70002-0298-00

06/2009

PowerLogic™ ION Enterprise™ 6.0


Power management software
User guide
Notices
This section describes the symbols used in this guide.

Danger
This alerts you to things that may cause serious injury to a person. 
Only qualified, properly trained personnel should perform these 
procedures.

Caution
This alerts you to things that may cause loss of data, damage to your 
computer or your device.

Note
A note provides you with additional information that you might want 
to consider.

Tip
This draws your attention to information that can help you perform a 
task more quickly or easily.
Documentation Conventions
This section describes the terms used to describe common methods or procedures 
used throughout this guide.

Clear Place the mouse cursor over the check box, then click the mouse button1 to remove
the check mark from the box.
Place the mouse cursor over a button or item, then press and release the mouse
Click
button.
Place the mouse cursor over a button or item, then press and release the mouse
Double-click
button twice.
Hold down the mouse button while moving the mouse cursor to highlight the
Drag
selection or move the selected item, then release the button.

Enter Type the information, then press ENTER on the keyboard.

Hover Move the mouse cursor over an object (i.e., a button) and pause over the object.

Point Position the mouse cursor over an item such as a menu command.

Press the specified key or combination of keys (for example, CTRL+ALT+DEL) on


Press
your keyboard.

Right-click Place the mouse cursor over an item, then press and release the right mouse button.

Place the mouse pointer over an option or check box, then click the mouse button to
Select
mark your selection.

Type Type the information in the space or box. DO NOT press the ENTER key.

1
“Mouse button” means the primary mouse button (left, by default), while “right mouse button” means
the secondary mouse button. This configuration can be switched for accessibility.
Contents

Chapter 1 Introduction ................................................................ 13


ION Enterprise Software Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Monitoring Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14
Management Applications  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14
Programming Applications   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  15

ION Enterprise Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

ION Enterprise Databases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Starting a Component of ION Enterprise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  19
Logging into a Component of ION Enterprise   . . . . . . . . . . . . . . . . . . . . . . . . . . . .  19
Ending a Session   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  19

Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Customizing and Navigating Interface Displays . . . . . . . . . . . . . . . . . . . . . 22


Adjusting the Display of a Window or Dialog Box   . . . . . . . . . . . . . . . . . . . . . . . .  22
Grid Table Controls  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  23

Chapter 2 Management Console ................................................. 27


The Management Console Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Management Console Network Components . . . . . . . . . . . . . . . . . . . . . . . 31

Setting Up Your Network in Management Console . . . . . . . . . . . . . . . . . . . 33


Adding a Server  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  33
Setting Up Devices for Direct Serial Communications   . . . . . . . . . . . . . . . . . . . . .  34
Setting Up Devices for Ethernet Gateway Communications   . . . . . . . . . . . . . . . .  34
Adding an Ethernet Device   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  35
Setting Up Devices for OPC Communications  . . . . . . . . . . . . . . . . . . . . . . . . . . . .  35
Adding a Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  36
Editing a Network Component  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  36
Deleting a Network Component  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  37

Accessing Meters with Advanced Security . . . . . . . . . . . . . . . . . . . . . . . . . 38

Configuring Connection Schedules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

System Log Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Setting Up Large Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43


The Duplicate and Configure Interface   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  43
Creating Multiple Copies of a Device  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  45
Configuring Multiple Devices  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  48
Editing Duplicated Device Information  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  50
Chapter 3 Management Console Tools ......................................... 53
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

User Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Users   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  56
Groups  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  58

License Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

Reporting Configuration Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Event Watcher Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62


Creating a Template   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  63
Adding an Event Watcher   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  64

Diagnostics Viewer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Starting Diagnostics Viewer  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  66
Service Diagnostics   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  67
Communications Diagnostics   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  68
Additional Commands  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  70

Device Upgrader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Using Device Upgrader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  71
Firmware Upgrade Error Codes   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  73

Remote Modem Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74


Using Remote Modem Setup  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  74

Virtual Processor Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75


Configuring the Virtual Processorʹs Modbus Service . . . . . . . . . . . . . . . . . . . . . . .  75
Modifying the Global Parameters  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  79

Time of Use Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80


Adding or Editing a Schedule  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  81
Adding or Editing a Sub‐Schedule  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  82
Configuring Seasons  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  83
Adding Special Days  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  85
Configuring Day Groups   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  86
Configuring TOU Names and TOU Periods  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  87

Chapter 4 Vista .......................................................................... 89


The Vista Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90

Vista User Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

Monitoring Your System in Vista . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

Viewing Real-Time Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98


Viewing Data with Numeric Objects   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  98
Viewing Data with Status Objects  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  99

Viewing Logged Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100


Using a Data Log Viewer  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  100
Using the Event and Global Event Log Viewers  . . . . . . . . . . . . . . . . . . . . . . . . . .  102
Displaying the Global Event Log Viewer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  103
Acknowledging Alarms   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  105

Controlling System Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107

Plotting Logged Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108


Plotting Logged Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  108

The Log View Plotter Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109


Viewing the Plot Display Tab   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  112
Viewing the Harmonics Analysis Tab   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  115
Viewing the Phasor Diagram Tab  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  116
Plotting Waveforms from Devices with High Sampling Rates . . . . . . . . . . . . . .  118
Adding Parameters to a Log View Plotter  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  119
Customizing the Log View Plotter Display  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  121
Overlaying Curves in the Log View Plotter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  125

Creating and Customizing a User Diagram . . . . . . . . . . . . . . . . . . . . . . . 127

Editing a User Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128


The Enable Undo Option   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  128
Adding a Diagram Object to a User Diagram  . . . . . . . . . . . . . . . . . . . . . . . . . . . .  128
Cutting, Copying, and Pasting a Diagram Object . . . . . . . . . . . . . . . . . . . . . . . . .  129
Copying a Group of Diagram Objects to a Framework  . . . . . . . . . . . . . . . . . . . .  130
Adjusting Diagram Object Layout and Size   . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  131

Customizing a Diagram Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133


Caption Options  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  134
Text Options  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  134
Edit Text Options  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  135
Link Options  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  135
Query Server Options  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  136
Display Options  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  136
Action Options  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  142
Box Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  143
Annunciation Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  144
Alarming Options   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  144

Linking a Diagram Object to a Data Source . . . . . . . . . . . . . . . . . . . . . . . 146

Querying the Database . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148


Using the Query Options  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  148
Using the Query Wizard  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  150

Customizing a Diagram Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155


Default Font   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  155
Background Color  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  155
Configuring Window Properties  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  156
Chapter 5 WebReach ................................................................ 161
WebReach Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
WebReach Installation After ION Enterprise is Installed   . . . . . . . . . . . . . . . . . .  162
Preliminary Setup   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  163
Displaying Vista User Diagrams Online   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  163
Viewing Historical (Trend) Data  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  164
Viewing Meter Events  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  166
Adding a Global Event Log Viewer   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  166
Stale Data or Error Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  167

Advanced WebReach Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168


Custom Network Diagram Setup  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  168
WebReach Registry Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  169

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170

Chapter 6 Web Reporter ........................................................... 171


Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Reporting Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  172

Web Reporter Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173

Report Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175


Default Report Definitions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  175
Creating a New Definition from a Default Report Definition . . . . . . . . . . . . . . .  179

Generating and Viewing a Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180


Report Ownership and Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  180
Entering Report Inputs  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  180
Saving a Report with its Inputs Defined   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  184
Generating a Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  184
Viewing a Report  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  184
Printing a Report  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  185
Saving a Report   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  185
Exporting a Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  186

Report Administration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187


Managing a Report   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  187
Sharing a Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  187
Creating Report Subscriptions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  188

Installing a Report Definition or a Report Pack . . . . . . . . . . . . . . . . . . . . . 191

Custom Report Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192

Running the ION Power Quality Aggregation Service Manually . . . . . . . . 193


Chapter 7 Designer .................................................................. 195
Getting Started with Designer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196

Node Diagrams and the Designer Interface . . . . . . . . . . . . . . . . . . . . . . . 197


The Designer Interface   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  197
The Node Diagram   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  198
Display Mode versus Edit Mode  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  200
Designer Shortcuts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  200
Designer Icons   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  201
Designer Windows   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  206

ION Module Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207

Using ION Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209


Adding a New ION Module   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  210
Deleting or Cutting an ION Module  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  211
Viewing a Node or Module as Text   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  213
Creating a Shortcut to an ION Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  214
Adding a Text Box to a Node Diagram   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  215

Linking ION Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217


Linking ION Modules Graphically  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  217
Linking ION Modules on the Same Node  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  218
Linking ION Modules Across Different Nodes . . . . . . . . . . . . . . . . . . . . . . . . . . .  219
Linking ION Modules Using the ION Tree  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  220
Deleting Links   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  222

Configuring ION Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224

Copying and Pasting ION Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230

Viewing Output Registers, Setup Registers, and Inputs . . . . . . . . . . . . . . . 239


Viewing Output Register Information  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  239
Viewing Setup Register Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  240
Viewing Input Information   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  240

Time of Use (TOU) Program Management . . . . . . . . . . . . . . . . . . . . . . . . 241


Advanced TOU Schedule Configuration  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  241

Virtual Processor Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244


Using the Virtual Processor  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  244
Distributed Control  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  245
Modbus Communications   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  248
Common Virtual Processor Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  250
Setting Global Parameters   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  252

Chapter 8 Database Manager ................................................... 255


Database Manager Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256

Common Database Management Procedures . . . . . . . . . . . . . . . . . . . . . . 258


Detaching then Re‐attaching Databases  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  258
Attaching a Database Using Database Manager  . . . . . . . . . . . . . . . . . . . . . . . . . .  258
Restoring an ION Database from a Backup  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  259

Manual Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260


Alarm Configuration  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  260
Archive   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  261
Attach . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  262
Backup  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  262
Defragment  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  262
Detach   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  262
Export Registry Setting  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  263
Modify Login   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  263
New ION Databases   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  264
Restore  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  264
SQL Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  265
Trim  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  265
Update Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  266
Upgrade Database  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  266

Scheduled Jobs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267


Scheduled Archive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  268
Scheduled Maintenance   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  270
Scheduled Trim   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  270
Scheduled Backup  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  271

Optimizing Database Query Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273

Log Inserter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274

Accessing the ION Database with 3rd-Party Applications . . . . . . . . . . . . . 275

Chapter 9 Modbus Device Importer ........................................... 277


Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278

ION Object Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281


Managers  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  281
Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  281
Registers   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  281

Main Console Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283

Main Toolbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284


File Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  284
Edit Menu  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  284
View Menu  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  286
Tools Menu  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  287
Settings Menu  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  290
Help Menu   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  290
Configure Logging and Calculation Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  290

Editing a Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291


Register Properties Defined  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  291
Shortcut Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 296
General Key Shortcuts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  296
Register Quick Edit Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  296
ION Map Information Pane  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  297
Modbus Register Information Pane   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  298

Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299


Data Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  299

Configuring Logging and Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301


Screen Overview   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  301
Configuring Register Logging  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  302
Configuring Low, High and Mean Calculation and Logging  . . . . . . . . . . . . . . .  303
Configuring Stale Data Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  303
Configuring Downstream Device Functionality  . . . . . . . . . . . . . . . . . . . . . . . . . .  304
Saving and Exiting  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  305

Chapter 10 ION Alert Monitor ..................................................... 307


ION Alert Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
Setting Up the ION Alert Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  309
Starting the ION Alert Monitor  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  312

Chapter 11 Downstream Device Assistant .................................... 313


Detecting Downstream Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314

Downstream Device Assistant Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315


Starting the Downstream Device Assistant  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  315
Basic View versus Advanced View  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  315
Displaying Physical Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  318
Sorting Data   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  318
Downstream Device Assistant Options  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  318

Downstream Device Assistant Functions . . . . . . . . . . . . . . . . . . . . . . . . . . 321


Renaming the Assigned Source  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  321
Cancelling Changes  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  322
Changing the Measurement Mapping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  322
Adding a New Downstream Device Mapping  . . . . . . . . . . . . . . . . . . . . . . . . . . .  322
Updating the Historical Data at a Later Time  . . . . . . . . . . . . . . . . . . . . . . . . . . . .  323
Activity Log   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  323

Downstream Device Assistant Commands . . . . . . . . . . . . . . . . . . . . . . . . 324

Appendix A Reporter ................................................................... 325


Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326

Creating a Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327


Generating a Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  330
Modifying the Finished Report  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  330
Types of Default Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331
Creating a Report Without a Template . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  335

Automatic Report Generation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336

Using Reporter on Secondary Server or Client . . . . . . . . . . . . . . . . . . . . . 337

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
1 Introduction
PowerLogic™ ION Enterprise™ software is a complete power management 
solution for energy suppliers and consumers. It allows you to manage energy 
information from metering and control devices installed in your facility or other 
remote locations. ION Enterprise offers control capabilities and comprehensive 
power quality and reliability analysis to help you reduce energy‐related costs.

ION Enterprise supports multiple communications standards and protocols 
available on various intelligent metering devices. You can also connect to existing 
power monitoring systems through industry standard protocols such as Modbus, 
OPC, DNP and XML.

ION Enterprise uses Microsoft SQL Server for efficient and secure data 
management. You can install the SQL Server 2005 Express Edition that comes with 
ION Enterprise (4 GB maximum database size) or, for larger database needs, you 
can use an existing SQL Server instance (Standard edition or better) to host the 
ION Enterprise databases.

In This Section

“ION Enterprise Software Components” on page 14
“ION Enterprise Services” on page 16
“ION Enterprise Databases” on page 18
“Starting a Component of ION Enterprise” on page 19
“Logging into a Component of ION Enterprise” on page 19
“Ending a Session” on page 19
“Additional Information” on page 21
“Customizing and Navigating Interface Displays” on page 22

© 2009 Schneider Electric. All rights reserved. Page 13


ION Enterprise Software Components PowerLogic ION Enterprise User Guide

ION Enterprise Software Components


This section outlines the ION Enterprise software components, and how they are 
used to build, monitor, maintain and customize your ION Enterprise system.

Monitoring Applications
These ION Enterprise programs are most commonly used in day‐to‐day power 
management tasks:

Vista
The “Vista” component of ION Enterprise displays graphical representations of 
your power monitoring system. Vista displays real‐time and historical 
information, visual objects that indicate the current status of your system, and 
interactive objects that you can use to perform certain actions such as 
acknowledging alarms.

NOTE
In this document, “Vista” refers to the Vista component of ION Enterprise. The Microsoft Windows Vista
operating system is referred to as “Windows Vista”.

WebReach
The “WebReach” component of ION Enterprise displays Vista user diagrams in a 
web browser.

Web Reporter
The “Web Reporter” component of ION Enterprise is the tool you use to create and 
generate common energy, demand or power quality reports.

Management Applications
The following ION Enterprise programs help you set up and maintain your power 
management system.

Management Console
Use the “Management Console” component of ION Enterprise to add and 
configure network components such as servers, sites (communication links) and 
devices. Management Console also provides access to system and database 
applications, and utilities to manage items such as user accounts and software 
licenses. These are described in the following topics:
“Database Manager” on page 255
“User Manager” on page 55

Page 14 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Programming Applications

“License Manager” on page 60
“Reporting Configuration Manager” on page 61
“Event Watcher Manager” on page 62
“Designer” on page 195
“Diagnostics Viewer” on page 66
“Device Upgrader” on page 71
“Remote Modem Setup” on page 74
“Virtual Processor Setup” on page 75
“Modbus Device Importer” on page 277
“Time of Use Editor” on page 80

Optional Components
The following optional components are also available if they have been ordered 
and then activated via License Manager:

OPC Server Assistant


This component checks the network for new sources of common or typical 
measurements to be exposed to the OPC Server. This is only available with the 
optional OPC Server license.

PQDIF Exporter
This component lets you export data to Power Quality Data Interchange Format 
(PQDIF) and set scheduled exports with notification. This is only available with 
the optional PQDIF Exporter license.

Programming Applications
These ION Enterprise applications help you customize elements in your system 
and configure third‐party devices so the system can recognize and utilize them:

Designer
Use the “Designer” component of ION Enterprise to perform a wide range of 
functions, from configuring setup registers of ION devices on your network to 
creating complex frameworks using a combination of ION modules from 
hardware or software nodes.

Modbus Device Importer


Use the “Modbus Device Importer” component of ION Enterprise to integrate 
third‐party Modbus devices into your ION Enterprise network.

Large System Setup Using Management Console


Use the Duplicate and Configure dialog box to set up large systems efficiently. See 
“Setting Up Large Systems” on page 43 for more information.

© 2009 Schneider Electric. All rights reserved. Page 15


ION Enterprise Services PowerLogic ION Enterprise User Guide

ION Enterprise Services


Many of ION Enterprise’s core components run as Windows Services. This allows 
your servers to continue monitoring your power management system when no 
users are logged on. In the event of a power outage, your system automatically 
resumes power monitoring when the power is restored. The table below outlines 
the ION Enterprise Services and whether the service is configured to start 
automatically or manually, by default.

NOTE
ION Network Router Service has many dependent ION Enterprise services. For example, the Virtual
Processor, ION Log Inserter Service, ION Site Service, and DDE services cannot start and operate without
it running.

Manual/
Service Name Description
Automatic

Checks the ION Enterprise computer’s communications ports continuously for high priority
ION Alert Monitor events occurring at remote modem sites. When this happens, Alert Monitor initiates a Manual
communications connection to the remote modem site.

ION Component Identifier


Locates local and remote ION Enterprise components. Manual
Service

Determines the connection status of sites and devices in the ION Enterprise system, and
handles allocation of resources such as modems. This service manages the state of site and
ION Connection Management
device connectivity for the ION Enterprise system. In order to establish the most appropriate Automatic
Service
state for the system, each connection and disconnection request is evaluated against the
overall state of the system and availability of communications channels.

Provides Dynamic Data Exchange (DDE) connectivity between devices and DDE compatible
ION DDE Service1 applications, such as Microsoft Excel.
Disabled

Monitors system events for conditions specified in Event Watcher Manager (see “Event
ION Event Watcher Service Automatic
Watcher Manager” on page 62).

Provides historical data collection and storage for your power-monitoring system. See “Log
ION Log Inserter Service Automatic
Inserter” on page 274.

Routes all information between ION Enterprise software components, such as client
workstations and the Log Inserter. The service dynamically detects changes to the network
ION Network Router Service Automatic
configuration, including the addition of new servers; it can also recognize new software
nodes, such as Vista, that are added to an existing server.

ION OPC Data Access Server Manages and is responsible for supplying OPC data to client applications. Manual

ION Power Quality


Periodically processes and aggregates new Power Quality event data. Automatic
Aggregation Service

Translates data from ION Enterprise databases to PQDIF file format and manages scheduled
ION PQDIF Exporter Service Manual
PQDIF exports.

Provides historical data retrieval for your power-monitoring system. See “Linking a Data Log
ION Query Service Automatic
Viewer or Event Log Viewer” on page 147 for more information regarding this service.

ION Real Time Data Service Manages and provides access to real time data from the power management system. Automatic

ION Report Subscription Service This service manages Web Reporter report subscriptions. Automatic

Page 16 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide ION Enterprise Services

Manual/
Service Name Description
Automatic

Manages communication links to and from ION Enterprise. ION Site Service is responsible for
handling packet communications to system devices and controlling direct device
communications. The service reacts to changes in network configuration: for example, often
ION Site Service Automatic
changes to certain channels, gates, ports, or device parameters can interrupt a connection.
You can add, delete, or change channels, gates, ports, and devices without restarting the ION
Site Service, ION Network Router Service, and ION Connection Management Service.

Provides coordinated data collection, data processing, and control functions for groups of
ION Virtual Processor Service meters. For more information on the Virtual Processor and its functionality, see “Virtual Automatic
Processor Setup” on page 75.

Manages subscriptions to XML data for Vista user diagrams. This service is used only by
ION XML Subscription Service WebReach. When you open a Vista user diagram in a web browser, the ION XML Subscription Automatic
Service creates a subscription and delivers the real-time data in XML format.

ION XML Subscription Store Stores XML data subscriptions for the power monitoring devices on the network. This service is
Automatic
Service used only by WebReach.

1 This service may not be available on all operating systems.

© 2009 Schneider Electric. All rights reserved. Page 17


ION Enterprise Databases PowerLogic ION Enterprise User Guide

ION Enterprise Databases


The ION Enterprise databases are typically installed on the Primary Server and 
run in the background of your ION Enterprise system. To connect to these 
databases, ION Enterprise uses the SQL Server instance you created when you 
installed ION Enterprise or configured SQL Server.
For information on managing these databases in ION Enterprise, see “Database 
Manager” on page 255.

Microsoft SQL Server Database


Microsoft SQL Server 2005 Express Edition (“SQL Server Express”) comes with 
ION Enterprise by default. SQL Server is the database engine that manages the 
ION Enterprise databases: the ION database (ION_Data), the Network 
Configuration database (ION_Network), and the System Events database 
(ION_SystemLog). To connect to the databases, ION Enterprise uses a SQL Server 
instance called ION, which is created when ION Enterprise is installed, unless a 
pre‐existing instance is specified when ION Enterprise is installed.

The Network Configuration Database


The Network Configuration database (“ION_Network”) stores information about 
your network topology — the network connections, computers and every connected 
device, including dialout modems. This information is used by the communications 
services (e.g., ION Network Router Service, ION Site Service) and other software 
components to manage data and control requests to and from the devices and the 
other ION Enterprise components (i.e., Vista, Designer).

The System Events Database


The System Events database (“ION_SystemLog”) stores data about events that 
occur during the operation of ION Enterprise components. For example, the event 
details about the communication service’s interactions with devices, details about 
controls initiated through Vista, and general or alarm level events that occur in the 
Virtual Processor are all inserted into the System Events database. These can then 
be viewed when you click the System Log Events icon in Management Console or 
through access to the ION_Data database using Vista (Event Log Viewer).
ION_SystemLog is not backed up. Some contents of the System Log — System 
Events with a priority of 192 or greater — are automatically inserted into the 
ION_Data database on a regular basis and can be viewed in Vista. 

The ION Database


The ION database (“ION_Data”) contains all the information collected from 
devices that have the ability to record data and from ION Enterprise components. 
This database uses the ION Log Inserter Service to gather data from all of the 
available sources, and then makes the data available to ION Enterprise 
components like Vista (through the ION Query Service) or Web Reporter (through 
direct database queries).

Page 18 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Getting Started

Getting Started
This section describes how to start, log on to and exit most components of ION 
Enterprise.

Starting a Component of ION Enterprise


Use one of the following methods to start the main components of ION Enterprise 
(i.e., Management Console, Vista or Web Reporter):
Open the ION Enterprise Tools folder on your desktop and double‐click the icon 
of the program you want to start.
Double‐click the ION Enterprise icon to open the ION Enterprise Taskpad, then 
click on one of the links.
Click Start > Programs > Schneider Electric > ION Enterprise Tools and select 
the program you want to start or click Start > Programs > ION Enterprise to 
launch the ION Enterprise Taskpad.

Logging into a Component of ION Enterprise


Most ION Enterprise programs require you to log in before you can access them.

At the logon prompt, type your user name and password in the appropriate box, 
then click OK. Some actions are restricted to certain users or groups, depending on 
how their login permissions were set up. See “User Manager” on page 55 for 
details. If you do not have a user name and password, log on in View Only mode 
for limited access. 

The default user name is “guest”. The default password is “0” (zero). The 
password field is case‐sensitive. For information on setting up user accounts and 
changing passwords, see “User Manager” on page 55.

After you log on, the program interface appears.

Ending a Session
There are two ways to end a session in a component of ION Enterprise:
Log off if you want to end the current user session but keep the program 
running, or
Exit if you want to close the program completely.

Some components offer both options; some only offer the Exit option.

© 2009 Schneider Electric. All rights reserved. Page 19


Ending a Session PowerLogic ION Enterprise User Guide

Logging Off
1. Select File > Logoff.
A message appears, prompting you to confirm your intention to log off.
2. Click Yes to log off or No to return to the program.
If you attempt to log off without saving your work, the program prompts you to 
save your changes. Click Yes to save your changes, No to discard them, or 
Cancel to return to the program.
After you log off, the ION Enterprise Logon screen appears.

Exiting
1. Select File > Exit.
A message appears, prompting you to confirm your intention to exit the 
application. 
2. Click Yes to exit or No to return to the program.
If you attempt to exit without saving your work, the program prompts you to 
save your changes. Click Yes to save your changes, No to discard them, or 
Cancel to return to the program.

Page 20 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Additional Information

Additional Information
For more information about ION Enterprise components, using devices with ION 
Enterprise, and ION architecture, see the following documents:
ION Enterprise 6.0 Commissioning Guide
ION Enterprise 6.0 System Requirements
Additional Device Support in ION Enterprise 6.0
OPC Server Assistant
PQDIF Exporter
Multilingual Support in ION Enterprise 6.0
ION System Security
Troubleshooting Serial Communications in PowerLogic ION Meters
Troubleshooting Meter Wiring
Upgrading ION Device Firmware
ION Reference

Visit www.powerlogic.com for more information and to obtain documentation.

© 2009 Schneider Electric. All rights reserved. Page 21


Customizing and Navigating Interface Displays PowerLogic ION Enterprise User Guide

Customizing and Navigating Interface Displays


The following sections describe ways to customize and navigate display windows, 
dialog boxes and tables in components of ION Enterprise.

Navigating Tree Structures


Information in ION Enterprise is often displayed in a tree. Click “+” to expand 
items in the tree or “‐” to collapse them.

Selecting Multiple Items in Tables, Tree Structures, Diagrams


and Folder Structures
To select adjacent items, select the first item, hold down the SHIFT key then click 
the last item.

To select non‐adjacent items, hold down the CTRL key then click to select the 
items.

To select adjacent items in Vista or Designer diagrams, drag a selection box around 
the items. All items in the box are selected.

Adjusting the Display of a Window or Dialog Box


The following sections describe how to resize and hide or reveal panes.

Resizing Panes
To resize panes in a window, point the mouse at the border where the two sections 
meet. When the resize handle appears, drag to move the border.

Dock (Pin) or Hide (Unpin) Pane


Some interfaces in ION Enterprise have panes that can be hidden (visible 
temporarily) or docked (visible all the time).

To hide or dock a pane, click the Pin/Unpin   button on the pane. When a pane 
is hidden, it is minimized to a button at the edge of the workspace. 

To temporarily show a hidden pane, hover the mouse over the button for that 
pane. Move the mouse away to hide the pane again.

Page 22 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Grid Table Controls

Grid Table Controls


Certain windows and utilities in ION Enterprise display information in “grid” 
tables. These tables have unique table and information display commands.
 

Group By Box Column Header Sort Icon Filter Icon Column Selector

Dynamic
Filter Area

Right-click
menu options

Select Columns/Column Selector


Some tables allow you to select which columns to include in the table.
1. In Management Console, hover over the column selector tab on the right side 
of the display window. In other interfaces, click the “Select Columns” link.
2. Select the boxes for the columns you want to include in the table. Clear the boxes 
for the columns you do not want to include in the table.

Adjust Column Width


To change the width of a column, point the mouse to the right edge of the column 
header. When the resize handle (double‐arrow pointer) appears, click and drag to 
adjust the width. To adjust the width for best fit, point to the right edge of the 
column header, then double‐click when the resize handle appears.

Best Fit
To adjust a column width to the best fit with the least amount of white space:
For one column, right‐click a column header and select Best Fit.
For all columns, right‐click on the column title area and select Best Fit (all 
columns).

Arrange Columns
To change the order of the columns, drag a column header to the left or right of its 
original position.

© 2009 Schneider Electric. All rights reserved. Page 23


Grid Table Controls PowerLogic ION Enterprise User Guide

Group by Column
To group data according to the contents of a particular column, drag the column 
header to the area above it (marked “Drag a column header here to group by that 
column”). To expand or collapse the groups, click the “+” or “‐” button. To expand 
or collapse all groups, right‐click the column header in the group by box and select 
Full Expand or Full Collapse, respectively. 

You can also group by multiple columns in a specific order, with sorting and 
filtering applied. 

To ungroup, drag the column header back to its original position (or right‐click the 
column header and select Ungroup).

To show or hide the Group By box, right‐click the column header and select or 
clear Group By Box.

Sorting Data in a Column


Click a column header to sort table rows according to data in that column. You can 
sort in ascending or descending order (indicated by an up or down arrow, 
respectively). To cancel sorting and return the column to its default state, right‐
click the column and select Clear Sorting.

Filtering Data in a Column


The following sections describe the available filtering options.

Using the Simple Column Filter


When the mouse is positioned over a column header, the Filter icon appears in the 
top right corner of the header. Click it to select one of the listed filter conditions and 
apply it to the data in that column. Select (Custom) to apply one or two logic 
conditions to filter the data. To cancel filtering and return the column to its default 
state, right‐click the column and select Clear Filter.

Page 24 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Grid Table Controls

Using the Dynamic Column Filter


Some tables have a row between the column header and the table data. This is the 
dynamic filter area.

To use the dynamic filter area, start typing the entry you want to filter on in the 
space above the applicable column. You can use an asterisk (*) at the beginning of 
the filter as a wildcard. Once you achieve the filter results you want, you can stop 
typing. For example, to filter out “DST” from “disturbance” in System Log Events, 
you only need to type “di”.

Using the Filter Builder


The Filter Builder is an advanced data filtering tool. Use it to create filters with 
multiple conditions across multiple columns. To use the Filter Builder:
1. Right‐click a column header and select Filter Editor. The Filter Builder dialog 
box appears.
2. Specify the filter conditions. 
The elements of the filter builder are: <Column Header> <Condition> <Value> 
Click an element to display the options available, then select the option you 
want to use. 

3. Select the <Column Header> and the <Condition> you want to apply. Type the 
<Value> to test for.
4. To add another filter, click the “+” button on the top.
5. Select a logic to apply to this new filter (in relationship to the current filter).
6. Repeat step 3. 
7. To remove a filter, click the delete (“x”) button beside it.

In the following example, the filter finds all devices whose names contain “FL1” 
and whose types begin with “ION”. 

© 2009 Schneider Electric. All rights reserved. Page 25


Grid Table Controls PowerLogic ION Enterprise User Guide

The rows returned are as follows:

Select the box to turn the filter on; clear it to turn the filter off. Click Edit Filter to configure
Click the “x” to cancel and exit the filter mode the filter conditions

Page 26 © 2009 Schneider Electric. All rights reserved.


2 Management Console
Use Management Console to add, remove or configure components, such as 
metering devices, in your ION Enterprise power management system. You can set 
up different types of sites (communication links such as Ethernet or serial), and set 
up connection schedules for these sites.

In addition, the Management Console Tools menu provides access to device and 
system configuration, maintenance and programming tools. See “Management 
Console Tools” on page 53 for details.

CAUTION
Unauthorized changes to network configuration can result in an unstable or unusable network, therefore
only users with Operator- or Supervisor-level access can make changes in Management Console.

In This Section

“The Management Console Interface” on page 28
“Management Console Network Components” on page 31
“Setting Up Your Network in Management Console” on page 33
“Accessing Meters with Advanced Security” on page 38
“Configuring Connection Schedules” on page 39
“System Log Events” on page 41
“Setting Up Large Systems” on page 43

© 2009 Schneider Electric. All rights reserved. Page 27


The Management Console Interface PowerLogic ION Enterprise User Guide

The Management Console Interface

Sort indicator Group By box Filter indicator Pin/Unpin Icon

Column Selector

System Setup pane


and icons

Mouse hover text

Display window: This area


displays the contents of the
selected system setup icon

Current filter applied Edit Filter button

Window Title
The window title displays the name of the software program and the current user.

System Setup Pane


The icons in the System Setup pane represent categories of items you can add, 
remove, set up, and view. Click an icon to go to the associated display window.

Display Window
The Display window shows the contents of the item currently selected in the 
System Setup pane.

Refresh
To manually refresh Management Console and reload its contents, select View > 
Refresh (or press F5). 

Page 28 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide The Management Console Interface

Options
Select Tools > Options to open the Options dialog box. Use this dialog box to 
change display settings for the System Log Events display window. 

Highlighting
Highlighting controls how Error events are displayed in the System Log Events 
display window. Select or clear the Enable Highlighting check box to turn 
highlighting on or off. Click Set Highlight Color to change the highlight color for 
Critical or Error events in the System Log Events display window.

Events
The Events section of the dialog box lets you control how many records appear in 
the System Log Events display window and how date and time are displayed. 

Customizing the Management Console Interface


You can customize what is displayed in the Management Console interface and the 
tables within the display windows: 
Select which columns appear in tables. 
Filter, sort and group data in tables. 

For instructions on using these features, see “Customizing and Navigating 
Interface Displays” on page 22.

Display Window Shortcut Menus


To access shortcut menus in the Display Window, first click the icon of the System 
Setup item you are interested in. Then right‐click in the display window area or on 
a network component to display the shortcut menu. The menu items available 
vary depending on the network component selected.

New displays the options available for adding new network items. 
Duplicate creates one or more copies of a selected item.

NOTE
For the Duplicate command, each one of the duplicates needs to be opened individually in order to
configure them. Duplicate and Configure allows you to create and configure multiple devices at the same
time.

Duplicate and Configure lets you perform batch cloning of devices. When 
multiple devices are selected, this right‐click shortcut becomes Configure 
Selected Devices which lets you perform setup functions such as batch 
renaming of devices.
Delete removes the selected items.
Connect and Disconnect let you manually connect to or disconnect from the 
selected site.

© 2009 Schneider Electric. All rights reserved. Page 29


The Management Console Interface PowerLogic ION Enterprise User Guide

NOTE
You cannot connect or disconnect an individual serial device in a site; you can only connect or disconnect
the site for that serial device.

Connect Ethernet and Disconnect Ethernet let you manually connect to or 
disconnect from the selected Ethernet device. 
Security accesses the Meter Security Settings dialog box. This is used by the 
software to gain access to security‐enabled devices (e.g., ION8600 or ION7650); 
it is only available from the shortcut menu for the Devices display pane.
Configure <Network Component> opens the <Network Component> 
Configuration dialog box (where <network component> is the component 
selected). Use this dialog box to make changes to the properties for the selected 
network component.

