception: A common path may be accordance with Section permitted for the first fifteen (15) 10.2.5.2 of this IRR. meters from any point. (See Section b. Not less than two separate exits shall be 10.2.13.1 of this IRR, if there are provided on every storey. high hazard contents). c. Not less than two separate exits shall be 2. The aggregate width of all aisles leading accessible from every part to each exit shall be equal to of every storey. 188 2. Exit access as required by para (1) (c) at least the required width of the exit. above, shall be permitted to 3. In no case shall aisle be less than eighty include a single exit access path for the centimeters (80 cm) in clear distances permitted as width. common path of travel. 4. In Class A stores, at least one (1) aisle of 3. A single means of egress shall be one and one-half meters (1.5 permitted in a Class C mercantile m) minimum width shall lead directly to an occupancy, provided that the travel distance exit. to the exit or to a mall 5. In the only means of entrance of does not exceed twenty meters (23 m). customer is through one (1) exterior 4. A single means of egress shall be wall of the building, two-thirds (2/3) of the permitted in a Class C mercantile required exit width shall be located in this wall, H. Doors 6. At least one-and one-half (1.5) of the 1. Every street floor door shall be in required exits shall be so located accordance with Section 10.2.5.3of as to be reached without going through this IRR, and a horizontal exit door, if used, check-out stands In no care in accordance with Section shall checkout stands or associated railings 10.2.5.6 of this IRR. or barriers obstruct exits or 2. All doors at the foot of stairs from upper required aisles or approached thereto. floors or at the end of stairs F. Measurement of Travel Distance to Exits leading to floors below the street floor shall Travel distance to exits shall be measured in swing with the exit travel. accordance with Section I. Exit Signs and Lighting 10.2.5.2 of this IRR. 1. Every mercantile occupancy shall have Exception: An increase in the above travel exit illumination and signs in distance to forty six (46) meters accordance with Section 10.2.5.11 and shall be permitted in a building completely 10.2.5.12 of this IRR. protected by an approved, 2. Every Class A and Class B store shall have supervised sprinkler system in accordance emergency lighting facilities with Section 10.2.6.5 of this IRR. conforming to Section 10.2.5.11 of this IRR. G. Discharge from Exits SECTION 10.2.13.3 PROTECTION In buildings with automatic fire suppression A. Protection of Vertical Openings system in accordance with 1. Any stairway, elevator shaft, escalator Section 10.2.6.5 of this IRR, one-half (0.5) of opening or other critical rated number of exit units of opening shall be enclosed or protected in stairways, escalators or ramps serving as accordance with Section required exits from floors above 10.2.6.2 of this IRR, except as permitted in or below the street floor, may discharge this Section. through the main street floor 2. Exceptions for Class A or Class B stores area, instead of directly to the street, a. In any Class A or Class B store, openings provided that: may be unprotected 1. Not more than one-half (0.5) of the between any two (2) floors, such as open required exit units from any single stairs or escalators floor considered separately discharge between street floor and the floor below, or through the street floor area. open stairs to second 2. The exits are enclosed in accordance with floor or balconies or mezzanines above the Section 10.2.6.2 of this IRR, street floor level (not to the street floor. both to the floor below the street floor and 3. The distance of travel from the above unless protected termination of the enclosure to an throughout by an approved, supervised outside street door is-not more than fifteen automatic fire suppression and one-half meters (15 .5 system). m). b. In any Class A or Class B store protected 4. The street floor doors provide sufficient throughout by an units of exit width to serve exits approved, supervised sprinkler system in discharging through the street floor in accordance with Section addition to the street floor itself, 10.2.6.5 openings may be unprotected per Section 10.2.13.1 o f this IRR. under the conditions 189 permitted by Section 10.2.6.2 of this IRR or 4. In a Class C store, interior finish shall be between the street floor Class A, B or C in accordance and the floor below the street and between with Section 10.2.6.3 of this IRR. street floor and C. Alarm Systems second floor or, if no openings to the floor Class A and Class B stores shall be provided below the street floor, with an automatic and between street floor, street floor balcony, or manual fire alarm system in accordance with mezzanine, and Section 10.2.6.4of this IRR. second floor, but not between more than D. Automatic Sprinkler Protection three (3) floor levels. Approved, supervised automatic sprinkler c. In existing Class A or Class B stores only system protection shall be one (1) floor above those installed in accordance with Section 10.2.6.5 otherwise permitted may open if such floor of this IRR in all mercantile is not used for sales occupancies as follows: purposes and the entire building is 1. Throughout all mercantile occupancies protected by an approved, three or more storeys in height. supervised automatic fire suppression 2. Throughout all mercantile occupancies system. exceeding one thousand one 190 hundred fifteen square meters (1,115 m2) in 3. Exceptions for Class C stores gross area. In any Class C store, openings may be 3. Throughout floor below the street floor unprotected between street having an area exceeding two floor and balcony or mezzanine. hundred thirty two square meters (232 m2) B. Interior Finish when used for the sale, 1. Interior finish of exits of all stores shall be storage or handling of combustible goods Class A and Class B in and merchandise. accordance with Section 10.2.6.3 of this IRR. E. Hazardous Areas 2. In any Class A or Class B store, interior 1. An area used for general storage, boiler or finish of the ceiling shall be Class furnace rooms, fuel A or Class B in accordance with Section 191 10.2.6.3 of this IRR, unless storage, janitor closet, maintenance shops completely protected by an approved, including woodworking supervised automatic fire and painting areas, and kitchens shall be suppression system in accordance with separated from other parts Section 10.2.6.5 of this IRR, in of the building by construction having a fire- which case Class C interior finish may be resistance rating of not less used in any Class A or Class B than one (1) hour, and all openings shall be store, interior finish of the' walls shall be protected with self-closing Class A, Class B or Class C in fire doors. accordance with Section 10.2.6.3 of this IRR. 2. Areas which high hazard contents as 3. In any mercantile occupancy, exposed defined in Division 4 of this portions of structural members Chapter, shall be provided with both fire- complying with the requirements for heavy resistive construction and timber construction may automatic fire suppression system. be permitted. Laminated wood shall be 3. Cooking equipment shall be protected in delaminate under the accordance with NFPA 96, influence of heat. Standard for Ventilation Control and Fire 1. Open-air mercantile, operations, such as Protection of Commercial open-air markets, gasoline Cooking Operations, unless the cooking filling stations, auto LPG refilling stations, equipment is one of the roadside stands for the sale of following types: farm produce and other outdoor mercantile a. Outdoor equipment; operations shall be so b. Portable equipment; arranged and conducted as to maintain free c. Equipment used only for food warming. and unobstructed ways SECTION 10.2.13.4 BUILDING SERVICE of travel at all times to permit prompt EQUIPMENT escape from any point of A. Air conditioning, ventilating, heating, danger in case of fire or other emergency, cooking, and other service with no dead ends in which equipment shall be in accordance with persons might be trapped due to display Division 7 of this Chapter. stands, adjoining buildings, B. An elevator shall not constitute required fences, vehicles, or other obstructions. means of exit. When mercantile 2. If mercantile operations are conducted in occupancies are more than three (3) storeys roof-over areas, they shall or more than three (3) be treated as mercantile buildings, provided storeys above the street floor and equipped that canopies over with automatic elevator, individual small stands to protect one (1) or more