Temperature Heat Detector and Combined Smoke + Heat Detector Installation Wiring Diagram 3. The base of the smoke detector can be mounted directly onto LOOP + most standard electrical junction boxes without using any type of mechanical adaptor. For surface wired installations the base COMPATIBLE adaptor P/N 882912 for two wire, P/N CONTROL PANEL . 884912 for four wire has cable entry points to accept standard
electrical conduit.
INSTALLING THE HEAD
1. Set the desired address via DIP switch on the back of the detector, TYPICAL WIRING DIAGRAM see ADDRESS SETTING section. When installed, terminals 4 and 6 are for connection of remote LED 2. Align the components as shown in Figure 2. THE GFE-AD SERIES DETECT ORS MUST BE CONNECTED 3. Fit the detector head onto the base and twist clockwise to secure TO A COMPATIBLE ANALOGUE ADDRESSABLE FIRE ALARM it. CONTROL PANEL. 4. After all detectors have been installed, apply power to the control THE INSTALLATION MUST BE IN COMPLIANCE WITH THE unit and activate the detection Loop. CONTROL PANEL SYSTEM INSTALLATION MANUAL. 5. Test the detector(s) as described in the TESTING section of this manual. WARNING TO PREVENT DETECTOR CONTAMINATION AND SUBSEQUENT Note: Do not install the detector head until the area is INVALIDATION OF WARRANTY, THE SMOKE DETECTOR MUST REMAIN thoroughly cleaned of construction debris, dusts, etc. Please COVERED UNTIL THE AREA IS CLEAN AND DUST FREE. refer to control panel technical information regarding the GENERAL DESCRITPTION maximum number of detectors installed on the same loop. GFE-AD series consists of: Photo electric smoke detectors, Rate of Rise and Fixed temperature detectors and combined smoke / heat detectors with advanced analogue addressable communications. DIP switches are provided for setting the detector’s address. GFE-AD-S: Analogue addressable smoke detector GFE-AD-S-L: Analogue addressable smoke detector with remote LED output GFE-AD-SH: Analogue addressable smoke and rate-of-rise and fixed Fig. 2 Fitting detector head onto base. Note Alignment marks temperature heat detector TESTING GFE-AD-SH-L: Analogue addressable smoke and rate-of-rise and All remote signaling systems, releasing devices and extinguishing fixed temperature heat detector with remote LED output systems should be disconnected during the test period and GFE-AD-H: Analogue addressable rate-of-rise and fixed temperature reconnected at the conclusion of testing. heat detector SMOKE SENSOR TESTING GFE-AD-H-L: Analogue addressable rate-of-rise and fixed Allow smoke from a cotton wick or a test smoke aerosol to enter the temperature heat detector with remote LED output detector-sensing chamber for at least 10 seconds. When sufficient Note: The base model no. for GFE-AD-S, GFE-AD-SH and GFE-AD-H smoke has entered the chamber, the detector will signal an alarm, this is P/N772912. The base model no. for GFE-AD-S-L, GFE-AD-SH-L and being indicated by illumination of the red LED. Make sure to clear smoke GFE-AD-H-L is P/N774912. out of the chamber before resetting in order to keep the detector INSTALLING THE BASE at its current sensitivity setting. 1. To insure proper fit of the detector head to the base, all wires HEAT SENSOR TESTING should be properly dressed at installation: (A) Position all the wires flat against terminals. The detector to be tested should be subject to a flow of warm air at (B) Fasten the wires away from connector terminals. a temperature of between 65°C and 80°C. (This requirement can 2. The detectors are intended for ceiling or wall mounting in be met by some domestic hair dryers). accordance with Proceed as follows: local Fire authority recommendations. 1. Switch on the warm airflow and check that temperature is correct and stable. INTENDED TO BE OPENED FOR SERVICING BY USERS. 2. From a distance of several inches, direct the airflow at the OPENING THE DETECTOR HEAD WILL VOID THE guard protecting the thermistor. The detector should alarm WARRANTY. within 60 seconds. ADDRESS SETTING. 3. Upon alarm immediately remove the heat source and Please consult the Address Dip switch setting chart for check that the red LED of the detector is illuminated. details of the Binary equivalent numbers. 4. If a detector fails to activate within 60 seconds, confirm Note: Switch 8 is always off. (Unused) connections and programming. If necessary replace and return to distributor for recalibration. SPECIFICATIONS NOTE: After testing, check that the system is returned to Operating Voltage Range: 17 to 28 VDC normal operation. Notify the appropriate authorities that Standby Current: 500µA @ 24 VDC the testing procedure has been completed and the Max. Alarm Current 5 mA @ 24 VDC (LED ON); system is active again. Max. Remote LED output current: [email protected]
MAINTENANCE Operating Humidity Range: 10% to 93% Relative Humidity,
non condensing The recommended minimum requirement for detector Operating Temperature Range: 0° to 49°C (32° to 120°F); maintenance consists of an annual cleaning of dust from the Certification: EN 54 part 5 / 7(0845 CPD 232.1482, 0845 detector head by using a low power vacuum cleaner. CPD 232.1483, 0845 CPD 232.1484) Height: 1.8 inches (46 CAUTION: DO NOT ATTEMPT TO DISASSEMBLE THE mm) with base , Diameter: 3.93 inches (100 mm) with base. DETECTOR. THIS IS A SENSITIVE DEVICE AND IS NOT
Address DIP switch settings
DIP SWITCH for address setting Dip switch
LIMITED WARRANTY STATEMENT
Global Fire Equipment Ltd. declares that this product is free from defects in material and workmanship. And it will repair or replace any product or part thereof which proves to be defective in workmanship or material for a period of 24 months from the date of purchase. Please visit the Global Fire Website for a full description of Global Fire Equipment’s LIMITED WARRANTY, which, among other things, limits the duration of warranties of merchantability and fitness for a particular purpose and excludes liability for consequential damages. Acceptance of order and/or original invoice which will become part of your sales agreement. Please contact Global Fire Equip directly for a return merchandise authorization (RMA) number before returning goods to the factory . Shipment must be prepaid and Global Fire repair or replace your returned detector.
Global Fire Equipment Ltda.
Urb. Vale da Amoreira, Lt. 16 & 17, Porta A, Cave, 8005-334 FARO, PORTUGAL