Page 30 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Management Console Network Components

Management Console Network Components


This section describes the different components in Management Console: Servers, 
Sites, Devices, Dial‐Out Modems, Connection Schedules, and System Log Events.

See “Setting Up Your Network in Management Console” on page 33 for 
information on adding these components to your network. 

Servers
A server is a computer in the ION Enterprise system that runs administrative 
software to control access to the network and its resources, such as metering 
devices.

Sites
A site is a group of devices in the ION Enterprise system that share a common 
communications link. A site can be a direct site, a modem site, an Ethernet gateway 
site, or an OPC site.

Direct Site
In a direct site, serial communications occur between a computer and one or more 
meters. The standards most commonly used on computers are RS‐232 (for 
connecting one device) and RS‐485 (for connecting a loop of up to 32 devices). 
When connecting to more than one serial device, use an RS‐232 to RS‐485 
converter.

Modem Site
In a modem site, communications occur between a remote modem (at the Modem 
Site) and a local modem (on the server). 

NOTE
Remote sites that use radio modems or leased-line modems are configured as Direct (Serial) Sites, not as
Modem Sites.

Modem sites can include traditional hardware modems (those that are configured 
and controlled by ION Enterprise) or WinModems (Windows modems). If 
multiple modems are set up in the modem site, ION Enterprise selects the first 
available modem to establish communications (this is referred to as “modem 
pooling”).

Ethernet Gateway Site


An Ethernet gateway site (for example, EtherGate or Modbus gateway) consists of 
an RS‐485 chain of devices that communicates with an Ethernet network via an 
Ethernet device. The Ethernet device acts as a gateway that transfers data between 
an Ethernet network and the devices connected to it via RS‐485. The gateway 
device converts RS‐232/RS‐485 communications to and from Ethernet.

© 2009 Schneider Electric. All rights reserved. Page 31


Management Console Network Components PowerLogic ION Enterprise User Guide

OPC Site
An OPC site consists of an OPC server that communicates with OPC‐compliant 
devices on the network.

Devices
A device is a meter or other component that communicates and gathers data, and 
is installed on a network.

Serial Devices
Serial devices belong to direct sites, modem sites, or Ethernet gateway sites — they 
communicate through a modem, RS‐232, RS‐485, or Ethernet‐to‐Serial gateway 
connection. You must have the appropriate sites configured first before you can 
add serial devices.

Ethernet Devices
Ethernet devices are those that are directly connected to the network via Ethernet. 
You can manually connect or disconnect your Ethernet device through the 
Management Console.

OPC Devices
OPC devices provide data in OPC format. You must have an OPC site configured 
to add an OPC device.

Dial-Out Modems
A dial‐out modem is one that a server computer uses to communicate with a 
remote modem at a modem site. The modem implemented can be a traditional 
hardware‐based modem or it can be a software‐based modem that uses the 
computer’s processor to emulate a traditional hardware‐based modem.

When a modem site needs to establish communications, it selects a modem from 
the list of modems configured in the modem site. You can add hardware modems 
or WinModems to the modem list.

NOTE
A WinModem is a modem that is directly controlled by the computer’s operating system.

Connection Schedules
Connection schedules are programmed routines for a server to regularly connect 
to and disconnect from sites (and their associated devices) and Ethernet devices. 
See “Configuring Connection Schedules” on page 39 for more information.

System Log Events


System Log Events lists events for the network. You can select what timeframe and 
components you want to view events for. See “System Log Events” on page 41 for 
more information.

Page 32 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Setting Up Your Network in Management Console

Setting Up Your Network in Management Console


The Primary Server contains all the ION Enterprise programs and it controls the 
overall operation of your energy management system. The primary server is 
displayed on the Server screen when you first start Management Console.

To start building your system, add and configure your sites and devices.

Adding Network Components


For details on adding various components, see the following sections. 

Follow the procedure below to add a new network component:
1. In the System Setup pane, select the icon for the type of item that you want to 
add (i.e., Site, Device, or Dial Out Modem). 
2. Right‐click in the display window, select New, and then select the specific type 
of network component from the shortcut menu. The options differ depending 
on which system setup icon you selected.
The Configuration dialog box appears.
3. Use the fields and drop‐down menus to configure properties. Mandatory items 
are highlighted in red. To configure advanced properties, right‐click in the 
dialog box and select Advanced Properties. For more shortcut menu options, 
see “Configuration Dialog Box Shortcut Menus”, below.
4.  Click OK to add the component.

Configuration Dialog Box Shortcut Menus


Right‐click the Configuration dialog box to access the following shortcut menu 
options:
Property Details: This opens a window that contains information on the 
selected property, including minimum and maximum allowable values, if 
applicable. 
Advanced Properties: This exposes all the property fields that are hidden in the 
default (basic) view. 
Reset All To Default: Resets all properties to their original values.

Adding a Server
Click the Servers icon, right‐click in the display window and select 
New > Computer. Fill in the mandatory Name field.

© 2009 Schneider Electric. All rights reserved. Page 33


Setting Up Devices for Direct Serial Communications PowerLogic ION Enterprise User Guide

Setting Up Devices for Direct Serial Communications


To set up devices for RS‐232 or RS‐485 communications on a direct serial loop, first 
add a direct site in Management Console and specify a serial communications port 
on the computer. 

Step1: Adding a Direct Site


Click the Sites icon. Right‐click in the display window and select New > Direct 
Site. Fill in the Name and Serial Port fields. Configure the other fields as you 
require.

Step 2: Adding a Device to the Direct Site


Click the Devices icon. Right‐click in the display window and select New > Serial 
Device on Direct Site. Fill in these fields:
Group: Type a name for the group or select an existing group from the list.
Name: Type the name you want to give the device.
Device Type: Select the type of the device.
Unit ID: Type the Unit ID of the device; the range is 1‐9999 for ION devices or 
1‐247 for Modbus RTU devices.
Site: Select the direct site you previously set up.

Configure the other fields as you require.

Setting Up Devices for Ethernet Gateway Communications


To set up devices for Ethernet gateway communications, first add and configure 
an Ethernet gateway site. Ethernet gateways that can be used include those that are 
simple Ethernet‐to‐Serial converters, or any gateway or data concentrator that 
provides ModbusTCP communications.

Step 1: Adding an Ethernet Gateway Site


Click the Sites icon. Right‐click in the display window and select New > Ethernet 
Gateway Site. 

Fill in the Name, TCP/IP Address and TCP/IP Port fields. The TCP/IP Port 
identifies which communications port is used to connect to the serial devices. The 
port you use depends on the type of Ethernet gateway you want to set up (i.e., use 
7801 for an EtherGate gateway via COM1 or use port 502 for a Modbus gateway). 

Configure the other fields as you require.

Page 34 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Adding an Ethernet Device

Step 2: Adding a Device to the Ethernet Gateway Site


Click the Devices icon. Right‐click in the display window and select New > Serial 
Device on Ethernet Gateway Site. Fill in these fields:
Group: Type a name for the group or select an existing group from the list.
Name: Type the name you want to give the device. 
Device Type: Select the type of device.
Unit ID: Type the Unit ID of the device; the range is 1‐9999 for ION devices or 
1‐247 for Modbus devices.
Site: Select the Ethernet gateway site you previously set up.

Configure the other fields as you require.

Adding an Ethernet Device


Click the Devices icon. Right‐click in the display window and select 
New > Ethernet Device. Fill in the Group, Name, Device Type and TCP/IP 
Address fields. Configure the other fields as you require.

NOTE
When you configure Ethernet or Ethernet gateway devices, you can specify either a hostname or an
IP address in the TCP/IP Address field.

Setting Up Devices for OPC Communications


To set up devices for OPC communications, first add an OPC site.

Step 1: Adding an OPC Site


Click the Sites icon. Right‐click in the display window and select New > OPC Site. 
Fill in the Name and Address fields. Configure the other fields as you require.

Make sure you follow the correct syntax when typing in the address for the OPC 
site. Select the Address field to see an example address in the Property Description 
section (near the bottom of the OPC Site Configuration dialog box).

Step 2: Adding a Device to the OPC Site

NOTE
At least one OPC Device Type needs to be preconfigured before an OPC Device can be created in
Management Console. Contact Technical Support for assistance.

Click the Devices icon. Right‐click in the display window and select New > 
OPC Device. Fill in the Group, Name, Device Type and Site (select the OPC site 
you previously set up). Configure the other fields as you require.

© 2009 Schneider Electric. All rights reserved. Page 35


Adding a Modem PowerLogic ION Enterprise User Guide

Adding a Modem
1. Click the Dial‐Out Modems icon, right‐click in the display window and select 
New, then select either Serial Modem (hardware modem) or WinModem 
(Windows modem).
2. Fill in the values for the mandatory fields:
For Serial modem, select the Modem Type from the list. If your modem is 
not in this list, select “Generic ION Modem ‐ Other”. Select the Serial Port 
where your modem is connected.
For WinModems, select the Modem Name from the list.
Configure the other fields as you require.
3. Click OK.

WinModem Installation Notes


Before you can use a WinModem, you must first install it on your computer (follow 
the instructions that came with the WinModem product). After you restart the 
computer, set up the WinModem:
1. In Microsoft Windows, click Start > Settings > Control Panel, then double‐
click Phone and Modem Options.
2. Click the Modems tab, select your WinModem, then click Properties.
3. Click the Advanced tab, then click Change Default Preference.
4. Set Port speed to match the baud rate that is used between the meter and the 
modem on the remote end of the connection (i.e., both modems must be set to 
the same baud rate). 
5. Set Flow Control to “None”.
6. Click OK to save your changes.

NOTE
You may need to restart your computer for the settings to take effect.

Editing a Network Component


1. Click the icon in the System Setup pane for the type of component you want to 
edit.
2. In the display window, right‐click the network component you want to edit and 
select Configure <Network Component> (with <Network Component> being 
the type of component you want to edit).
3. Make the required changes. To display all configurable fields, right‐click in the 
Configuration dialog box and select Advanced Properties.

4. Click OK when you are finished to save your changes.

Page 36 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Deleting a Network Component

NOTE
If you rename a group or device in Management Console, you will not be able to access the data that is
already stored in the database using the previous group or device name. New data will be added to the
database using the new name.

Deleting a Network Component


1. Click the System Setup icon for the type of component you want to delete.
2. In the display window, right‐click the network component you want to delete 
and select Delete (or select the item and press the DELETE key).
3. Click Yes to confirm the deletion or No to cancel.

NOTE
When you delete a Site or a Server, all devices associated with it are also deleted.

© 2009 Schneider Electric. All rights reserved. Page 37


Accessing Meters with Advanced Security PowerLogic ION Enterprise User Guide

Accessing Meters with Advanced Security


If you have a meter in your network with Advanced Security enabled, use 
Management Console to allow ION Enterprise Services to access the meter:
1. Right‐click the device that has Advanced Security enabled and select Security. 
The Meter Security Settings dialog box appears.
2. From the Software Access dropdown list, select the user (configured on the 
meter using Designer or ION Setup) that has the access settings that you want to 
give ION Enterprise services and components to the device. 
3. Click Match Password and type the password for that user in the Password field 
then re‐type it in the Confirm Password field. 
4. Select the check box if you want to allow the software to send secure time 
synchronization signals to the meter. Clear the check box if you do not want to 
send secure time synchronization signals to the device.
5. Click OK.

Page 38 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Configuring Connection Schedules

Configuring Connection Schedules


You can schedule the times when the server connects to a site or Ethernet device. 

Adding a Connection Schedule


Click the Connection Schedules icon, right‐click in the display window, then select 
New > Connection Schedule. The Scheduled Site Connection dialog box appears. 
The following sections describe the available tabs and how to configure them.

General Settings Tab


On the General Settings tab:
Type the name of your connection schedule (for example “Daily Reading”) in 
the Name field. 
Type a description of the connection schedule, if required. 
Make sure Enabled is selected if you want to enable the schedule.
Select the date from which the schedule is valid.

Sites Tab
On the Sites tab:
Click the box beside the sites and devices to select those that you want to include 
in the connection schedule. A check mark appears beside an item to indicate that 
it is included in the connection schedule.
Set your Site Connection Settings. To enter the minimum and maximum time to 
stay connected, type the time in the fields or use the arrows to change the time.
Set the Connection Priority. The higher the number, the greater the priority 
given to that schedule if there are concurrent connection requests.

© 2009 Schneider Electric. All rights reserved. Page 39


Configuring Connection Schedules PowerLogic ION Enterprise User Guide

Schedule Tab
On the Schedule tab:
Set up the date schedule for the connection (the default is Daily). Schedule 
options vary depending on the type of schedule selected.
Daily: Occurs every day.
Weekly: Occurs on the selected day at the specified frequency (in number of 
weeks) and stays active for the specified duration. For example, if you set 
Frequency to 2, Day of week to Sunday and Active Duration to 2, the 
connection occurs every second Sunday and stays active for two days.
Monthly ‐ Day of Week: Occurs at the specified frequency (in months), in 
the week and on the day specified and for the specified duration. For 
example, if you set Frequency to 3, Day of Month to 2nd and Sunday, and 
Duration to 1, the connection occurs every third month on the second 
Sunday and stays active for 1 day.
Monthly ‐ Day of Month: Occurs at the specified frequency (in months), on 
the specified date of the month, and for the duration specified. For example, 
if you set Frequency to 2, Day of Month to 15th and Duration to 2, the 
connection occurs on the fifteenth day of every second month and stays 
active for 2 days.
Set up the time period for the connection to occur by setting a start and an end 
time. In the Start Time and End Time fields, type the time or use the arrows to 
change the time.
 

If you configure a full‐day (i.e., 24‐hour) daily schedule, make sure you allow 
enough time between the end time and the start of the next connection to avoid 
connection problems. For example, to add a 2‐minute gap to a 24‐hour schedule, 
set the Start Time to 0:00:00 and the EndTime to 23:58:00.

Page 40 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide System Log Events

System Log Events


System Log Events lists events for components in the system. This information 
comes from the ION_SystemLog database.
 

TIP
For instructions on filtering and sorting columns and customizing the display, see “Customizing and
Navigating Interface Displays” on page 22.

Viewing System Log Events


To view System Log Events:
1. Select System Log Events from the System Setup pane.
2. Select the system components for which you want to view events (i.e., servers, 
sites, devices). 
If there are no events for a particular system component, that check box is 
unavailable. 

© 2009 Schneider Electric. All rights reserved. Page 41


System Log Events PowerLogic ION Enterprise User Guide

3. Select the minimum priority level of events to be displayed (see below for more 
information on priority levels).
4. Click Modify to change the date/time filter applied to the System Events Log 
display. See “System Log Filter Setup” on page 42.
5. To view details of an event, double‐click on the entry in the event log.

Priority
Priority classifies what type of event has occurred. The value corresponds to the 
severity of the event: the higher the number, the more severe the event. 

The priority is contained in the ION_SystemLog database as a number. In the 
System Events Log display, the priority levels are displayed as text strings. The 
priority numbers are mapped to the text strings as follows: 
Diagnostic 0-5 Warning 21-63 Critical 192-255

Information 6-20 Error 64-191

By default, the Cutoff setup register of Log Inserter’s System Log Controller 
module is set to 192. This means that system events with a priority less than 192 
are not transferred to the ION_Data database and therefore cannot be viewed in 
Vista using the Global Event Log Viewer. If you want to view lower priority events 
in Vista, use the above priority mapping as a guide to set the Cutoff setup register 
to a lower value (using Designer).

System Log Filter Setup


The System Log Filter Setup dialog box lets you change the date and time filter 
applied to the System Events Log display.
1. Click Modify to display the System Log Filter Setup dialog box. 
2. Select the time range by which you want to filter from the dropdown list. To set 
up a custom filter, select Custom Date Range then use the dropdown lists and 
arrows in the Select a Date Range dialog box to specify the start and end of the 
range.
3. Click OK.

Page 42 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Setting Up Large Systems

Setting Up Large Systems


To perform batch network setup of devices, create the first device in Management 
Console (see “Adding Network Components” on page 33) using a logical naming 
scheme. After you create this first device, you can then use it to create multiple 
duplicate devices and configure their properties.

The Duplicate and Configure Interface

Scroll left
Scroll right
Start & End spin box

Duplicate and
Configure area

Hide/Show
Columns area

Table Editing
area

NOTE
When table rows are filtered in the Duplicate and Configure tool, changes done using the configuration
editors on the top pane of the window affect only the devices that are visible in the Table Editing area. If
you want to apply the changes to all devices, clear the filter first before making the changes.

The Duplicate and Configure Area


The Duplicate and Configure area has different sections depending on the type of 
device you are duplicating.

Ethernet devices have the following sections:
Configure Names: Use this section to create the duplicates.
Configure TCP/IP Addresses: Use this section to create a sequence of IP 
addresses to assign to the duplicates after they have been created.

© 2009 Schneider Electric. All rights reserved. Page 43


The Duplicate and Configure Interface PowerLogic ION Enterprise User Guide

Configure TCP/IP Ports: The port number used in the original device is 
automatically assigned to all the duplicates. If required, use this section to select 
a different port number for all the displayed devices in the Table Editing area 
(changes made in this area are applied to all devices, including the original).
Configure Unit IDs: This section is disabled by default, since unit IDs do not 
apply to typical Ethernet devices. (To enable this section, you must first set up 
the Table Editing area so that the “Unit ID” column is visible).

Serial devices have the following sections:
Configure Names: Use this section to create the duplicates.
Configure Unit IDs: Use this section to create a sequence of unit IDs to assign to 
the duplicates after they have been created.
Configure Serial Sites: The serial site used in the original device is 
automatically assigned to all the duplicates. If required, use this section to select 
a different serial site for all the displayed devices in the Table Editing area 
(changes made in this area are applied to all devices, including the original).

OPC devices have the following sections:
Configure Names: Use this section to create the duplicates.
Configure OPC Address: Use this section to create a sequence of addresses to 
assign to the duplicates after they have been created.
Configure OPC Sites: The OPC site used in the original device is automatically 
assigned to all the duplicates. If required, use this section to select a different 
OPC site for all the displayed devices in the Table Editing area (changes made in 
this area are applied to all devices, including the original).

The Table Editing Area


When making configuration changes in the Duplicate and Configure interface, 
these changes are applied only to the rows that are visible in the Table Editing area.

See “Customizing and Navigating Interface Displays” on page 22 for instructions 
on filtering and sorting data in the table.

NOTE
To discard your changes since the last saved state, click Revert. You can also press CTRL+Z to undo the
last action. To redo the last action, press SHIFT+CTRL+Z. You can only undo your last action (one undo).

Page 44 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Creating Multiple Copies of a Device

Creating Multiple Copies of a Device


This section describes how to duplicate and configure devices.

Step 1: Configuring the First Device


1. Add the first device using your logical naming scheme. 
For example, you can use a scheme like “FL1_PNL1A.CCT01” to name a 
device that is installed on the “1st Floor” of the building, “electrical panel 1A”, 
and “Circuit breaker #1”. Type “FL1_PNL1A” as the group name and “CCT01” 
as the device name when you configure the first device.
2. Right‐click the device you want to duplicate and select Duplicate and 
Configure. The Duplicate and Configure interface appears.

Step 2: Configuring Names


In the Configure Names area, the device name is displayed. Each letter and 
number is selectable. A group of numbers is treated as a single entity. For example, 
in the name “MY8600” the entities you can select are “M”, “Y” and “8600”. Leading 
zeroes are also supported, so you can set sequences such as “01, 02, 03” or “001, 
002, 003”.

1. Select a letter or number in the device name. The Start box displays the 
selected number/letter, which is the start value. Use the up or down arrow in 
the spin box to change the start value, or simply type it in the box.
2. Click the up or down arrow on the End box edit the range, or type the end value 
in the box. To clear the range and start over, click Remove Parameters.
3. For letters, select Upper Case or Lower Case, depending on whether you require 
upper case or lower case letters.
4. Set exceptions for individual values or a range of values, if required. Exceptions 
reduce the number of names created (i.e., total generated names minus the 
exceptions). See“Setting Exceptions to Generated Sequences” on page 46. 

Once you have finished configuring names, you can duplicate the device. See 
“Step 3: Duplicating the Device”, below, for more information.

© 2009 Schneider Electric. All rights reserved. Page 45


Creating Multiple Copies of a Device PowerLogic ION Enterprise User Guide

Example
For example, if you select the first “1” from the example naming scheme and set 
the End spin box to “2”, two names are generated (the original, plus one duplicate). 
If you select a letter and set its Start value to “A” and the End value to “C”, three 
names are generated (the original, plus two duplicates).

The total number of generated names is the product of the first range multiplied 
by the next, and so on until the last range, as indicated in the following graphic.

The total generated names is the product:


[2 x 3 x 10] = 60

Setting Exceptions to Generated Sequences


The Exceptions option applies to the Configure Names and Configure TCP/IP 
Addresses sections only.
1. To set exceptions to the range of generated values, click Edit (this button is 
unavailable until you change the name or IP value).

List of current exceptions

2. Use the Add number or Add character (as applicable) spin box to set a value to 
exclude from the range you have specified, then click Add. Repeat to set 
additional values to exclude. To set a range of values to exclude, select Add 
number range or Add character range, then use the Start and End spin boxes to 
set the range to exclude. 
Click Add. Repeat to set additional ranges of values to exclude.

Page 46 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Creating Multiple Copies of a Device

NOTE
You cannot add the same number or letter to the list of exceptions more than once. If the Add button is
disabled, check that the numbers or letters are not already included in the exceptions list near the top of
the window.

3. Use the Remove number or Remove character spin box to remove the exception 
that was set for a given value (i.e., put it back in as an acceptable value). Use the 
Remove number range or Remove character range spin boxes to remove the 
exception that was set for a range of values. Click Remove.

Step 3: Duplicating the Device


Once you have finished configuring names, you are ready to duplicate the device. 
Click Duplicate. The duplicated devices appear in the Table Editing area.

Original device

Asterisks indicate pending changes


that have not yet been saved.

Click Apply to save your changes and continue editing devices, click OK to save 
your changes and return to Management Console, or click Revert to undo unsaved 
changes. 

Duplicated Devices in Management Console

Duplicated devices are always


disabled when they are added to
Management Console

Step 4: Configuring Duplicated Devices


See the following section, “Configuring Multiple Devices”, for instructions on 
configuring other properties for multiple devices. 

© 2009 Schneider Electric. All rights reserved. Page 47


Configuring Multiple Devices PowerLogic ION Enterprise User Guide

Configuring Multiple Devices


After you have duplicated the devices, you can select and configure any or all of 
them.
1. If you have closed the Duplicate and Configure interface, select the devices 
you want to configure from the Devices display window in Management 
Console. Right‐click and select Configure Selected Devices (this option is 
only available if multiple devices are selected). 
The Configure Selected Devices interface appears. This interface has the same 
layout and controls as the Duplicate and Configure interface; see “The Duplicate 
and Configure Interface” on page 43 for information.

NOTE
Devices affected by a configuration change (that has not been saved) are identified by an asterisk in the
first column of the Table Editing area.

2. Scroll to the right in the Duplicate and Configure area to view the Configure 
TCP/IP Addresses, Unit IDs, Ports and Sites sections of the interface 
(depending on the type of device being configured). Configure these 
parameters as described in “Configuring Addresses, Ports, Unit IDs and Sites” 
on page 49 then click Configure at the bottom of the applicable interface section.

NOTE
Configuration changes only affect the devices that are currently displayed in the Table Editing area. Use
the column sorting and filtering features, described in “Customizing and Navigating Interface Displays”
on page 22, to control which devices are displayed in the table. If you want to apply the changes to all
devices, clear any filtering before making the changes.

3. Click Apply to save your changes and continue working or click OK to save 
your changes and return to Management Console. 

NOTE
If you changed the name of one or more devices, a warning displays with a list of devices that will be
renamed. If data for those devices already exist in the ION_Data database and you still proceed with the
renaming, then the existing data associated with the old device name is lost (“orphaned”).

Click Continue to proceed or Cancel to go back and edit the device 
configuration.
4. When you have finished, click OK to save your changes and return to 
Management Console or click Cancel to discard your changes. 
If you click Cancel, a dialog box prompts you if there are pending (unsaved) 
changes when you click Cancel. Click Yes to discard the changes and return to 
Management Console, or No to return to the configuration window and 
continue editing. 
If inappropriate values (such as a device that is renamed with the same name as 
another existing device) are encountered, a message displays with error details. 
You cannot save the configuration changes until you have corrected the errors.

Page 48 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Configuring Multiple Devices

Configuring Addresses, Ports, Unit IDs and Sites


The following sections describe how to configure addresses, ports, and unit IDs.

Text color is red if the number of items


does not match the number of items in
the Table Editing area. If the numbers
match, the text color is black.

Configuring TCP/IP Addresses


1. Select the section of the IP address that you want to configure. The Start box 
displays the selected number/letter, which is the start value. Use the up or 
down arrow in the spin box to change the start value, or simply type it in the 
box.
2. Click the up or down arrow on the End box edit the range, or type the end value 
in the box. To clear the range and start over, click Remove Parameters.
3. Set exceptions for individual values or a range of values, if required. Exceptions 
reduce the number of addresses created (i.e., total generated addresses minus 
the exceptions). See“Setting Exceptions to Generated Sequences” on page 46. 
4. Click Configure at the bottom of the Configure TCP/IP Addresses section.

Configuring Unit IDs


The following instructions apply to serial devices (and Ethernet devices that 
require a unit ID).
1. Use the up or down arrow in the Start spin box to change the start value, or 
simply type it in the box.
2. Click the up or down arrow on the End box edit the range, or type the end value 
in the box.
3. Click Configure at the bottom of the Configure Unit IDs section.

NOTE
To edit the unit ID of an Ethernet device, you must first add the Unit ID column to the table in the Table
Editing area.

Configuring Sites
1. From the dropdown list, select the site you want to use for the selected serial 
or OPC devices.
2. Click Configure at the bottom of the Configure Sites section.

© 2009 Schneider Electric. All rights reserved. Page 49


Editing Duplicated Device Information PowerLogic ION Enterprise User Guide

Configuring Ports
1. From the dropdown list, select the port you want to use for the selected 
Ethernet devices. 
2. Click Configure at the bottom of the Configure Ports section.

Editing Duplicated Device Information


The following sections describe how to quickly edit the properties of duplicated 
devices in the table editing area.

Copying Device Information from a Spreadsheet


Sometimes device names do not follow any particular naming pattern. In this case, 
you can use the copy/paste function to apply configuration changes directly to the 
Table Editing area. 

First, you need to add a new device in Management Console, then create as many 
duplicates of the device as the quantity of items you are pasting. 

If you have a Microsoft Excel spreadsheet that contains a list of these devices to 
add to Management Console, you can use the Configure Names area to create 
duplicates of that device type, then use the Table Editing area to copy and paste 
the device properties from the Excel spreadsheet.

Example: Copy and Paste 20 Ethernet Devices from Excel


1. Make sure the names in the Excel spreadsheet conform to the naming 
convention “[Group].[DeviceName]”.
2. Add the first device and set up its properties in Management Console. You can 
assign it a simple device name such as “A.B1” since it will be overwritten when 
the values are copied and pasted from Excel. Set the Enabled property to No 
(this makes sure that Management Console does not attempt to connect to the 
device).
3. Click OK to add the device.
4. Right‐click the device and select Duplicate and Configure.
5. Select the “1” in the Configure Names box, then use the End spin box to set the 
value to 20.
6. In the Hide/Show Columns area, clear the check box of all non‐editable columns 
to hide those that contain grayed out values. Also hide the columns you do not 
want to paste over or those that are not included in the Excel spreadsheet.
7. On the Excel spreadsheet, arrange the columns so they match the order of the 
columns on the Table Editing area. Hide all columns on the Excel spreadsheet 
except those corresponding to columns on the Table Editing area.
8. Select the cells in Excel and copy them (CTRL+C).

Page 50 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Editing Duplicated Device Information

9. On the Table Editing area, click on the first cell under the Name column to select 
it, then paste the contents of the clipboard (CTRL+V).
10. Click Apply to save your changes or click OK save your changes and return to 
Management Console.

Using Find and Replace to Edit Device Information


Use the Find and Replace feature to modify matching characters in the device 
names or in any other editable columns on the device table. The Find and Replace 
feature does not work on read‐only columns.
1. Right‐click the device table and select Find and Replace (or press CTRL+H).
2. Type the characters you want to search for in the Find box. Do not use wildcard 
characters (“*”). Note that the search is case‐sensitive.
3. Find in column lists all available columns. Select the column you want to search 
in.
4. In the Replace box, type the characters you want to use to replace the characters 
in the Find box. If you want to delete characters from a column value, leave the 
Replace box blank.
5. Click Preview to list the search results in the table. The Replace with column 
displays the new name or value resulting from the Find and Replace operation.
6. Use the check box in the Select column to select the rows for which you want to 
change values. Click Select All to select all the items or Clear Selected to clear 
all.
7. Click Apply to save your changes or Cancel to discard your changes
8. Click OK to save your changes and close the dialog box.

© 2009 Schneider Electric. All rights reserved. Page 51


Editing Duplicated Device Information PowerLogic ION Enterprise User Guide

Page 52 © 2009 Schneider Electric. All rights reserved.


3 Management Console Tools
Management Console tools are additional programs that help you manage and 
monitor your ION Enterprise network.

In This Section

“Introduction” on page 54
“User Manager” on page 55
“License Manager” on page 60
“Reporting Configuration Manager” on page 61
“Event Watcher Manager” on page 62
“Diagnostics Viewer” on page 66
“Device Upgrader” on page 71
“Remote Modem Setup” on page 74
“Virtual Processor Setup” on page 75
“Time of Use Editor” on page 80

© 2009 Schneider Electric. All rights reserved. Page 53


Introduction PowerLogic ION Enterprise User Guide

Introduction
The following programs are available in ION Enterprise, and can be started 
through the Management Console’s Tools menu:
User Manager allows you to configure ION Enterprise user login names, access 
levels and passwords.
License Manager allows you to upgrade your software license to provide 
additional device, client and software support.
Reporting Configuration Manager allows you to set up options for Web 
Reporter.
Database Manager allows you to perform and schedule maintenance tasks on 
your ION Enterprise databases. See “Database Manager” on page 255.
Designer allows you to configure devices and add custom functionality to 
them; see “Designer” on page 195.
Diagnostics Viewer provides detailed records of all system and network events 
as well as communication states and problems.
Device Upgrader allows you to upload new firmware to network meters or 
devices.
Remote Modem Setup allows you to configure dialup modems that will be 
used at remote power management networks.
ION Virtual Processor Setup allows you to configure the ION Virtual 
Processor Service for user‐programmed functionality.
Modbus Device Importer allows you to add Modbus devices to the ION 
Enterprise network; see “Modbus Device Importer” on page 277.
Event Watcher Manager allows you to set event conditions to report on and 
link those conditions to devices.
Time of Use Editor allows you to define a time of use schedule that is used by 
selected reports such as Energy and Demand.

Commands for Optional Components


The Update OPC Server and PQDIF Exporter commands appear in the Tools 
menu if these optional components were purchased with ION Enterprise (or 
activated later using the appropriate upgrade software license). See the OPC 
Server Assistant and PQDIF Exporter documentation for more information on 
these features.

Page 54 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide User Manager

User Manager
User Manager allows you to add users and edit user information, such as 
passwords, access level, and organizational information. You can also use User 
Manager to define groups of users for use in Web Reporter subscriptions. 
You must have supervisor level access to use User Manager, otherwise the menu 
option is unavailable.

Access Levels

Access Level

Supervisor (5)
View Only (1)

Controller (3)

Operator (4)
Observer\

User (2)
Type of Operation Allowed by Default

View Vista or Designer diagrams YES YES YES YES YES

Acknowledge alarms1 YES YES YES YES

Trigger events1 YES YES YES

Connect/disconnect sites or devices YES YES YES

Modify network configuration (using Management Console) YES YES


Edit Vista or Designer diagrams YES

Administer software security (i.e., add users) YES

1
Supervisors can configure Vista objects (i.e., control objects or the global event log viewer) to allow
different access levels to perform different actions (i.e., trigger events or acknowledge alarms). See
“Customizing a Diagram Object” on page 133 for more information on configuring access levels for
Vista objects.

Starting User Manager


1. Start Management Console. Log in using an account with supervisor level 
access.
2. Select Tools > User Manager.

TIP
You can customize the User Manager display by filtering and sorting. For instructions on using these
features, see “Customizing and Navigating Interface Displays” on page 22.

© 2009 Schneider Electric. All rights reserved. Page 55


Users PowerLogic ION Enterprise User Guide

Symbols Used in the Updated Column


The following symbols are used in the Updated column to display the status of 
information in a row:

* Information in the row has been modified since it was last saved.

! There is an error in the information in the row.

+ The row is new since the user or group information was last saved.

Users
Use the Users tab to view, add and edit users and user information. Information 
that is required but is missing or incorrect is marked by an exclamation mark  .

List of users

Edit User Account


section

Available access
levels

Message area

Adding Users
1. Click New. A new row appears in the list of users and the fields in the Edit 
User Account section are empty.
2. Enter the user information (username and password are required; other 
information is optional):

Page 56 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Users

Username: Type a username for the new user (maximum length: 50 
characters; no spaces allowed). 
Password: Type a password for the new user (maximum length: 50 
characters; no spaces allowed).
Re‐enter Password: Re‐enter the password you typed in the password field. 
An exclamation mark appears beside this field unless the content of the two 
password fields matches. 
Access Level: Select an access level for the user. See “Access Levels” on 
page 55 for an outline of the different access levels and their permissions.
First Name: Type the user’s given name.
Last Name: Type the user’s family name.
Organization: Type the user’s organization.
Business Email: Type a business email address for the user.
Mobile Email: Type a mobile email address for the user.
3. Click Apply to save the changes or click OK to save the changes and exit User 
Manager.
During the ION Enterprise software installation, two default user names (“guest” 
and “supervisor”) are created, both with a default password of “0” (zero). Since 
both these user names have supervisor level access, the default password should 
be changed or the accounts removed after you add a new user with supervisor 
level access.