elevators and escalators merchandise from the weather shall shall be designed and not be construed to constitute buildings for equipped for fire emergency use by fire the purpose of this fighters as specified in Division 7 Chapter. of this Chapter. Key operation shall transfer C. Combined Mercantile and Residential automatic elevator Occupancies. operation to manual and bring elevator to No dwelling unit shall have its sole means of the street floor for use of fire exit through any mercantile service. The elevator shall be situated so as occupancy in the same building. to be readily accessible by Exception No. 1: Where the dwelling firefighters. occupancy and exits therefrom are SECTION 10.2.13.5 SPECIAL PROVISIONS separated from the mercantile occupancy by A. Self-Service Stores construction having a fire 1. In any self-service store, no check-out resistance rating of at least one (1) hour. stand or associated railings or Exception No. 2: Where the mercantile barriers shall obstruct exits or required occupancy is protected by aisles or approaches thereto. automatic fire suppression system in 2. In every self-service store where, wheeled accordance with Section 10.2.6.5 of carts or buggIes are used by this IRR. customers, adequate provision shall be Exception No. 3: Where an existing building made for the transit and with not more than two (2) parking of such carts to minimize the dwelling units above the mercantile possibility that they may obstruct occupancy is protected by an exits. automatic fire detection systems in 192 accordance with Section 10.2.6.4 of B. Open-Air Mercantile Operations this IRR. D. Covered Malls and Walkway. A covered or roofed interior area used as a The contents of business occupancies shall pedestrian public way and be classified as ordinary connecting buildings housing individual or hazard in accordance with Division 4 of this multiple tenants. Use of the Chapter. For purposes of the term covered mall shall include covered design of an automatic fire suppression walkways. system, as office occupancy shall 1. Covered Mall and Walkways. - A covered be classified as "Light hazard occupancy". or roofed interior area used C. Occupant Load as a pedestrian public way and connecting 1. For purposes of determining required buildings housing exits, the occupant load of individual or multiple tenants. Use of the business purposes shall be no less than one term covered mall shall (1) person per nine and include covered walkways. three tenths square meters (9.3 m2) of gross 2. A covered mall and all buildings floor area. connected to it shall be treated as a 2. In the case of mezzanine or balcony open single mercantile building and shall be to the floor below of other subject to the requirements for unprotected vertical openings between 193 floors, the occupant load of mercantile occupancies, except as provided the mezzanine or other subsidiary floor level herein. shall be added to that of 3. Exit Details the street floor for the purpose of a. Every covered mall shall have no less than determining required exits. However, two (2) exits located in no case shall the total number of exit remote from each other. units be less than would be b. No less than one-half (0.5) the required required if all vertical openings were exit widths for each Class A enclosed. or Class B store connected to a covered mall 194 shall lead directly SECTION 10.2.14.2 EXIT DETAILS outside without passing through the mall. A. General c. Every mall shall be provided with 1. All exit facilities shall be in accordance unobstructed exit access, parallel with Section 10.2.5.10 of this IRR to and adjacent to the connected buildings: and this Division. However, only types of This exit access shall exits specified in Subsection b extend to each mall exit. on types of exits may be used as required d. In no case shall an exit access through a exit facilities in any business covered mall be less than occupancy with access thereto and ways of three (3) meters and sixty six centimeters travel therefrom in (66 cm) in clear width. accordance with Section 10.2.5.2 of this IRR. DIVISION 14. BUSINESS OCCUPANCIES 2. If, owing to differences in grade level, any SECTION 10.2.14.1 GENERAL REQUIREMENTS street floor exits are at points A. Classification of Occupancy above or below the street or ground level, Business Occupancies shall include all such exits shall comply with buildings and structures or parts the provisions for exits from upper floors or thereof with occupancy described in Division floors below the street floor. 3 of this Chapter. 3. Stairs and ramps serving two (2) or more B. Classification of Hazard of Contents floors below a street floor occupied for business use shall be permitted floor plus the required capacity of stairs and in accordance with para ramps discharging (4) and (5) below. through the street floor. 4. Where two (2) or more upper floors D. Number of Exits below the street floor are occupied 1. Exits shall comply with the following, for business use, the same stairs or ramps except as otherwise permitted by shall be permitted to serve para (2) through (6) below: each. a. The number of means of egress shall be in 5. An inside open stairway or inside open accordance with Section ramp shall be permitted to 10.2.5.2 of this IRR. serve as a required egress facility from not b. Not less than two (2) separate exits shall more than one (1) floor level be provided on every below the street floor. storey. 6. Floor levels below that are below the c. Not less than two (2) separate exits shall street floor; are used only for be accessible from every storage, heating, and other service part of every storey. equipment; and are not subject to 2. Exit access, as required by para (D) (1) (a) business occupancy shall have means of through (c) above, shall be egress in accordance with permitted to include a single exit access Division 16 (Storage Occupancies) of this path for the distances IRR. permitted as common paths of travel. B. Types of Exits 3. A single exit shall be permitted for a room 1. Exits shall be restricted to the following or area with a total permissible types: occupant load of fewer than 100 persons, a. Doors. provided that the following b. Stairs and smoke proof enclosures. criteria are met: c. Horizontal exits. a. The exit shall discharge directly to the d. Ramps. outside at the level of exit e. Exit Passageways discharge for the building. f. Fire escape ladders b. The total distance of travel from any 195 point, including travel within C. Capacity of Means of Egress the exit, shall not exceed 30 meters. 1. The capacity of means of egress shall be c. The total distance of travel specified in in accordance with Section para (3) (b) above shall be 10.2.5.2 of this IRR. on the same floor level or, if traversing of 2. The clear width of any corridor or stairs is necessary, such passageway serving an occupant stairs shall not exceed four thousand five load of fifty (50) or more shall be not less hundred seventy than 1.12 meters. millimeters (4570) mm in height and the a. It is not the intent that this provision apply stairs shall be provided with to non-corridor or nonpassageway complete enclosures to separate them from areas of exit access, such as the spaces any other part of the between rows building, with no door openings therein. of desks created by office layout or low- 196 height partitions. d. A single outside stair in accordance with 3. Street floor exits shall be sufficient for the Section 10.2.5.4 of this IRR occupant load of the street shall be permitted to serve all floors 2. Dead-end corridors shall be permitted in permitted within the 4570 mm accordance with the vertical travel limitation. following: 4. Any business occupancy not exceeding a. In buildings protected throughout by an three (3) storeys, and not approved, supervised exceeding an occupant load of 30 people automatic sprinkler system in accordance per floor, shall be with NFPA 13, Standard permitted a single separate exit to each for the Installation of Sprinkler Systems, floor, provided that the dead-end corridors shall not following criteria are met: exceed fifteen meters (15 m). a. This arrangement shall be permitted only b. In buildings other than those complying where the total travel with para (c) below, deadend distance to the outside of the building does corridors shall not exceed six meters (6 m). not exceed thirty c. It is recognized that dead ends exceeding meters (30 m) and where the exit is the permitted limits exist enclosed in accordance with 197 Section 10.2.6.2of this IRR, serves no other and, in some cases, are impractical to levels, and discharges eliminate. The directly