Transformer: Application of Transformers
Transformer: Application of Transformers
Application of Transformers
Principle of Transformer
The word Transformer refers to transfer something from one place to other .
A Transformer is a static or stationary piece of apparatus by means of which electric power in
one circuit is transformed into electric power of the same frequency in another circuit.
Although transformers have no moving parts, they are essential to electromechanical energy conversion. They make it
possible to increase or decrease the voltage so that power can be transmitted at a voltage level that results in low
costs, and can be distributed and used safely.
Primary winding: This is a simple coil which is wound by copper wires. This winding generates the required magnetic flux
whenever a active AC source is connected across it. It is a closed coil, so whenever an AC voltage is applied across it, current starts
flowing. And this flow of current leads to develop an alternating magnetic field surrounding the coil. This winding is used to
develop the main magnetic field into the transformer. As the flux generation and creation of magnetic field is initiated from here,
so this winding is termed as the primary winding. The primary winding is the input section of a transformer.
Core: Core gives the strong mechanical support for the windings as well as serves the necessary path for the magnetic fluxes. Core
is generally made up with soft iron or laminated silicon steel. When the magnetic fluxes are generated in the primary winding, it
confines them and after that those fluxes are passing through the core. Both primary and secondary windings are connected with
a common core. As this magnetic core offers a low reluctance path for the generated magnetic fluxes, so most of the fluxes will go
through the core. So they are guided to the secondary winding through the magnetic core.
Secondary winding: This is also a copper winding similar to the primary, but the number of turns are different. The generated
magnetic fluxes will link this secondary winding by mutual induction method after passing through the magnetic core. Output of a
transformer is always taken from the secondary winding terminal that is the load is always connected with this terminal.
Power Transformer: Power transformers are used at each end of transmission line in generating stations and substations for
stepping up or down the voltage level.
Current transformer: This transformer is used for the measurement of electric current.
Potential transformer: These type of transformers are used to step down the voltage to low value which can be fed to relay for
protection purpose.
Instrument transformers: Current transformers and potential transformer both are called the instrument transformer because
their main fuction is to transform high currents and voltages to a standardized low and easily measurable values.
Auto transformer : It is a single winding transformer and a common winding is used as both primary and secondary winding.
Consider an ideal transformer [Fig. 32.13 (a)] whose secondary is open and whose primary is connected to sinusoidal alternating voltage
V1. This potential difference causes an alternating current to flow in the primary.0.
Transformer on No Load
Even ,when the transformer is on no-load, the primary input current is not wholly
reactive. The primary input current under no-load conditions has to supply (i) iron
losses in the core i.e. hysteresis loss and eddy current loss and (ii) a very s1nall amount
of copper loss in primary ( there being no Cu loss in secondary as it is open). Hence,
the no-load primary input current I0 is not at 90° behind VI but lags it by an angle Φ0 <
90°. Noload input power –
The secondary current sets up its own m.m.f. (=N2I2) and hence its own flux Φ2 which is in opposition to the
main primary flux Φ which is due to I0. The secondary ampere-turns N2 I2 are known as demagnetising
amp- turns. The opposing secondary flux Φ2 weakens the primary flux Φ momentarily, hence primary back
e.m.f. E1 tends to be reduced. For a moment V1 gains the upper hand over E1 and hence causes more
current to flow in primary.
Let the additional primary current be I2’ It is known as load component of primary current. This current
is antiphase with I2’ The additional primary m.m.f. N1 12 sets up its own flux Φ2’ which is in opposition to
Φ2 (but is in the same direction as Φ) and is equal to it in magnitude. Hence, the two cancel each other out.
So, we find that the magnetic effects of secondary current 12 are immediately neutralized by the additional
primary current I2’ which is brought into existence exactly at the same instant as I2. The whole process is
illustrated in Fig. 32.17.
Hence, whatever the load conditions, the net flux passing through the core is approximately the same as
at no-load. An important deduction is that due to the constancy of core flux at all loads, the core loss is also
practically the same under all load conditions.