Changing User Information


1. Select the username associated with the information you want to change. 
2. Type the new information in the Edit User Account section of the Users tab. 
After you edit a user’s information, an asterisk appears beside that user in the list 
of users until you click OK to save the information. 
3. Click Apply to save the changes or click OK to save the changes and exit User 
Manager.

Deleting a User
1. Select the username of the user you want to delete then click Delete. The row 
disappears from the list of users. You cannot delete the user account you are 
currently logged in with—the Delete button becomes unavailable.

NOTE
You cannot use the Revert button to undo a deletion. To undo a deletion, click Cancel to exit out of User
Manager without saving your changes.

2. Click OK to save your changes and exit User Manager. 

© 2009 Schneider Electric. All rights reserved. Page 57


Groups PowerLogic ION Enterprise User Guide

Groups
Use the Groups tab of User Manager to define groups of users. Groups can be used 
to determine access to reports in Web Reporter. Information that is required but is 
missing is marked by an exclamation mark  .

List of groups

Edit User Groups


section

Defining Groups
1. On the Groups tab, click New. A new row appears in the lists of groups.
2. In the Edit User Group section of the tab, enter the name (required) and 
description of the group.
3. To add a user to the selected group, select the username from the Users list and 
click the right arrow button  .
4. To remove a user from the selected group, select the username from the 
Members Of list and click the left arrow button  .
5. Click Apply to save your changes or click OK to save your changes and exit User 
Manager.

Page 58 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Groups

Changing Group Information


1. Select the group associated with the information you want to change.
2. Type the new information in the Edit User Group section of the Groups tab. Use 
the right and left arrow buttons to add or remove users from the selected group, 
as needed. After you edit a group’s name or description, an asterisk appears 
beside that group in the list of groups until you click OK to save the information. 
3. Click Apply to save your changes or click OK to save the changes and exit User 
Manager.

Deleting Groups
To delete a group, select the group from the list and click Delete. 

NOTE
You cannot use the Revert button to undo a deletion. To undo a deletion, click Cancel to exit out of User
Manager without saving your changes.

© 2009 Schneider Electric. All rights reserved. Page 59


License Manager PowerLogic ION Enterprise User Guide

License Manager
For additional device or client user support (e.g., Vista clients) for your ION 
Enterprise system, or to add OPC and/or PQDIF options, order the appropriate 
license from Schneider Electric.

When you receive your new license, use License Manager to upgrade the number 
of supported devices and client users in your system:
1. Log in to Management Console.
2. Click Tools > License Manager. The License Manager dialog box appears.
The current product key number, number of devices in the system, and 
maximum number of devices supported are listed in the System Info section.
3. Type the new product key in the Product Key field. Click OK.

The System Info section lists the updated support information from the newly 
activated product key. If the new key supports additional features or options, these 
are made available immediately, without restarting Management Console.

Page 60 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Reporting Configuration Manager

Reporting Configuration Manager


Use the Reporting Configuration Manager option in the Tools menu to configure 
options for Web Reporter such as the database to report on and subscription 
delivery options.
1. Open Management Console and select Tools > Reporting Configuration 
Manager. The Reporting Configuration dialog box appears.
2. Select the Reports tab to configure general reporting options:
From the dropdown list in the Reports Database section, select the database 
on which you want to run reports. Only those databases compatible with 
Web Reporter are listed.
Use the slider in the Report Timeout section to set the time (in seconds) after 
which Web Reporter stops trying to complete a report generation task.
3. Select the Subscriptions tab to configure settings related to report subscriptions:
SMTP Server: Type the network server name from which the report 
subscriptions are emailed. 
“From” Display Name: Type the name that you want to appear in the 
“From” field of an emailed report.
“From” Email Address: Type the email address that you want to appear in 
the “From” field of the emailed report. 
Default “Overwrite Existing File” Setting: Select the check box to set the 
default setting for the “Overwrite Existing File” check box that appears in 
the Subscriptions dialog box when you select “File share” for the 
subscription Delivery Mode. If you select this check box, the existing report 
is overwritten by default. If you clear this check box, the new report is given 
a unique filename and the existing report is not overwritten.
4. Click OK to save your changes.

© 2009 Schneider Electric. All rights reserved. Page 61


Event Watcher Manager PowerLogic ION Enterprise User Guide

Event Watcher Manager


The Event Watcher Manager defines events for the “On Event” selection in report 
subscriptions. See “Creating Report Subscriptions” on page 188 for more 
information on report subscriptions.

The Event Watcher Manager interface consists of two tabs: 
Event Watchers: An event watcher links a device or group of devices to the 
conditions defined in a template.
Templates: A template defines the conditions that make up an event. 

TIP
For instructions on using filtering, sorting, and column selection to customize the Event Watcher Manager
interface, see “Customizing and Navigating Interface Displays” on page 22.

Opening Event Watcher Manager


To access Event Watcher Manager, select Tools > Event Watcher Manager in 
Management Console.

Symbols Used in the Updated Column


The following symbols are used in the Updated column to display the status of 
information in a row:

* Information in the row has been modified since it was last saved.

! There is an error in the information in the row.

+ The row is new since the event watcher or template information was last saved.

Page 62 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Creating a Template

Creating a Template
Before adding an event watcher, you must have a template that defines the 
conditions to be watched. You can use one of the default templates or create your 
own. Use the Templates tab to define and edit templates.

List of
templates

Template
editing area

Template Conditions Area

Event Watcher Manager comes with default templates that cannot be modified. 
You can create custom templates if the default templates do not provide what you 
need.

To define a custom template:
1. Click New in the top right corner of the tab. A new row appears in the main 
table for the new template.
2. Type a name for the template. Type a description for the template if desired.
3. Use the Template Conditions section to set the conditions to be watched. See 
“Using the Template Conditions Section”, below.
4. Click Apply to save your changes, click OK to save your changes and exit Event 
Watcher Manager, or click the Event Watchers tab to set up an event watcher.

© 2009 Schneider Electric. All rights reserved. Page 63


Adding an Event Watcher PowerLogic ION Enterprise User Guide

Using the Template Conditions Section


Use this section of the interface to configure the condition the template watches 
for.
1. Add a condition:
To add a condition from the event log, click Select from Event Log. The 
Select Event Log Lines dialog box appears. To select an event, click on the 
boxes at the left of the table to select a check box. Click on the check box 
again to clear the check mark. Click OK to return to the Templates tab.
To add a condition without selecting from the event log, click New. A new 
row appears in the table for the new condition.

NOTE
It is recommended that you use Select From Event Log to add conditions. This ensures that the syntax is
correct. If the syntax is not correct, the event watcher will not work. Conditions only appear in the Select
Event Log Lines dialog box after they have occurred in the system.

2. Select the parameters you want to include in the condition by selecting or 
clearing the check boxes below the Template Conditions table. The available 
parameters are: Priority, Cause, Cause Value, Effect, Effect Value. You must 
include at least one parameter. If you select multiple parameters, the event 
watcher only activates when all parameters are met. 

The Logic of the Template Conditions


The conditions within a row of the Template Conditions table must all be true for 
the condition to be met. For example, if you have a row with a Priority of greater 
than 220 and an Effect Value of Disturbance, both of these must be met for the 
condition to be true. If you have multiple rows in the table, the condition is met if 
any of the rows are true. For example if you have a row with Priority greater than 
220 and a row with an Effect Value of Disturbance, the condition is met if either of 
these are true.

Deleting and Reverting


To delete a template condition, select the condition from the Template Condition 
table and click the Delete button in the Edit <Template> section. To delete a 
template, select the template from the main table and click the Delete button in the 
top right corner of the tab.

To undo changes, click Revert.

Adding an Event Watcher


To add an event watcher, you need a template. You can use one of the default 
templates or define your own (see “Creating a Template” on page 63).

Page 64 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Adding an Event Watcher

List of Event
Watchers

Event Watcher
Editing Area

List of devices in the system

1. Click New to add a new event watcher. A new row appears in the main table 
for the new event. Use the Event Watcher Editing Area to define the event 
watcher.
2. Type a name for the event watcher.
3. Select the template you want to use from the Template dropdown list.
4. Type a description of the event watcher if desired. 
5. From the Devices table, select the devices you want to include in the event 
watcher. Click the check boxes to the left side of the devices to select or clear a 
device.

NOTE
Checking Select All will include any Query Server, Log Inserter or Virtual Processor instances in the system.
It also includes any devices or software nodes added in the future.

6. Click Apply to save your changes, click OK to save your changes and exit Event 
Watcher Manager, or click the Templates tab to edit the templates.

Deleting and Reverting


To delete an event watcher, select the event watcher from the table and click 
Delete.

To undo changes, click Revert.

© 2009 Schneider Electric. All rights reserved. Page 65


Diagnostics Viewer PowerLogic ION Enterprise User Guide

Diagnostics Viewer
Diagnostics Viewer is the ION Enterprise tool for troubleshooting network 
communications problems and related network errors.

Starting Diagnostics Viewer


1. Start Management Console and log in.
2. Click Tools > System > Diagnostics Viewer.

TIP
For instructions on using filtering, sorting, column selection and pin/unpin to customize the Diagnostics
Viewer display, see “Customizing and Navigating Interface Displays” on page 22.

Pin/Unpin button Diagnostics tabs

Dynamic Filter field

Expand/collapse tree

Navigation pane Diagnostics information pane

Refresh Tree View


If you add a new device in Management Console while Diagnostics Viewer is 
open, you can refresh the tree view (to display the new device) by collapsing then 
expanding the root node of the tree (i.e., “ION Enterprise Diagnostics”).

Navigation Pane
Diagnostics information is grouped as follows:
Service Diagnostics: Contains diagnostics information for certain ION 
Enterprise services (ION Network Router Service, ION Site Service and ION Log 
Inserter Service).
Communication Diagnostics: Contains diagnostics information for the ION 
Enterprise sites, hardware devices and software nodes.

Select an item in the navigation pane to display its diagnostics information.

Page 66 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Service Diagnostics

Diagnostics Information Pane


The diagnostics information pane displays detailed data about the state of your 
power monitoring system and devices.

Service Diagnostics
Service Diagnostics records communication problems and similar events 
occurring with ION Enterprise software components.

Communication Server Diagnostics


Information about the communications server is arranged in these tabs:
Console Messages lists all ION Network Router Service and ION Site Service 
console messages for the current session.

TIP
The blank area below the Description column header is a dynamic filter field. Type the wildcard character
(*) in front of the text you want to search (for example, *warning). The diagnostics information pane
automatically displays only those records that match the text you typed in the box.

Connection Status displays the current status of ION Enterprise software 
components connected to Network Router.
Tree States displays the ION tree status of all nodes (hardware devices and 
software nodes).

Log Inserter Diagnostics


The Log Inserter diagnostics information pane is split into two sections. The top 
section (Select Nodes pane) contains the available nodes, while the bottom section 
contains the node details.

Select Nodes to Display


In the Select Nodes pane, select the check box beside a node to display its 
diagnostics information. Clear the check box to hide that node’s diagnostics 
information.

TIP
If there are many nodes and you want to display only a few of them, right-click the Select Nodes area
then select Clear All. Select only the nodes you want to display. To display all the nodes again, right-click
the Select Nodes area and select Select All.

© 2009 Schneider Electric. All rights reserved. Page 67


Communications Diagnostics PowerLogic ION Enterprise User Guide

Node Details
The node details are organized in these tabs:
Node Information displays Log Inserter statistics for the selected node(s).
Node Performance displays aggregate log performance statistics for the selected 
node(s).
Log Performance displays log performance statistics for each log in the selected 
node(s).

Communications Diagnostics
Communications Diagnostics provides diagnostics information for sites and 
devices connected to the workstation. 

Site Overview
Diagnostics information for the sites are contained in these tabs:
Site Summary displays communications statistics for each site.
NetUser Status displays the number of ION programs currently in the ION 
Network Router Service queue (awaiting processing) and the total number of 
ION programs already processed.

NOTE
Requests and responses transmitted between the ION Enterprise components are referred to as “ION
programs”.

Site/Device Diagnostics
Diagnostics information for sites and devices are summarized in these tabs:
Communication Status displays error rates and connection statistics for the 
selected site or device. The following information is available from the 
Communications Status tab:

Column Description

Node The device (or software node) name.

Requests The number of communications requests transmitted to the meter.

Responses The number of successful responses received.

Total Errors The total number of errors.

Total Error Rate The ratio of Total Errors to Requests.

The error rate in the last 64 requests. This can indicate a trend in
Sliding Error Rate
communications performance.

Average Response Time Average time in seconds for the meter to respond.

Last Response Time The last response time, in seconds.

Page 68 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Communications Diagnostics

Column Description

The number of timeout errors. A timeout occurs when no data is


Timeouts
received in response to a request.

The number of bad packets received, i.e., those that failed the error-
Bad Checksums
detection checksum.

Broken Connection Errors Number of times the connection was lost to the meters on a site.

The number of incomplete packets received, i.e., those that did not have
Incomplete Frames
all the expected bytes.

Bad Frames The number of received packets that had an internal error.

Hardware Errors Number of errors reported by the computer’s communication hardware.

Misc Errors Number of other errors that do not fit any of the above descriptions.

Site Status displays site statistics such as connection status and totals.
Polling Status displays the number of programs currently in the ION Site 
Service queue (awaiting processing) and the total number of programs already 
processed.

Communication Status vs. Site Status


This section explains the difference between the statistics provided on the 
Communication Status tab and those on the Site Status tab.

“Total Errors” in the Communication Status tab is an ION Site Service derived 
statistic, while “Bad Responses” in the Site Status tab is a client derived statistic.

To explain this difference, consider a situation where a direct site is experiencing 
timeouts. Communications with the device is attempted according to two 
parameters: Connect Attempts (an advanced site property in the Management 
Console) and Maximum Attempts Multiple (an advanced device property in the 
Management Console). Multiplying the values of these two properties determines 
the number of attempts made to re‐establish communications with the device.

For instance, if Connect Attempts is set to “1” and Maximum Attempts Multiple 
is set to 3, the device will go offline after 3 attempts (i.e., 1 x 3). 

The “Total Errors” statistic increases by one every time ION Site Service detects a 
timeout. However, the “Bad Responses” statistic only reports a problem if the 
device goes offline (i.e., when Connect Attempts and Maximum Attempts 
Multiple are exceeded). 

Using the previous example, consider the case where four timeouts occurred and 
the device went offline. In this case, “Total Errors” increases by four, while “Bad 
Responses” only increases by one. If only two timeouts occurred, “Total Errors” 
would increase by two, while “Bad Responses” would not change.

© 2009 Schneider Electric. All rights reserved. Page 69


Additional Commands PowerLogic ION Enterprise User Guide

Additional Commands
The following sections describe additional display options and shortcut menus 
available in Diagnostics Viewer.

Diagnostic Details
In the tabs on the diagnostics information pane, double‐click a row to display its 
Diagnostic Details screen. This displays the diagnostic information for the 
selected item only. 

Use the Previous and Next buttons to view the details of other rows in that tab of 
the diagnostics information pane.

To copy information to the clipboard, select the rows you want to copy, then press 
CTRL+C.

Diagnostics Information Pane Shortcut Menu Options


Right‐click in the diagnostics information pane to display a shortcut menu. The 
following table lists all the commands available (though not all displays provide 
all the commands listed):

Right-click Option Description

Update Refreshes the information in the diagnostic table.


Resets the information in the diagnostic table (not available in the
Reset
Communications Server Diagnostics display).
Copy All Copies all selected information to the clipboard.

Enabled by default, this option is only available in the Console Messages tab
of the Communications Server Diagnostics display. This option automatically
Auto Scroll scrolls and selects the latest console message. Clear this option to disable
scrolling (i.e., select and view an older console message without jumping to
the latest one when Diagnostics Viewer refreshes).

Displays the Options dialog box where you can change the diagnostics refresh
Options
rate. Note that changing this value can affect ION Enterprise performance.

Page 70 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Device Upgrader

Device Upgrader
Use Device Upgrader to upgrade the firmware on one or more ION meters of the 
same type in a single session. Supervisor level access is required to upgrade 
devices.

To reduce the risk of upgrade errors, make sure the computer power option is set 
to always stay on and screensavers are disabled. If you are using a laptop, plug it 
into a wall outlet and set the power option to “do nothing” if the lid is closed.

CAUTION
If you have data in the meter you want to keep, make sure you upload and/or save it before upgrading.
Stored data in the meter’s memory is completely erased during a firmware upgrade. This data includes
waveforms, data recorders, min and max values, and integrator values (e.g., kWh).

Using Device Upgrader


1. Obtain the applicable upgrade (.upg) files for your device from the website or 
from Technical Support. 
2. Save the files in a folder accessible on the computer.
3. Stop the ION Log Inserter Service and ION Virtual Processor Service.
4. Start Management Console.
5. Click Tools > System > Device Upgrader. Type your username and password in 
the log in prompt. A dialog box displays with recommendations and warnings 
regarding the upgrade operation. After reading the recommendations and 
warnings, click OK.
If you need to implement any changes because of the recommendations and 
warning, close Device Upgrader, make the changes then re‐open Device 
Upgrader and continue.
The Device Upgrader window appears.

© 2009 Schneider Electric. All rights reserved. Page 71


Using Device Upgrader PowerLogic ION Enterprise User Guide

6. Select the device type of the device(s) you want to upgrade from the List 
Devices of Type box.
7. Select the name(s) of the device(s) you want to upgrade in the Select Devices to 
Upgrade box. 
8. In the Select Revision section, click Select File. Locate and select the upgrade 
(.upg) file that you saved in step 2, then click Open.
9. Select or clear the Save/Restore framework check box (selected by default). If 
selected, this keeps a copy of your current framework template during the 
upgrade. After the firmware upgrade is complete, Device Upgrader restores 
your framework template.

NOTE
The Device Upgrader loads new meter firmware that does not contain any framework templates. If you
want to preserve customizations you have made to your device framework, make sure “Save/Restore
framework” is selected. However, if you intend to replace the existing meter framework with a new one
(e.g., a new default meter template that you have downloaded), clear “Save/Restore framework”.

10. If you are upgrading multiple devices, specify in the Failure Handling area how 
the Device Upgrader responds to an unsuccessful upgrade:
Select Halt After, then enter a number in the box to specify how many 
attempts Device Upgrader should make before stopping during a failed 
upgrade. By default, the utility is set to stop after the first failed upgrade.
Select Ignore All to attempt to upgrade all of the selected devices regardless 
of the number of devices that fail to upgrade.
11. Click Upgrade to upgrade the selected devices.
The Upgrade Status box shows the stages of the upgrade process. The 
completed progress bar indicates what percentage of the upgrade is complete. 
Each completed upgrade is listed in the Upgrade Status box.
12. Restart the ION Log Inserter Service and ION Virtual Processor Service.

Page 72 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Firmware Upgrade Error Codes

Firmware Upgrade Error Codes


The following table describes the various error codes that may occur when you 
upgrade your deviceʹs firmware.

Error Code Description

0, 1, 2, 3, 4, 5, 6, 7, 8, or 9 Indicates a negative acknowledgment to a request. Contact Technical Support for assistance.

Device timed out while downloading firmware. Probable causes: a) poor communication or b) the device
100
stopped functioning.

101, 102, 103, 104, 105 Indicates a bad response to a request. Contact Technical Support for assistance.

Device Upgrader was unable to prepare the device to accept new firmware. Try to upgrade the device again.
106
Contact Technical Support for assistance if the problem persists.

Device Upgrader was unable to verify the device's new firmware. Try to upgrade the device again. Contact
107
Technical Support for assistance if the error persists.

Device Upgrader was unable to download a firmware packet. Try to upgrade the device again. Contact
108
Technical Support for assistance if the error persists.

Device Upgrader was unable to retrieve the device framework. Probable causes: a) time out or b) device not
109
functioning.

Device Upgrader was unable to retrieve the device's firmware revision. Probable causes: a) time out, b) device
110
not functioning, or c) cannot access the device's firmware revision register.
Device Upgrader cannot save the device framework to the file <device_name>.conf. Make sure the ION
150
Enterprise\config\upgrade directory exists and that you have write permissions.
The Device Upgrader failed to successfully upgrade a device and left a <device_name>.conf file. Probable
151, 155 cause: you are attempting to upgrade a different device than the one that the Device Upgrader previously
failed.

The information in the file <device_name>.conf is corrupted or unrecognizable by the Device Upgrader.
152
Contact Technical Support for assistance.

Device Upgrader was unable to restore the device setup. Probable causes: a) time out or b) device not
154
functioning.

Device Upgrader was unable to restore the device framework completely to the file <device_name>.conf. This
156
error is most likely caused by a full hard drive.

© 2009 Schneider Electric. All rights reserved. Page 73


Remote Modem Setup PowerLogic ION Enterprise User Guide

Remote Modem Setup


Use Remote Modem Setup to preconfigure dialup modems that will be connected 
to meters at remote locations. Hardware‐based and software‐based (WinModems) 
modems are supported.

Remote Modem Setup provides access to a database that contains configuration 
data for a variety of modems you can pick from. Remote Modem Setup also 
provides direct access to your modem so you can customize settings and 
troubleshoot its operation.

Preliminary Setup
Follow the instructions in your modem’s documentation to set up and connect the 
modem to one of your computer’s serial ports. Select a port that the ION Enterprise 
Communications Server is not using.

Using Remote Modem Setup


1. Start Management Console.
2. Click Tools > System > Remote Modem Setup. The Remote Modem Setup 
dialog box appears.
3. Set the Port to the serial communications port that the computer uses to 
communicate with (and set up) the modem. Set the Baud Rate to match the 
modem’s baud rate. 

NOTE
To reduce possible communication issues, set the computer, modems and meters to the same baud rate.

4. Set the following properties for the remote modem:
Select the type of modem from the Type box. 
Set the Site Baud Rate.
To set the modem to answer after a specified number of rings, select Auto 
Answer, then type the appropriate number in the Number of Rings box.
To save the modem configuration data in the modem’s onboard memory, 
select Store Profile. This feature allows the modem to revert to the saved 
settings after a power failure. Clear Store Profile to disable this feature.
To turn on the modem’s internal speaker, select Speaker On, then select a 
setting from the Volume list. Clear Speaker On to disable this feature.
5. Click Send to save the settings to the modem.
If there are DIP switch settings required for the modem that is being configured, 
a message displays with instructions on which switches to turn on or off. Set the 
DIP switches on the modem as instructed.

The modem is now ready to be used at the remote power monitoring site.

Page 74 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Virtual Processor Setup

Virtual Processor Setup


The Virtual Processor (VIP) is the ION Enterprise service (“ION Virtual Processor 
Service“) that provides coordinated data collection and aggregation, control, and 
mathematical analysis of power monitoring system data from groups of metering 
or similar intelligent devices. Use Virtual Processor Setup to configure a Virtual 
Processor Modbus Service for defining sites and devices in a Modbus network, and 
to set up the communications port for it. Virtual Processor Setup can also be used 
to improve the performance of the ION Virtual Processor Service by modifying its 
global operating parameters.

See “Virtual Processor Service” on page 244 for application examples using the 
Virtual Processor.

Configuring the Virtual Processor's Modbus Service


NOTE
This information is provided for the benefit of customers who have legacy implementations of Modbus
communications using the Virtual Processor. Users that are setting up new Modbus communications
should refer to “Modbus Device Importer” on page 277. Modbus support in the Virtual Processor will be
removed in a future version of ION Enterprise.

When setting up your Modbus network, make sure that your Modbus port is 
different from the port that connects to your ION devices. The Virtual Processor 
requires a communications port for Modbus separate from any communications 
port defined as a site in the Management Console.

Setting up a Virtual Processor’s Modbus Network


1. Start Management Console.
2. Click Tools > System > ION Virtual Processor Setup. The Virtual Processor 
Setup utility (“VIP.ComputerName” where ComputerName is the name of the 
workstation) is displayed as an item in the tree view. 

Double‐click an item to expand or collapse it.
The buttons available vary depending on the item selected in the tree.
3. Expand Modbus Network to show “Master Sites” and “Slave Ports”.

© 2009 Schneider Electric. All rights reserved. Page 75


Configuring the Virtual Processor's Modbus Service PowerLogic ION Enterprise User Guide

Adding a Modbus Master Ethernet Site


1. Select Master Sites then click Add Site.
2. Select Ethernet (RTU) then type the following in the appropriate fields:
TCP/IP Address: the TCP/IP address of the Master site or gateway
TCP/IP Port: the TCP/IP port number used to connect to the COM port used 
by the Modbus network (for example, TCP/IP port 7802 connects to an 
EtherGate device’s COM2 port).
3. Click OK.

NOTE
Do not use 502 for the TCP/IP port. Modbus/TCP packets use the TCP/IP protocol and are sent to this
registered port number. At this time, the Virtual Processor does not support Modbus/TCP (MBAP).

Adding a Modbus Master Serial Site


1. Select Master Sites then click Add Site.
2. Select Serial Site, then set COM Port to the serial port of your computer that you 
want to assign as your Modbus Master. The Virtual Processorʹs Modbus Import 
and Modbus Export modules then use this COM port to communicate to the 
Modbus slave devices.
3. Click OK.

NOTE
The COM port used to define a Master Site must be different from the COM port used for connecting to
ION devices.

Configuring the Modbus Master Site Parameters


Select the site and expand the tree until the parameters under Settings are 
displayed. Select the parameter you want to change, and then click Modify 
<setting> (where <setting> is the setting selected).
Transmit Delay: The amount of time the Virtual Processor waits between 
sending out requests. The supported range is from 10 to 60000 milliseconds. 

NOTE
For Ethernet sites, specifying too small a value for Transmit Delay may overload the network.

Receive Timeout: The time period the Virtual Processor allows for establishing 
communications. The supported range is from 100 to 60000 milliseconds. 

NOTE
For Ethernet sites, the protocol used is Modbus RTU which does not identify packets. Therefore, specifying
too small a value for Receive Timeout may cause timeout errors, which could result in packet mix-up.
Specify a value that avoids timeouts.

Page 76 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Configuring the Virtual Processor's Modbus Service

Baud Rate (serial sites only): The Baud rate used for Modbus communications 
to serial sites. Supported values are 300, 1200, 2400, 4800, 9600, 19200, 38400, 
57600, 115200.
Parity (serial sites only): This setting specifies whether or not parity is active 
(and if it is active, the type of parity; i.e., Odd, Even, Mark, or Space). Parity 
refers to a technique of checking whether data has been lost or overwritten 
when it is moved from one place in storage to another, or when transmitted 
between devices and/or computers.
Stop Bits (serial sites only): The number of stop bits supported by the site. 
Supported values are a minimum of 1, 1.5 and 2. Stop bits signal the end of a 
unit of transmission on a serial line.
Data Bits (serial sites only): The number of data bits (i.e., bits that contain 
information or data) supported by the site. Supported values range from a 
minimum of 4 and a maximum of 8.

Adding Modbus Devices


1. Select the Modbus Master site to which you want to add a Modbus device. 
Expand the tree to display Settings and Devices. Select Devices, then click Add 
Device. The Add Modbus Device(s) dialog box appears.
2. Enter the Name and Unit ID of the Modbus device in the appropriate fields. For 
Ethernet devices, set Unit ID to 100. The Name must be unique among all the 
sites serviced by the Virtual Processor. The Unit ID must be unique inside a 
given site. Click Add.
3. Repeat the previous step to add more Modbus devices to the same site. When 
you have finished connecting all the Modbus devices to that site, click OK.

NOTE
A Modbus device name must start with a letter, followed by letters, numbers and/or underscores. The
Modbus device name must not contain spaces. The supported range for a Modbus device Unit ID is 1 to
247. Do not use “0” (zero) as it is reserved for broadcast messages.

Renaming a Modbus Device


1. Select the Modbus device you want to rename. Click Rename Device. The 
Modbus Device Name dialog box appears.
2. Type the new name, then click OK.

NOTE
If you rename or delete Modbus devices, all Modbus Export or Modbus Import modules that previously
referred to that renamed or deleted Modbus device are mapped to “not_a_valid_device” when you restart
the Virtual Processor. Designer displays these modules as offline (outlined in red).

Deleting a Modbus Device


1. Select the Modbus device you want to delete.
2. Click Delete Device then click OK to confirm the deletion.

© 2009 Schneider Electric. All rights reserved. Page 77


Configuring the Virtual Processor's Modbus Service PowerLogic ION Enterprise User Guide

Adding a Communications Port for the Modbus Slave


TIP
If you want to use ION data in your Modbus network, you need to convert the data to Modbus. Use
Designer to open the Virtual Processor node and create Modbus Slave modules, then set them up to map
the registers and apply the proper conversion from ION data to Modbus.

1. Expand Modbus Network to display Master Sites and Slave Ports. Select 
Slave Ports, then click Add COM Port. The Modbus Port/Site dialog box 
appears.
2. Set the COM Port to the port you want to use as a Modbus Slave port (this is the 
port that the Modbus Master uses to read Modbus data from the Virtual 
Processorʹs Modbus Slave modules). Click OK.

NOTE
The Modbus Slave port must not be set to the same port as any ION or Modbus Master ports.

3. Expand the COM port you have just added to display Settings.
4. Expand Settings to show the items below it.
5. Select Unit ID then click Modify Unit ID. The Modbus Slave Unit ID dialog 
box appears.
6. Enter the Modbus Slave device unit ID. Click OK.
7. If you want to modify the Baud Rate, select Baud Rate then click Modify Baud 
Rate. Select the new baud rate from the dropdown list, then click OK. 
8. If necessary, configure the Parity, Stop Bits and Data Bits.

Changing Port Assignment for a Modbus Master or Slave


1. Select the port you want to reassign, and then click Rename Port. The Modbus 
Port/Site dialog box appears.
2. From the dropdown list, select the port you want to reassign to the Modbus 
master or slave (see “Adding a Modbus Master Ethernet Site” on page 76 or 
“Adding a Communications Port for the Modbus Slave” on page 78).

Deleting a Modbus Master Site or Slave Port


NOTE
Deleting a Modbus Master Site also deletes all devices connected to it.

1. Click on the site or port you want to delete, and then click Delete Port or 
Delete Site (depending on the item selected).
2. Click OK to confirm the deletion.

Page 78 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Modifying the Global Parameters

Final Steps After Saving and Exiting


When you have finished using Virtual Processor Setup, click Save to save your 
changes, then click Exit to close the window.

In order for the changes to take effect, you must stop then restart the ION Virtual 
Processor Service.

Modifying the Global Parameters


Typically you do not need to change the default Virtual Processor’s Global 
Parameters. However, the settings in the following table can be modified to try to 
optimize system performance. To view and select the settings, expand Global 
Parameters.

Global Parameter Value Range Description Notes

Frequent module updates contribute to the


The interval at which ION modules workstation's processor load. By increasing the
Module Update Period 50 to 1000 ms inside the Virtual Processor are Module Update Period, you reduce the number
updated. of times a module executes in a given time
period.

Increasing the Configuration Saver Period


The interval at which the Virtual
significantly reduces the processor load if you
Configuration Saver Period 10 to 600 seconds Processor writes its configuration data
have a large Virtual Processor configuration
to the workstation's hard disk.
file.

The interval at which the Virtual


You can increase the period for less critical
Processor gets information from other
Client Polling Period 500 to 300000 ms Virtual Processor applications and reduce the
nodes in the network (for example,
period for more critical applications.
another Virtual Processor or a device).

The interval at which the Virtual


Reducing this value increases the rate at which
Processor responds to requests for
Server Polling Period 200 to 1440000 ms these responses are sent; however, this can
information from client nodes such as
also increase network traffic.
Vista or the Log Inserter.

© 2009 Schneider Electric. All rights reserved. Page 79


Time of Use Editor PowerLogic ION Enterprise User Guide

Time of Use Editor


Time of Use (TOU) schedules created with the Time of Use Editor are designed to 
be used with Web Reporter. When you use a TOU schedule in a report, the report 
data is presented according to the information you set up in the schedule. See 
“Energy Cost” on page 176 for information on the Energy Cost Report.

A typical TOU has On Peak, Off Peak and Shoulder periods. Since rate schedules 
vary not only by day and week, but also by season, the TOU schedules can be set 
up to match your precise needs. 

To configure TOU schedules for use with Designer, see “Time of Use (TOU) 
Program Management” on page 241.

Opening the Time of Use Editor


To access the Time of Use Editor, select Tools > System > Time of Use Editor in 
Management Console.

Time of Use Editor Interface


Schedule Name

Schedule Description

Navigation Pane Tab Display Pane

Use the navigation pane to navigate through the schedules, access the right‐click 
menus for schedules and sub‐schedules, and select an item to display associated 
tabs in the tab display pane.

Overview: Creating a TOU Schedule


To create a TOU schedule, you need to:
1. Add a schedule. See “Adding or Editing a Schedule” on page 81.
2. Add a sub‐schedule, if you need more than one sub‐schedule. See “Adding or 
Editing a Sub‐Schedule” on page 82.
3. Add a season, if you need more than one. See “Configuring Seasons” on page 83.

Page 80 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Adding or Editing a Schedule

4. Configure special days (i.e., holidays) to include in your TOU schedule. See 
“Adding Special Days” on page 85.
5. Add day groups, if you need groups other than the default day groups. See 
“Configuring Day Groups” on page 86.
6. Add TOU names, if you need names other than the default names. See “Defining 
TOU Names” on page 87. 
7. Assign TOU periods to TOU names. “Defining TOU Periods” on page 88.

To view a sample schedule, right‐click in the navigation pane and select Import 
Schedule. Select SampleSchedule.tou from the ..\ION Enterprise\system\etc 
folder and click Open. 

Adding or Editing a Schedule


This section describes how to add a blank schedule, and import or copy an existing 
schedule.

Adding a Blank Schedule


1. Select File > New Schedule. The Add a Schedule dialog box appears.
2. Type a name and description for the schedule. Click the arrow beside the 
effective date to bring up a calendar where you can select the effective date of the 
schedule. 
3. Click OK. That schedule name appears in the list in the navigation pane.