to the outside. City/Municipal Fire Marshal having b. A single outside stair in accordance with jurisdiction might permit such Section 10.2.5.5 of this IRR dead ends to continue to exist, taking into shall be permitted to serve all floors. consideration any or all 5. A single means of egress shall be of the following: permitted from a mezzanine within a i. Tenant arrangement business occupancy, provided that the ii. Automatic sprinkler protection common path of travel does iii. Smoke detection not exceed twenty three meters (23 m), or iv. Exit remoteness thirty meters (30 m) if 3. Limitations on common path of travel protected throughout by an approved, shall be in accordance with the supervised automatic sprinkler following: system in accordance with NFPA 13, a. Common path of travel shall not exceed Standard for the Installation of thirty meters (30 m) in a Sprinkler Systems. building protected throughout by an 6. A single exit shall be permitted for a approved, supervised maximum two-storey, single-tenant automatic sprinkler system in accordance space/building that is protected throughout with NFPA 13, Standard by an approved, for the Installation of Sprinkler Systems. supervised sprinkler system in accordance b. Common path of travel shall not exceed with NFPA 13, Standard for thirty meters (30 m) within the Installation of Sprinkler Systems and a single tenant space having an occupant where the total travel to the load not exceeding 30 outside does not exceed thirty meters (30 persons. m). c. In buildings other than those complying E. Arrangement of Means of Egress with para (3) (a) or (b) 1. Means of egress shall be arranged in above, the common path of travel shall not accordance with Section 10.2.5.2 exceed twenty three of this IRR. meters (23 m). d. It is recognized that common paths of occupants. travel exceeding the 3. Emergency lighting in accordance with permitted limits exist and, in some cases, 10.2.5.11 of this IRR shall be are impractical to provided for all underground and limited eliminate. The authority having jurisdiction access structures. might permit such 4. Means of egress shall have signs in common paths of travel to continue to exist, accordance with Section 10.2.5.12 taking into of this IRR. consideration any or all of the following: SECTION 10.2.14.3 PROTECTION i. Tenant arrangement; A. Protection of Vertical Openings ii. Automatic sprinkler protection; and 1. Vertical openings shall be enclosed or iii. Smoke detection. protected in accordance with iv. Exit remoteness section 10.2.6.2of this IRR, unless otherwise F. Travel Distance to Exits permitted by the following: 1. In buildings protected throughout by an a. Unenclosed vertical openings in approved, supervised accordance with Section 10.2.6.2 sprinkler system in accordance with NFPA of this IRR shall be permitted. 13, Standard for the b. Exit stairs shall be permitted to be Installation of Sprinkler Systems, the travel unenclosed in two-storey, single distance shall not exceed tenant spaces that are provided with a single sixty one meters (61 m). exit in accordance 198 with Section 10.2.14.2 para “D” (6) of this 2. In buildings other than those complying IRR. with para (1) above, the travel c. Unprotected vertical openings shall be distance, measured in accordance with permitted in existing Section 10.2.5.2 of this IRR, buildings complying with all of the following: shall not exceed forty-six meters (46 m). 199 G. Discharge from Exits i. Where protected throughout by an Exit discharge shall comply with Section approved automatic 10.2.5.2 of this IRR. sprinkler system in accordance with NFPA H. Exit Signs and Lighting 13, Standard for the 1. Exit illumination shall be provided in Installation of Sprinkler Systems. accordance with Section 10.2.5.11 ii. Where no unprotected vertical opening of this IRR. serves as any part of 2. Emergency lighting shall be provided in any required means of egress. accordance with Section iii. Where required exits consist of exit doors 10.2.5.11 of this IRR in any building where that discharge directly any one of the following to grade in accordance with Section conditions exists: 10.2.5.3, outside stairs in a. The building is two (2) or more storeys in accordance with Section 10.2.5.4, height above the level of smokeproof enclosures in exit discharge. accordance with Section 10.2.5.4, or b. The occupancy is subject to fifty (50) or horizontal exits in more occupants above or accordance with Section 10.2.5.6 of this IRR. below the level of exit discharge. d. Floors that are below the street floor and c. The occupancy is subject to three hundred are used for storage or (300) or more total other than a business occupancy shall have a. Manual means in accordance with Section no unprotected 10.2.6.4of this IRR. openings to business occupancy floors. b. Means of an approved automatic fire B. Interior Finish detection system that 1. Interior finish shall be in accordance with complies with Section 10.2.6.4 of this IRR, Section 10.2.6.3 of this IRR. and provides protection 2. Interior wall and ceiling finish. throughout the building. a. Interior wall and ceiling finish material c. Means of an approved automatic sprinkler complying with Section system that complies 10.2.6.3 of this IRR shall be Class A or Class B with Section 10.2.6.5 of this IRR, and in exits and in exit provides protection throughout access corridors. the building. b. Interior wall and ceiling finishes shall be 3. Occupant notification. During all times Class A, Class B, or Class C that the building is occupied, in areas other than those specified in para the required fire alarm system, once (a) above. initiated, shall perform one of the 3. Interior floor finish following functions: a. Interior floor finish shall comply with a. For new and existing building, it shall Section 10.2.6.3 of this IRR. activate a general alarm in b. Interior floor finish in exit enclosures shall accordance with Section 10.2.6.4 be Class I or Class II. throughout the building. A C. Detection, Alarm, and Communications positive alarm sequence in accordance with Systems Section 10.2.6.4 of this 1. A fire alarm system in accordance with IRR shall be permitted. Section 10.2.6.4 of this IRR shall b. For existing building, a pre-signal system be provided in all business occupancies in accordance with where any one of the Section 10.2.6.4 of this IRR shall be following conditions exists: permitted. a. The building is two (2) or more storeys in c. For new and existing building, it shall height above the level of activate an alarm signal in a exit discharge. continuously attended location for the b. The occupancy is subject to fifty (50) or purpose of initiating more occupants above or emergency action by personnel trained to below the level of exit discharge. For existing respond to building, the emergencies as follows: occupancy is subject to one hundred (100) i. Emergency action shall be initiated by or more occupants means of live voice above or below the level of exit discharge. public address system announcements 200 originating from the c. The occupancy is subject to three hundred attended location where the alarm signal is (300) or more total received, unless occupants. For existing building, the otherwise permitted by para (iii) below. occupancy is subject to one ii. The live voice public address system shall thousand (1000) or more total occupants. be permitted to be 2. Initiation. Initiation of the required fire used for other announcements, provided alarm system shall be by one of that the emergency the following means: action use takes precedence over any other accordance with NFPA 96, Standard for use. Ventilation Control and Fire iii. In lieu of live voice public address system Protection of Commercial Cooking announcements, Operations, unless the cooking any other occupant notification means in equipment is one of the following types: accordance with a. Outdoor equipment Section 10.2.6.4 of this IRR shall be b. Portable equipment not flue connected permitted. c. Equipment used only for food warming 201 SECTION 10.2.14.4. BUILDING SERVICE D. Protection from Hazard UTILITIES 1. Hazardous areas including, but not limited Utilities shall comply with the provisions of to, areas used for general Section 10.2.7.1 of this IRR. storage, boiler or furnace rooms, and A. Heating, ventilating, and air-conditioning. maintenance shops that include Heating ventilating, and airconditioning woodworking and painting areas shall be equipment shall comply with the provisions protected in accordance of Section with Section 10.2.6.8 of this IRR. 10.2.7.2 of this IRR. 2. It is not the intent of this provision that