𝛷2 = 𝛷2′ ∴ 𝑁2𝐼2 = 𝑁1𝐼2′ ∴ 𝐼2′ = 𝑁𝑁21 × 𝐼2 = 𝐾𝐼2
Fig 32.17
Equivalent Resistance:
Similarly, equivalent primary resistance as referred to secondary is 𝑅1′ = 𝐾2𝑅1. In the figure below, secondary resistance has been
referred to primary side leaving secondary circuit resistanceless. The resistance 𝑅1 + 𝑅2′ = 𝑅1 + 𝐾𝑅22 is known as the equivalent or
effective resistance of the transformer as referred to primary
and may be designated as 𝑅01.
It is to be noted that.
1. A resistance of 𝑅1 in primary is equivalent to 𝐾2𝑅1 in secondary. Hence, it is called equivalent resistance as referred to
secondary i.e. 𝑅1.
2. A resistance of 𝑅2 in secondary is equivalent to 𝐾𝑅22 in primary. Hence, it is called the equivalent secondary resistance as
Magnetic Leakage
2
2
2
1
and
𝑋01 = 𝑋1 + 𝑋2′ = 𝑋1 + 𝐾𝑋
𝑋02 = 𝑋2 + 𝑋1′ = 𝑋2 + 𝐾 𝑋
fig. 32.37
from 𝑉1. The value of 𝑋0 = 𝐸𝐼01 and of 𝑅0 = 𝐸𝐼𝑤1. It is clear that 𝐸1 𝑎𝑛𝑑 𝐸2 are related to each other by expression 𝐸21 = 𝐸𝐸12 = 𝐾
Transfer Voltage, Current, and Impedance either to the primary or secondary
The primary equivalent of the secondary induced voltage is
fig. 32.38
The same relationship is used for shifting an external load impedance to the primary.
The total equivalent circuit of the transformer is
obtained by adding in the primary impedance as
shown in Fig. 32.39. This is known as the exact
equivalent circuit but it presents a somewhat
harder circuit problem to solve.
It should be noted that in this case 𝑋0 = 𝑉𝐼µ1 .
+
(𝒁
𝑍𝑚 = impedance of the
exciting circuit
This is so because there are two
parallel circuits, One having an impedance of 𝑍𝑚 and
other having 𝑍2′ and 𝑍𝐿′ in series with each other.
Transformer Tests
Open Circuit or No-Load test:
The no-load
vector diagram is shown right side
If 𝑊 is the
wattmeter reading then 𝑊 = 𝑉1𝐼0cos (𝛷0)
𝑊
𝐺 or 𝐺 =
∴ cos(𝛷0) = 𝑉 𝑊1 0
𝐼 𝐼µ = 𝐼0 sin(𝛷0),
𝐼𝑤 = 𝐼0 cos(𝛷0) ∴ 𝑋0 = 𝑉𝐼µ1 and 𝑅0 = 𝐼𝑉𝑤1
Or since the current is practically all exciting current when a transformer is on no-load (i.e. 𝐼0 ≅ 𝐼µ) and as the
voltage drop in primary leakage impedance is small, hence the exciting admittance 𝑌0 of the transformer is given
by 𝐼0 = 𝑉1𝑌0 or 𝑌0 = 𝑉𝐼01 . The exciting conductance 𝐺0 is given by 𝑊 = 𝑉12 0 0 𝑉12
The core loss of a transformer depends upon the frequency and the maximum flux density when the volume and the thickness of the
core laminations are given. The core loss is made up of two parts (i) hysteresis loss 𝑊ℎ = 𝑃𝐵𝑚𝑎𝑥1.6 𝑓 as given by Steinmetz's
empirical relation and (ii) eddy current loss 𝑊𝑒 = 𝑄𝐵𝑚𝑎𝑥2 𝑓2 where Q is a constant. The total core-loss is given by
𝑾𝒊 = 𝑾𝒉 + 𝑾𝒆 = 𝑷𝑩𝟏𝒎𝒂𝒙.𝟔 𝒇𝟐 + 𝑸𝑩𝟐𝒎𝒂𝒙𝒇𝟐
If we carry out two experiments using two different frequencies but the same maximum flux density, we should be able to find the
constants P and Q and hence calculate hysteresis and eddy current losses separately.
|
|
|
|
|
|
|
|
|
| It may also be noted that 𝑽𝟐 = 𝑲𝑽𝟏 − 𝑰(𝑹𝟎𝟐 + 𝒋𝑿𝟎𝟐) = 𝑲𝑽𝟏 − 𝑰𝟐𝒁𝟎𝟐
|
|
| Total Approximate Voltage Drop in Transformer:
| With O as the centre and radius OC draw an
arc cutting OA produced at M. The total
voltage drop 𝑰𝟐𝒁𝟎𝟐 = 𝑨𝑪 = 𝑨𝑴 which is
approximately equal to AN. From B draw B
D perpendicular on OA produced. Draw
CN perpendicular to OM and draw BL
parallel to OM.