Copying an Existing Schedule


1. In the navigation pane, right‐click the schedule that you want to copy. 
2. Select Save as New Schedule. The Save as New Schedule dialog box appears.
3. Enter a name and description for the new schedule. 
4. Click OK. The new schedule appears in the navigation pane with the attributes 
of the copied schedule.

Importing a Schedule
1. Place the schedule that you want to import into a folder that can be accessed 
from the computer.
2. In the navigation pane, right‐click an empty area of the navigation pane then 
select Import Schedule. The Open dialog box appears.
3. Navigate to the folder where you placed the schedule. Select the schedule and 
click Open. 
The schedule is imported with the extension “_imported”. For example, a 
schedule named “ScheduleA” becomes “ScheduleA_imported”.

© 2009 Schneider Electric. All rights reserved. Page 81


Adding or Editing a Sub-Schedule PowerLogic ION Enterprise User Guide

Exporting a Schedule
To export a schedule to use in another TOU installation:
1. Right‐click on the schedule you want to export in the navigation pane. Click 
Export. The Save As dialog box appears.
2. Select the folder where you want to save the schedule.
3. Enter a schedule name in the File name box.
4. Click Save. 
The schedule is saved with the extension “.tou”. For example, “ScheduleB” 
becomes “ScheduleB.tou”.

Editing an Existing Schedule


To edit a schedule name or description:
1. From the navigation pane, right‐click a schedule name then click Edit 
Schedule. The Edit a Schedule dialog box appears.
2. Change the schedule name or description.
To change the effective date, you must make the change to the sub‐schedule(s). 
See “Editing a Sub‐Schedule Effective Date” on page 83.
3. Click OK. 

Deleting a Schedule
To delete a schedule, right‐click the schedule name in the navigation pane then 
select Delete Schedule. This deletes the entire schedule, including any sub‐
schedules. 

Adding or Editing a Sub-Schedule


When you add the basic schedule, it contains one sub‐schedule, with the effective 
date (start date) you entered for the schedule. To add additional sub‐schedules 
with alternate effective dates, follow the instructions in the following sections.

Expand a schedule to display its sub‐schedule(s). Sub‐schedules are listed in order 
of their effective dates.

TIP
If you want to have more than one sub-schedule with the same seasons, day groups, TOU periods, etc.,
configure the first sub-schedule then right-click on it and select Save as New SubSchedule.

Page 82 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Configuring Seasons

Adding a Blank Sub-Schedule


1. Right‐click the schedule name and select New SubSchedule. The New 
SubSchedule dialog box appears.
2. Click the arrow beside the effective date to bring up a calendar where you can 
choose an effective date for the new sub‐schedule.
3. Click OK.
The sub‐schedule displays in the navigation pane. Continue configuring the 
sub‐schedule by adding seasons and day groups.

To add a new sub‐schedule that has the same settings as an existing sub‐schedule, 
see “Copying an Existing Sub‐Schedule”, below. 

Copying an Existing Sub-Schedule


1. Right‐click the sub‐schedule that you want to copy and select Save as New 
SubSchedule. The New SubSchedule dialog box appears.
2. Click the arrow beside the effective date to bring up a calendar where you can 
choose an effective date for the new sub‐schedule.
3. Click OK. The new sub‐schedule displays in the navigation pane with the same 
attributes (other than effective date) of the sub‐schedule you copied.

Editing a Sub-Schedule Effective Date


1. Right‐click the sub‐schedule for which you want to change the effective date, 
then select Edit Effective Date. The Edit SubSchedule Effective Date dialog 
box appears.
2. Click the arrow beside the effective date to bring up a calendar where you can 
choose an effective date for the new sub‐schedule.
3. Click OK.

Deleting a Sub-Schedule
To delete a sub‐schedule, right‐click the sub‐schedule name in the navigation pane 
and select Delete. This also deletes all seasons in that sub‐schedule (and any day 
groups, special days, etc., that they contain).

Configuring Seasons
Use seasons to create timeframes for presenting data in reports. A newly created 
schedule has a single season, called All Year. Expand a sub‐schedule to view its 
seasons.

If you only need one season (All Year), you can skip the steps below and go to 
configuring special days. 

© 2009 Schneider Electric. All rights reserved. Page 83


Configuring Seasons PowerLogic ION Enterprise User Guide

Configuring Seasons
Use the Define a Season tab to set up or edit the time spans for each season.

NOTE
A date can only belong to one season; you cannot overlap dates in one season with dates in another.

1. From the navigation pane, select the sub‐schedule to which the season 
belongs.
2. In the tab display pane, select the Define a Season tab. 
After you add a sub‐schedule, the tab displays only one season (All Year) that 
covers the entire year. The season is listed at the top of the tab, and the calendar 
that shows the days and months that belong to that season is full. To make room 
to add other seasons, you must edit the All Year season.
3. Select All Year from the Define a Season tab and click Edit. The Edit a Season 
dialog box appears.
4. In the Season Name field, type the name of one of the seasons you want to define 
(for example, Summer). 
5. Set the Start Date and End Date for the season. You can specify fixed start and 
end dates (i.e., 12/31) or relative start and end dates (i.e., the last Saturday of 
October). 
Fixed Date: Click on the month or day portion of the date then either type the 
new date or use the up and down arrows beside the date to edit it.
Relative Date: Select the day and month from the dropdown lists. 
For the end date, select the Time of Day the season ends (Start of Day or End of 
Day). If you select Start of Day, the season ends at 12:00:00 AM on the selected 
day; if you select End of Day, the season ends at 12:00:00 AM on the next day so 
there are no gaps in the schedule.

NOTE
If you use relative dates, you can configure a schedule that may become invalid in future years. Be careful
when you configure the schedule that there will be no missing or overlapping days in the schedule in
future years. For example, rather than scheduling one season to end on the 1st Sunday in June and the
next to start on the 1st Monday in June, it is better to schedule the first season to end at Start of Day on
the 1st Sunday in June and the next season to start on the 1st Sunday in June.

6. If this is a split season (where there is a gap between two parts of the season), 
select the Split Season check box and add a second sets of dates. For example, 
winter is typically a split season because it occurs in the first and last months of 
the year.
7. Click OK. 
The calendar on the Define a Season tab now shows one season with the rest of 
the year unassigned.
8. Click Add to create additional seasons. Repeat steps 4 to 6 to name the season 
and define the start and end dates.

Page 84 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Adding Special Days

NOTE
Do not leave any dates unassigned: unassigned dates are not calculated in the reports.

Editing a Season
1. On the Define a Season tab, select the season you want to edit then click Edit. 
The Edit a Season dialog box appears. 
2. Make the changes you require then click OK. 

Deleting a Season
To delete a season, select the season in the Define a Season tab then click Delete. 
This also deletes the day groups and TOU periods configured for that season.

Adding Special Days


After you define a sub‐schedule, you need to set up holidays and other special 
days. You can define holidays that occur on the same date every year or at some 
other regular interval (such as the third Thursday in November). You can also 
define special days, such as inventory days, that might occur regularly and require 
special treatment in reports.

Use the Define Special Days tab to set up holidays and other special days.
1. In the navigation pane, select the sub‐schedule for which you want to define 
special days. 
2. In the tab display pane, select the Define Special Days tab.
3. Click Add. The Add a Special Day dialog box appears.
4. Type a name for the special day in the Name field. 
5. Select the frequency of the day:
One time only: Enter the date for a single day that does not repeat in future 
years; for example, a special day for your organization that does not repeat 
every year.
Repeat yearly: Enter the date; for example, a holiday that occurs on the 
same date every year.
Repeat on: Complete the fields in the Repeat On section to define how the 
day repeats and in which months it occurs. Select whether is occurs on a 
particular date of the selected month(s) (Day) or a relative day (i.e., Last 
Saturday) in the selected month(s).
6. Repeat steps 3 to 5 to add additional special days.
7. Click OK to save your changes and return to the Define Special Days tab.
See “Configuring Day Groups” on page 86 for instructions on how to apply special 
days to a sub‐schedule.

© 2009 Schneider Electric. All rights reserved. Page 85


Configuring Day Groups PowerLogic ION Enterprise User Guide

Deleting a Special Day


To delete a special day, select the special day in the Define a Special Day tab then 
click Delete.

Configuring Day Groups


Day groups define how days of the week are divided into groups. 
Day groups can include:
days of the week
special days, such as holidays or other specially designated days (such as 
inventory days)

Default settings are weekdays (Monday to Friday) and weekends (Saturday and 
Sunday) but you can add additional groups. There can be a maximum of 47 day 
groups in any season.

Make sure that all days have been accounted for since unaccounted time is not 
included in any reports.

Adding a Day Group


Before you add a day group, make sure that you have defined seasons and special 
days for the sub‐schedule.
1. In the navigation pane, select the season for which you want to define day 
groups. The Define DayGroups tab appears in the tab display pane.
2. Click Add. The Add a DayGroup dialog box appears.
If the Add button is unavailable, there are no free days to add to a day group. A 
day can only belong to one day group. To add another day group, you must first 
remove days from an existing day group.
3. Type a name for the day group.
4. Select one of the following options:
Day of week: Select the check box(es) for the day(s) you want to include. A 
day can belong to only one day group; if a day is unavailable, it already 
belongs to an existing group. If all days are unavailable, you can only 
include special days in this group unless you remove days from another day 
group. 
Special Day(s) Only: Select the special day in the Include Special Days list 
then click to select or clear the day. Days with a check mark beside them are 
included in the day group. You can only include a special day in one day 
group. 
5. Click OK. The name is added to the day group list.

Page 86 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Configuring TOU Names and TOU Periods

Editing a Day Group


1. On the Define DayGroups tab, select the day group you want to change, then 
click Edit. The Edit a Day Group dialog box appears.
2. Make the changes you require then click OK.

Deleting a Day Group


To delete a day group, select the day group in the Define DayGroups tab then 
click Delete. When you delete a day group, you also delete the TOU periods 
configured for that day group. If you add a day group again, you will need to 
reconfigure the TOU periods.

Configuring TOU Names and TOU Periods


When you run reports, the reports calculate and display data according to the 
information you enter in the Define TOU Periods and Define TOU Names tabs.

NOTE
You need to define TOU names and periods for each schedule that you create. Be sure to apply a TOU
name to every square on the calendar. Unaccounted time causes your reports to display inaccurate
information.

Defining TOU Names


A TOU name is a designation that is used to differentiate billing rates. Three TOU 
Names are already defined: On Peak, Off Peak and Partial Peak. You can edit or 
delete these names, or add new names.

Defining TOU Names


1. In the navigation pane, select the day group for which you want to define TOU 
names then select the Define TOU Names tab. 
2. Click Add. The Add a TOU Name dialog box appears.
3. Type the TOU name you want to add then click OK. The TOU name is added to 
the list of TOU names.

Editing an Existing TOU Name


1. Select the TOU Name in the list on the Define TOU Names tab and click Edit. 
The Edit a TOU Name dialog box appears. 
2. Type the new name in the TOU name field. 
3. Click OK. 

Deleting a TOU Name


Select the TOU name in the list on the Define TOU Names tab and click Delete.

© 2009 Schneider Electric. All rights reserved. Page 87


Configuring TOU Names and TOU Periods PowerLogic ION Enterprise User Guide

NOTE
If you delete a TOU name, the TOU periods assigned to the name are replaced with “Unaccounted”.
Deleting a TOU name in a particular schedule affects all sub-schedules in that schedule.

Defining TOU Periods


A TOU period is the time span within the 24‐hour period to which you apply a 
TOU name (such as 8:00 a.m. to 5:00 p.m. for On Peak). You must have TOU names 
defined before you can associate TOU periods with those names. 

Two TOU names are already defined: On Peak and Off Peak. You can edit or delete 
these names, or add new names.

Adding TOU Periods


Select a day groups to set up the TOU time periods (on‐peak, off‐peak, etc.) for that 
group.
1. In the navigation pane, select the day group for which you want to define a 
TOU period then select the Define TOU Periods tab. 
2. Click Add. The Add a Time Period dialog box appears.
3. In the Start Time field, type the time that the period begins, or select the hours 
and minutes and use the up and down arrows to set the start time.
4. In the Stop Time field, type the time that the period begins, or select the hours 
and minutes and use the up and down arrows to set the stop time.
5. From the Time of Use Name dropdown list, select the TOU name to associate 
with the time period. 
6. Click OK.

To add a split time period (i.e., a time period that spans from 19:00 to 6:00), you 
must add two separate time periods and associate them with the same time of use 
name.

If you want to expand a time period into time that already belongs to another 
period, you must first edit the other time period to clear the time.

Continue adding time periods until the 24 hour period is filled. Unaccounted time 
blocks cause your reports to display inaccurate information.

Editing TOU Periods


1. Highlight the period you want to edit and click Edit. The Edit a Time Period 
dialog box appears.
2. Make the required changes then click OK.

Deleting TOU Periods


To delete a period, highlight the period and click Delete.

Page 88 © 2009 Schneider Electric. All rights reserved.


4 Vista
Vista is the ION Enterprise component that displays and controls your power 
monitoring/management system.

For information on starting and logging on to Vista or ending your Vista session, 
see “Getting Started” on page 19.

In This Section

“The Vista Interface” on page 90
“Vista User Diagrams” on page 93
“Monitoring Your System in Vista” on page 96
“Viewing Real‐Time Data” on page 98
“Viewing Logged Data” on page 100
“Adding a Global Event Log Viewer” on page 104
“Acknowledging Alarms” on page 105
“Controlling System Functions” on page 107
“Plotting Logged Data” on page 108
“The Log View Plotter Interface” on page 109
“Customizing the Log View Plotter Display” on page 121
“Overlaying Curves in the Log View Plotter” on page 125
“Creating and Customizing a User Diagram” on page 127
“Adding a Diagram Object to a User Diagram” on page 128
“Customizing a Diagram Object” on page 133
“Linking a Diagram Object to a Data Source” on page 146
“Querying the Database” on page 148
“Customizing a Diagram Window” on page 155

© 2009 Schneider Electric. All rights reserved. Page 89


The Vista Interface PowerLogic ION Enterprise User Guide

The Vista Interface


The Vista interface consists of a main screen with a title bar, a menu bar, a toolbar, 
a workspace, a status bar and (in Edit mode) a toolbox.

For information on opening or generating a Vista, see “Generating, Opening and 
Closing a User Diagram” on page 94.

The Vista interface with a user diagram showing realtime values

Menu Bar Toolbar

Click a tab to Click to return to


display its data the Network
Diagram view

Workspace

Status Bar

Click this grouping object


to open another window
containing more data Receive/Transmit
Toolbox Status Indicators

Toolbar
The toolbar offers quick access to the commands that are used most frequently. 
Each command on the toolbar is also available from the menus.

Page 90 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide The Vista Interface

Restore to Up One
Open Zoom 100% Cut Paste Level

Save Fit to Plot Copy Layout Help


Window Selected
Data

Zoom
Select View > Zoom In or click the Zoom button to change the mouse pointer to a 
crosshair. Use this pointer to drag an outline around the area you want to enlarge.

Restore to 100%
Select View > Restore to 100% or click the Restore to 100% button to return to the 
normal view.

Fit to Window
Select View > Fit to Window or click the Fit to Window button to force the user 
diagram to fit in the current window.

Up One Level
Select File > Up One Level or click the Up One Level button to return to the 
previously displayed window. Note that this also closes the current window. If 
you want to be prompted when you reach the top level of a diagram, make sure 
Options > Browse closes active window is selected.

Workspace
The main area in the center of the Vista screen is the workspace. The workspace is 
used to display information such as user diagrams and data and event viewers.

Status Bar
The status bar displays:
the status line, which describes any active processes and provides a brief 
description of the currently selected command or toolbar button.
the current time on the workstation.
a progress indicator bar.
two communication status lights.

Toolbox
In Edit mode, the toolbox also appears on the screen. You can add objects to the 
user diagram using the toolbox. See “Creating and Customizing a User Diagram” 
on page 127 for more information on the toolbox and Edit mode.

© 2009 Schneider Electric. All rights reserved. Page 91


The Vista Interface PowerLogic ION Enterprise User Guide

Other Display Features


Vista offers several display features to assist you when viewing a user diagram. 
Some of these are accessible through the toolbar and menu options (see “Toolbar” 
on page 90). Those only accessible through menu options are: 

Browse Closes Active Window


Select Options > Browse closes active window to have each window that you 
open replace the previous one. This option is selected by default. Without this 
option selected, any previously opened windows remain open.

Arrange All
Select Window > Arrange All to tile all open windows in the workspace.

Display Mode and Edit Mode


There are two display modes in Vista, which affect how you navigate a user 
diagram. Whether or not the toolbox is shown indicates the mode you are in: if the 
toolbox is open, you are in edit mode; if it is closed, you are in display mode.
Display mode allows you to monitor your system, view system data, and 
control some aspects of your system. In Display mode, single‐click objects to 
view the information they contain or perform their associated action. 
Edit mode allows you to configure the appearance and function of user 
diagrams and diagram objects. In Edit mode, double‐click objects to view the 
information they contain or perform their associated action. Right‐click on 
objects to view configuration options. See “Creating and Customizing a User 
Diagram” on page 127 and “Customizing a Diagram Object” on page 133 for 
more information. 

When instructed to click a diagram object, either single‐click or double‐click, 
depending on the mode you are in. 

Page 92 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Vista User Diagrams

Vista User Diagrams


This section explains how to use Vista user diagrams to view real‐time and logged 
data from your power‐monitoring system. The information that you obtain from 
your ION Enterprise network is represented graphically in a user diagram.

What is a User Diagram?


A user diagram is a configurable display that consists of two main elements:
Diagram objects are configurable graphic icons that display your system 
information. Each diagram object displays a single piece of information from 
somewhere in your power monitoring network. In some cases, diagram objects 
are stored within grouping windows.
Grouping object: In some cases, a user diagram stores related information 
within a grouping object. Click on a grouping object to open a grouping window 
and display its contents.

NOTE
To configure a grouping object to open a grouping window, see “Specifying Action for Numeric, Status,
or Grouping Objects” on page 142.

Grouping windows are a type of folder or “sub‐window” that contain diagram 
objects. Vista uses grouping windows to logically organize diagram objects 
within a user diagram. When closed, a grouping window is usually represented 
by a grouping object icon. 

User diagram (contains diagram


objects and grouping objects)

Diagram object

Click a grouping
object to open its
grouping window.

TIP
It is better to use grouping objects to open other user diagrams rather than to open grouping windows.
Large numbers of grouping windows in a user diagram can slow the performance of Vista.

© 2009 Schneider Electric. All rights reserved. Page 93


Vista User Diagrams PowerLogic ION Enterprise User Guide

You can create as many user diagrams as you want and edit each one to suit your 
needs. You can share user diagrams with multiple users over your network, and 
users can view them simultaneously and share the same information. For more 
information on creating user diagrams, see “Creating and Customizing a User 
Diagram” on page 127.

Default User Diagrams


Vista provides a set of pre‐configured user diagrams that you can use to display 
data. These default diagrams provide a standard set of options that you can use to 
access your deviceʹs most commonly required functions.

The default diagram displays real‐time data. It includes a simple power system 
illustration that displays the various real‐time parameters measured by the device.

Generating, Opening and Closing a User Diagram


A user diagram is identified by its “.dgm” extension. You can generate, open, and 
close user diagrams as needed.

Generating a Network Diagram


The network diagram displays your entire power‐monitoring system by linking to 
individual default user diagrams that display data from each device in your 
system. When you generate a network diagram, Vista automatically locates all 
devices in your system and displays them. This diagram is saved with the default 
name “network.dgm”.

1. Select File > Generate Network Diagram.
The network diagram appears in the workspace containing icons that represent 
groups of devices on your system. 
2. Click on one of the grouping objects to open a window and display the node 
icons contained within.
3. Click a node icon to display the user diagram for the associated device.
4. Save the network diagram.

NOTE
Regenerating a network diagram and saving it overwrites the previously saved (network.dgm) file.

Opening a User Diagram


To open a user diagram:
1. Select File > Open.
2. Navigate to the user diagram you want to open and select it from the Open 
Diagram dialog box.
3. Click Open to open the selected user diagram.

Page 94 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Vista User Diagrams

Specifying the User Diagram that Opens for a Given User


To set a specific Vista workspace and set of diagrams to open every time a given 
user logs on:
1. Log on to Vista using the particular user’s logon credentials.
2. Organize Vista to appear as you want it to appear on startup.
3. Click Save, then close Vista.
4. Use Windows Explorer to navigate to the ...\ION Enterprise\config\cfg\ud 
folder.
5. Locate the .wsu file for the user you are setting up (i.e., <username>.wsu). Right‐
click and select Properties.
6. Select the Read‐only attribute, then click OK.

NOTE
Applying the Read-only attribute prevents the workspace information from being modified, so Vista opens
the same way for a given user every time. The user can still to modify and save user diagrams (if allowed
by their access level).

Closing a User Diagram


To close a user diagram:
Select File > Close to close the current diagram.
Select File > Close All to close all diagrams.

Navigating a User Diagram


After you open a user diagram, you can use it to interact with your power‐
monitoring system. Each user diagram displays system information through 
diagram objects, which you can use to monitor and control various aspects of your 
system.

© 2009 Schneider Electric. All rights reserved. Page 95


Monitoring Your System in Vista PowerLogic ION Enterprise User Guide

Monitoring Your System in Vista


Use Vista user diagrams to display real‐time and logged data, monitor events and 
alarms, and control a variety of system functions.

How Data is Displayed


Information in your user diagram is displayed using diagram objects. Each 
diagram object communicates a single piece of information from somewhere in 
your power‐monitoring network; for example, a single numeric object displays 
numeric data from a single source.

There are seven types of diagram objects: grouping, text, numeric, status, data log 
viewer, event log viewer, and control. Each type of object performs a specific type 
of function. 

In most cases, you can identify an objectʹs function by a caption, a label, or both (the 
text object does not use a caption or a label). 
By default, the caption is usually located below the diagram object and identifies 
the node to which the diagram object is connected. The caption can be modified 
to display a custom description. See “Caption Options” on page 134 for more 
information.
When a label is used, it is usually displayed to one side of the diagram object. By 
default, the label identifies the register (on the node) to which the diagram object 
is connected. The label can be modified to display a custom label name. See 
“Text Options” on page 134 for more information.

TIP
To toggle between default labels and custom labels, select or clear Options > Show Default Labels. You
can identify the type of diagram object by pointing to it with the mouse. The object type appears on the
status line.

Identifying Stale Data


Real‐time data that has not been refreshed is referred to as stale data. Vista detects 
stale data as it occurs and identifies it with a colored border. By default, Vista 
identifies data as stale after 30 seconds (for meter diagrams, the default value is 60 
seconds). Position the mouse pointer over an object to display a ToolTip that 
explains why the data has become stale.

The stale data settings are user‐configurable on a per‐diagram basis, and can be 
customized by anyone with the necessary access level.

Changing the Stale Data Settings


To change the amount of time (in seconds) that Vista uses to identify stale data:
1. Right‐click the background and click Properties.
2. Click the Updates tab and change the settings in the Stale Data section.
3. Click OK.

Page 96 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Monitoring Your System in Vista

Changing the Flag Settings for Stale Data


To change the flag color:
1. Click Options > Flag Colors.
2. Click the Edit button for the flag color you want to change, select the new color 
and click OK.

Identifying Errors in Communication


Vista detects errors (such as disabled devices, security access restrictions, or 
configuration errors) and identifies these with a colored border around an object 
(orange, by default). The border color can be customized (see previous section, 
“Changing the Flag Settings for Stale Data”). Position the mouse pointer over an 
object that Vista is indicating has an error to display a ToolTip that explains the 
error.

© 2009 Schneider Electric. All rights reserved. Page 97


Viewing Real-Time Data PowerLogic ION Enterprise User Guide

Viewing Real-Time Data


Vista uses numeric objects and status objects to display real‐time data. Numeric 
objects display real‐time numeric values and status objects display real‐time 
Boolean (ON/OFF) information.

Viewing Data with Numeric Objects


Vista uses numeric objects to display real‐time numeric data from your power‐
monitoring system. Numeric objects can display many types of data, such as line 
voltage or current, power or energy levels, harmonics, or demand parameters.

Depending on their configuration, numeric objects can display data in different 
formats: alphanumeric, dial, horizontal or vertical bar, or scrolling graph.

Display Styles for Numeric Objects

Alphanumeric Partial Dial Full Dial Horizontal Bar Vertical Bar

Timestamped

PC Timestamped

Scrolling Graph Arc Meter Timestamp Only

See “Customizing the Display of a Numeric Object” on page 136 for more 
information on configuring numeric objects.

Using Flags on a Numeric Object


In some cases, a numeric object may use flags to indicate the low and high limits 
of the displayed parameter.

When used on a dial display, flags appear as colored areas at either end. When 
used on other types of numeric objects, flags change the objectʹs background color 
to indicate that a low or high limit is currently exceeded. By default, the low flag 
color is blue and the high flag color is red.

Flags are stored in the workspace file on a per‐user basis. They are configurable 
and can be customized by anyone who has the necessary access level. Configurable 
settings include flag color, low limit and high limit. See “Display Options” on 
page 136 for more information on configuring flags.

Page 98 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Viewing Data with Status Objects

Viewing Data with Status Objects


Vista uses status objects to display Boolean (ON/OFF) conditions in your system. 
A status object may display the status of a digital output (such as a relay), a digital 
input (status input), or a setpoint in your system.

The default status object appears as an indicator light that changes color to indicate 
various conditions. Gray indicates the status object is not linked or not receiving 
data. 

Like most diagram objects, status objects can be modified by any user with an 
appropriate access level. Depending on how a status object has been configured, 
its appearance and function can differ significantly from the default settings.

A status object that has been customized can appear as an alphanumeric display 
(for example, “ON” or “OFF”) or a custom image (three images representing ON, 
OFF, and UNCONNECTED). See “Customizing the Display of a Status Object” on 
page 139 for more information.

NOTE
In some cases, the active state of a status object may have been changed (inverted) so that an active state
appears as inactive and vice versa. See “Annunciation Options” on page 144 for more information.

© 2009 Schneider Electric. All rights reserved. Page 99


Viewing Logged Data PowerLogic ION Enterprise User Guide

Viewing Logged Data


Data and events recorded by the devices in your system are regularly transferred 
by the Log Inserter from each device to the database. Vista uses the ION Query 
Service to transfer this information from the database to your workstation. Vista 
provides two ways to view logged data and events: the Data Log Viewer and the 
Event (and Global Event) Log Viewer.

The Data Log Viewer displays data logs from all devices represented in the 
active user diagram. You can use the Data Log Viewer to display waveform and 
trend data in tabular format. You can also select a range of logs from the viewer 
and display the data graphically in the log view plotter.
The Event Log Viewer typically displays events and alarms from each device 
represented in the active user diagram. The Event Log Viewer is used primarily 
to monitor low‐priority events and alarms associated with the active user 
diagram. Each Event Log Viewer is associated with a single user diagram.
The Global Event Log Viewer is a special version of the Event Log Viewer used 
primarily to display high‐priority events and alarms for your entire system. The 
Global Event Log Viewer is not associated with any single user diagram; the 
event information it displays is common, or global, to the entire system.

Using a Data Log Viewer


Use a Data Log Viewer to view system data stored in the database. Data Log 
Viewers display historical trend data (from data recorders) and waveform data 
(from waveform recorders).

You can select any data displayed in a Data Log Viewer and plot it as a graph or 
copy it to another application (for example, Microsoft Excel) where you can 
perform advanced calculations or include it in a report.

NOTE
See “Querying the Database” on page 148 for information on log viewer configuration.

Displaying a Data Log Viewer


Click on a Data Log Viewer object in your user diagram. The Data Log Viewer 
appears. 

Page 100 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Using a Data Log Viewer

Each Data Log Viewer displays data as a table of columns and rows. Each labeled 
column contains a single type of data and each numbered row represents a single 
data record.

Plotting a Range of Data from the Data Log Viewer


You can plot data from a Data Log Viewer in the Log View Plotter.
1. Highlight the cells containing the data that you want to plot. The range of data 
can be selected in one of three ways:
 To graph trends for all parameters over a particular time span, select a 
group of rows.
 To graph the trend for a specific parameter using all available records, select 
the entire column.
 To graph multiple parameters over a specific time span, click on the first cell 
in the desired range then drag to highlight the last cell of the range.
2. Select Edit > Plot Selected Data or click  .
The Log View Plotter window appears, displaying a graphical representation of 
the selected data. See “Plotting Logged Data” on page 108 for more 
information.

TIP
To quickly plot a single waveform, double-click on its waveform symbol in the Data Log Viewer.

Copying a Selection to Another Application


1. Highlight the cells containing the data that you want to copy.
2. Select Edit > Copy or click  . This copies the selection to the Windows 
Clipboard. Switch to another application and paste the selection.

© 2009 Schneider Electric. All rights reserved. Page 101


Using the Event and Global Event Log Viewers PowerLogic ION Enterprise User Guide

Using the Event and Global Event Log Viewers


Events and alarms that occur in your system are recorded by the meter and 
transferred via Log Inserter to the database.
Vista provides two ways to view event records stored in the database:
The Event Log Viewer displays events and alarms from the device(s) 
represented in the active user diagram. Use it to monitor low‐priority events and 
alarms associated with the active user diagram. 
The Global Event Log Viewer displays events and alarms for your entire 
system. Use it to monitor high‐priority events and alarms for the entire system. 
The Global Event Log Viewer operates independently of any user diagram.

The difference between the Global Event Log Viewer and the Event Log Viewer is 
essential when setting up alarming. The Event Log Viewer is associated with a 
single user diagram, so alarms only update when the user diagram is open. The 
Global Event Log Viewer does not require a user diagram and updates as soon as 
you start Vista.

NOTE
See “Using the Query Options” on page 148 for information on log viewer configuration.

TIP
To quickly display the user diagram for any device represented in an Event or Global Event Log Viewer,
double-click on the node name (in the node column) of a device to display its user diagram.

Displaying an Event Log Viewer


Click an Event Log Viewer object in your user diagram. The Event Log Viewer 
appears.

Page 102 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Displaying the Global Event Log Viewer

The Event Log Viewer displays logged events in a table of columns and rows. Each 
labeled column contains a single category or event description and each numbered 
row represents a single event record.

Typically, Event Log Viewers display the following information:
Timestamp: This indicates the event’s date and time.
Priority: This determines the relative significance of the event. Each type of 
event has a numeric value assigned to it that represents its relative priority level. 
See “Alarming Options” on page 144 for more information.
Cause: This is the label and value describing the cause of the event. For example, 
if the label is “Setpoint #1” and the value is “Active,” then the event was caused 
by setpoint #1 changing to an active state.
Effect: This is the label and value describing the effect of the event. For example, 
if label is “Relay #1” and the value is “Forced On,” then the effect of the event 
was to force relay #1 on.
Ack_time: This is the date and time that an alarm was acknowledged. Any 
event with a priority level that exceeds the alarm threshold appears highlighted 
in red until the alarm is acknowledged.

When an alarm occurs, Vista can notify you in several ways: a beeping sound, a 
flashing title bar, a message box, or a custom sound. If you have sufficient security 
clearance, you can acknowledge alarms. See “Acknowledging Alarms” on 
page 105 for more information.

NOTE
Because Event Log Viewers are associated with a single user diagram, they only update and alarm when
the user diagram is open. All Event Log Viewers need to be re-opened if a diagram is closed or the
software is shut down.

Displaying the Global Event Log Viewer


The Global Event Log Viewer displays event data stored in the database. It 
includes records retrieved from meter and Virtual Processor event logs, as well as 
records transferred from the system log database. Users share a single Global 
Event Log Viewer and, generally, the information displayed is common, or global, 
to the entire system. 

NOTE
We recommend that you do not delete the Global Event Log Viewer. If the pre-configured Global Event
Log Viewer is deleted, a new one must be created and configured. If one user deletes it, the Global Event
Log Viewer is automatically deleted from all workstations. Only a user with Supervisor-level access can
delete a Global Event Log Viewer.

You can add multiple Global Event Log Viewers (if you have sufficient authority). 
You can change each viewerʹs filter criteria to query the database for events from 
a specific node or group of nodes or for events with a certain priority level.

© 2009 Schneider Electric. All rights reserved. Page 103


Displaying the Global Event Log Viewer PowerLogic ION Enterprise User Guide

Adding a Global Event Log Viewer


Select Edit > Add Global Event Log Viewer. A Global Event Log Viewer window 
appears.

The new Global Event Log Viewer is preconfigured with default link and query 
information. However, you can link the viewer to another log server using the 
procedure described in “Linking a Data Log Viewer or Event Log Viewer” on 
page 147.

If you want to reconfigure a Global Event Log Viewer, right‐click in the viewer 
window to display the Event Log Viewer Configuration dialog box. You can edit 
the Caption, Query Server, Query or Alarming options in the same way you edit 
these options on an individual Event Log Viewer. See “Customizing a Diagram 
Object” on page 133 for information on configuring these options.

NOTE
When you add a Global Event Log Viewer to your workstation, it is automatically added to all Vista
workstations in your network.

Viewing the Global Event Log Viewer


To view the Global Event Log Viewer, select Window > Global Event Viewer. The 
Global Event Log Viewer appears. 

TIP
To temporarily “hide” the Global Event Log Viewer, clear View > Show Global Event Viewer. You are not
notified of any alarms while the Global Event Log Viewer is hidden. If you want to continue to be notified
of alarms, you can minimize the Global Event Log Viewer rather than hiding it.

Page 104 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Acknowledging Alarms

Acknowledging Alarms
Every type of event has a prioritized value that identifies its relative significance 
on a scale of 0 (zero) to 255. By default, Vista identifies any event with a priority of 
128 (default) or greater as an alarm.

The event record is highlighted in red, and identified under the “ack_time” 
column as “ALARM.” The “cause_value” column lists the source of the alarm and 
the “effect_value” column describes the event.