B. Elevators, escalators, and conveyors, rooms inside individual tenant elevators, escalators, and spaces that are used to store routine office conveyors shall comply with the provisions supplies for that tenant be of Section 10.2.7.5 of this IRR. required to be either separated or 202 sprinklered. C. Rubbish chutes, incinerators, and laundry 3. High hazard contents areas. High hazard chutes. Rubbish chutes, contents areas, as classified incinerators, and laundry chutes shall in Division 4, shall meet the following comply with the provisions of criteria: Section 10.2.7.4 of this IRR. a. The area shall be separated from other SECTION 10.2.14.5 COMBINED BUSINESS parts of the building by fire AND MERCANTILE OCCUPANCY barriers having a fire resistance rating of not In any building occupied for both business less than 1 hour, with and mercantile purposes, the entire all openings therein protected by ¾-hour, building shall have exits in accordance with fire protection-rated, Division 14 of this Chapter. self-closing fire door assemblies. Exception: If mercantile occupancy sections b. The area shall be protected by an are effectively segregated from automatic extinguishing system business section, exit facilities may be in accordance with NFPA 13, Standard for treated separately. the Installation of SECTION 10.2.14.6 HIGH RISE BUILDINGS Sprinkler Systems. All business occupancy buildings fifteen (15) 4. The requirement for separating high meters or more in height shall be hazard contents areas from other provided throughout with approved, parts of the building is intended to isolate supervised sprinkler system, fully electrically the hazard, and Section supervised designed in accordance with 10.2.6.8 of this IRR is applicable. NFPA 13: Standard for the Installation 5. Cooking Equipment. Cooking equipment of Sprinklers (latest edition); or shall be shall be protected in designed with a system that will provide equivalent safety. Building height shall be open air as distinguished from enclosure measured from the ground level to with buildings, such as floor of the topmost storey. those often found in oil refining and In addition to the above requirements, all chemical processing plants buildings regardless of height shall where equipment is in the open platforms comply with other applicable provisions of used for necessary the Fire Code of the Philippines and access, sometimes with roofs or canopies to this IRR. provide some shelter, DIVISION 15. INDUSTRIAL OCCUPANCIES but no walls. SECTION 10.2.15.1 REQUIREMENTS 2. Occupant Load A. Sub – Classification of Occupancy and a. The occupant load of industrial Occupant Load occupancies for which exits are to 1. Sub – Classification of Occupancy be provided shall be one (1) person per nine a. General Industrial Occupancy. Industrial and three-tenths occupancies that square meters (9.3 m2) gross floor area, conduct ordinary and low hazard industrial provided that in Special operations conducted Purpose Industrial Occupancy and for Open in buildings of conventional design suitable Industrial Structures, for various types of the occupant load shall be the maximum industrial process. number of persons to This include multi-storey buildings where occupy the area under any probable floors are occupied by conditions, and further different tenants, or buildings suitable for provided that in existing industrial such occupancy and occupancies, the Chief, BFP or his therefore subject to possible use for types of duly authorized representative may waive industrial process with requirements for a high density of employee population. additional exits if the existing exits are b. Special Purpose Industrial Occupancy. adequate for the maximum Includes industrial number of persons actually employed. occupancies that conduct ordinary and low b. Every auditorium, restaurant, office, hazard industrial garage and medical facility in operations in buildings all except high connection with industrial occupancies shall hazard occupancy, have exits in designed for and suitable only for particular accordance with the other applicable types of operations, Sections of this IRR. 203 c. Exit requirements for specific occupancies characterized by a relatively low density of shall comply with this employee population Division. with much of the area occupied by SECTION 10.2.15.2 EXIT DETAILS machinery or equipment. A. General c. High Hazard Industrial Occupancy. Includes Each required exit shall be in accordance industrial occupancies with the applicable Sections of that use high hazard materials or processes Division 4 of this Chapter, with access or house high hazard thereto and ways of travel contents. therefrom in accordance with Section d. Open Industrial Structures. - Includes 10.2.5.2 of this IRR. operations conducted in the B. Types of Exits 1. Exits shall be restricted to the following will not be necessary to travel more than permissible types: thirty one meters (31 m) a. Doors from any point to reach the nearest exit for b. Stairs, or smokeproof enclosures buildings not protected by 204 a complete automatic fire suppression c. Horizontal exits system, or forty six meters (46 d. Ramps m) in a building protected by an approved, e. Slide Escapes supervised sprinkler C. Minimum Corridor Width system in accordance with Section 10.2.6.5 The minimum width of any corridor or of this IRR. passageway serving as a required 2. From every point there shall be at least exit or means of travel to or from required two (2) separate exits exit shall be one hundred accessible, so arranged as to be reached by twelve centimeters (112 cm) in the clear. different paths of travel D. Capacity of Exits in different directions. Capacity of means of egress shall be Exception: A common path of travel may be determined in accordance with permitted for the first Section 10.2.5.2 of this IRR. fifteen meters (15 m) from any point; i.e., no E. Number of Exits dead-end may be more At least two (2) exits shall be provided for 205 every floor or section, including than fifteen and one-half meters (15.5 m) floors below the floor of exit discharge used deep. for industrial purposes or uses G. Discharge from Exits incidental thereto. At least one of which A maximum of fifty (50%) percent of the shall be reached without exits may discharge through traversing another storey. areas on the floor of exit discharge provided: Exception: For rooms or areas with a total 1. Such exits discharges to a free and capacity of less than twenty five unobstructed way to the exterior (25) persons having direct exit to the street of the building, which way is readily visible or to an open area outside the and identifiable from the building at ground level, with a total travel point of discharge from the exit. distance from any point of not 2. The floor of discharge into which the exit over fifteen and one-half meters (15.5 m), a discharges is provided with single exit may be permitted. automatic fire suppression system and any Such travel shall be on the same floor level. other portion of the level of If the traversing of stairs is discharge with access to the discharge area required, there shall not be a vertical travel is provided with or more than four and sixtenths automatic fire suppression system meters (4.6 m) and such stairs shall be protection or separated from it in provided with complete accordance with the requirements for the enclosures to separate them from any other enclosure of exits (see part of the building with no Section 10.2.6.2 of this IRR). door openings therein. Exception: If the discharge area is a vestibule F. Travel Distance to Exits or foyer with no 1. Exits shall be as remote from other as dimension exceeding three (3) meters and practicable, so arranged that it separated from the remainder of the floor or discharge by of egress may be unprotected provided, construction providing that, all required exits shall protection at least the equivalent of wired consist of smoke-proof enclosure or outside glass in steel frames, and stairway in accordance serving only for means of egress including with Section 10.2.5.5 or horizontal exits in exits directly to the outside, accordance with Section the requirements of Section 10.2.6.2 of this 10.2.5.6 of this IRR. IRR may be waived. B. Interior Finish. 3. The entire area on the floor of discharge Interior finish shall be Class A, Class B or is separated from areas Class C. below by construction having a minimum of C. Detection, Alarm and Communications two (2) hour fireresistance Systems rating. 