Where 𝛷1 = 𝛷2 = 𝛷 (𝑎𝑝𝑝𝑟𝑜𝑥).
The approximate voltage drop for leading power factor becomes
(𝐼2𝑅02𝑐𝑜𝑠 𝛷 ± 𝐼2𝑋02𝑠𝑖𝑛 𝛷)
In general, approximate voltage drop is (𝐼2𝑅02𝑐𝑜𝑠 𝛷 ± 𝐼2𝑋02𝑠𝑖𝑛 𝛷). It may be
noted that approximate voltage drop as referred to primary is
(𝐼1𝑅01𝑐𝑜𝑠 𝛷 ± 𝐼1𝑋01𝑠𝑖𝑛 𝛷)
= (𝐼2𝑅02 cos 𝛷 − 𝐼2𝑋02 sin 𝛷) + ( 𝐼2𝑋02 cos𝛷2 +0𝑉 𝐼22𝑅02 sin 𝛷)2
= (𝐼2𝑅02 cos 𝛷 ± 𝐼2𝑅02 sin 𝛷) + ( 𝐼2𝑋02 cos 𝛷2 ±0𝑉 𝐼22𝑅02 sin 𝛷)2
Percentage drop is
= (𝐼2𝑅02 cos 𝛷−𝐼2𝑋02 sin 𝛷) × 100 + (𝐼2𝑋02 cos 𝛷 ± 𝐼2𝑅02 sin 𝛷)2 ×
100
0𝑉2 20𝑉2
The upper signs are to be used for a lagging power factor and the lower ones for a leading power factor.
Regulation of Transformer
The voltage regulation of the transformer is the percentage change in the output voltage from no-load to full-load.
The voltage regulation can be defined in two ways - Regulation Down and Regulation up.
Regulation down: This is defined as the change in terminal voltage when a load current at any power factor is applied, expressed as
a fraction of the no-load terminal voltage.
|𝑉𝑛𝑙| − |𝑉𝑙|
𝑅𝑒𝑔𝑢𝑙𝑎𝑡𝑖𝑜𝑛 =
|𝑉𝑛𝑙|
Regulation up: Here again the regulation is expressed as the ratio of the change in the terminal voltage when a load at a given
power factor is thrown off, and the on load voltage
|𝑉𝑛𝑙 | − |𝑉𝑙 |
𝑅𝑒𝑔𝑢𝑙𝑎𝑡𝑖𝑜𝑛 =
|𝑉𝑙 |
𝑉1 = 𝐼2 ′ (𝑅𝑒 + 𝑗𝑋𝑒 ) + 𝑉2 ′
𝑂𝐷 = 𝑉1 = √ [𝑂𝐴 + 𝐴𝐵 + 𝐵𝐶 ]2 + [𝐶𝐷 ]2
′
2 + 𝐼2 ′ 𝑅𝑒 cos 𝛷 + 𝐼2 ′ 𝑋𝑒 sin 𝛷 ]2 + [𝐼2 ′ 𝑋𝑒 cos 𝛷 − 𝐼2 ′ 𝑅𝑒 sin 𝛷]2
−1 𝑋𝑒
𝑅𝑒
′
1 2 (𝑅𝑒 + 𝑗𝑋𝑒 ) + 𝑉2 ′
′
2 + 𝐼2 ′ (cos 𝛷 − 𝑗 sin 𝛷)(𝑅𝑒 + 𝑗𝑋𝑒 )
|𝑉1 |−|𝑉2 ′ |
|𝑉 ′ |
= √ (1 + 𝑉1 )2 + 𝑉2 2 − 1
𝐼1 = 𝐼2′.
= √[𝑉
Hence RegulationR =
2