By default, Vista plays a ʹbeepʹ to annunciate an event with a priority between 128‐
191, and a beep combined with a flashing display to annunciate an event with a 
priority between 192‐255. To customize these options, see “Alarming Options” on 
page 144. 

When you acknowledge an alarm, Vista records the time the alarm was 
acknowledged (in the “ack_time” column) and your user ID (in the “user_name” 
column).

NOTE
In some cases, your access level may not be sufficient to acknowledge an alarm; for example, a critical
alarm may require Supervisor access. This is a user-configurable option. See “Alarming Options” on
page 144 for more information.

Acknowledging an Alarm
1. Open an Event Log Viewer or the Global Event Log Viewer, then do one of the 
following:
To acknowledge a single alarm, click on the word ALARM in the 
“ack_time” column or highlight the row containing the alarm.
To acknowledge all alarms to date, click on the “ack_time” column heading.
A confirmation box appears, asking if you want to acknowledge the selected 
alarm(s).
2. Select Yes to acknowledge the alarm(s) or No to cancel.

If you acknowledge the alarm but do not have a sufficient access level, the alarm 
remains unacknowledged and the message “Insufficient Authorization” appears 
in the status line.

© 2009 Schneider Electric. All rights reserved. Page 105


Acknowledging Alarms PowerLogic ION Enterprise User Guide

Silencing Alarms
If you are not ready or able to acknowledge an alarm, you can silence it until it can 
be acknowledged. Select Options > Silence Outstanding Alarms to silence alarms.

NOTE
Acknowledging an alarm does not change the operating conditions that caused the alarm. You must
ensure that the cause is corrected to remove the alarm condition.

Page 106 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Controlling System Functions

Controlling System Functions


You can use control objects to send commands from Vista to a node.

Each control object in your user diagram is configured to perform a single 
function. When you click a control object, it performs the specified function. For 
example, you could click a control object to clear an energy accumulator, toggle a 
relay, reset a counter, or adjust the value of an analog output device.

The default appearance of a control object depends on the function it has been 
configured to perform:

Boolean Pulse Numeric

Regardless of their appearance, all control objects are used the same way—to use 
a control object, click it.

NOTE
For information on configuring the message, appearance and access level of control objects, see
“Customizing the Action for a Control Object” on page 143 and “Customizing the Display of a Control
Object” on page 141.

When you click on a control object, one of the following happens, depending on 
how the control object is configured:
Vista performs the specified action immediately.
Vista displays a confirmation message. Click Yes to proceed or No to cancel the 
operation.
Vista requests a password. Type your logon password then click OK to proceed.

Depending on the function, a dialog box requesting the meter password may also 
appear. If so, type the meter password then click OK to proceed.

© 2009 Schneider Electric. All rights reserved. Page 107


Plotting Logged Data PowerLogic ION Enterprise User Guide

Plotting Logged Data


This section describes how to use and customize the Log View Plotter to view 
logged data in a graphical representation. Use the Log View Plotter to graphically 
show trends in numeric data, display logged waveforms, display phasor 
diagrams, and perform harmonics analysis on waveform data. You can also plot 
Sag/Swell voltage disturbances and compare them to industry standard voltage 
tolerance curves (such as the CBEMA/ITIC curve).

NOTE
You can copy information displayed by Vista Log Viewers to the Windows Clipboard and paste it into
other Windows applications.

Plotting Logged Data


1. Select data from a data log viewer:
To graph trends for all parameters over a particular time span, select a 
group of rows.
To graph a trend for a specific parameter using all available records, select 
an entire column.
To graph multiple parameters over a specific time span, select the first cell in 
the desired range and drag to highlight to the last cell of the range.
2. Select Edit > Plot Selected Data or click  .
Vista plots the data and displays it in the Log View Plotter window.

Page 108 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide The Log View Plotter Interface

The Log View Plotter Interface


The Log View Plotter is a Vista window that graphically displays selected data. 

Legend

Calculations
Window

The default display is the Plot Display tab. Depending on the type of data selected, 
the Log View Plotter may also offer a Harmonics Analysis tab and a Phasor 
Diagram tab.

In all cases, the Log View Plotter offers additional information in two floating 
boxes: the Legend and the Calculations window.

The Legend
Each line or bar in the graph is represented by a pattern of the same color in the 
legend.

TIP
Click on the curve sample in the legend to select its equivalent in the graph.

Displaying the Legend


1. Right‐click on the background of the Log View Plotter window.
2. Select Graph Options in the pop‐up menu. The Graph Options dialog box 
appears.
3. Select the Show legend check box then click OK.

© 2009 Schneider Electric. All rights reserved. Page 109


The Log View Plotter Interface PowerLogic ION Enterprise User Guide

The Calculations Window


The Log View Plotter calculates several values for every line or bar in the graph. 
You can view the results of these calculations in the Calculations window. 

The Calculations window updates automatically, displaying a range of calculated 
values based on the currently selected parameter. By default, all values displayed 
in the Calculations window are calculated from the first parameter. To view the 
calculations for a different parameter, select the line or bar you want.

For example, to view the calculations for a curve on the Plot Display tab, click on 
the curve line in the graph or on its line pattern in the legend. When you click a 
different tab, the Calculations window displays the values relevant to that tab.

Displaying the Calculations Window


1. Right‐click on the background of the Log View Plotter window.
2. Select Graph Options from the pop‐up menu. The Graph Options dialog box 
appears.
3. Select the Show calculations check box then click OK.

Changing Graph Options


When using the Log View Plotter, you can adjust the graph options to change the 
title of a graph or the way data is displayed.
1. Right‐click on the graph background then select Graph Options. The Graph 
Options box appears.
Type a name for the graph in the Title box. This name appears in the title 
bar of the Log View Plotter window. The default is Log View Plotter. 
Select or clear the Show legend and Show calculations check boxes to 
show or hide the legend and Calculations window.
Select the Align triggers check box to align the trigger times of all 
waveforms in the graph. (When multiple waveforms are plotted, their 
trigger times are not always correlated.)
Select Separate curves vertically to display each curve separately.

NOTE
See “Calculating Harmonics Using More Than One Cycle” on page 115 for more information on the
System Frequency and # of cycles for harmonics options.

2. Click OK to save your changes.

Page 110 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide The Log View Plotter Interface

Displaying Curve Data in a Table


After you plot data in the Log View Plotter, you can select a curve and display its 
data points in a table. This option is only available on the Plot Display and 
Harmonic Analysis tabs.
1. Right‐click on the curve line in the Plot Display or Harmonic Analysis tab and 
select Data from the pop‐up menu.

Plot Display tab: The data points are displayed. The X column lists the x‐
axis coordinates and the Y column lists the y‐axis coordinates. The first 
column (#) assigns a number to each set of points.
Harmonic Analysis tab: A window appears listing each harmonic number 
and the magnitude of each harmonic for each parameter. The first column 
numbers the rows. The X column lists the harmonics number and the Y1, 
Y2, Y3, etc., columns list the harmonic values for each bar in the harmonics 
histogram. Rows where the X value is not an integer (i.e., .5, 1.5, 2.25) 
contain sub‐harmonic values.
2. Click Format to change the number of significant digits displayed in the X and 
Y columns or to change the width of these columns.
Width defines the number of characters the column can display. 
Precision defines the number of significant digits displayed.
3. Click Copy to copy columns to the clipboard. This allows you paste a copy of the 
data into another application, such as a spreadsheet program or a text file.

NOTE
The Log View Plotter can only display one data table at a time. If you want to display tabular data for
another curve (from the same graph or a different one), you must first close any open data window.

© 2009 Schneider Electric. All rights reserved. Page 111


Viewing the Plot Display Tab PowerLogic ION Enterprise User Guide

Viewing the Plot Display Tab


The Plot Display tab depicts the specified parameters as curves against a graph.

Each parameter is plotted in a different color. The legend identifies the color of 
each curve in the selection and what it represents. Click on a curve to select it or 
right‐click on it to display additional options. The timestamp at the top of the tab 
identifies the first point in the selected curve.

The vertical axis (y‐axis) represents the specified range; the horizontal axis (x‐axis) 
represents time. Vista automatically adjusts the scale of the y‐axis and x‐axis to 
accommodate the largest parameter(s) in the selection. Right‐click on either axis to 
change the scale of its properties; right‐click on the axis numbers to change their 
format.

The time unit indicator in the lower right corner identifies the time scale of the x‐
axis (for example, “h” indicates an hourly scale). Possible time scale units include 
months, days, hours, minutes, and seconds.

Zooming in on the Plot Display Tab


To zoom in on the Plot Display tab, click on the Zoom button   then drag a 
selection box around the area you want to view. To view the entire plot, click the 
Restore to 100% button  .

Page 112 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Viewing the Plot Display Tab

Calculations Window Parameters for the Plot Display Tab


The Calculations window updates automatically, displaying the following values 
for the currently selected curve: 

Value Label Description

Cursor 1 The timestamp and the y-value of the selected curve at Cursor 1.

Cursor 2 The timestamp and the y-value of the selected curve at Cursor 2.

The time difference between Cursor 1 and Cursor 2, and the difference between the
Delta C
y-values at Cursor 1 and at Cursor 2.

Min The minimum value of the selected curve between the two cursors.
Max The maximum value of the selected curve between the two cursors.

The maximum peak-to-peak value of the selected curve between the two cursors
dpeak
(Max-Min).
1 The average value of the selected curve between the two cursors.
Avg

RMS 1 The root mean squared value of the selected curve between the two cursors.

The integration of the selected curve between the two cursors with respect to time in
Int(H) 1 hours (for example, if the curve is in kW, the information is displayed in kWh.)

1
The last three values (Avg, RMS, Int(H)) on the Calculations window are only available on plots where
the x-axis represents time. They are not offered on other types of plots (for example, CBEMA plots).

Both numeric data and waveform data can be plotted in the same graph. On 
waveform plots, the trigger time is represented by a red vertical line.

Using the Cursor Lines


There are vertical cursor lines at either end of the curves in the Log View Plotter. 
These cursor lines define the start and end points used by the Calculations 
window. By default, Cursor 1 is located on the leftmost point of the selected curve 
and Cursor 2 on the rightmost point. 

To define a new start point, drag Cursor 1 along the curve to the new start point. 
Repeat this procedure with Cursor 2 to define a new end point. You can also use 
the arrow keys to move the active cursor left or right. The active cursor is identified 
by a small box that appears where the cursor line meets the curve. Use the TAB key 
to switch the active cursor between Cursor 1 and Cursor 2.

As the cursor line moves from point to point along the curve, the information in 
the Calculations window is updated. You cannot drag Cursor 1 past Cursor 2 or 
vice versa.

© 2009 Schneider Electric. All rights reserved. Page 113


Viewing the Plot Display Tab PowerLogic ION Enterprise User Guide

De-indexing Parameters and Specifying Y-offsets


If you are plotting multiple parameters with different magnitudes, the lower 
magnitude values may be difficult to see in the default graph. Vista allows you to 
index any parameter to a different axis that can be scaled and offset independently 
from the other axes. 

The new axis automatically assumes a scale appropriate for the selected 
parameter. In this way, you can plot parameters of different magnitudes on the 
same graph (such as voltage and current).

De-indexing a Parameter or Offsetting a Parameter on the Y-axis


1. Right‐click on the graph background to display the pop‐up menu. In the last 
section of the pop‐up menu, highlight the curve you want to change.
The curveʹs sub‐menu appears. (You can also access the sub‐menu directly by 
right‐clicking on the parameter curve or on its curve sample in the legend.)
2. Select Options from the sub‐menu. The Curve Option dialog box appears. 
3. Choose one of the four axis options for the selected parameter. The axis is 
indicated by the location of the tick marks.
Specify a Y‐offset if required. This shifts the selected parameter up the y‐axis (or 
down for a negative number) by the amount you specify.
4. Click OK. A new axis appears with a default title and a scale appropriate for the 
selected parameter.
The scale of the default axis can also be adjusted to accommodate the remaining 
curves. A parameter has an asterisk after it in the legend if it has been offset.

Repeat these steps for each parameter that you want to de‐index from the default 
axis. You can assign more than one parameter to an axis and the scale adjusts 
accordingly to incorporate each new parameter. For example, if you have plotted 
three voltage parameters and three current parameters, you can select the current 
curves and assign each of them to another common axis, leaving the three voltage 
curves to share the default axis.

Displaying Power Factor Data


If you have plotted power factor data (from historical logs) in the Log View Plotter, 
you can improve the display to avoid discontinuity by setting the vertical axis to 
Power Factor Display (‐100,+100).

Setting Any Vertical Axis for Power Factor Display


1. Right‐click on the vertical axis or right‐click on the graph background and 
select the axis after you have plotted the power factor data.
2. Select Power Factor Display from the pop‐up menu. A check mark appears 
beside the option to indicate that it is selected.

You can plot other non‐power factor data on the same graph; however, you should 
not plot the new data on the same axis as the power factor data. De‐index the new 
data on a separate axis as described in “De‐indexing a Parameter or Offsetting a 
Parameter on the Y‐axis” on page 114.

Page 114 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Viewing the Harmonics Analysis Tab

Viewing the Harmonics Analysis Tab


If any of the parameters you have plotted is a waveform, you can display a 
histogram of the signalʹs harmonic content by selecting the Harmonics tab on the 
Log View Plotter window. The resulting histogram shows the harmonics for all 
waveforms in the plot.

NOTE
The cycle used is the first full cycle to the right of Cursor 1on the Plot Display tab.

The total harmonic distortion (THD), K‐factor and Crest factor values for this 
waveform are displayed in the Calculations window.

To view the calculations for another parameter, click on it in the graph or on its 
curve sample in the legend. The Calculations window updates automatically. The 
currently selected parameter is indicated above the calculations.

Calculating Harmonics Using More Than One Cycle


By default, the harmonics are calculated using one cycle. You can increase the 
number of cycles by any power of two cycles (i.e., 2, 4, 8, 16, 32 or 64) up to the 
maximum number of cycles available for the waveform.
1. Right‐click on the background of the graph area then select Graph Options. 
The Graph Options dialog box appears.
2. Select the number of cycles over which harmonics calculations are to be 
performed from the “# of cycles for harmonics” list.
3. Select the appropriate frequency in the “System Frequency” box, if the 
waveform you are analyzing came from a system with a frequency other than 
50Hz or 60Hz. (For example, if the waveform was captured from a 400 Hz 
system using a 3710 ACM, specify “400Hz” in this box.)

© 2009 Schneider Electric. All rights reserved. Page 115


Viewing the Phasor Diagram Tab PowerLogic ION Enterprise User Guide

NOTE
The Harmonics Analysis tab is only available for waveform records. Vista does not perform a harmonics
analysis for trend data or for waveforms with less than eight samples per cycle. You cannot display the
harmonics of more than 16 parameters at a time.

Viewing the Phasor Diagram Tab


If you have plotted waveforms for all three voltages and/or currents of your 
system, you can view this information as a phasor diagram. The phasor diagram 
graphically displays the three phases (voltages and/or currents), showing their 
relative magnitudes and angles.

You can use a phasor diagram to evaluate important aspects of your power system 
such as voltage balance, per‐phase loading, and type of load (or generator 
operating mode). A phasor diagram also provides a way to identify PT or CT 
wiring problems.

NOTE
The timestamp at the top of the Phasor Diagram tab is based on the time of Cursor 1 on the Plot Display
tab.

To display a phasor diagram, select the Phasor Diagram tab from the Log View 
Plotter window.

The Phasor Diagram and calculations are derived from a one‐cycle window 
starting at Cursor 1 on the Plot Display tab. The magnitude and angle of the 
selected phase is displayed in the Calculations window.

Page 116 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Viewing the Phasor Diagram Tab

NOTE
The Log View Plotter conforms to the convention where all phasors are plotted with respect to V1 (always
at 0°) and rotate in a positive counter-clockwise direction. On a balanced power system, all three phases
should appear 120 degrees apart.

To edit a phasor displayed on a phasor diagram, right‐click on a parameter in the 
legend to display a pop‐up menu where you can change the phasorʹs color or 
delete the phasor from the diagram.

Symmetrical Components
The Log View Plotter calculates the symmetrical components of your power 
system — the positive, negative, and zero sequences relative to the first phase — 
for the cycle selected. If you have plotted waveforms for three voltages and/or 
currents, you can access their symmetrical component calculations. To produce 
correct symmetrical components, the waveforms must have been plotted in the 
correct order (for example, V1, V2, V3 — not V1, V3, V2).

The analysis of an unbalanced system, such as determining the effects of a system 
fault, is made simpler by using symmetrical components. Symmetrical 
components are a mathematical tool that allows any system of three unbalanced 
phasors to be represented by three balanced phasor systems. The total current or 
voltage in any phase wire is expressed as the sum of three balanced, three‐phase 
components.

Positive Sequence Components (1) ‐ these consist of three phasors that are equal in 
magnitude and displaced from each other by 120º and have the same phase 
sequence as the original phasors.

Negative Sequence Components (2) ‐ these consist of three phasors that are equal 
in magnitude and displaced from each other by 120º and have the phase sequence 
opposite to that of the original phasors.

Zero Sequence Components (0) ‐ these consist of three phasors that are equal in 
magnitude and with zero phase displacement from each other.

If the original phasors of voltages are Va, Vb, and Vc, then the symmetrical 
components would be as follows:
Va = Va1 + Va2 + Va0 
Vb = Vb1 + Vb2 + Vb0 
Vc = Vc1 + Vc2 + Vc0

The symmetrical components function, as implemented inside some ION meters, 
is useful for steady state analysis (unbalance), since the parameters are updated 
every second. However, when determining the symmetrical components during a 
fault, per‐cycle analysis is required. For this application, you do not need real‐time 
updates from the meter, because you are only interested in the relatively short time 
before, during, and after a system fault. This information is contained in the 
waveforms recorded when triggered by a disturbance.

© 2009 Schneider Electric. All rights reserved. Page 117


Plotting Waveforms from Devices with High Sampling Rates PowerLogic ION Enterprise User Guide

Viewing Symmetrical Components


1. From a waveform Data Log Viewer (such as Waveforms/Sequence of Events), 
select all three phases of a fault (voltage or current).
2. Select Edit > Plot Selected Data.
3. Drag the Cursor and move it to the location of the fault.
4. Click on the Phasor Diagram tab to view the Symmetrical Components in the 
Calculations window.

Plotting Waveforms from Devices with High Sampling Rates


Waveforms from devices with high sampling rates can be quite large. These large 
waveforms are split by ION Enterprise into a series of smaller waveforms when 
displayed in the data log. To plot all the sections of the waveform in Vista, you 
must select all the rows that relate to the waveform before you click the Plot button. 
All the rows related to the one waveform have the same timestamp. For example, 
in the following image, you would select rows 28 to 34 to plot the entire waveform.

When the waveform is displayed, you may need to zoom in to view the area of the 
waveform you are interested in. To zoom in, drag a selection box around the area 
you are interested in.

Page 118 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Adding Parameters to a Log View Plotter

Adding Parameters to a Log View Plotter


After you have created a graph and the Log View Plotter window is visible, you 
can add additional parameters to the graph by copying and pasting them into the 
graph. These parameters can be copied from the same data log viewer, a different 
data log viewer, or from a different Windows application such as Microsoft Excel. 
The x and y‐axes are automatically re‐scaled to accommodate the new parameters.

When adding waveforms to the log view plotter, you can correlate all of their 
trigger times. See “Customizing Graph and Legend Options” on page 124 for more 
information.

Adding Data from a Data Log Viewer


You can add additional parameters from any data log viewer configured to 
provide compatible time‐based data. Any added parameter is plotted using the 
same x‐axis used by the existing curves. To avoid confusion ensure that the column 
you selected for your x‐axis in the data log viewer (from which you are adding 
data) contains the same parameter (typically a timestamp) as the original data log 
viewer.

Adding Additional Parameters from a Data Log Viewer


1. Select the range of cells you want to plot. Ensure that it contains the same type 
of information (timestamps) as the data already being plotted.
2. Select Edit > Copy.
3. Click on the title bar of the existing Log View Plotter window then select Edit > 
Paste. The parameters you selected are added to the graph.

If you want to plot waveforms on the same graph as historical data, the historical 
data should originate from high‐speed data recorders and span a short time range, 
typically a few waveform cycles (<1 second).

Adding Events from an Event Log Viewer


You can add events to a waveform or trend plot. This is useful for comparing 
abnormalities of the waveform or trend shape with any corresponding events that 
happened in the same time period.

Adding Events from an Event Log Viewer to a Waveform


1. Select the row(s) you want to add in the Event Log Viewer.
2. Select Edit > Copy.
3. Click on the title bar of the existing Log View Plotter window then select Edit > 
Paste. The copied event records are added to the graph.

Each event is represented in the Log View Plotter as a diamond symbol. A 
diamond symbol is added to the legend and diamond symbols appear at the 
appropriate areas along the top of the diagram.

Point to a diamond symbol to display a description of the event in the status bar at 
the bottom of the screen.

© 2009 Schneider Electric. All rights reserved. Page 119


Adding Parameters to a Log View Plotter PowerLogic ION Enterprise User Guide

Adding Data from a Spreadsheet or Text File


You can select data from a spreadsheet or text file and paste it into an existing 
graph. This is useful if you want to compare trends from different times, 
waveforms showing different system events, and other analysis applications.

Ensure that the first column of data in the spreadsheet or text file is the same type 
as the first column in the data log viewer from which the log plot originated. In 
particular, for timestamps, make sure the complete timestamp is contained in a 
single column and that it uses the same date and time format as defined in the 
Windows Control Panel. If the date portion of the timestamp is in one column and 
the time is in another, or if the format is different in any way, the data cannot be 
pasted into the Log View Plotter.

When you paste data into a graph, from both spreadsheets and text files, the Log 
View Plotter interprets the first row of data in the selection as a heading. The first 
row in your selection is used to label the parameter in the legend. So, if the first row 
is not already used for column headings, insert a row and type in the label you 
want to appear in the Log View Plotter. 

To copy data from a text file, the text file must be formatted correctly. Each column 
in the text file must be separated by a tab and there must be a hard return at the 
end of each row.

The first row


is a heading

The date and time are separated Columns are A hard return
by the @ symbol or a space separated by a tab begins a new row

Adding Data to a Graph from a Spreadsheet or Text File


1. Open the spreadsheet or text file. 
2. Copy the range of values you want to plot, including the first column and the 
first row. Include other columns in your selection, if required.
3. Click on the title bar of the Log View Plotter window then select Edit > Paste.
The parameters you copied and pasted are added to the graph. The axis scales 
are adjusted automatically to include the new data.

You can define a trigger for waveform records containing timestamps when you 
copy records from other applications. Simply add an exclamation mark to the end 
of the timestamp to indicate that it is the trigger time. For example, the exclamation 
mark at the end of 22/05/1998@02:00:41.035 PM! indicates that the trigger occurred 
at this time.

Page 120 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Customizing the Log View Plotter Display

Customizing the Log View Plotter Display


Many display attributes for each curve can be adjusted. In most cases, if you right‐
click on an area of the graph, either a pop‐up menu or a dialog box appears with 
configuration options. Unless otherwise noted, the options you specify for the Log 
View Plotter window are saved and restored every time you plot data from the 
original data log viewer. If you plot data from a different data log viewer, its graph 
has its own optional settings.

Customizing an Axis
After you have plotted data in the Log View Plotter, use the following instructions 
customize the axis or gridlines, change an axis label’s format or add an axis title, or 
change the font or color used on all axes. You can also change the scale of an axis.

Configuring an Axis
1. Right‐click on the graph background to display the pop‐up menu. Highlight 
the axis from the menu to reveal the sub‐menu. You can also right‐click on the 
axis to access the sub‐menu directly.
2. Select Axis Properties from the sub‐menu. A dialog box appears. 

Range: Make changes in the From and To boxes to adjust the axis range.
Ticks: Make changes in the Major every and Sub‐divided by boxes to 
adjust the frequency of major and minor ticks respectively.
Grid: Select or clear the Major and Minor check boxes to turn graph 
gridlines on or off. Click the Style buttons to change to the line style or 
width of major and minor gridlines.
Logarithmic scale: Select this check box to enable the logarithmic scale 
option.
Line: Click this button to display the Line Parameters dialog box and 
change the line style or the width of the axis.
3. Click OK to save your changes.

© 2009 Schneider Electric. All rights reserved. Page 121


Customizing the Log View Plotter Display PowerLogic ION Enterprise User Guide

NOTE
The axis range and the frequency of the major ticks are not stored in the diagram but are recalculated
for every new plot.

Changing the Color of an Axis or the Gridlines


1. Right‐click on the graph background to display the pop‐up menu. Highlight 
the axis from the menu to reveal the sub‐menu. You can also right‐click on the 
axis to access the sub‐menu directly.
2. Select Axis Color, Major Grid Color, or Minor Grid Color from the sub‐menu. 
The Color dialog box appears.
3. Select the color you want or click Define Custom Colors for more options.
4. Click OK to save your changes.
The axis or the major or minor gridlines change to the color you selected.

Changing the Format of the Axis Labels or Adding an Axis Title


1. Right‐click on the graph background to display the pop‐up menu. Highlight 
the axis from the menu to reveal the sub‐menu. You can also right‐click on the 
axis labels to access the sub‐menu directly.
2. Select Axis Labels from the sub‐menu.The Axis Labels dialog box appears. 
3. Select the format in which you want the axis labels to appear.
Decimal is used by default (for example, .01, .02, .03) but if the labels are too large 
or too small, select Scientific (1.0 x 10‐2, 2.0 x 10‐2, 3.0 x 10‐2...) or Engineering 
(1m, 2m, 3m...).
4. Determine the axis title: select None to have no axis title or Text to enter your 
own title.
For time‐based plots, the default x‐axis title is “s” if the timestamps of the data 
spans a number of seconds, “mn” for minutes, “h” for hours, “d” for days, “m” 
for months. (This applies to the Plot Display tab only.)
For non time‐based plots (CBEMA or harmonics), you can change the title. Select 
Text and type the title in the edit box. The title must be nine characters or less.
5. Click OK to save your changes.

NOTE
If the first column of the source data includes a space or @ sign, the Log View Plotter assumes time on
the horizontal axis and automatically determines the units based on timestamp information. The axis title
is updated whenever the window is updated.

Changing the Font Used on All Axes


1. Right‐click anywhere in the graph background and select Graph Font. The 
Font dialog box appears.
2. Specify the font, style, size, effects and color options that you want to use for the 
axes labels.
3. Click OK to save your changes.

Page 122 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Customizing the Log View Plotter Display

Customizing Curve Style


When displaying multiple parameters, Vista distinguishes between parameters 
using color. Each parameter is listed in the graph legend accompanied by a sample 
of its associated curve. The color of a curve can be changed after you have plotted 
data in the Log View Plotter.

If color is not enough to distinguish one curve from another—for example, if you 
plan to print the graph on a black and white printer—you can change the curve 
style after you have plotted data in the Log View Plotter.

By default:
Each curve is shown by a thin line that connects each point of data. You can 
customize the style of each curve independently and show or hide the 
coordinates of each data point.
Harmonics are displayed in a bar graph. You can distinguish between 
parameters by customizing the display style of each parameter. Display options 
include bar type, hatching, width and color.

Use the following instructions to customize curve styles, bar styles, and curve 
colors.

Changing the Style of a Curve on the Plot Display Tab


1. Right‐click on the graph background to display the pop‐up menu. Highlight 
the curve from the menu to reveal the sub‐menu. You can also right‐click on 
the parameter curve in the diagram or its entry in the legend to access the sub‐
menu directly.
2. Select Curve Properties from the sub‐menu. The Curve Style dialog box 
appears. 
Select the type of curve you want from the Type list. Vista offers seven curve 
types: a simple line, a line with symbols, a scatter plot of markers, horizontal 
or vertical bars, or 3‐D horizontal or vertical bars.   
Select Spline (available for Line or Line + Symbol types) if you want the line 
that connects each point to be a smooth curve. If you leave it cleared, each 
pair of points is connected by a straight line.
Select Fill Area (available for Line type) to fill the area under the curve with 
the line color. Clear the check box to leave the area under the curve 
transparent.
The Marker section is available for Line + Symbol and Scattered types of 
lines. Specify the shape, size, and style of the marker used for the points. The 
Style options apply only to geometric shapes (e.g., circles, boxes, diamonds, 
etc.).
For any line type, click Line to change the width and the style (e.g., solid, 
dotted, dashed, etc.) of the line. For bar graph types, a dialog box appears 
where you can specify the hatching pattern and the width of the bars.
3. Click OK to save your changes.

© 2009 Schneider Electric. All rights reserved. Page 123


Customizing the Log View Plotter Display PowerLogic ION Enterprise User Guide

Changing the Bar Style for the Harmonics Analysis Tab


1. Right‐click on the bar (or on its curve sample in the legend) and select Curve 
Properties. The Bar Graph Configuration dialog box appears. 
2. Select the type of bar to use from the Type list. This selection is applied to all bars 
in the graph. Three bar styles are available:
Group Bars: Shows bars side‐by‐side
Deep Bars: Shows bars one behind the other
Stacked Bars: Shows bars stacked one on top of the other vertically 
3. Select a hatching style for the selected bar from the Hatching list. This selection 
is applied to the currently selected bar only.
4. Set how wide you want each bar to be in the Width text box. The specified width 
is applied to all bars in the graph. The default depends upon the number of 
parameters.
5. Click OK to save your changes.

Changing the Color of a Curve


1. Right‐click on the graph background to display the pop‐up menu. Highlight 
the curve from the menu to reveal the sub‐menu. You can also right‐click the 
curve in the diagram or its entry in the legend to access the sub‐menu directly.
2. Select Curve Color from the sub‐menu. The Color dialog box appears.
3. Select the color you want or click Define Custom Colors for more options.
4. Click OK. The curve changes to the color you selected.

Customizing Graph and Legend Options


After you have plotted data in the Log View Plotter, you can change the color of 
the graphing area (and the legend) and define a font for the legend.

Changing the Color of the Graphing Area


1. Right‐click anywhere in the graph background and select Background Color. 
The Color dialog box appears.
2. Select the color you want or click Define Custom Colors for more options.
3. Click OK. The graphing area changes to the specified color.

Changing the Font Used in the Legend


1. Right‐click on the background of the legend. The Font dialog box appears.
2. Specify the font, style, size, effects, and color options that you want to use for the 
legend text.
3. Click OK to save your changes.

Page 124 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Overlaying Curves in the Log View Plotter

Removing Graph Parameters


After you have plotted data in the Log View Plotter, you can remove a parameter 
from the graph.
1. Right‐click on the graph background to display the pop‐up menu. Highlight 
the curve you want to remove from the menu to reveal the sub‐menu. You can 
also right‐click the curve in the diagram or its entry in the legend to access the 
sub‐menu directly by right‐clicking on the curve.
2. Select Delete Curve from the sub‐menu. The curve is deleted without further 
prompting.

Overlaying Curves in the Log View Plotter


After you plot data in the Log View Plotter, you can overlay a curve onto your 
graph to help analyze sag/swell data. This applies to devices that measure 
disturbances in voltage and store the magnitude and duration of these 
disturbances. When these values are inserted into the ION_Data database, they 
provide a series of coordinates that can be plotted on a voltage tolerance curve. A 
voltage tolerance curve is often used to categorize the severity of a voltage 
disturbance.

NOTE
Most Vista queries are plotted against timestamps (with the timestamp as the x-axis); however, any query
that uses the ION Sag/Swell module must be plotted against duration. When plotting sag/swell data,
select Duration as the X-parameter of the Log View Plotter.

Vista provides common curves or voltage tolerance envelopes that can be used as 
overlays in the Log View Plotter:

CBEMA/ITIC: These curves (described by the IEEE 446 standard) define an 
upper and a lower bound on the types of disturbances that electrical equipment 
is likely to tolerate. It plots disturbance magnitude against disturbance duration 
and indicates at what points a voltage disturbance is likely to disrupt or damage 
equipment. Points near or outside the voltage tolerance envelope indicate 
events that could interrupt or damage electrical equipment.

© 2009 Schneider Electric. All rights reserved. Page 125


Overlaying Curves in the Log View Plotter PowerLogic ION Enterprise User Guide

SEMI F47‐0200: This specification defines the voltage sag tolerance capability 
required for semiconductor processing equipment, though it is now used by 
other industries. According to the specification, equipment must tolerate sags to 
50% of nominal voltage for up to 200 milliseconds, sags to 70% of nominal 
voltage for up to 0.5 seconds, and sags to 80% of nominal voltage for up to 1 
second. Points above the voltage tolerance curve indicate disturbances that 
exceed these specifications.

Overlaying Curves on Plotted Data


To overlay one of the provided curves, you need a data log viewer that contains 
the magnitude and duration values for the sag/swell disturbances. The Duration 
column must be set as the X‐parameter for the Log View Plotter—it appears in blue 
in the data log viewer table (See “X‐Parameter for Log View Plotter” on page 149 
for more information on setting the X‐parameter for Data Log Viewers). The 
Magnitude values can be in any one of the other columns.

1. In the Data Log Viewer, select a range of cells to be plotted.
2. Select Edit > Plot Selected Data. The Log View Plotter window appears with 
Duration as the x‐axis and Magnitude as the y‐axis.
3. Right‐click on the graph and select Overlay Curve from the pop‐up menu. The 
Overlay Curve dialog box appears.
4. Select the text file containing the curve data that you want to overlay (from the 
...\ION Enterprise\config\lvp directory).
5. Click Open. The selected curve appears in the graph.
You can review each point in your data and see where it falls in relation to the 
curve.

NOTE
This process automatically changes your x-axis scale to logarithmic.

Page 126 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Creating and Customizing a User Diagram

Creating and Customizing a User Diagram


The following sections describe:
How to customize an existing user diagram by customizing the appearance and 
function of a diagram object or diagram window.
How to create a new user diagram. 
The various types of diagram objects and how to use each type to add function 
to your user diagram.