1. An approved automatic fire detection and H. Signs, Lighting, and Exit Signages alarm system shall be 1. Signs designating exits or ways of travel required on all industrial occupancies except there to shall be provided in for buildings with less accordance with Section 10.2.5.12 of this than 25 employees where such building shall IRR. be equipped with 2. Exit lighting shall be provided in manual fire alarm system. accordance with Section 10.2.5.11 of 2. Not less than one (1) fire alarm box shall this IRR. be installed for buildings 3. Emergency lighting shall be provided in equipped with automatic fire detection and accordance with Section alarm system. 10.2.5.11 of this IRR. 3. If buildings are equipped with approved, SECTION 10.2.15.3 PROTECTION supervised automatic A. Protection of Vertical Openings sprinkler system, the flow of water shall 1. Every stairway, elevator shaft, escalator initiate the fire alarm system. opening and other vertical D. Extinguishing Requirement opening shall be enclosed or protected in 1. Every high hazard occupancy shall have accordance with Section automatic fire suppression 10.2.6.2 of this IRR. system protection or other equivalent Exception No. 1: Unprotected vertical protection as may be openings connecting not more appropriate to the particular hazard, 206 including explosion venting for than three (3) storeys used for industrial any area subject to an explosion hazard, occupancy only maybe designed to minimize danger permitted in accordance with the conditions to occupants in case of fire or other of Section 10.2.6.2 of this emergency before they have IRR, with approved, supervised sprinkler time to utilize exits to escape. system. 2. Portable fire extinguishers shall be Exception No.2: In any existing building only, installed in accordance with Section where provided with 10.2.6.7 of this IRR. approved, supervised sprinkler system in 3. Standpipe systems shall be installed in accordance with Section accordance with Section 10.2.6.5 of this IRR, vertical openings not 10.2.6.6 of this IRR. constituting as required means 207 DIVISION 16. STORAGE OCCUPANCIES SECTION 10.2.16.1 GENERAL STORAGE doors may be opened manually in case of OCCUPANCIES power failure A. Occupancy Load to permit exit travel. The occupant load, in number of persons for 208 whom means of egress and 4. Travel Distance to Exits other provisions are required, shall be Every area used for the storage of high determined on the basis of the hazard commodities shall have maximum probable population of the space an exit within twenty three meters (23 m) of under consideration. any point in the area B. Exit Details where persons may be present, except 1. Types of Exits where automatic fire Means of egress for storage occupancies suppression system protection is provided, shall be restricted to the distances may be increased following types: to thirty meters (30 m). a. Doors 5. Signs, Lighting and Exit Signages b. Stairs and Smokeproof Enclosures a. Means of egress shall be installed with c. Horizontal Exits signs that comply with d. Ramps Section 10.2.5.12 of this IRR. e. Slide Escapes b. Means of egress shall be properly 2. Capacity of means of egress illuminated in accordance with The capacity of means of egress shall be Section 10.2.5.11 of this IRR. determined in accordance c. Emergency lighting shall be provided on with Section 10.2.5.2, para “C” of this IRR. normally occupied areas 3. Number of Exits and on component of means of egress. a. Every building or structure used for SECTION 10.2.16.2 PROTECTION storage and every section A. Protection of Vertical Opening thereof considered separately shall have at 1. Any vertical opening shall be protected in least two (2) separate accordance with Section means of egress, as remote from each other 10.2.6.2 of this IRR except for existing open as practicable. stairs and open ramps shall Exception: In rooms or spaces of less than permitted where connecting only two floor one thousand three levels. hundred ninety four square meters (1,394 2. Existing unprotected vertical opening in m2) gross area where less buildings protected than ten (10) persons may normally be throughout by approved supervised present, at least one (I) sprinkler system in accordance means of egress shall be provided for any with Section 10.2.6.5 of this IRR, vertical person employed openings not constituting as therein. required means of egress may be b. Every storage area shall have access to at unprotected provided, that, all least one (1) means of required exits shall consist of smoke-proof exit which can be readily opened, not enclosure or outside stairway subject to locking at any in accordance with Section 10.2.5.5 or time that any persons are therein, and not horizontal exits in accordance dependent on any with Section 10.2.5.6 of this IRR. power-operated doors except where the B. Detection, Alarm and Communications design of the poweroperated Systems 1. An approved automatic fire detection and comply with the rules on Industrial alarm system shall be Occupancies, except if the parking required on all industrial occupancies except and repair sections are effectively separated for buildings with by not less than 1-hour fire ordinary or low hazard not exceeding 2,000 resistive construction, the parking and repair square meters where such sections shall be treated building shall be equipped with manual fire separately. alarm system. B. Exit Details 2. Not less than one (1) fire alarm box shall 1. Number and Types of Exits be installed for buildings Every floor of every parking structure shall equipped with automatic fire detection and have access to at least two alarm system. (2) separate exits. Such exits shall be 3. If buildings are equipped with approved, provided with doors, interior stairs supervised automatic of smokeproof towers, outside stairs or a sprinkler system, the flow of water shall horizontal exit in accordance initiate the fire alarm system. with this IRR. 209 Exception No. 1: In an open -type parking C. Extinguishing Requirement structure with open ramps 1. Every high hazard occupancy shall have not subject to closure, the ramp may serve automatic fire suppression in lieu of the second exit, system protection or other equivalent provided the ramp discharges directly protection as may be outside at the street level. appropriate to the particular hazard, Exception No. 2. For parking structure including explosion venting for extending only (1) floor level any area subject to an explosion hazard, below the floor of exit discharge, a ramp designed to minimize danger leading directly to the to occupants in case of fire or other outside may serve in lieu of the second exit. emergency before they have 2. Arrangement of and Travel Distance to Exit time to utilize exits to escape. a. Exits in parking structures shall be so 2. Portable fire extinguishers shall be arranged that no point in the installed in accordance with Section area will be more than forty five meters (45 10.2.6.7 of this IRR. m) from the nearest exit 3. Standpipe systems shall be installed in 210 accordance with Section other than a ramp on the same floor level. 10.2.6.6 of this IRR. Exception no. 1: travel distance may be SECTION 10.2.16.3 SPECIAL PROVISION FOR increased to ninety one PARKING STRUCTURES meters (91 m) for open floors of open A. General Requirements parking structures. The following provisions apply to parking Exception no 2: travel distance may be structures of closed or open type, increased to sixty meters above or below ground, but not to (60 m) for enclosed parking structures mechanical or exclusively attendant completely protected by an parking facilities, which are not occupied by approved, supervised sprinkler system in customers and thus require a accordance with Section minimum of exits. Where repair operations 10.2.6.5 of this IRR. are conducted the exits shall b. Exits shall be so arranged that from any point in the parking structures, the paths of travel to the two (2) m). Dwarf or "smash" doors in doors exits will be in different accommodating aircraft may be directions, except that a common path of used to comply with these requirements. All travel may be permitted doors designated as exits for the first fifteen (l 5) meters from any shall be kept unlocked in the direction of point. exit travel while the area is c. If fuel pumps are located within any occupied. closed parking garage, exits 211 shall be so located that travel away from the 2. Exits from mezzanine floors in aircraft fuel pump in any storage or servicing areas shall be direction which leads to an exit, with no so arranged that the maximum travel to dead end in which reach the nearest exit from occupants might be trapped by fire or any point on mezzanine shall not exceed explosion at any fuel pump. twenty three meters (23 m). Such exit shall lead to the outside of the Such exits shall lead directly to a properly building on the same level enclosed stairwell or down stairs: no upward travel permitted discharging directly to the exterior or to a unless direct outside suitably cut-off area or to exits are available from that floor. outside stairs. Any storey below the storey at which is B. Signs being dispensed shall have Exits signs shall be provided above all doors exits direct to the outside via outside stairs and exit ways in accordance or doors at ground level. with Section 10.2.5.12 of this IRR. C. Illumination of Means of Egress SECTION 10.2.16.5 SPECIAL PROVISIONS FOR Every public space, hallway, stairway and GRAIN ELEVATORS other means of egress shall A. In grain elevators, there shall be at least have illumination and emergency lighting one (1) stair tower from storeys facilities in accordance with below the floor of exit discharge to the floor Section 10.2.5.11 of this IRR. of exit discharge and from D. Exit Marking the floor of exit discharge to the top floor of Signs in accordance with Section 10.2.5.12 the working house enclosed of this IRR shall be provided for on a dust tight non-combustible shaft. all required exits and exit access. B. Noncombustible doors of the self-closing SECTION 10.2.16.4 SPECIAL PROVISIONS FOR type shall be provided at each AIRCRAFT HANGARS floor landing. A. Exit Details C. An exterior stair or basket ladder type fire 1. Exits from aircraft storage of servicing escape accessible from all areas shall be provided at working levels of the head house that intervals of not more than forty (40) meters provides access to the top of the on all exteriors waIls or adjoining structure and that provides a aircraft hangars. There will be a minimum of continuous path to the means of two (2) exits serving each egress. aircraft storage or servicing area. Horizontal D. An exterior stair or basket ladder type fire exits through interior fire escape accessible from all walls shall be provided at intervals of not working levels of the head house that more than thirty meters (30 provides passage to the ground level. DIVISION 17. MISCELLANEOUS STRUCTURES employed therein, may be of any type of Any building or structure occupied for construction, and may be purposes not covered by Division 8 served by ladders instead of stairs. However, through 17 of this IRR shall have exits and if used for living or sleeping related safeguards in accordance with purposes, it shall at least comply with exit the fundamental principles of this Chapter, requirements of Section 10.2.12.6 and shall comply with the following for family dwellings. provisions where applicable. E. Utility/transmitter building shall be SECTION 10.2.17.1 TOWERS provided with appropriate type of A. Any tower utilized for such purposes as automatic fire extinguishing system and, if observation, signaling, either as an subject to occupancy by independent structure or on top of a technician/authorized personnel, automatic building, shall be permitted to have fire alarm system and a single stairway or ramp exit if all of the portable fire extinguishers shall also be following conditions are met: provided. 1. The tower is of such size as not to be F. Advertisement structures shall be made of subject to occupancy by more fire-resistant materials including than twenty five (25) persons at any floor its signage components. level. SECTION 10.2.17.2 PIERS AND WATER- 2. The tower shall not be used for living or SURROUNDED STRUCTURE sleeping purposes. A. This Section applies to water-surrounded 212 structures or piers occupied as a 3. The construction shall be fire-resistant, place of amusement, passenger terminal or noncombustible or constructed used for any purpose other of heavy timber. The interior finish, if any, is than for the mooring of vessels and handling Class A or Class B, and of cargo. Such piers shall be there shall be no combustible materials in, provided with means of exit from any under, or in the immediate structures thereon and to the shore vicinity of the tower except necessary appropriate to the character or occupancy furniture such as bare wooden of the pier in general or metal chairs or benches. accordance with the applicable sections of B. In each tower where there is no Division 8 through 17 of this occupancy below the top floor level and IRR. the conditions required by para “A” (1) B. Any pier so occupied, extending more through (3) above are met, stairs than forty six meters (46 m) from may be open with no enclosure required or, the shore, shall be so arranged as to where the structure is entirely minimize the possibility that fire in or open, fire-escape type stairs may be used. under the pier, may block escape of C. Stairs shall be Class B for new occupants to shore by one or more construction. For existing towers, outside of the following measures: stairs or fire-escape type stairs may be 1. It must be provided with two (2) separate allowed ways of travel to shore, by D. A tower such as a forest observation two (2) well-separated walkways or tower and a railroad signal tower, independent structures. designed for occupancy only of not more 2. The pier deck must be open fire-resistant than three (3) persons and supported with noncombustible materials. 213 1. Any area subject to occupancy by fifty 3. The pier deck must be provided with (50) or more persons, from automatic fire suppression system which there is no direct access to outdoors protection for combustible structure and for or to another area and no superstructure, if any. outside light or ventilation through 4. It should be completely open and windows, shall be equipped with unobstructed and is fifteen meters approved, supervised automatic fire (15 m) in width if less than one hundred fifty suppression system protection in two meters (152 m) long; or accordance with Section 10.2.6.5 of this IRR. its width is not less than ten (10%) percent 2. Any underground structure, building, or of its length if over one floor area lacking direct hundred fifty two meters (152 m) long. outside access or windows and having C. Any building or structure surrounded by combustible contents, interior water such as a lighthouse shall finish, or construction, if subject to have sufficient outside area of ground as on occupancy by more than one an island, or fire-resistant hundred (100) persons shall have automatic platform, to provide an adequate area of smoke venting facilities in refuge from any fire in the accordance with Division 6 of this Chapter in structure. Means shall be available for addition to automatic transportation of occupants away fire suppression system protection. from such structures to the shore or other 3. Any underground structure or windowless places of safety such as by boat building, for which no or helicopter, in case of fire or other 214 emergency, within a reasonable natural lighting is provided, shall be period of time. provided with emergency lighting SECTION 10.2.17.3 IMMOBILIZED VEHICLE in accordance with Section 10.2.5.11 of this AND VESSELS IRR. A. Any house trailer or similar vehicle, B. Underground Structures railroad car, street car, truck or bus Where required from underground from which the wheels have been removed, structure involving upward travel such provided with a permanenttype as ascending stairs or ramps, such upward foundation, or otherwise fixed so that it is exits shall be cut off from main not mobile shall be floor areas and shall be provided with considered as a building and shall be subject outside smoke venting facilities or to the requirements of this other means to prevent the exits serving as Rule which are applicable to buildings of flues for smoke from any fire in similar occupancy. the area served by the exits, thereby making B. Any ship, barge, or other vessel, which is the exits impassable. permanently moored or aground C. Windowless Buildings and is occupied for purposes other than Every windowless building shall be provided navigation, shall be subject to with outside access panels on the requirements of this Rule applicable to each floor level. Such panels shall be buildings or similar occupancy. designed for use of firefighters. SECTION 10.2.17.4 UNDERGROUND DIVISION 18. OPERATING FEATURES STRUCTURES AND WINDOWLESS BUILDINGS SECTION 10.2.18.1 GENERAL A. General Fire exit drills shall be conducted in coordination with the Office of the City/Municipal Fire Marshal. fire exit drills. A. Fire Exit Drills B. Furnishing and Decorations 1. Fire exit drills conforming to the 1. No furnishing, decorations, or other provisions of this Division shall be objects shall be so placed as to regularly conducted