NOTE
You must have the appropriate security clearance to edit or create a user diagram. To determine if you
can edit a diagram, select Options > Show Toolbox. If you can select this option, then you can edit a
diagram. Consult your network administrator if you need to change your access privileges.

NOTE
Any changes you make to a default diagram affect all other devices using the same diagram.

Creating a New User Diagram


To create a new user diagram, login to Vista and select File > New. A new (blank) 
user diagram appears. You can only create a new user diagram if you have 
Supervisor‐level access. 

To automatically generate a network diagram based on devices added using 
Management Console, see “Generating a Network Diagram” on page 94. 

Saving a User Diagram


To save changes you made to a user diagram:
1. Select File > Save to save a new or existing user diagram or File > Save As to 
save a user diagram under a new name. The Save New Diagram box appears.
2. Type a name for the diagram in the File name box then click Save.

By default, Vista points to the root of the \ud directory when you attempt to save 
a new diagram. If required, you can create a new folder within that directory to 
store your customized diagrams, rather than storing them in the \ud folder. 

NOTE
This \ud directory should be located on a networked drive where it can provide multiple users with access
to saved user diagrams.

© 2009 Schneider Electric. All rights reserved. Page 127


Editing a User Diagram PowerLogic ION Enterprise User Guide

Editing a User Diagram


To edit a user diagram, the Diagram Objects toolbox must be displayed. To open 
the toolbox, select Options > Show Toolbox. If the Show Toolbox option is grayed 
out, your user account does not have sufficient access; contact your system 
administrator.

The Enable Undo Option


The Enable Undo option enables or disables the undo feature in Vista. With this 
option active, you are allowed to undo or “step backward” up to three times. This 
feature is enabled by default. If you disable the undo feature, you lose the ability 
to undo any previous changes. You cannot enable the feature and undo changes 
made prior to enabling the feature. A check mark appears beside Enable Undo in 
the Options menu when this option is selected.

NOTE
The Show Toolbox option must be selected for the Enable Undo option to become active — it remains
unselectable otherwise.

Adding a Diagram Object to a User Diagram


You can add a new diagram object to a user diagram by dragging it from the 
Diagram Objects toolbox.

Types of Diagram Objects


Diagram objects provide the interface to ION registers in your network. Each 
diagram object performs a single function. For example, a single numeric object 
placed in a user diagram displays numeric data from a single source. There are 
seven types of diagram objects available on the Diagram Objects toolbox:

Grouping Object: Group a number of related objects within a separate grouping 
window. Click on a grouping object to open the grouping window and display its 
contents.

Text Box: Display independent headings, titles, and comments in a user diagram.

Numeric Object: Display real‐time numeric values such as Volts, Amps or kW.

Status Object: Display Boolean data (On/Off, Yes/No, 1/0, etc.) to indicate the 
status of a digital output (relay), digital input (status input) or setpoint. The image 
can be customized and it can be configured to use animation.

Data Log Viewer: Display data logs stored in the ION_Data database (including 
archives from previous versions of ION Enterprise), show waveform data 
(waveform capture, waveform recorder) and trends (data recorders) using tables, 
and provide data for plotting.

Page 128 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Cutting, Copying, and Pasting a Diagram Object

Event Log Viewer: Display event logs stored in the ION_Data database (including 
archives from previous versions of ION Enterprise), show event records from 
devices and other components, and display and acknowledge alarms.

Control Object: Send commands to a device on your network (for example, clear 
an energy accumulator, toggle a relay, reset a counter, or adjust the value of an 
analog output device).

To add a function to a user diagram, choose the type of diagram object you want, 
drag it into the user diagram then link it to the appropriate register in a node. The 
following sections explain how to add and link a diagram object.

See “Monitoring Your System in Vista” on page 96 for more information on the 
function and basic use of each type of diagram object.

Adding a Diagram Object to a User Diagram


1. Select Options > Show Toolbox if the toolbox is not displayed. The toolbox 
appears in the workspace.
2. Click on the diagram object you want and drag it from the toolbox to the 
diagram.
In most cases, the object appears in the window as the icon from the toolbox. 
However, there are two exceptions:
A text box appears in the window as a rectangular box that displays the 
default message: “Your text goes here.”
A numeric object appears in the window as a rectangular box with a only 
colon (:). This indicates that the object is not yet linked to a node. 
The object is now ready to be linked to a real‐time or logged data source. See 
“Linking a Diagram Object to a Data Source” on page 146 for details on linking 
an object to a source.

NOTE
When a diagram object is placed in a window, it automatically uses the same node as the window. If you
want to change this source, either relink each diagram object or change the default window link before
placing the objects.

Cutting, Copying, and Pasting a Diagram Object


Use the Cut, Copy and Paste commands on the Edit menu to make a copy of a 
diagram object and paste it into another window or user diagram.

You can paste the copy as many times as you like to create multiple versions of an 
object. Each copy retains all of the attributes and linkage information of the 
original.

© 2009 Schneider Electric. All rights reserved. Page 129


Copying a Group of Diagram Objects to a Framework PowerLogic ION Enterprise User Guide

Cutting or Copying a Diagram Object


1. Select the object(s).
2. Do one of the following:
To remove the original, select Edit > Cut then click Yes to confirm the 
deletion or No to cancel.
To retain the original, select Edit > Copy. The selection is copied to the ION 
Enterprise clipboard.

NOTE
The ION Enterprise clipboard is a temporary storage area that holds any information cut or copied from
Vista. It should not be confused with the Microsoft Windows Clipboard.

After the object is copied to the ION Enterprise clipboard, you can paste it into the 
active window.

Pasting a Diagram Object


1. Select the window you want to paste to.
2. Select Edit > Paste. The object appears in the active window.

Copying a Group of Diagram Objects to a Framework


A Vista framework is a template that you can use to record the layout of a group 
of diagram objects.

When you select Edit > Copy to framework, Vista saves the selection (including 
the type and location of each diagram object) as a file. You can then use the Paste 
from framework command to copy the group layout to another diagram or 
grouping window. This is useful for replicating a single configuration on multiple 
workstations. You can store a saved framework with its own filename and retrieve 
it anytime.

Copying a Group of Diagram Objects to a Framework


1. Select the group of objects you want to copy.
2. Select Edit > Copy to framework. The Copy to framework dialog box appears.
3. Type a name for the framework in the File name box then click Save. The 
framework file extension (.fwu) is added automatically.
The selection is saved as a framework.
After you save a group of objects as a framework, you can paste it to another 
window.

Page 130 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Adjusting Diagram Object Layout and Size

Pasting a Group of Diagram Objects from a Framework


1. Select the window you want to paste to.
2. Select Edit > Paste from framework. The Paste from framework dialog box 
appears.
3. Navigate to the framework you want to paste and click Open. The framework 
selection appears in the active window.

Adjusting Diagram Object Layout and Size


This section describes how to move, align and resize diagram objects.

Moving Diagram Objects


You can move a single diagram object or a group of diagram objects within a single 
window or from one window to another.
1. Select the object(s) you want to move.
2. Drag the selected object(s) to the new location.

You can also use the arrow keys on the keyboard to move the selected diagram 
object(s) one space at a time. 

When diagram objects overlap, use the Send to Back command to place one object 
beneath the others. Select the object then select Edit > Send to Back (or press 
CTRL+K).

Resizing a Single Diagram Object


You can adjust the size of a diagram object to make it larger or smaller or you can 
stretch it horizontally or vertically to change its shape. 
1. Click on the diagram object to select it.
2. Do one of the following:
To make the object larger or smaller, drag a corner handle.
To stretch the object horizontally or vertically, drag a middle handle.

Resizing a Diagram Object(s) to a Standard Size


The Size tab in the Layout dialog box lets you automatically resize a diagram object 
or group of diagram objects to a set of standard dimensions.
1. Select the diagram objects you want to resize.
2. Select Edit > Layout or click  . The Layout dialog box appears. 
3. Select the Size tab. 

© 2009 Schneider Electric. All rights reserved. Page 131


Adjusting Diagram Object Layout and Size PowerLogic ION Enterprise User Guide

4. Edit the horizontal and vertical dimensions of the object(s) as required.
Select No change to make no changes to that dimension.
Select Shrink to smallest or Grow to largest to adjust the width and/or 
height to match that of the smallest or largest object in the selected group.
Select Pixels to enter the exact width or height in pixels.
You can also combine horizontal and vertical options on a single selection. For 
example, if you select Shrink to Smallest in the Horizontal section and 30 pixels 
in the Vertical section, the entire selection is resized to the width of the shortest 
object and the specified height of 30 pixels.
5. Click OK to save your changes.

Aligning Diagram Objects Relative to Each Other


The Align tab of the Layout dialog box lets you specify the horizontal and vertical 
arrangement of the selected objects.
1. Select the diagram objects that you want to align.
2. Select Edit > Layout or click  . The Layout dialog box appears. 
3. Select the Align tab to specify the horizontal and vertical alignment of the 
object(s). 
The options in the Horizontal and Vertical areas determine the criteria by which 
you can align diagram objects. For example, if you select Left sides under 
Horizontal and Space evenly under Vertical, Vista aligns all objects in the 
selection by their left sides (using the leftmost object for reference) and 
distributes them evenly along a vertical axis.
4. Select the options you want then click OK.

Aligning Diagram Objects on a Grid


The Grid tab of the Layout dialog box lets you activate and configure an invisible 
grid. Objects placed onto the grid snap to the nearest gridline to help align and 
space them evenly.

To activate or deactivate the grid:
1. Select Edit > Layout or click  . The Layout dialog box appears. 
2. Select the Grid tab.
3. Select one of the following options:
No grid turns the grid off.
Grid size in pixels activates the grid. Type a number in the “Grid size in 
pixels” box to specify the size of the grid (distance between grid lines).
4. Click OK to save your changes.

Page 132 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Customizing a Diagram Object

Customizing a Diagram Object


After you have placed and linked a diagram object, you can customize it. Right‐
click on a diagram object in edit mode to display the configuration options 
available for that object type.

Customizing a Diagram Object


1. Right‐click the diagram object. The <Object> Configuration dialog box appears 
(where <Object> is the type of diagram object selected).
2. Select the appropriate tab and make your changes. Repeat this step for the other 
tabs until you have made all your desired changes.
3. Click OK to save your changes to the diagram object.

The options available vary depending on the tab and the object selected. See the 
sections below for details on the options available for different tabs and objects. 

The Preview Pane


Use the Preview pane to view how your proposed changes will appear in the 
diagram. 

For some tabs, you access dialog boxes by right‐clicking on the image in the 
Preview pane (for example, the Display tab of a numeric object). More information 
is given in the relevant sections that follow. 

Available Configuration Options


The following table lists the various configuration options available for each type 
of diagram object.

Available Option Tabs

Link (or Query


Caption Text Edit Text Display Action Box Annunciation Query3 Alarming
Node)1 Server2
Grouping Object x x x x x

Text Box Object x x x

Numeric Object x x x x x x x
Status Object x x x x x x x

Data Log Viewer x x x

Event Log Viewer x x x x


Control Object x x x x x x

1
Node is the tab available with Grouping Objects
2
Query Server is only available on Grouping, Numeric, Status and Control objects when the Action is
set to something other than None.
3
See “Querying the Database” on page 148 for information on configuring this option.

© 2009 Schneider Electric. All rights reserved. Page 133


Caption Options PowerLogic ION Enterprise User Guide

Caption Options
To view caption options, right‐click on the object then select the Caption tab.

Use the Caption tab to add custom, user‐defined text to a diagram object. The 
Caption tab is available for the following diagram objects: Grouping, Numeric, 
Status, Data Log Viewer, Event Log Viewer, and Control.
The Caption tab contains three sections: Caption, Font, and Position.

The Caption section determines whether a diagram object displays a textual 
comment along with the diagram object’s icon. This section has three options:
Select None to display no caption.
Select Use default to display the default Vista caption (i.e., the device name or 
data source).
Select Use custom to display the text that you type into the field provided.

The Font section allows you to change the font used in a caption. This section has 
two options:
Select Inherit from parent window to use the default font.
Select Custom to specify a custom font. Click Font to display the Font dialog box 
and change the font, size, style or color.

The Position section has two options:
Select Top to place the caption above the diagram object.
Select Bottom to place the caption below the diagram object. 

Text Options
Some diagram objects have a text label integrated into the display. To edit the 
appearance of this label, use the options offered on the Text tab. The Text tab is 
available for the following diagram objects: Numeric, Status, Control, and Text.

NOTE
You can edit the text displayed in a text label. For a numeric, status or control object, use the Label section
of the Link tab. For a text box object, use the Edit Text tab.

To view the Text options, right‐click on the object then select the Text tab. The Text 
tab has two sections: Font and Position.

The Font section has two options: 
Select Inherit from parent window to use the default font 
Select Custom to specify a custom font. Click Font to display the Font dialog box 
and change the font, size, style or color.
The Position section has three options — Left, Center and Right — to define the 
alignment of the text in relation to the diagram object. Use the Preview area located 
beside the Text tab to view your proposed changes.

Page 134 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Edit Text Options

Edit Text Options


To view the Edit Text options, right‐click on the object then select the Edit Text tab.

Use the Edit Text tab to specify a text message for the text box. The Edit Text tab is 
available on the text box object only. 

The Edit Text tab has two options:
Use default displays the window link information (i.e., the node).
Use custom displays your custom text message.

If you select custom, use the text box to enter your text. The text box supports 
multiple lines of text. If your message appears incomplete or truncated after you 
enter text and click OK, you can adjust the dimensions of the text box object. To 
resize a text box, select it then drag its handles.

The font used in the text box is based on the default setting specified for the active 
window. Use the Text tab to specify a different font or position for the text box. Use 
the Box tab to specify a border style or change the background color.

Link Options
To view the link options, right‐click on the object then select the Link tab.

Use the Link tab to link a diagram object to a real‐time source, and to specify a new 
text label. The Link tab is available for the following diagram objects: Numeric, 
Status, and Control.

NOTE
To set a real-time source for a grouping object, use the Node tab.

The Link tab contains two sections: Link and Label. 

Use the Link section to specify a real‐time source for the diagram object. See 
“Linking a Numeric, Status or Control Object” on page 146 for more information.

Use the Label section to change the objectʹs text label. The Label section has three 
options:
Select None to display no label.
Select Use node label to display the nodeʹs register label. This is the default.
Select Custom to display the label that you type into the text field provided. The 
custom labels you create are stored in the user diagram and are only available to 
users of your diagram. 

© 2009 Schneider Electric. All rights reserved. Page 135


Query Server Options PowerLogic ION Enterprise User Guide

NOTE
If you have specified custom labels in your diagram, or custom labels have been applied to an ION meter
at the device level, you can display the default labels at any time by selecting Show Default Labels from
the Options menu. This displays the default label of the data source instead of the label assigned in the
device or in the user diagram.

Query Server Options


Use the Query Server tab to connect a diagram object to a Query Server. The Query 
Server tab is available on the Data Log Viewer and Event Log Viewer objects. See 
“Linking a Data Log Viewer or Event Log Viewer” on page 147 for more 
information.

The Query Server tab is also available on grouping objects and any object 
configured to open a grouping window or user diagram. In this case, use the 
Query Server tab to specify a default Query Server for the associated grouping 
window or user diagram. See “Query Server: Setting a Default Query Server for a 
Window” on page 157 for more information.

Display Options
Use the Display tab to customize the appearance of a diagram object. The Display 
tab is available for the following diagram objects: Numeric, Status, Control, and 
Grouping.
The Display tab offers a unique set of options for each type of diagram object. To 
view the display options, right‐click on the diagram object then select the Display 
tab.

Customizing the Display of a Numeric Object


Numeric objects display real‐time data in your user diagram. The default numeric 
object appears as a rectangular alphanumeric display with a single decimal place 
of resolution and no unit symbol. You can customize the display to change any of 
these default elements. 

NOTE
Vista supports a maximum of 59 non-alphanumeric numeric objects within a single window. To change
the way numbers are displayed (thousands separator and decimal point), use the Regional Settings option
of the Windows Control Panel. You can also use this option to customize the time and date styles. (The
year/month/day format can be modified, and the clock can be changed from am/pm to 24 hour.)

Setting Display Style


The Display style box lets you select a new style from the list of available choices. 
The following styles are available:

Page 136 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Display Options

Alphanumeric Partial Dial Full Dial Horizontal Bar Vertical Bar

Timestamp with value

Timestamp only

Scrolling Bar Arc Meter PC Timestamp

Alphanumeric: Default style. General‐use text display.
Partial Dial: General use voltage, current, harmonic distortion, etc.
Full Dial: Power factor, bi‐directional power flow, etc.
Horizontal Bar: General use.
Vertical Bar: General use.
Scrolling Graph Display: General use. Displays recent readings on a scrolling 
graph.
Arc Meter Display: General use voltage, current, harmonic distortion, etc.
Timestamped Display: Displays the value, and the date and time the value was 
measured by the device. Useful for min./max. values.
Timestamp Only: Same as time‐stamped, but does not display a value. Can be 
used as a clock.
PC Timestamped Display: Displays the value, and the date and time the value 
was received by Vista.

Setting Units and Resolution


Use the Units box to type the unit name for the measured value (e.g., “Volts” or 
“Amps”). This name is displayed on the numeric object. 

In certain cases, the value is scaled. For example, if the unit name begins with K, 
M, or G (e.g., kV or MVolts), the displayed value is adjusted accordingly. 
However, if the unit contains certain letters (i.e., kW or kVA), the scaling factor is 
reduced by 1,000 (for example, if the unit begins with K, the value is not scaled and 
M is scaled by 1,000). The reason for this is that most devices provide these values 
already scaled.

Use the Resolution box to specify the number of decimal places to be displayed for 
a numeric object. The default value is 1, but this can be increased to take advantage 
of any extra resolution available from the data source.

NOTE
Specifying higher resolution does not result in higher accuracy than the specified accuracy of the device.

© 2009 Schneider Electric. All rights reserved. Page 137


Display Options PowerLogic ION Enterprise User Guide

Setting the Font Options


Use the Ticks Labels Font section to define font options (such as style, size, and 
color) for the numeric object. This section has two options:
Select Inherit from parent window to use the default style.
Select Custom to specify a custom style, then click Font to display the Font 
dialog box and make your changes.

Setting Flags
Use the Flags button to display the Normal Operating Range dialog box. Use this 
dialog box to set a Low Limit and a High Limit and define a normal operating 
range to be displayed on the numeric object. After flags have been set, you can use 
them to quickly determine whether a reading is within the normal range you 
defined.

The effect of setting these limits depends on the display style you have specified. 
For example, on the Partial Dial, Full Dial, and Arc Meter displays, flags appear as 
colored ranges on the dial. On other types of numeric objects, the flag function 
changes the objectʹs background color whenever a limit is exceeded.

By default, Low Flag color is blue and High Flag color is red; however, you can 
specify any colors you want. Select Options > Flag Colors to display a dialog box 
where you can edit these options. 

NOTE
The flags used in Vista are not linked to setpoints in ION meters. Setpoint activity is automatically logged
by the Log Inserter. Setpoint status can be monitored using a status object and/or data log viewer.

Other Display Options for Vertical or Horizontal Bar Graphs


In the Preview section of a vertical or horizontal bar graph Display tab:
Right‐click on the axis labels to display the Axis Labels dialog box. Select the 
Format (Decimal, Scientific, or Engineering) and determine the Axis Title (none 
or custom text).
Right‐click the axis tick marks to display the Vertical or Horizontal Axis dialog 
box. Configure the Range, Ticks and Grid style. Select Logarithmic scale to 
enable the logarithmic scale option.

Other Display Options for Partial Dial, Full Dial and Arc Meter Displays
To configure meter parameters on partial dial, full dial or arc meter displays, right‐
click anywhere in the Preview section of the Display tab.
Set the Range, Arc Position, Ticks, and dial Position. For full and partial dial 
displays, set the label position to inside or outside. Click Line Attributes to set the 
style and width of the dial.

Page 138 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Display Options

Other Display Options for Scrolling Graphs


In the Preview section of the Display tab:
Right‐click the vertical or horizontal axis tick marks to bring up the Vertical and 
Time Axis dialog boxes. Set the Range and Ticks, and (for the vertical axis) Grids 
Style.
Right‐click on the vertical axis labels to display the Axis Labels dialog box. Select 
the Format (Decimal, Scientific, or Engineering) and determine the Axis Title 
(none or custom text).
Right‐click on the graph background to display the Scrolling Graph dialog box 
where you can set the Sample Interval and Relative Reset. 

The sample interval determines the resolution of the X‐axis in seconds. It 
should be set between one tenth and one hundredth of the X‐axis range; for 
example, when extending the range to one hour (3600 seconds), the sample 
interval should be set to approximately 60 seconds.
The relative reset is a percentage that determines the amount the scrolling 
graph shifts back upon filling the plotting area. (For example, a relative reset of 
0.5 shifts back 50%; a relative reset of 0.99 scrolls the most smoothly.)

Customizing the Display of a Status Object


Status objects display the status of Boolean “on/off” conditions in one of three 
ways: an indicator light, an alphanumeric field, or a custom image. 

To view the display options of a status object, right‐click on the object then select 
the Display tab. 

NOTE
To invert the default color scheme, select “Invert active state” from the Annunciation tab.

The Display tab has three options:
Select Default image to display the default indicator light image, which changes 
color to indicate various conditions: by default, green indicates an OFF 
condition, red indicates an ON condition and gray indicates a status object that 
is not connected or is not receiving information. 
Select Custom images to use custom images for each condition. Custom images 
can show animation, customized buttons, alarm messages, etc.
Enter the filename of the image in the appropriate box (ON, OFF, or 
Unconnected). To hide the status object in a given state, leave the appropriate 
box blank.
Currently, the custom image option supports the following graphic file 
formats: BMP, WMF (Windows Metafile), EMF, and AVI (without audio and 
uncompressed or compressed using RLE8 compression).
You can use three different files to represent the three display states (ON, OFF, 
and Unconnected) of a status object. Each of these files can also be of a different 
type (e.g., BMP, AVI, and WMF).

© 2009 Schneider Electric. All rights reserved. Page 139


Display Options PowerLogic ION Enterprise User Guide

NOTE
Vista no longer uses the 6-frame bitmap format for Boolean custom images. However, if you are a user
of an earlier version of Vista and have upgraded, your existing graphics still work. If the “6-frame bitmap”
check box is selected, you can use the same file for all three states. Vista uses the first frame to display
the Unconnected state, the second frame for the OFF state, and the last frame for the ON state. If no file
name is provided in the entry box of a state, nothing is displayed when the status object is in that state.

Select Alphanumeric to display the Boolean state labels stored in the device and 
choose custom colors to visually indicate the corresponding states.
For example, suppose “Running” has been stored in a meter as the label for the 
Boolean register that stores the ON condition of a motor relay and “Stopped” 
for the OFF condition. You can show this register label together with the status 
label using the alphanumeric display style. You can override the meter labels 
on the Link tab.
Click ON Color and OFF Color to specify the colors associated with each 
condition.

Customizing the Display of a Grouping Object


The grouping object can be displayed as the default image, a custom image, or no 
image. You can customize the display to change any of these default elements.

To view the display options of a grouping object, right‐click on the object then 
select the Display tab. 

The Display tab has three options:
Select Default image to use the default image for a grouping object that appears 
in the toolbox.
Select Custom image to display a custom image. Enter the filename of the image 
you want to use. The filename should include the fileʹs extension (for example, 
.bmp, .wmf, .emf, or .avi).
Select None to hide the grouping object. With no image specified, the grouping 
object is transparent unless you select it (displaying the handles). If you move 
the mouse over a transparent object, the status line displays the size and object 
type (for example, “30x30:Grouping Object” in the status line means the hidden 
object is a grouping object and its size is 30 pixels by 30 pixels). 
Hiding a grouping object is especially effective when using a custom 
background image; you can integrate your transparent grouping objects into 
the image by placing them at the appropriate points on the drawing. Users can 
display site‐specific information by double‐clicking on the appropriate spot in 
the background. See “Image: Displaying a Background Image” on page 156 for 
information on using a custom background.

Page 140 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Display Options

Customizing the Display of a Control Object


A control object appears differently depending on the type of register to which it 
is linked. This same criteria also determines the display options available. 
To view the display options of a control object, right‐click the object then select the 
Display tab.

The options available depend on the type of control object.

External Numeric
A control object that is linked to an External Numeric module appears as an 
alphanumeric display box. The Display tab has the following sections: Border and 
Background Color.

In the Border section, select Hide to show no border or select Show to display a 
border. If you select Show, you can specify the width in pixels and click Color to 
choose a color for the border.

In the Background Color section, select Transparent for no background or select 
Custom then click Color to define a color for the background. 

External Pulse
A control object that is linked to an External Pulse module appears as a button icon, 
by default. The Display tab has three options: Default image, Custom image and 
None. 

Select Default image to display the button icon. Select Custom image and click 
Browse to select a different image. Select None to show no image (the control 
object is hidden but still functions).

External Boolean
A control object that is linked to an External Boolean module appears as a switch 
icon, by default. The Display tab has two options: Default image or Custom 
images. 

Select Default image to display the switch icon. Select Custom images then click 
Browse to define custom images for ON, OFF and Unconnected. To hide the 
control object for a given state, leave the appropriate box blank. Currently, the 
custom image option supports the following graphic file formats: BMP, WMF 
(Windows Metafile), EMF, and AVI (without audio and uncompressed or 
compressed using RLE8 compression).

NOTE
Vista no longer uses the 6-frame bitmap format for Boolean custom images. However, if you are a user
of an earlier version of Vista and have upgraded, your existing graphics still work. If the “6-frame bitmap”
check box is selected, you can use the same file for all three states. Vista uses the first frame to display
the UNCONNECTED state, the second frame for the OFF state, and the last frame for the ON state. If
no file name is provided in the entry box of a state, nothing is displayed when the status object is in that
state.

© 2009 Schneider Electric. All rights reserved. Page 141


Action Options PowerLogic ION Enterprise User Guide

Action Options
To view the action options, right‐click on the diagram object then select the Action 
tab. 

Use the Action tab to specify the response of a diagram object when it is clicked (in 
Display mode) or double‐clicked (in Edit mode).

The Action tab is available for the following diagram objects: Numeric, Status, 
Grouping, and Control objects. Depending on the type of diagram object, the 
Action tab displays one of two sets of options:
Specify an action for a numeric, status, or grouping object
Customize the action for a control object

Specifying Action for Numeric, Status, or Grouping Objects


NOTE
If you change the action for a grouping object that is already associated with a grouping window, the
existing window (and any objects within it) is deleted. Vista displays a warning before performing this
action.

When you right‐click on a numeric, status, or grouping object, the Action tab 
displays the available options:
Select None if you do not want the object to support an action. This is the default 
for numeric, status, and grouping objects.
Select Open Grouping Window to open a grouping window when the object is 
clicked. You can use this grouping window to display additional information. 
For example, if a numeric object displays a total value (such as total kW), you 
can display specific information (such as kW readings for each phase) in an 
associated grouping window.
The Open Diagram for Meter Template option is used by default each time a 
network diagram is generated. Each meter icon in the network diagram is set to 
open the default diagrams that match that meterʹs configuration.
Select Open User Diagram to open a user diagram when the object is clicked. 
Type the full path and filename into the field provided or click Browse to locate 
the diagram you want. Using this action, you can choose a diagram object that 
displays a representative reading from an independent diagram and use it to 
open the other diagram when clicked.
Select Open File to open a file when the object is clicked. Type the full path and 
filename into the field provided or click Browse to locate the file you want. The 
file can be a third‐party program or some other document; if a document is 
specified, then the program associated with the file extension is launched and 
the specified document is loaded into the application.
Select Open Web Page to open a specified webpage in your default web browser 
when the object is clicked. Type the complete address into the field provided.

Page 142 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Box Options

NOTE
When you select any action other than None, the Query Server tab is added to the top of the object
configuration box. You can use this tab to specify a source of logged data for the new user diagram or
grouping window. If you enter only the filename into the field provided (and do not specify a directory),
Vista defaults to ..\ION Enterprise\config\diagrams\ud.

Customizing the Action for a Control Object


To view the action options of a control object, right‐click on the control object and 
select the Action tab.

The Action tab offers three options that you can use to define how the control 
object responds when clicked:
Select No confirmation to have no confirmation message displayed.
Select Message box confirmation to display a message box when the object is 
clicked. The message box requires the user to click either OK or Cancel.
Select Password confirmation to request the user’s logon password when an 
object is clicked.

The Level to operate list allows you to specify the access level required to perform 
the action. See “User Manager” on page 55 for more information on access levels 
and their permissions.

Box Options
To view the Box options, right‐click on the object then select the Box tab.

Use the Box tab to add a border or background color to a diagram object. The Box 
tab is available for the following diagram objects: Numeric, Text Box, and any 
status object that has been configured as an alphanumeric display
The Box tab has two sections:
Border lets you adjust a border’s width and color as well as whether or not it is 
displayed. Select Hide to remove the border or Show to display it. If you select 
Show, click Color to define a border color and type a number in the Width in 
pixels field to change the line thickness.
Background Color lets you set the background color of an object. Select 
Transparent to use the background color of the parent window or select Custom 
and click Color to select another color.

© 2009 Schneider Electric. All rights reserved. Page 143


Annunciation Options PowerLogic ION Enterprise User Guide

Annunciation Options
To view the annunciation options, right‐click on the status object then select the 
Annunciation tab. 

Use the Annunciation tab to specify how users are notified of a change of status. 
The Annunciation tab is available on the Status Object only.

NOTE
The Annunciation feature requires that the Status Object’s diagram is displayed; if the display is closed
or minimized, then the annunciation feature does not work.

To view the annunciation options, right‐click on the status object then select the 
Annunciation tab. 

The Annunciation tab has three options that set the action that Vista performs 
when a status object becomes active:
Select Command line to automatically launch another application in the event 
of a change in status. Type the programʹs executable (.exe) command into the 
field provided or click Browse to locate the appropriate file.
Select Message box to specify an annunciation message. Type your message into 
the field provided. The first line of text appears as the title of the message box.
Select Invert active state to change the way the status object reacts to an active 
state. When this option is selected, the status object treats an active state as 
inactive and vice‐versa. This is useful, for example, in cases when you want to be 
notified if a function (such as a cooling fan) switches off.

NOTE
If you select the Invert active state check box, this also inverts the default colors of the status object.

Alarming Options
Every type of event that occurs in an ION Enterprise network has a prioritized 
value that identifies its relative significance on a scale of zero to 255. By default, 
Vista identifies any event with a priority of 128 or greater as an alarm.

To view the Alarming options, right‐click on the Event or Global Event Log Viewer 
then select the Alarming tab. 

Use the Alarming tab to create or delete a priority range, specify the security level 
required to acknowledge an alarm, or customize the way Vista annunciates an 
alarm.

Page 144 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Alarming Options

The Alarming tab has three main sections:
Priority ranges lists the currently configured alarm ranges. When you select a 
range in the Priority ranges section (for example “Range 192‐255”), the other 
sections (Level to Acknowledge and Annunciation) display the current settings 
for that range. You can proceed to modify any of these settings for the specified 
range. (Your changes affect only the currently selected priority range.)
Click New to add a new priority range. In the Priority dialog box, type a 
number representing the lower limit of the new range then click OK. The upper 
limit of the new range is automatically defined by the lower limit of the existing 
range. For example, if you have an existing range of 128‐191, you can type 100 
then click OK and the range 100‐127 appears. To delete an existing range, select 
it and click Delete.
The Level to acknowledge list specifies the access level required to 
acknowledge alarms in the selected range.
Annunciation lets you customize the way Vista annunciates an alarm:
Select Beep to play a beeping sound.
Select Flash to have a flashing display.
Select Command line to have Vista to automatically launch another 
application in the event of an alarm. Type the programʹs executable (.exe) 
command into the field provided or click Browse to locate the appropriate 
file. This option can be used to automatically alert other users of specific 
events through paging systems, fax transmissions, or any other command 
line capable application.
Select Message box to display an annunciation message. When you select 
this option, type your message into the field provided. The first line of text 
appears as the title of the message box and the remaining text appears as the 
content of the message box.
By default, Vista uses a beeping sound to annunciate an event with a priority 
between 128‐191 and a beeping sound combined with a flashing display to 
annunciate an event with a priority between 192‐255.

NOTE
If your computer is equipped with a sound card, you can replace the default alarm sound with a custom
sound. Save the sound file you want to use as “alarm.wav” and store it in the ..\ION Enterprise\system\etc
directory.

© 2009 Schneider Electric. All rights reserved. Page 145


Linking a Diagram Object to a Data Source PowerLogic ION Enterprise User Guide

Linking a Diagram Object to a Data Source


After placing an object in your user diagram, you need to link the object to a data 
source. Some types of diagram objects require a real‐time data source and others 
require a logged data source:
Numeric, status, and control objects require a real‐time data source. You can link 
these diagram objects to a device.
Event Log Viewers and Data Log Viewers require a logged data source. You can 
link these diagram objects to any log in your system.

Linking a Numeric, Status or Control Object


This section describes how to link a numeric, status, or control object to a node. 
Numeric, status, and control objects display real‐time data. After you have placed 
one of these objects into a user diagram, you should link it to a real‐time data 
source. An object cannot receive or display information until it is linked.

Specifying a Real-Time Link to a Node


1. Right‐click on the diagram object you want to link. The Configuration dialog 
box appears.
2. Select the Link tab.
The Link tab contains two sections: Link and Label. Use the Label section to 
define a label for the diagram object (see “Link Options” on page 135 for 
information on the Label section) and use the Link section to choose a real‐time 
source.
3. Select one of the following:
Inherit from parent window: The selected diagram object defaults to the 
same node used by the parent window (the window in which the object 
resides). You must specify a real‐time register within the node, but the node 
itself is pre‐selected.
Custom: Allows you to select a new node. Select ION to choose a different 
device than that used by the parent window. 
4. Click Edit Link. The Create Link dialog box appears. 
5. Specify a node, manager, module and output register.
Double‐click the node in the Nodes box that contains the data source you want. 
If you chose Inherit from parent window in step 3, the node is preselected.
Double‐click the manager you want (e.g., Power Meter modules) from the 
Managers box.
Double‐click the module you want from the Modules box (e.g., Power Meter).
Double‐click the output register you want from the Output Registers box 
(e.g.,Vll avg).