in schools and in other obstruct exits, access thereto, egress occupancies where therefrom, or visibility thereof. specified by the provisions of Divisions 8 2. Furnishing or decorations shall be treated through 17 of this Chapter, or with flame retardant where by appropriate action of the City/Municipal required by the applicable provisions of the Fire Marshal having Fire Code and this IRR. jurisdiction over the area. The Chief, BFP or 3. No furnishing or decorations of an his duly authorized explosive or highly flammable representative shall exercise discretion for character shall be used in any place of the necessary modifications assembly or other occupancy. in detail of procedures to make the drills C. Automatic Fire Suppression System more effective for their All automatic fire suppression systems intended purposes. required by this Chapter shall be 2. Fire exit drills, where required, shall be continuously maintained in reliable held with sufficient frequency to operational condition at all times and familiarize all occupants with the drill such periodic inspections and tests shall be procedure and to have the made to assure proper conduct of the drill a matter of established maintenance. routine. D. Alarm and Fire Detection Systems 3. Drills shall be held at unexpected times 1. Systems shall be under the supervision of and under varying conditions qualified and competent to simulate the unusual conditions obtaining persons, who shall cause proper tests to be in case of fire. made at specified intervals 4. Planning and conduct of drills shall be the and have general charge of all alternations responsibility of the and additions. management and/or owners of business 2. Systems shall be tested at intervals as establishments. Such recommended by the planning and drill shall be made in City/Municipal Fire Marshal having consultation and coordination with jurisdiction. the City/Municipal Fire Marshal having 3. Fire alarm signaling equipment shall be jurisdiction. restored to service as promptly 5. In the conduct of drills, emphasis shall be as possible after each test or alarm and shall placed upon orderly be kept in normal evacuation under proper discipline rather conditions ready for operation. Equipment than upon speed. As such, requiring rewinding or no running or horse play shall be permitted. replenishing shall be rewound or 215 replenished as promptly as possible 6. Drills shall include suitable procedures to after test or alarm. make sure that all persons in E. Fire Retardant Paints the building, or all persons subject to the Fire retardant paints or solutions shall be drill, actually participate. reapplied at such intervals as 7. Fire alarm facilities, where available, shall necessary to maintain the necessary flame be used in the conduct of retardant properties. F. Recognition of Means of Egress jurisdiction are taken to prevent ignition or Hangings or draperies shall not be placed any combustible materials. over exit doors or otherwise C. Special Food Service Devices located as to conceal or obscure any exit. Portable cooking equipment shall be Mirrors shall not be placed on permitted only as follows: exit doors nor in or adjacent to any exit in 1. Equipment fueled by small heat sources such a manner as to confuse which can be readily the direction of exit. extinguished by water, such as candles or 216 alcohol-burning equipment G. Preventive Maintenance Record (including "solid alcohol") may be used. Preventive maintenance records shall be Adequate precautions prepared and submitted to the satisfactory to the City/Municipal Fire City/Municipal Fire Marshal every after Marshal having jurisdiction are inspection and test. taken to prevent ignition of any combustible SECTION 10.2.18.2 PLACES OF ASSEMBLY materials. A. Drills 2. Candles may be used on tables for food The employees or attendants of places or service if securely supported public assembly shall be trained on substantial non-combustible bases, so and drilled in the duties they are to perform located as to avoid danger in case of fire, panic, or other of ignition of combustible materials and only related emergencies in order to be of if approved by the greatest service in effecting the City/Municipal Fire Marshal having orderly exit of occupants. jurisdiction. Candle flames shall be B. Opens Flame Devices protected. No open flame lighting devices shall be used 3. "Flaming Sword" or other equipment in any place of assembly. involving open flames and flamed Exception No. I: Where necessary for 217 ceremonial or religious purposes, the dishes such as cherries jubilee, crepes City/Municipal Fire Marshal having suzette, etc., may be permitted jurisdiction may permit open flame provided that necessary precautions are lighting under such restrictions as are taken, and subject to the necessary to avoid danger of approval of the City/Municipal Fire Marshal ignition of combustible materials or injury to having jurisdiction. occupants. D. Smoking Exception No. 2: Open the flame devices 1. Smoking in places of assembly shall be may be used on stages where a regulated by the necessary part of theatrical performances City/Municipal Fire Marshal having provided that adequate jurisdiction. precautions, satisfactory to the 2. In rooms or areas where smoking is City/Municipal Fire Marshal having prohibited, plainly visible "NO jurisdiction, are taken to prevent ignition of SMOKING" signs shall be posted. any combustible materials. 3. No person shall smoke in prohibited Exception No. 3: Gas lights may be permitted areas. provided that adequate 4. Where smoking is permitted, suitable ash precautions satisfactory to the trays or receptacles should City/Municipal Fire Marshal having be provided in convenient locations. E. Decorations and Stage Scenery 1. Combustible materials shall be treated 1. Fire exit drills shall be conducted regularly with an effective flame in accordance with the retardant material. Stage settings made of applicable provisions of the following combustible materials shall paragraphs. likewise be treated with flame retardant 2. There shall be at least four (4) exit drills a materials. year in consultation and 2. Only noncombustible materials or fire coordination with the City/Municipal Fire retardant pressure treated wood Marshal having jurisdiction may be used for stage scenery or props, on over the area. the audience side of the 3. Drills shall be conducted during class proscenium arch. hours; during the changing of 3. The City/Municipal Fire Marshal having classes; when the school is at assembly; jurisdiction over the area shall during the recess or gymnastic impose controls on the volume and periods; etc., so as to avoid distinction arrangement of combustible between drills and actual fires. If contents (including decorations) in places of a drill is called when pupils are going up and assembly to provide down the stairways, as adequate level of safety to life from fire. during the time classes are changing, the F. Seating pupils shall be instructed to 1. Seats in assembly occupancies form in line and immediately proceed to the accommodating more than two nearest available exit in hundred (200) persons shall be securely an orderly manner. fastened to the floor except 4. Every fire exit drill shall be an exercise by together in groups of not less than three (3) the school management. or more than seven (7) and Teachers shall have a complete control of as permitted by the next paragraph. All seats the class. Great stress shall in balconies and be laid upon the execution of each drill in a galleries shall be securely fastened to the brisk, quiet, and orderly floor, except in places of manner. Running shall be prohibited. In case worship. there are pupils 2. Seats not secured to the floor may be incapable of holding their places in a line permitted in restaurants, night moving at a reasonable clubs, and other occupancies where the speed, provisions shall be made to have fastening of seats to the floor them taken care of by the may be impractical; Provided, that in the more sturdy pupils, moving independently area used for seating of the regular line of march. (excluding dance floors, stage, etc.), there 5. BFP personnel shall be appointed to assist shall be not more than one in the proper execution of all (1) seat for each one and four-tenths square drills. The searching of toilets and other meters (1.4 m2) of net rooms shall be the duty of the floor area and adequate aisles to reach exits teachers or other members of the staff. shall be maintained at all 6. As drills simulate an actual fire condition, times. pupils shall not be allowed to 218 obtain anything after the alarm is sounded, SECTION 10.2.18.3 EDUCATIONAL even when in classrooms, OCCUPANCIES which would contribute to the confusion. A. Drills 7. Each class or group shall proceed to a senior member of the staff. A copy of the primary predetermined point latest inspection form shall outside the building and remain there while be posted in a conspicuous place in the day a check is made to make care facility. sure that all are accounted for, leaving only 2. An approved fire evacuation plan shall be when a recall signal is implemented at least once given to return to their classrooms, or when every two (2) months. dismissed. Such points shall 3. Furnishing and decorations in child day be sufficiently far away from the building care centers shall be in and from each other as to accordance with the provisions of Section avoid danger from any fire in the building, 10.2.18.1 of this IRR. interference with fire 4. Waste baskets and other waste containers department operations, or confusion shall be made of noncombustible between different classes or materials and provided with close fitting groups. An alternate assembly point shall be covers. planned for and used 5. Child-prepared artwork and teaching during other drills to ensure safety of the materials may be attached children if and when the directly to the walls but shall not exceed primary assembly point cannot be used by twenty (20%) percent of the any reason. wall area. 8. Where necessary for drill lines to cross SECTION 10.2.18.4 HEALTH CARE roadways, signs reading "STOP! OCCUPANCIES SCHOOL FIRE DRILL" or equivalent shall be A. Evacuation Plan and Fire Exit Drills carried by assigned 1. The administration of every hospital, 219 nursing home and residentialcustodial personnel to the traffic intersecting points in care institution shall have an approved order to stop the flow evacuation plan for traffic during the period of the drill. the guidance of all persons in the event of B. Signals fire. Copies of such plans 1. All fire exit drill alarms shall be sounded shall be made available to all supervisors on the fire alarm system and and personnel. All employees not on the signal system used to dismiss shall be instructed and kept informed of classes. their detailed duties under the 2. Whenever any of the school authorities plan. A copy of the plan shall be readily determine an actual fire exists, available at all times, in the they shall immediately call the nearest fire telephone operator’s position, or at the station. At the same time, security center. they shall try to extinguish the fire as 2. Every bed intended for use by institutional circumstances permit. occupants shall be easily 3. In order to ensure that pupils will not 220 return to a burning building, the movable under conditions of evacuation and recall signal shall be one that is separate and shall be equipped with distinct from and cannot the type and size of casters to allow easy be mistaken for any other signals. mobility, especially over elements C. Child Day Care Centers of the structure such as expansion plates 1. Fire prevention inspection shall be and elevator conducted monthly by a trained thresholds. The City/Municipal Fire Marshal DIVISION 19. SPECIAL PROVISION FOR HIGH having jurisdiction may RISE BUILDINGS make exceptions in the equipping of beds SECTION 10.2.19.1 SCOPE intended for use in areas This Division deals with life safety from fires limited to patients such as convalescent, and similar emergencies in high rise self-care or psychiatric buildings. It covers fire safety features in patients. construction and protection of exits 3. Fire exit drills in hospitals shall include the and passageways, and provisions for fire transmission of a fire alarm protection. signal and simulation of emergency fire SECTION 10.2.19.2 DEFINITION conditions except that the A high rise building is one in which the movement of infirm or bed-ridden patients distance between the floor of the to safe areas or to the 221 exterior or the building is not required. Drills topmost storey and the ground level is shall be conducted fifteen meters (15 m) or more. Building quarterly on each shift to familiarize hospital height shall be measured from the lowest personnel (nurses, interns, level of fire department vehicle maintenance personnel and administrative access to the floor of the highest occupiable staff) with signals and storey. emergency action required under varied SECTION 10.2.19.3 SMOKE CONTROL conditions. High rise buildings shall be designed in such SECTION 10.2.18.5 RESIDENTIAL a manner that the levels of smoke OCCUPANCIES concentration in protected spaces can be A. Hotel Emergency Organization maintained within values that can 1. All employees of hotels shall be instructed be tolerated by occupants. The protected and drilled in the duties they spaces shall include stairwells, at are to perform in case of fire, panic, or other least one elevator shaft, and floor spaces related emergencies. readily accessible to all occupants 2. Drills of the hotel emergency organization and large enough to accommodate them. In shall be held twice a year the spaces to which the covering such points as the operation and requirement for control of smoke level maintenance of the applies, the atmosphere shall not available first aid fire appliances, the testing include more than one (1%) percent by of guest alerting devices, volume of the contaminated and a study of instruction for emergency atmosphere emanating from the fire area. duties. SECTION 10.2.19.4 SPRINKLER SYSTEMS B. Dormitories, Lodging and Rooming Houses PROTECTION Fire exit drills shall be regularly conducted at High rise buildings shall be protected with least twice a year. approved, supervised sprinkler SECTION 10.2.18.6 MERCANTILE, BUSINESS, systems designed and installed in AND INDUSTRIAL OCCUPANCIES accordance with NFPA 13, Standard for In every mercantile, business and industrial Installation of Sprinkler Systems. The occupancies subject to approved, supervised sprinkler systems occupancy with fifty (50) or more persons, must protect all floor spaces including every fire exit drills shall be held at least closet and concealed spaces twice a year. and plenums of certain configuration and construction – particularly where combustible materials are located such as b. Fire alarm systems. exposed electrical wiring, c. Automatic fire detection systems. combustible duct work, and combustible d. Elevator car lighting. sound/thermal insulation. The e. Escape route lighting. system shall be interconnected to a fire f. Exit sign illumination. command center of the building. g. Stairway doors SECTION 10.2.19.5 FIRE COMMAND CENTER 7. Controls for unlocking stairway doors A. For buildings ten (10) storeys or more, a simultaneously. fire command center shall be 8. Telephone for fire department use with provided in a location approved by the controlled access to the public City/Municipal Fire Marshal telephone system. having jurisdiction and shall contain the 9. Fire pump status indicators. following features: 10.Status indicators and controls for air 1. The emergency voice/alarm handling systems. communication system unit must have 11.The fire fighters control panel for smoke the following features: control systems. a. Provide a predetermined message to the 12.Emergency power and standby power fire area where the alarm status indicators. originated, actuated by a smoke detector, 13.Schematic building plans indicating the sprinkler head, water typical floor plan and flow device, or manual fire alarm. The detailing the building core, means of egress, message must provide fire protection systems, applicable information and directions to firefighting equipment and fire department occupants. access. b. The fire department two-way 14.Public address system, where specifically communication system must operate required by other rules of this between the fire command center and every code. elevator, elevator B. Shut off valves and water flow devices at lobby, exit stairway, and exit access corridor. the riser connection must be A telephone station provided on each floor. Combined or jack shall be provided in each fire pump sprinkler/standpipe systems must have room. an individual control valve and check valve 2. The fire department communication unit. at each sprinkler connection. 3. Fire detection and alarm system annunciator unit 222 4. Elevator floor location and operation annunciator. 5. Sprinkler valve and water flow display panels. 6. Emergency generator supervision devices, manual start and transfer features. Emergency power must be available within ten (10) seconds to operate the following: a. Emergency voice/alarm communication systems.