Page 146 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Linking a Diagram Object to a Data Source

6. Click OK in the Create Link dialog box to save your changes.
The Create Link dialog box disappears and the new link information is 
displayed along the lower edge of the Configuration dialog box.
7. Click OK on the Configuration dialog box to save your new configuration.

Linking a Data Log Viewer or Event Log Viewer


The Event Log Viewer and Data Log Viewer display logged data. After you have 
placed an Event Log Viewer or Data Log Viewer object into a user diagram, you 
need to link it to the ION Query Service.

Linking a Diagram Object to the ION Query Service


1. Right‐click on the Event or Data Log Viewer object you want to link.
2. Select the Query Server tab in the Configuration dialog box. 
The Query Server tab has two options:
Select Inherit from parent window to have the selected diagram object 
default to the same Query Server used by the parent window (the window 
in which the object resides). If you select this option, click OK to exit, skip 
the following steps, and continue with “Querying the Database” on 
page 148.
Select Custom Query Server and click Edit Link to display a dialog box 
where you can select a new Query Server link.
3. Select Custom Query Server and click Edit Link. The Create Link dialog box 
appears. 
Use this dialog box to specify the Query Server, Query Manager, Query 
module, and Query register. 
Double‐click on the Query Server that you want from the Nodes box.
Double‐click Query Modules from the Managers box.
Double‐click on the Query module that you want from the Modules box.
Double‐click on the Query Register that you want from the Output Registers 
box.
4. Click OK on the Create Link dialog box to save your changes.
The name of the selected ION Query Service is displayed as the Group Name on 
the Query Server tab of the Configuration dialog box.
5. Click OK on the Configuration dialog box to accept your new configuration.

After you have linked a diagram object to a log server, you need to define a query 
to specify the type(s) of logged data that you want the object to display. See 
“Querying the Database” on page 148 for more information.

NOTE
If the Query Server has multiple Query modules that are accessing multiple databases, you need to select
the Query module that is connected to the database that contains the data of interest.

© 2009 Schneider Electric. All rights reserved. Page 147


Querying the Database PowerLogic ION Enterprise User Guide

Querying the Database


The Data Log Viewer, the Event Log Viewer and the Global Event Log Viewer 
query the database, extract logged data, and display that data in Vista.

A query is a set of instructions that the log viewer uses to request particular data 
from the database. Each log viewer has its own individual query. Editing this 
query information changes what data the query retrieves and the way a log viewer 
displays that data.

Right‐click on the data or event log viewer object and select the Query tab to view 
the query options or access the Query Wizard. Use the query options to define the 
way a viewer displays data and the Query Wizard to edit the actual query.

NOTE
Anytime you place and link a new Data Log Viewer or Event Log Viewer, you need to specify a query for
it. You can specify a query using the Query Wizard.

Using the Query Options


To define the way a log viewer displays information, configure its query options.

To view the query options for an Event Log Viewer, Data Log Viewer, or Global 
Event Log Viewer, right‐click on the viewer object. The Configuration dialog box 
appears. Select the Query tab.

The upper section of the Query tab offers two buttons:
Edit Query starts the Query Wizard, a user‐friendly interface that helps you edit 
the query.
Edit SQL accesses the SQL statement via Windows Notepad so you can edit the 
query directly using SQL, if preferred.

NOTE
If you edit a query directly (i.e., by editing the SQL statement), your changes may not be accessible to the
Query Wizard. This is not a problem unless you intend to use the Query Wizard as well.

The Options section of the Query tab offers the following options:
Records uploaded at a time: This option specifies the number of records Vista 
uploads into active memory (RAM) when you first open a Data or Event Log 
Viewer. The maximum value is 9999. As you scroll down the list of records, Vista 
uploads additional records as needed. You may want to change this default 
value if, for example, you want to select a large number of records for plotting, 
without scrolling down repeatedly.

Page 148 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Using the Query Options

Update automatically: This option is disabled (cleared) by default. The Data or 
Event Log Viewer does not display any new records; rather, the Log Viewer 
initially uploads the specified number of records (for example 100) and does not 
update again unless it is closed (and its query results deleted) then reopened.
With this option selected, the Log Viewer continually receives and displays 
new records up to a maximum of 1000 records; the Log Viewer checks for new 
records every 20 seconds. However, the updates can consume a noticeable 
amount of CPU power, especially if several Log Viewers remain open 
simultaneously or if Log Viewers are uploading waveform data.
The Global Event Log Viewer is hard‐coded to update automatically every 10 
seconds. This prevents you from missing alarms.
Delete query on close: This option is enabled (selected) by default. The Log 
Viewer clears its temporary records from active memory (RAM) upon closing so 
that every time a Log Viewer is opened, the database is queried again and all 
available records are displayed. (This option does not affect any original records 
stored in the database.)
If this option is disabled, Vista caches the record set returned to the Log Viewer, 
meaning that if the Log Viewer is closed then reopened, the table is populated 
from memory and not from the database. Any new records inserted into the 
database during the time the Log Viewer was initially open do not appear.

NOTE
Since it is recommended that Update automatically remain disabled in all but the most compelling
circumstances, it is important that the Delete query on close option remains enabled.

Use parent node: With this option selected, the log viewer uses the same node 
linkage as the parent window. The node is also pre‐selected in the Query Wizard 
‐ you should not select this option if you intend to query more than one node or 
query the global event log.

X-Parameter for Log View Plotter


For a Data Log Viewer, the X‐Parameter for Log View Plotter section is offered at 
the bottom of the Query tab. Use this section to specify a column to be used on the 
X‐axis of the Log View Plotter. This section offers two options:
Timestamp is selected as the X‐parameter by default. In some cases, you may 
need to specify a different X‐parameter. For example, when you are plotting 
disturbances, you need to plot your data against the Duration column.
Use column # lets you specify a new x‐parameter. In the field provided, type the 
column number that you want to use as the X‐parameter (e.g., 3). When you 
click OK on the Data Log Viewer Configuration box, the specified column 
changes to blue.

NOTE
In the Data Log Viewer, the column specified for the X-parameter is colored blue for easy identification.

© 2009 Schneider Electric. All rights reserved. Page 149


Using the Query Wizard PowerLogic ION Enterprise User Guide

Using the Query Wizard


The Query Wizard helps you edit an existing query or create a new query for a 
Data Log Viewer, Event Log Viewer, or Global Event Log Viewer.
1. Right‐click on the log viewer that you want to configure.
2. Select the Query tab in the Configuration box.
3. Click Edit Query. The Query Wizard appears.
The Query Wizard consists of four steps designed to guide you through the 
process of editing a query. These steps are described in more detail in the 
following sections.
Selecting the node(s) to query.
Specifying logs within the specified node(s).
Specifying columns and specifying filters.
Choosing a sort order.
Depending on the type of query (new or existing), you may not need to perform 
all four steps. When you start the Query Wizard, it automatically opens on the 
appropriate step in the process.
4. Use the four buttons at the bottom of the Query Wizard to move through or exit 
the Query Wizard:
Use the Back and Next buttons to navigate through the dialog boxes.
Click Cancel to quit the Query Wizard and discard your changes.
Click Finish to quit the Query Wizard and save your changes.
5. When finished, click OK to save your changes and close the viewer 
configuration box.
The following example describes each step in the process of creating a typical 
query: configuring a Data Log Viewer to display waveforms for three phases (V1, 
V2, V3).

Step 1: Selecting the node(s)


The Available list displays the available nodes (device or software) and the 
Selected list displays the currently selected nodes.

Select a node (or nodes) for your query. If a node has already been specified or you 
select Use Parent Node on the Query tab, the Query Wizard proceeds directly to 
Step 2: Specifying logs.
1. Click Edit Query on the Query tab of the Log Viewer Configuration dialog box 
to start the Query Wizard.
2. Highlight the name of the node that you want from the Available list and click 
Add. The node appears in the Selected list. Repeat this procedure to add 
additional nodes for this query, if required.
If you want to remove a node from the Selected list, highlight the node and click 
Remove. The node disappears from the Selected list.
3. Click Next to continue.

Page 150 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Using the Query Wizard

NOTE
If you want to view or edit a node's SQL statement directly, highlight the node in the Selected list and click
the SQL button. The Windows Notepad displays the SQL statement for the specified node.

Step 2: Specifying logs


Specify one or more data logs to query. If a valid query has already been specified, 
the Query Wizard proceeds directly to Step 3: Specifying columns.

The Available list displays the logs available on the specified node. The Selected 
list displays the currently selected logs.
1. Highlight the name of the log(s) that you want from the Available list and click 
Add. The log(s) appears in the Selected list.

NOTE
Check for additional tabs. If you selected more than one node in step 1, this box requires you to specify
logs for each node. Each tab is labeled “Node 1,” “Node 2,” etc. and is identified at the top of each tab.
Select “Advanced log view” to access any logs whose configuration has changed over time. This check
box enables access to old configurations of snapshot logs.

2. Click Next to continue.

Step 3: Specifying Columns and Filters


Choose columns and specify filter settings.

Use the Select the columns to appear in the Log Viewer section to add or remove 
a column from your log viewer and the Filter section to establish a range for your 
query and to screen out unwanted data.

© 2009 Schneider Electric. All rights reserved. Page 151


Using the Query Wizard PowerLogic ION Enterprise User Guide

If you selected multiple logs in step 2, this box contains a tab for each log. Specify 
the column and filter information for each tab.

Specifying Columns to Appear in the Log Viewer


The Available list displays the available columns and the Selected list displays the 
currently selected columns. The Selected list displays the columns in the same 
order (left to right) that they will appear in the log viewer (top to bottom).

To specify the columns to appear in the Log Viewer: 
1. Highlight the name of the column(s) you want then click Add. The column(s) 
appears in the Selected list.
Select the asterisk (*) at the top of the Available list to select all available 
columns. 
For example, if you want to select some basic columns for the first waveform log 
you chose in the last step, you could highlight timestamp, node, and V1 in the 
Available list.

NOTE
The * column option shows all inputs connected to a recorder for Data Log Viewers. For example, use the
* option if you are using a framework and the configuration of the data log is different for several meters.
The * option is not available if more than one table is selected, as in the example. To support alarm
annunciation, an Event Log Viewer requires the following three columns: priority, ack_time and recordID.

2. Repeat this procedure for each column that you want (and for each tab).

3. Adjust the order of the items in the Selected column—highlight the column 
name you want to move in the Selected (in order) list then click the up or down 
arrows to move it. The columns are listed from top to bottom in the order they 
will appear from left to right.

For example, if you want the Timestamp column to be the first (leftmost) column 
in your log viewer, highlight “timestamp” in the Selected (in order) section then 
click the up arrow to move it to the top of the list. 
After you have selected the columns you want, proceed to specify filter settings.

Specifying a Filter
Use the Filter section to construct one or more filter statements for your log viewer. 
Filters are useful for restricting the scope of your query or specifying a priority 
range for alarms.

To edit an existing filter statement, double‐click on it.

Page 152 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Using the Query Wizard

Select a column Select an operator Select a value

Click here to replace the


selected filter statement Select an additional
with a new one value
Click here to add
Click here to insert the brackets to your
new filter statement into filter statement
the box below
Use the AND/OR/NOT
Click here to delete the buttons to string filter
selected filter statement statements together
from the box below

For example, if you want to instruct the log viewer to display data for the past 
month (excluding today), you could use the following procedure:
1. In the first box, select “timestamp”.
2. In the second box, select “BETWEEN”.
3. In the third box, select “last_month_to_date()”.
4. In the fourth box, select “today_12AM()”.
5. Click Insert.
The following filter appears in the box below the filter controls:
“timestamp” BETWEEN last_month_to_date() and today_12AM()

NOTE
When setting priorities for a Global Event Log Viewer, specify high priorities to prevent the viewer from
filling up with low-priority events.

If you wanted to instruct an Event Log Viewer to display only unacknowledged 
alarms, create a filter that only displays alarms that have no acknowledgement 
time (ack‐time).
1. In the first box, select “ack‐time”
2. In the second box, select “IS NULL”
3. Click Insert.
The following filter appears in the box below the filter controls:
“ack_time” IS NULL
As you construct a filter statement, each field offers options based on your 
selection in the previous field(s). For example, if you select “priority” in the first 
field, the third field becomes a text field where you can type a numeric value; if you 
select “timestamp” in the first field, the third field displays time‐based options 
(i.e., now, today 12AM, yesterday, etc.). 

© 2009 Schneider Electric. All rights reserved. Page 153


Using the Query Wizard PowerLogic ION Enterprise User Guide

Time-related functions

now_() The current time.

today_12AM() Today at 00:00:00.

yesterday() Yesterday at 00:00:00.


last_week() Seven days ago at 00:00:00.

this_month() The first day of this month at 00:00:00.

last_month_to_date() The same date of the month one calendar month ago at 00:00:00.

last_month() The first day of the last calendar month at 00:00:00.

last_quarter_to_date() The first day of the month three calendar months ago at 00:00:00.

The second field offers a standard set of operators. 

Operator-Specific Data
If you select an operator that requires additional information, Vista displays a 
dialog box where you can specify the required data.

For example, if you select the “node” column in the first field then select the “IN” 
operator from the second field, a dialog box appears requesting that you specify 
the node you want to use. 

If you specify any column other than “node” then select “IN”, a box appears 
requesting numeric values.

After you have specified a filter, click Next to continue.

Step 4: Choosing a Sort Order


Specify a sort order. The sort order is the order in which records appear in the 
viewer.
1. Highlight the name of the column to sort by in the Available Columns list then 
click Add. The column appears in the Sort Order list.
Available Columns displays the columns you chose in step 3. 
2. Double‐click on the column in the Sort Order list to select either an ascending or 
descending sort order.
The Sort Order list displays the column(s) that dictate the order in which the 
records are sorted.
3. Click Finish to save your changes and quit the Query Wizard.
4. Click OK in the Configuration box to save your changes.

Page 154 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Customizing a Diagram Window

Customizing a Diagram Window


You can customize the appearance and configuration of any window within a user 
diagram. You can customize a windowʹs font or background color, or configure 
window properties such as background image, real‐time and logged data links, 
double‐click action, and stale data settings.

In many cases, Vista uses the properties specified for the parent window as the 
default settings for any diagram objects or grouping windows contained within. 
By modifying a setting in the parent window, you automatically modify the same 
property on all objects inside the window that share this setting. (For example, any 
object with an option set to Inherit from parent window shares this information.) 
This can be useful when adding multiple diagram objects that are all linked to the 
same source.

To access any of these options, right‐click anywhere in the background of the user 
diagram or window that you want to customize.

NOTE
Right-clicking in the background of a window displays a pop-up menu of available options; however,
right-clicking on any object in the window while in Edit mode (including transparent objects such as text
boxes or grouping windows) displays the configuration options for that object.

Default Font
The font you select becomes the default setting for all captions and text labels 
within the window.

Changing the Default Font


1. Right‐click in the background of a user diagram and select Default Font. The 
Font dialog box appears.
2. Set the default font, style, size, effects, color, and format that you want.
3. Click OK to save your changes.

Background Color
The default background color is gray. However, you can display any solid color as 
a background for any window in your user diagram.

Changing the Background Color


1. Right‐click in the background of a user diagram and select Background Color. 
The Color dialog box appears 
2. Select the color that you want or click Define Custom Colors for more options.
3. Click OK to save your changes.

© 2009 Schneider Electric. All rights reserved. Page 155


Configuring Window Properties PowerLogic ION Enterprise User Guide

Configuring Window Properties


To view the Window Properties Configuration options, right‐click in the 
background of any window in your user diagram and select Properties. 

The Window Properties Configuration dialog box appears with five option tabs: 
Image, Query Server, Node, Action and Updates.

Image: Displaying a Background Image


To view the image options, select the Image tab on the Window Properties 
Configuration dialog box. Use the Image tab to specify a background image for the 
active diagram or grouping window.

The Image tab has two options:
Select None if you do not want to display a background image, or if you prefer 
to display a single color.
Select Custom image to display a background image. Enter the path and 
filename of the image you want to display. Vista supports images saved in the 
following formats: Windows bitmap (.bmp), Windows metafile (.wmf), or 
Windows Enhanced metafile (.emf).
You can create your own background image using a scanned photograph or a 
drawing created within a standard graphics program. Some ideas include:
An engineering drawing of your installation depicting the power distribution 
system and the location of critical elements.
A single line diagram illustrating the power distribution network or the 
individual components of your facility.
An aerial photograph of your facility depicting the approximate location of your 
monitoring equipment.
A satellite image or geographical map depicting your transmission and 
distribution network.

The following illustration depicts a sample Vista background with hidden 
diagram objects (here the object is visible by the handles because it is selected in 
Edit mode): 

Page 156 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Configuring Window Properties

You can integrate your diagram objects into the image by placing them at the 
appropriate points on the drawing. Users then display site‐specific information by 
clicking on the appropriate spot in the background.

Specifying a Custom Background Image


1. Right‐click in the background of the window you want to customize and select 
Properties. The Window Properties Configuration dialog box appears. 
2. Select the Image tab. 
3. Select Custom image and click Browse.
4. Select the image file you want to use and click Open.
5. Click OK to set this image as the background.

Query Server: Setting a Default Query Server for a Window


Use the Query Server tab to specify a logged data source for any window in a user 
diagram. The Query Server that you select provides the default source of logged 
data for all Event Log Viewers, Data Log Viewers and Grouping Objects within the 
window. 

Setting a Default Query Server for a Window


1. Right‐click in the background of the window and select Properties.
2. Click the Query Server tab in the Window Properties Configuration box.
3. Select either Inherit from parent icon or Custom Query Server.
Select Inherit from parent icon for the active window to default to the same 
Query Server used by the parent icon. (The parent icon is the diagram object 
that you clicked to open this window.)
Select Custom Query Server then click Edit Link to display a dialog box 
where you can select a new Query Server link. 
When you click the Edit Link button, the Create Link dialog box appears.

© 2009 Schneider Electric. All rights reserved. Page 157


Configuring Window Properties PowerLogic ION Enterprise User Guide

Use the Create Link dialog box to specify a query:
1. Double‐click on the Query Server that you want from the Nodes box.
2. Double‐click on Query Modules from the Managers box.
3. Double‐click on the Query that you want from the Modules box.
4. Double‐click on the query register that you want from the Output Registers box.
5. Click OK to save your changes.
The name of the selected Query Server and register are displayed as the Group 
Name on the Query Server tab of the Window Properties Configuration box.

Node: Setting the Default Node for a Window


Use the Node tab to specify a real‐time source for any window (or grouping object) 
in a user diagram. The node that you select provides the default source of real‐time 
data for all numeric, status, and control objects within the window. It also is the 
parent node for any Data Log Viewer or Event Log Viewer objects placed in the 
window. 

Setting a Default Node for a Window


1. Right‐click anywhere in the background of the window and select Properties 
from the pop‐up menu. The Window Properties Configuration dialog box 
appears.
2. Select the Node tab.
3. Do one of the following:
Select Inherit from parent icon to use the same node as the parent icon (the 
diagram object you double‐clicked to open the window).
Select Custom to select a different node. Select ION and click Select to 
display the Select Node dialog box. Select a default real‐time source for the 
window from the nodes available.
4. Click OK to save your changes.

Action: Specifying an Action for a Window


You can specify an action for Vista to perform upon opening or closing a particular 
window. For example, if you want Vista to automatically engage a modem tool 
(such as the Connection Manager) every time you open a certain grouping 
window, you can specify the tool as an action.

Specifying an Open or Close Action


1. Right‐click in the background of the user diagram or grouping window then 
select Properties. The Window Properties Configuration dialog box appears.
2. On the Action tab, select Command line on open or Command line on close. 
3. Click Browse. In the Browse dialog box, locate the program you want, select the 
.exe file and click Open.
The specified file and path name appears in the box below the selected option.
4. Click OK to save your changes.

Page 158 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Configuring Window Properties

NOTE
To remove an action, clear the check box beside the option.

Updates: Setting the Time Interval


Data that is not updated is considered stale data. Vista detects stale data as it 
occurs and identifies it with a colored border around the diagram object (the 
default color is yellow). 

On the Updates tab, you can specify how often Vista updates the data displayed 
the interval of time Vista uses to detect stale dataVista. The Updates tab has two 
sections:
Update Period allows you to specify how often data in that window is 
refreshed.
Stale Data allows you to specify whether data is highlighted and how old data 
must be to be considered “stale”.

NOTE
The Update Period and Stale Data settings also apply to WebReach.

Changing the Update and Stale Data Settings


1. Right‐click in the background of the window, select Properties. The Window 
Properties Configuration dialog box appears. Select the Update tab.
2. Enter a numeric value in seconds in the Update data period or Stale data timeout 
fields to set the intervals.
3. Select or clear the Highlight stale data check box to enable or disable checking 
for stale data.
4. Click OK to save your changes.

To change the color of the stale data border, close the Window Properties 
Configuration box, then select Options > Flag Colors. In the Flag Colors box, click 
Edit beside “Stale Flag Color” to display a dialog box where you can select a 
different color.

© 2009 Schneider Electric. All rights reserved. Page 159


Configuring Window Properties PowerLogic ION Enterprise User Guide

Page 160 © 2009 Schneider Electric. All rights reserved.


5 WebReach
WebReach enables ION Enterprise to display Vista user diagrams in a web 
browser. With WebReach, multiple users can access and display network and 
other diagrams created in Vista, without installing additional software.

NOTE
Currently only Microsoft Internet Explorer (version 6.0 and later) is supported by ION Enterprise.

In This Section

“WebReach Support” on page 162
“Displaying Vista User Diagrams Online” on page 163
“Advanced WebReach Configuration” on page 168
“Custom Network Diagram Setup” on page 168
“Troubleshooting” on page 170

© 2009 Schneider Electric. All rights reserved. Page 161


WebReach Support PowerLogic ION Enterprise User Guide

WebReach Support
The WebReach component of ION Enterprise employs a thin client design, 
allowing users to access and display Vista diagrams in a web browser. WebReach 
manages all the necessary data processing and system functions at the server and 
uses XML to process Vista objects and data for display on the web pages. 

Use a web browser from any machine on your network to view the Vista user 
diagrams of devices in your power management system. Objects that can be 
displayed in the web browser include real‐time numeric data, full or partial 
gauges, background graphics or diagrams, and basic views of event, data and 
waveform logs.

Although identical in many ways to Vista, WebReach has certain differences and 
limitations:
AVI objects are not supported; they appear as grey boxes on screen.
The diagram displayed by WebReach are read‐only; control objects such as On/
Off and Trigger switches are disabled.
The time displayed by WebReach is the local time at the web server, not at the 
client computer.

NOTE
To ensure the correct local time is displayed in WebReach, ensure that the following are configured
correctly on the meter: TZ Offset, DST Start, DST End, and DST Offset.

WebReach Installation After ION Enterprise is Installed


WebReach is automatically installed and enabled if IIS (Internet Information 
Services) is detected during the ION Enterprise primary server installation.

To install WebReach after ION Enterprise has already been installed on the 
primary server:
1. Install the IIS Windows component (consult Windows help for more 
information).
2. Open Windows Control Panel and double‐click Add or Remove Programs.
3. Select Change or Remove Programs. Select ION Enterprise, then click Change. 
The InstallShield Wizard starts.
4. Select Modify then click Next.
5. Follow the installer directions to install WebReach.

Page 162 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Preliminary Setup

Preliminary Setup
Before you can see the WebReach pages, a network diagram (“network.dgm”) 
must exist. WebReach processes each element in the network diagram and 
converts them for display in the web browser. The easiest way to create a network 
diagram is to automatically generate it in Vista. 

Generating the Network Diagram Automatically


1. Start Vista.
2. Click File > Generate network diagram.
3. Click File > Save.

WebReach displays this generated network diagram as its home page.

Displaying Vista User Diagrams Online


Use a web browser to view the web version of the network diagram.

From any Internet Explorer Web Browser


1. Start Internet Explorer.
2. In the address field, enter http://ComputerName/Web where ComputerName 
is the server’s computer name or its IP address and Web is the virtual root. If 
you changed the default virtual root, substitute the appropriate value for “Web” 
in the address. For example, if the server’s computer name is Server2, you would 
type http://Workstation2/Web.
The ION Enterprise web interface login appears. 
3. Enter your username and password then click the WebReach tab.
4. The network diagram you created in Vista is displayed. Click an icon to display 
its contents (e.g., meters belonging to that group).

From the Primary Server


1. Launch the ION Enterprise taskpad and click Web Reporter. The web interface 
login appears. 
2. Enter your username and password then click the WebReach tab.

© 2009 Schneider Electric. All rights reserved. Page 163


Viewing Historical (Trend) Data PowerLogic ION Enterprise User Guide

Viewing Historical (Trend) Data


WebReach provides a web‐based graphing utility for viewing historical data. This 
utility allows you to select the date range and the data that you want to view.

Viewing Historical Data Graphically

Click Device Click Change Date Range to


Diagram to return change the range of dates for
to the main device which data is displayed
diagram screen. Select the data you want
to appear in the graph

Click Show
Graph/Show
Table to toggled Click Edit Graph
between graph to change how the
and table views graph is displayed

1. Click the meter icon to open its diagram, then click the link or tab that contains 
the button for the trending information you want to view.
2. Click the Data Log Viewer button   that corresponds to the data log you want 
to view. The date selection screen displays.
3. Select the timeframe for which you want to view data. To specify a date range, 
select “Between these dates” then click the calendar icons  to set a start and 
end date.
4. Click Show Table. The data log screen displays.
5. Select the check boxes for the parameters you want to graph.
6. Click Show Graph.

Page 164 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Viewing Historical (Trend) Data

NOTE
The first time you click Show Graph, you may be prompted to install software from Steema Software SL.
Click Install to install the software and view the graph.

7. Select or clear the check boxes in the legend to show or hide the corresponding 
data in the graph.
8. Manipulate and control the displayed screen by doing the following:
To zoom in on the graph, drag the mouse pointer around the portion you 
want to zoom in on.
To move across the graph, right‐click and drag your mouse in the direction 
you want to move.

NOTE
To return to the original view of the graph, refresh your browser display. Click Show Table to return to
the data table screen.

Editing the Graph


To change the appearance of the graph, click Edit Graph (near the top right corner 
of the screen). The Editing dialog box displays, where you can set parameters that 
change the graph’s appearance. You can also export the graph to various image 
formats and configure options for printing the graph.

RMS Waveform Plotting


WebReach plots the calculated RMS values for waveforms. To show or hide these 
RMS values, select or clear the appropriate box.
 

© 2009 Schneider Electric. All rights reserved. Page 165


Viewing Meter Events PowerLogic ION Enterprise User Guide

Viewing Meter Events


Viewing meter events is similar to viewing historical data.

NOTE
You cannot acknowledge alarms on the screens generated by WebReach since control functions are not
supported.

Viewing the Meter Events


1. Click the meter icon to open its diagram, then click the link or tab that contains 
the Meter events button.
2. Click the Meter events button  . The date selection screen displays.
3. Set the date range, then click Show Table. The Meter events screen displays:

Adding a Global Event Log Viewer


To display the Vista Global Event Log Viewer online, you need to create an Event 
Log Viewer object in the Vista diagram and link it to the Global Event Log. To add 
this object to the home page for WebReach:
1. Open network.dgm in Vista and make sure you are at the top level (i.e., title 
bar displays “User Diagram:network”). Select Options > Show Toolbox to 
switch to Edit mode.
2. Drag an Event Log Viewer object onto the diagram.
3. Right‐click to display its properties.
4. Click the Query tab. Click Edit Query.
5. Select Global, then click Add. Click Next.
6. Select Global Event Log, then click Add. Click Next.
7. In the Available section, select the columns you want to display, then click Add.   
If you want to change to order of selected columns, select the column in the 
Selected section then use the up or down arrow buttons to move it accordingly. 
Click Next.

Page 166 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Stale Data or Error Indicators

8. Select the column you want to assign as the first sorting criteria, then click Add. 
Repeat for the second sorting criteria, and so on. In the Sort Order section, 
double‐click a column to change its sort order (e.g., change from “ascending” to 
“descending”).
9. Click Finish.
10. Click File > Save.

Stale Data or Error Indicators


WebReach uses the Vista stale data settings for its diagrams. Stale data and errors 
are displayed in the web browser as follows:
A yellow border surrounding an object indicates stale data.
An orange border surrounding an object indicates an error in communications, 
security access, configuration, or other system error.

NOTE
See “Identifying Stale Data” on page 96 for information on stale data. Although you can change the stale
and error flag colors in Vista, the color indicators for these flags do not change in WebReach. Contact
Technical Support if you need to change the default WebReach flag colors.

© 2009 Schneider Electric. All rights reserved. Page 167


Advanced WebReach Configuration PowerLogic ION Enterprise User Guide

Advanced WebReach Configuration


This section covers customization and advanced configuration information for 
WebReach and is intended for advanced users only.

CAUTION
If you use Registry Editor incorrectly, you can cause serious problems that may require you to reinstall
your operating system.

Custom Network Diagram Setup


This section describes how to change the default home page that WebReach 
displays.

If you have a custom network diagram on the primary server that you want to use 
instead of the automatically generated network diagram:
1. Start Windows Registry Editor and navigate to:
HKEY_LOCAL_MACHINE\SOFTWARE\Schneider Electric\ION 
Enterprise\6.0\WebReach
2. Right‐click to add a new string value and name it “NetworkDiagram”.
3. Right‐click NetworkDiagram, select Modify, then type the path and name of 
your custom network diagram in the Value data field. 
4. Click OK.

For more information, refer to the NetworkDiagram item in the table under the 
section “WebReach Registry Settings” on page 169. If there is no NetworkDiagram 
entry in the registry, then the default value “x‐pml:/diagrams/ud/network.dgm” is 
used.

The Network Diagram navigation button located on the date range page and the 
results page is automatically updated to link to the custom network diagram you 
specified. However, the Network Diagram button that exists in each meter user 
diagram uses a hard‐coded link to “x‐pml:/diagrams/ud/network.dgm”. Use Vista 
to manually update the Network Diagram link in the meter user diagrams.

Changing the link for the Network Diagram button


1. Start Vista and select Options > Show Toolbox to switch to Edit mode.
2. Right‐click the Back to Network button. The Grouping Object Configuration 
dialog box appears. 
3. Select the Action tab and select Open User Diagram.
4. Click Browse to locate your custom network diagram. Select the diagram 
filename, then click Open.
5. Click OK to save your changes.

Page 168 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide WebReach Registry Settings

WebReach Registry Settings


The registry keys for WebReach are located in 
HKEY_LOCAL_MACHINE\SOFTWARE\Schneider Electric\ION 
Enterprise\6.0\WebReach.

This table lists the default WebReach registry entries and settings:
 

Default Registry Entries Default Setting Description

Timeout period for the autodiagram components to communicate with the device
AutoDiagramTimeout 20000 milliseconds
and determine the appropriate template to open.

Time limit for a diagram subscription to update its timestamp. If the subscription is
ExpireTimeLimit 600 seconds
not updated within this time period, it is considered expired and is removed.

HTTPRefreshInterval 10 seconds The webpage refresh rate.

The name (tag) that the subscription service uses to find WebReach-related
SubscriptionObject pmlitem:webreachstore:
information.

The part of the web address that points to the WebReach-generated Vista
VirtualDirectory ION
diagrams for displaying in the browser.

XMLRefreshInterval 3000 milliseconds The real time data update rate on the webpage.

This table lists the optional registry entries you can set for custom functionality.
 

Optional Registry Entries Default Setting Description

This value specifies the network diagram to display as the homepage for
x-pml:/diagrams/ud/
NetworkDiagram WebReach. The value can be a relative path, such as the default setting, or it can
network.dgm
be an absolute file path (e.g., D:\customdiagrams\ud\networkB.dgm).

This value determines how long WebReach waits for the results of a query to
return from the database before timing out. If this registry entry is not created or
no QueryTimeout value is specified, WebReach times out after 60 seconds.
QueryTimeout See description
This optional registry entry is useful if you know that a query will take more than
60 seconds to return its results and you do not want WebReach to time out before
then. Specify a value that gives you enough time to get your query results.

© 2009 Schneider Electric. All rights reserved. Page 169


Troubleshooting PowerLogic ION Enterprise User Guide

Troubleshooting
WebReach depends on the ION XML Subscription Service and ION XML 
Subscription Store Service to function properly. If you are experiencing difficulties 
with WebReach pages (such as getting an error message when you try to open a 
device diagram), check to make sure these services have been started.

No Real-time Data is Displayed


This may be caused by security settings being reset by a Microsoft Windows 
update. If this is the case, open Internet Explorer, select Tools > Internet Options, 
then click the Security tab. Click the Trusted sites icon, then click Sites. Add the 
WebReach website (i.e., “http://<computer name>/Web ”) to the Trusted sites zone.

“Page cannot be displayed” Error


This may be caused by complex or large queries, such that the results do not arrive 
within the default WebReach timeout setting of 60 seconds. If you suspect this is 
the case, add the custom DWORD registry key “QueryTimeout” and set it to a 
higher decimal value (e.g., “120”).

Tick Labels for Gauges are Unreadable


This may occur if you specify an unsupported font for the Ticks Label Font. To fix 
this, select only TrueType or OpenType fonts in Vista. 

Page 170 © 2009 Schneider Electric. All rights reserved.


6 Web Reporter
You can use the Web Reporter of ION Enterprise to define, generate and manage 
comprehensive reports, based on information contained in your databases. This 
section discusses the elements of reporting in ION Enterprise, such as the default 
report definitions, generating and viewing reports, export formats, and 
subscriptions.

NOTE
SQL Server Reporting Services must be installed before you install ION Enterprise in order for Web
Reporter to be installed. If you installed ION Enterprise with Reporting Services not present and would like
to install Web Reporter, contact Technical Support.

You cannot use reports that were created in earlier versions of ION Enterprise in 
Web Reporter. However, you can still use Reporter, the reporting interface from 
earlier versions of ION Enterprise. For instructions, see “Appendix A: Reporter” 
on page 325.

In This Section

“Introduction” on page 172
“Web Reporter Interface” on page 173
“Default Report Definitions” on page 175
“Creating a New Definition from a Default Report Definition” on page 179
“Generating and Viewing a Report” on page 180
“Entering Report Inputs” on page 180
“Printing a Report” on page 185
“Saving a Report” on page 185
“Exporting a Report” on page 186
“Report Administration” on page 187
“Managing a Report” on page 187
“Sharing a Report” on page 187
“Creating Report Subscriptions” on page 188
“Installing a Report Definition or a Report Pack” on page 191
“Custom Report Definitions” on page 192
“Running the ION Power Quality Aggregation Service Manually” on page 193

© 2009 Schneider Electric. All rights reserved. Page 171


Introduction PowerLogic ION Enterprise User Guide

Introduction
The Web Reporter interface allows you to define and generate reports from 
historical data. You can modify, save and export a report, and create subscriptions 
to saved reports. Users with supervisor‐level access can also install new report 
definitions. 

See “Generating and Viewing a Report” on page 180 for information on generating 
and viewing reports.

NOTE
Currently only Microsoft Internet Explorer (version 6.0 and later) is supported by ION Enterprise.

Web Reporter Terminology


Report Definition: The report definition defines such things as layout, which 
inputs need to be completed to run the report, and what information in the 
database is accessed for that report.
Default Reports: The report definitions included in Web Reporter to address 
common reporting needs.
Report Input Parameters (or Inputs): Parameters that must be entered before a 
report can be generated. Default inputs are included for most of the default 
report definitions.
Report: A report that has been saved with some or all of its input parameters.
Defined Report: A report that has been saved with all of its input parameters 
completed.
Data Access Layer: This provides a consistent way to access database resources 
for advanced users who are creating custom reports. If you are using the default 
reports definitions that come with Web Reporter, this application layer is 
transparent. 

Starting Web Reporter


See “Getting Started” on page 19 for information on starting and logging in to Web 
Reporter. Once you have started and logged in, click the Web Reporter tab.

Reporting Configuration
Use the Reporting Configuration Manager option in the Management Console 
Tools menu to configure options for Web Reporter such as the database to report 
on and subscription delivery options. See “Reporting Configuration Manager” on 
page 61 for more information.

Page 172 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Web Reporter Interface

Web Reporter Interface


There are three main elements of the Reports page interface: report menu bar, 
report selection pane and report display pane.

Menu Bar

Report Parameter
Report Icon Input Area

Report Options

Saved Report Icon

Report Selection Pane Report Display Pane

Menu Bar
The report menu bar contains the following options: File and Help.

File
The File menu has four options:
New allows you to create a new report definition by copying one of the default 
report definition.
Manage brings up the Manage Reports dialog box which allows you to do the 
following:
Select Manage to move, delete, rename or copy a report. See “Managing a 
Report” on page 187.
Select Share to make a report available to individual users and groups. See 
“Sharing a Report” on page 187.
Select Subscribe to schedule a report to be generated and delivered in a 
prescribed manner on a defined schedule. See “Creating Report 
Subscriptions” on page 188.
Save allows you to save the selected report. See “Saving a Report” on page 185 
for more information.
Install Report Definition allows you to upload or update a single report 
definition. See “Installing a Report Definition or a Report Pack” on page 191 for 
more information. 

© 2009 Schneider Electric. All rights reserved. Page 173


Web Reporter Interface PowerLogic ION Enterprise User Guide

Install Report Pack allows you to upload or update a report pack. See 
“Installing a Report Definition or a Report Pack” on page 191 for more 
information.

Help
The Help menu displays the Web Reporter online help.

Report Selection Pane


The report selection pane allows you to select a report to view or generate. Select 
the report you want from the list of available reports and report definitions. The 
report appears in the report display pane.

Report names are preceded by a report icon  . Reports with a white circle in the 
report icon require you to enter at least some of the inputs. Reports with a green 
circle in the report icon have been saved with all of their inputs defined; you do not 
complete any of the inputs before the report is generated.

NOTE
If the report definition you are interested in does not appear in the report selection pane, select Install
Report or Install Report Pack from the File menu to upload the definition.

Report Display Pane


The report display pane is the area where the generated report displays. If the 
report requires that you enter inputs, the report parameter input area displays at 
the top of the pane.

Report Options
This bar, located above a generated report, allows you to:
Create a subscription to the report. See “Adding a Subscription” on page 188 for 
more information. 
Navigate through pages of the report. See “Viewing a Report” on page 184.
Print the report. See “Printing a Report” on page 185.
Export the report in formats such as PDF, Excel, and TIFF. See “Exporting a 
Report” on page 186.

Report Parameter Input Area


This area of the report display pane appears when you select a report that requires 
you to enter inputs. The inputs vary depending on the report selected. See 
“Entering Report Inputs” on page 180 for information on the inputs for default 
reports. 

After generating the report, you can click the “show inputs” or “hide inputs” links 
in the top‐right corner of the report display pane to show or hide the report 
parameter input area.

Page 174 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Report Definitions

Report Definitions
This section outlines the default report definitions included with Web Reporter, 
and how to create a new definition by copying one of the existing default report 
definitions.

Default Report Definitions


The default report definitions are preconfigured for the most common reporting 
needs. The following is a list of the default report definitions supplied: 

100 ms Energy Usage by Shift System Configuration

EN50160 Event History Tabular

EN50160 Mains Signaling IEC61000-4-30 Trend

Energy Cost Load Profile

Energy Period over Period Power Quality

100 ms
Use the 100 ms report definition to create a report of selected 100 ms 
measurements. The report displays timestamped values for each 100 ms 
measurement selected.

EN50160
EN50160 is a set of power quality standards used by certain energy suppliers and 
energy consumers. There are two default report definitions available: EN50160 
and EN50160 Mains Signaling.

The EN50160 definitions use the following types of data from devices: supply 
voltage dips; temporary overvoltages; supply voltage unbalance; harmonic 
voltage; interharmonic voltage; frequency and magnitude; flicker; and short‐ and 
long‐term interruptions.

NOTE
To run EN50160 reports in Web Reporter, the ION Power Quality Aggregation Service must be started.
This service is run by default only on new data. To run the service on pre-existing data, see “Running the
ION Power Quality Aggregation Service Manually” on page 193.

EN50160
Use the EN50160 report definition to create a report containing comprehensive 
analysis of all EN50160 compliance data logged by multiple meters. The 
compliance summary is based on the EN50160 limits for each observation period: 
each default EN50160 measurement indicates a pass or fail on the compliance test 
with a Y (yes) or N (no) respectively.

© 2009 Schneider Electric. All rights reserved. Page 175


Default Report Definitions PowerLogic ION Enterprise User Guide

EN50160 Mains Signaling


Use the EN50160 Mains Signaling report definition to create a report for signal line 
frequency statistics for multiple sources, for each observation period.

Energy Cost
Use the Energy Cost report definition to create a report on energy consumption 
and peak demand levels over a period of time, categorized by time of use. The 
Energy Cost report definition uses energy and demand measurements.

With an Energy Cost report, you can use a time of use (TOU) schedule that you 
define using the Time of Use Editor (see “Time of Use Editor” on page 80) or you 
can set a flat rate in the Set Rates dialog box (see “Entering Report Inputs” on 
page 180).

NOTE
This report is intended to be used for positive power flow applications only (where kW and kVAR are both
positive). Use with bi-directional flow will give incorrect results.

Energy Period over Period


Use the Energy Period over Period report definition to create a report that allows 
you to compare a measurement from multiple devices over specified time periods 
(i.e., this week vs. the same week from the previous month).

Energy Usage by Shift


Use the Energy Usage by Shift report definition to create a report that allows you 
to compare a measurement from multiple devices for specified time periods (or 
shifts). This allows you to compare energy usage between shifts (i.e., 6:00‐1:00 vs. 
1:00 to 8:00).

Event History
Use the Event History report definition to create a report of events or alarms that 
have occurred in the system. It includes the following information on the events: 
timestamp; source name; event description; and event priority.
If no event has occurred that matches the inputs entered when generating the 
report, no data is returned.

IEC61000-4-30
Use the IEC61000‐4‐30 report definition to create a report on IEC61000‐4‐30 
compliance information by observation period (3 second, 10 minute, or 2 hour) for 
one or more sources.

The IEC61000‐4‐30 report definition provides the following types of information: 
voltage profile; THD profile; unbalance profile; flicker profile; frequency profile; 
and summary table.

Page 176 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Default Report Definitions

Load Profile
Use the Load Profile report definition to create a graphical representation of 
demand or load levels over a period of time. The profile shows peak loads — 
points on the graph where peak electricity demand is high. A load trend report can 
be used to analyze the electrical loads at the time of maximum demand. This 
information creates opportunities for developing strategies to improve energy 
management.

The Load Profile report definition uses similar measurements to the Energy Cost 
report definition but does not use a TOU schedule.

Power Quality
Use the Power Quality report definition to create a report that summarize the 
number and severity of voltage sags, swells and transients over a period of time. 
The finished report also includes a graphical representation of the disturbances.

The power quality report allows you to view historical PQ data, aggregated into 
power quality incidents. An incident is a summary, or aggregated event, which 
represents a number of individual events (sags, swells) that was registered by the 
same device in a small window of time. Throughout this section, disturbance refers 
to a sag, swell, or transient event in the Event Log, while incident refers to a group 
(1 or more) of disturbances. 

NOTE
To run power quality reports in Web Reporter, the ION Power Quality Aggregation Service must be
started. This service is run by default only on new data. To run the service on pre-existing data, see
“Running the ION Power Quality Aggregation Service Manually” on page 193.

The generated report displays:
A summary of incidents, incident interval, and number of disturbances. 
The details of the worst disturbances for each power quality incident in the 
report.
Statistics for each power quality incident in the report (for example, first 
timestamp, duration, and the number of transients, sags and swells within the 
incident).

From the report, you can view either details for an incident or waveform details.

PQ Incident Detail
To view details of an incident, click the incident in the First Timestamp column of 
the Statistics table. 

© 2009 Schneider Electric. All rights reserved. Page 177


Default Report Definitions PowerLogic ION Enterprise User Guide

Detailed information about a single power quality incident is displayed, including:
A CBEMA plot containing the power quality disturbances for the selected 
incident.
The timestamps, types, durations, phases and magnitudes of disturbances in the 
selected incident, with the worst event in the selected incident highlighted 
(worst event = largest magnitude x duration).
The power quality settings of the device that registered the disturbance (i.e., sag/
swell limits, transient threshold, etc.).

To return to the PQ Summary report, use the browser’s back button.

PQ Waveform Detail
To view the waveform details of an incident, click the incident in the Time column 
of the Worst Disturbances table.

The waveform details presents all of the waveforms that were recorded for a 
disturbance. It displays a waveform chart along with an optional table with 
waveform values.

The following waveform plots and data are displayed, based on the timestamp 
selected:
A summary waveform plot, displaying a plot of the V1, V2 and V3 waveforms.
An individual waveform plot for each of:
V1 and I1
V2 and I2
V3 and I3
If the source queried has digital input logging enabled over the time interval of 
the waveforms, a waveform showing the digital input status.
The timestamp for the time the waveforms were triggered.
The sampling frequency of the waveforms.

To return to the PQ Summary report, use the browser’s back button.

System Configuration
Use the System Configuration report definition to create a report containing details 
about devices in your network, including: device names and types; 
communications information (i.e., IP address, unit ID, protocol) for devices; sites 
to which devices belong; status of sites (offline or online); and descriptions of the 
devices in the system (if a description was entered in Management Console).

Page 178 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Creating a New Definition from a Default Report Definition

Tabular
Use the Tabular report definition to create a report of data in a tabular format. You 
can create a report with multiple measurements from multiple sources. This data 
can then be exported for use in another program, such as Microsoft Excel.

The generated report contains the following information: source; measurement; 
timestamp; and value.

Trend Report
Use the Trend report definition to create a report that displays trend information 
in a line, column, bar, or pie chart. You select devices and measurements for a 
selected period of time.

You can choose to report on either:
one or more measurements for a single source, or 
a single measurement for multiple sources.

Creating a New Definition from a Default Report Definition


You can create a new report definition by copying one of the existing default 
definitions.

To create a new report definition:
1. Click File > New. The New Report from Definition dialog box appears. Click 
“+” to expand the navigation tree to view the default report definitions. 
2. Select the report definition you want to copy and click Next. 
3. Type a name for the new report definition in the Name field. Select a location for 
the new report definition from the navigation tree, or click New Folder to create 
a new folder.
4. Click Save. The new report definition is added to the report definitions in the 
report selection pane.

© 2009 Schneider Electric. All rights reserved. Page 179


Generating and Viewing a Report PowerLogic ION Enterprise User Guide

Generating and Viewing a Report


This section describes how to generate and view reports.

Report Ownership and Access


Access to a report is user‐specific and can be assigned by a user with supervisor 
level access or the owner of the report. 

The owner of the report is the user who saved the report (see “Saving a Report” on 
page 185).

Entering Report Inputs


Some reports require that you enter inputs, such as the date range of data to be 
included in the report. When this is the case, the report parameter input area 
displays when you select a report from the report selection pane. You must 
complete the necessary inputs before you can generate the report. 

When you display a report that includes inputs, you can display or hide the report 
parameter input area. To do this, click the “show inputs” or “hide inputs” link in 
the top‐right corner of the report display area after the report has generated.

Inputs for Default Report Definitions


The following sections outline the inputs for the default report definitions. The 
inputs available vary depending on the type of report.

Aggregation Interval
This input determines how data is aggregated for the report (i.e., day, week, etc.). 
From the dropdown list, select the aggregation interval that you want to use.

Chart Type
Use the dropdown list to select the type of chart you want to use to display the 
report results (i.e., line, bar, etc.).

Evaluation Limits
Click Configure to configure the EN50160 parameters used in the report. Default 
values are provided based on the EN50160 standard. 

Click the links in the dialog box to access configuration options for various 
measurements included in the report:
Basic Configuration: Type the maximum percentage of intervals in an 
observation period that the component can fail to meet the EN50160 N1 and N2 
requirements before the component is considered non‐compliant. 
Supply Voltage Dips: Type the maximum percentage of intervals in an 
observation period that the RMS value can drop below 90% of the nominal 

Page 180 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Entering Report Inputs

voltage for each duration and depth presented in the dialog box before the 
component is considered non‐compliant.
Short and Long Interruptions: Type the maximum percentage of intervals in an 
observation period that the RMS value can be less that 1% of the nominal voltage 
for the given duration before the component is considered non‐compliant.
Temporary Overvoltages: Type the maximum percentage of intervals in an 
observation period that the RMS value can exceed the nominal voltage by each 
magnitude for each duration presented in the dialog box before the component 
is considered non‐compliant.

NOTE
The EN50160 standard defines the observation period for the above components as one week.

Event Priority
Select the priority level(s) of the alarms or events that you want report on.

Flicker Baseline High


Type the Flicker Baseline High, if the default is not appropriate for your needs.

Flicker Baseline Low


Type the Flicker Baseline Low, if the default is not appropriate for your needs.

Frequency Baseline High


Type the Frequency Baseline High, if the default is not appropriate for your needs.

Incident Interval
Select the incident interval that you want to use in the report (i.e., 20 seconds, 10 
minutes, 1 week).

Include Data Warnings


Select whether or not to show data warnings in the generated report.

Measurement(s) (Reports other than Load Profile)


Use this input to select the measurements you want to include in the report.

Click Select Measurement to display the Source Selector dialog box. Click the “+” 
and “‐” to expand and collapse items in the navigation tree. Click “Select All” or 
“Select None” in the top‐right corner to select or clear all the check boxes. For 
reports where you can select multiple measurements, click the check box beside a 
measurement (or group of measurements) to select it. For reports where you can 
only select a single measurement, click on the measurement name to select it. 

When you are finished selecting measurements, click OK.

Measurements (Load Profile Report)


This input determines whether the report is calculated using demand or power 
measurements. Select either Demand or Power from the dropdown list.

© 2009 Schneider Electric. All rights reserved. Page 181


Entering Report Inputs PowerLogic ION Enterprise User Guide

Nominal Frequency
Type the nominal frequency of the system (i.e., 60).

Nominal Voltage
Type the nominal voltage of the system (i.e., 120).

Period
The Period input contains the following fields and dropdown lists:
Timezone: Select whether you want to view timestamps in either Server Local 
Time or UTC (Universal Coordinated Time).
Aggregation Period: Select the block of time for which you want to compare 
data (i.e., day, week).
Comparison Type: Select what period of data you want to compare the selected 
Aggregation Period to (i.e., today vs. the same day from the previous month or 
current month vs. the same month from the previous year). The options vary 
depending on the Aggregation Period selected.
Number of Comparisons: Enter the number of periods you want to compare.
Aggregation Interval: This input appears when you select Month for the 
Aggregation Period. Select how you want data grouped for the report: by date 
(Day of Month) or the day of the week.
Selected Dates: This box displays the dates of the data that will appear in the 
report based on the options selected.

For example, to compare the selected measurements for the same day of the month 
over the last 12 months, set Aggregation Period to Day, set Comparison Type to 
Today vs. Same Weekday From Previous Month, and enter 12 in the Number of 
Comparisons field.

Rates
Use this input to set up parameters for energy cost reporting. Click Configure 
Rates to access the Energy Rates dialog box.
Click Energy and Demand to configure basic rate parameters for the report. 
In the Select Measurements section, click the check box beside a 
measurement to include it in the report. 
In the Select Billing Calculation section, select Flat Rate or select TOU 
Schedule. If you select TOU Schedule, select a time of use schedule from the 
dropdown list (see “Time of Use Editor” on page 80 for information on 
configuring a time of use schedule). 
In the Set Rates section, enter the rates for the select measurements.
In the Set Demand Calculation section, select the calculation method used to 
determine demand: Independent (peak demand is calculated independently 
for each source) or Coincident (the demand measurements of the sources 
are correlated with the peak demand of the main meter). If you select 
Coincident for the calculation method, click Main Meter to select the source 
to which you want to correlate the demand measurements.
Click Wages to include WAGES (Water, Air, Gas, Electricity, Steam) 
measurements in the report. Click the +/‐ buttons to add or remove 

Page 182 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Entering Report Inputs

measurements. Enter a name for the measurement the click Select Source and 
Select Measurement to select a source and measurement. Enter a rate for the 
measurement in the Rate field.
Click Additional Fees to add additional rate information to the report. Enter a 
name in the Rate Name field and rate information in the Amount field.

Reporting Period
Use this input to select the timeframe for the data you want to view in the report.

Select the reporting period from the dropdown list. Most of the options in the 
timeframe dropdown end on the day that you are running the report. To run a 
report that starts and ends in the past, select Fixed Date. Type a start and end date 
in the date boxes or click the arrows beside the dates to display a pop‐up calendar 
and select a date. Type a time in the time boxes or click the up and down arrows 
beside the time to adjust the hours or minutes up or down.

Select whether you want to view timestamps in either Server Local Time or UTC 
(Universal Coordinated Time).

Sampling Period
Select the sampling period to use for the IEC61000‐4‐30 report: 2 hour, 10 minute 
or 3 second.

Shifts
Use the +/‐ buttons to add additional shifts. For each shift, enter a name and set the 
start and end time for the shift.

To configure a shift that spans midnight, add two shifts and give them the same 
name. For example, to set up a day shift and a night shift, add three shifts: Day 
from 8:00 AM to 8:00 PM, Night from 8:00 PM to 12:00 AM, and Night from 12:00 
AM to 8:00 AM.

Signaling Voltage 1, 2 and 3 Eval Limit [%]


Type the maximum percentage of intervals in an observation period in which the 
mean value of the signaling voltage can exceed the curve defined in the EN50160 
standard before that mains signaling voltage is considered non‐compliant.

Show EN50160 Configuration Parameters


Select whether or not to show the configuration inputs entered in the Configure 
Evaluation Limits dialog box in the report.

Source(s)
Use this input to select the devices you want to include in the report. 

Click Select Sources to display the Source Selector dialog box. From the dropdown 
list, select the way in which you want to display the sources (i.e., device type, 
group name, etc.). Click the “+” and “‐” to expand and collapse items in the 
navigation tree. Click the check box beside a device (or group of devices) to select 
it. Click “Select All” or “Select None” in the top‐right corner to select or clear all 
the check boxes. 

© 2009 Schneider Electric. All rights reserved. Page 183


Saving a Report with its Inputs Defined PowerLogic ION Enterprise User Guide

When you are finished selecting devices, click OK.

THD Baseline
Type the THD Baseline, if the default is not appropriate for your needs.

Title
Type a title for the report in the text box.

Unbalanced Baseline
Type the Unbalanced Baseline, if the default is not appropriate for your needs.

Voltage Baseline
Type the Voltage Baseline, if the default is not appropriate for your needs.

Saving a Report with its Inputs Defined


After you display a report, you can save a version of the report with some or all of 
these inputs included. For example, you may want to always generate an Energy 
Cost report for a certain number of devices for the previous month. When you save 
the report, you can save it with the inputs for the devices and time period 
predefined.

See “Saving a Report” on page 185 for more information.

Generating a Report
To generate a defined report (a report saved with all inputs defined and saved), 
select the report from the report selection pane. The report is generated and 
displayed in the report display pane.

To generate a report from report definition or from a partially defined report:
1. Select the report you want to generate from the report selection pane.
2. Complete the required inputs (see “Entering Report Inputs” on page 180).
3. Click Generate Report. The report displays in the report display pane.

NOTE
Each report icon has a small circle on its lower right corner. If the circle is green, it is a Defined Report—
it has all of its inputs completed. If the circle is white, you need to fill in inputs before you can generate it.

Viewing a Report
After you generate a report, you can do any of the following:

Click   to subscribe to the report. See “Creating Report Subscriptions” on 
page 188.

Page 184 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Printing a Report

Click the forward and backward arrows   to 
navigate through the pages of report (if there are multiple pages).

Print the report  . See “Printing a Report” on page 185.


Export the report as a PDF, Excel, XML, HTML or TIFF file. See “Exporting a 
Report” on page 186.
Click “show inputs” or “hide inputs” to show and hide the report inputs.

Printing a Report
Click the Print button  . The Print dialog box appears. Select the printer from 
the list and configure other options as you require then click OK.

If the report you want to print has multiple columns of data (e.g., if it has multiple 
measurements or multiple sources) in a table, the columns may be printed on 
multiple pages.

NOTE
The first time you print a report, you may be prompted to install an ActiveX control. Click Install to accept
this control.

Saving a Report
To save a report with some or all of its inputs defined:
1. Display a report that has its inputs completely filled in (either select a defined 
report or enter the required inputs and click Generate Report).
2. Click File > Save. The Save Report dialog box appears.
3. Type a name for the report in the Name field.
4. In the location box below the Name field, select the location for the saved report 
or click New Folder to create a new folder for it (note that you cannot nest one 
folder inside another).
5. From the section at the bottom of the dialog box, select the inputs that you want 
to save and deselect those you do not want to save with the report.
You can save a report with only part of its inputs completed. When you generate 
one of these reports, you need to enter information for the inputs that were not 
saved.
6. Click OK. The report is saved with the inputs you have selected.

© 2009 Schneider Electric. All rights reserved. Page 185


Exporting a Report PowerLogic ION Enterprise User Guide

Exporting a Report
You are able to export generated reports in a number of different formats (the 
formats available vary depending on the version of SQL Server you are using):

PDF Creates a PDF of the report that you can view in Adobe Reader.

Creates a version of the report in Excel format that you can view in Microsoft
Excel
Excel.
Creates an XML version of the report that you can view in your browser or other
XML
compatible program.
Creates an HTML version of the report that you can view in your browser or
HTML
other compatible program.

TIFF Creates a TIFF image version of the report.

To export a report, select the format you want from the “Select a format” 
dropdown list. The File Download dialog box appears, asking whether you want 
to save the file or open it (if a compatible program exists on the computer).

If you export a report to PDF or TIFF format that has multiple columns of data (e.g., 
if it has multiple measurements or multiple sources) in a wide table, the columns 
may be appear on multiple pages in the exported file.

Page 186 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Report Administration

Report Administration
The following sections describe the options available in the Manage Reports dialog 
box.

Managing a Report
Use the Manage option in the Manage Reports dialog box to create a new folder, 
delete or rename a folder or report, or move or copy a report from one folder to 
another.

1. Click File > Manage and select the Manage radio control.
2. From the list box, select the report (or folder) that you want to manage.
3. Select one of these options:
New Folder: When the Create New Folder dialog box appears, type the 
name of the new folder and click OK. The new folder appears in the list.
Delete: A prompt appears asking you to confirm the deletion (unless you 
have selected an empty folder—in this case the folder is deleted without 
confirmation). Click OK to delete the report. If there are any subscriptions 
for the report, the prompt informs you of the subscriptions.
Rename: Type the new name in the field at the bottom of the screen. Click 
Update to save the change.
Copy: Select the location where you want to copy the report and click 
Update. The report is copied to that location. The name of the copied report 
is “Copy of <report>”, where <report> is the original report name. 
Move: Select the new location and click Update. The report is moved to the 
new location.

Sharing a Report
Use the Share option on the Manage Reports dialog box to make a report available 
to a user or group. Users with supervisor‐level access can share any report; all 
other users can only share reports that they own.
1. Click File > Manage and select the Share radio control.
2. Select the report that you want to share from the list box.
3. Select the user(s) or group(s) you want to share the report with from the 
Available Users & Groups box, then click the right arrow to move the user(s) or 
group(s) to the Share List. 
To unshare a report, select the users or groups from the Share List and click the 
left arrow.
Select “Order by type” to order the lists alphabetically by group then by user.
4. Click Apply.
The report is available to the users in the Share List.

© 2009 Schneider Electric. All rights reserved. Page 187


Creating Report Subscriptions PowerLogic ION Enterprise User Guide

Creating Report Subscriptions


What is a Subscription?
A subscription is a report which is delivered in a specified manner at a defined 
interval. For example, a subscription can be configured so a report is generated 
monthly and sent via e‐mail to a group of people.

Subscription Configuration
Before configuring certain types of subscriptions, you need to configure reporting 
subscription options such as the SMTP server for email subscriptions or how to 
handle files when report subscriptions are written to a fileshare. See “Reporting 
Configuration” on page 172 for information on configuring these options.

Adding a Subscription
You can only create subscriptions for reports you have access to (see “Sharing a 
Report” on page 187). The report must be a saved report that has all of its inputs 
defined (see “Generating and Viewing a Report” on page 180 and “Saving a 
Report” on page 185).

1. Click File > Manage and select the Subscribe radio control.
2. Select the report to which you want to create a subscription from the list, then 
click Add to add a new subscription. The Add New Subscription dialog box 
appears.
3. Type a name for the subscription in the Name field. This is the name that 
displays in the list of subscriptions.
4. Select the output format.
5. Select a delivery mode:
Email: Click Distribution List. Enter the e‐mail address(es) to which you 
want to send the report and click Add after each address (select an address 
from the list and click Remove to remove it). Click OK when the list is 
complete. In the Add New Subscription dialog box, type the text you want 
in the subject line of the email in the Subject field.
File share: Type the location of the computer and folder where you want the 
report to be saved. You must type the absolute pathname to the folder 
(including the drive letter). The Windows user account “IONUser” must be 
configured with valid credentials to read and write to that fileshare. See you 
system administrator for assistance. To overwrite an existing report (if one 
exists in the folder), select “Overwrite existing file”. To leave an existing file 
in the folder and save the new report with a new name, clear “Overwrite 
existing file”.
Printer: From the dropdown list, select the printer to which you want to 
send the report.

NOTE
For printed subscriptions, the printer must be a local printer on the Primary Server. For information on
setting a network printer as a local printer, consult Microsoft Windows documentation.

Page 188 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Creating Report Subscriptions

6. In the Subscription Schedule section, define the schedule on which you want the 
report to be generated and delivered:
On Alarm: Select this option to configure the subscription to run on an 
alarm. Select the event you want to trigger the subscription from the list. To 
use this option, you must first configure an Event Watcher. See “Event 
Watcher Manager” on page 62 for information on creating an Event 
Watcher.
Once: Select this option to run the report once at the specified day and time. 
Use the arrow beside the Date field to bring up a calendar where you can 
select the date. Type the time into the Time of Day box or use the up/down 
arrows to change the hours and minutes.
Hourly: Select this option to run the report every hour. Select the time from 
the dropdown list (i.e., on the hour, 15 minutes after the hour, etc.).
Daily: Select this option to run the report once per day at the specified time. 
Type the time into the Time of Day box or use the up/down arrows to 
change the hours and minutes.
Weekly: Select this option to run the report once per day at the time and on 
the day of the week that you specify. Select the day from the dropdown list. 
Type the time into the Time of Day box or use the up/down arrows to 
change the hours and minutes.
Monthly — Monthly by Date: Select Monthly then select Monthly by Date 
to run the report on selected dates in the calendar month at a specified time. 
Type the dates in the On calendar day(s) field. Separate multiple dates with 
a comma. To select a range of continguous dates, separate the first and last 
date in the range with a hyphen. For example, to schedule the report to run 
on the 1st, 10th to 15th, and 20th days of the month, type 1, 10‐15, 20. After 
you have entered the dates, type the time into the Time of Day box or use 
the up/down arrows to change the hours and minutes.
Monthly — Monthly by Day: Select Monthly then select Monthly by Day to 
run the report on a specific day of the week in a selected week of the month 
at a specified time. For example, to set the subscription to run on the 
Monday of the last week of the month, select Last and Monday from the 
dropdown lists. Type the time into the Time of Day box or use the up/down 
arrows to change the hours and minutes.
7. Click Test Now to test that the report subscription configuration is functioning.
8. Click Save to save the subscription.
The subscription appears in the list of subscriptions for the selected report.

Subscription Errors and Solutions


Certain warnings may appear when you try to add subscriptions. Depending on 
the situation, you may not be able to add the subscription or you may be able to 
add it but the output will not be delivered successfully.

© 2009 Schneider Electric. All rights reserved. Page 189


Creating Report Subscriptions PowerLogic ION Enterprise User Guide

The following is a list of possible warnings, their cause and solutions.

Warning Cause Solution

The SQL Server Agent (ION) On the Primary Server, click Start > Settings >
SQL Agent service service is not running. Control Panel. Select Administrative Tools,
not started Subscriptions cannot be then select Services. Right-click the SQL Server
delivered. Agent (ION) service and select Start.

The ION Report On the Primary Server, click Start > Settings >
Report Subscription Subscription Service is not Control Panel. select Administrative Tools,
Service not started running. Subscriptions then select Services. Right-click the ION Report
cannot be delivered. Subscription Service and select Start.

On the Primary Server, open the Reporting


“From” e-mail The e-mail “from” address Configuration dialog box in Management
address incorrectly is either not set or has the Console (Tools > Reporting Configuration).
configured wrong configuration. Enter a valid email address. For example,
[email protected].

The file share pathname Enter a valid UNC (Universal Naming


Path syntax invalid
entered is not correct. Convention) pathname.

Page 190 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Installing a Report Definition or a Report Pack

Installing a Report Definition or a Report Pack


Report definitions can be developed by Schneider Electric or any other 
organization skilled at developing content for Microsoft Reporting Services. 
Report packs can only be developed by Schneider Electric. To create report 
definitions, report developers use Microsoft Business Intelligence Studio, which 
comes with SQL Server. 

After a report definition is developed, you can install it. After a report definition is 
installed and access to it is granted, users can begin creating and saving reports 
from that definition.

Report Definition Versus Report Pack


For the purpose of installing report definitions and report packs, a report 
definition is a single .rdl file whereas a report pack includes all files for a complex 
report or series of reports.

Installing or Updating a Report Definition


1. Click File > Install Report Definition. The Install Report Definition dialog 
box appears.
2. Click Browse to navigate to the location of the .rdl file. Select the file and click 
Open then click Install.
For a new report definition, use File > New to add it to the report selection pane.
For an existing report definition, a confirmation message appears, asking if you 
want to update all reports associated with the definition. Click OK to continue.

Installing or Updating a Report Pack


1. To make a report pack available for upload, copy it into the ReportPack 
directory (../ION Enterprise/web/ReportPacks/).
2. Click File > Install Report Pack. The Report Pack Install dialog box appears.
3. Select the report pack that you want to install. Click Install.

© 2009 Schneider Electric. All rights reserved. Page 191


Custom Report Definitions PowerLogic ION Enterprise User Guide

Custom Report Definitions


You can use Microsoft Business Intelligence Studio to create custom report 
definitions.

Custom report definitions should only be created by users with a solid 
understanding of the database access layer, Microsoft Business Intelligence Studio 
and Reporting Services.

Contact Schneider Electric if you require specialized report definitions.

Page 192 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Running the ION Power Quality Aggregation Service Manually

Running the ION Power Quality Aggregation Service


Manually
To run power quality and EN50160 reports in Web Reporter, the ION Power 
Quality Aggregation Service must be started. This service performs calculations 
for these reports.

By default, this service is only run on new data. For pre‐existing data, you must 
run this service manually. 

To run the service manually:
1. Select Start > Run (or press START+R) to display the Windows Run dialog box.
2. Click Browse to navigate to the EventCollector.Cli.exe (located in the ..\..\ION 
Enterprise\system\bin\ folder) then type /a. 
3. Click OK. 
The ION Power Quality Aggregation Service runs in archive mode. This can 
take a significant amount of time.

If you do not want to run the service on pre‐existing data, you can still generate 
power quality reports on that data using Reporter (see “Appendix A: Reporter” on 
page 325 for more information).

© 2009 Schneider Electric. All rights reserved. Page 193


Running the ION Power Quality Aggregation Service Manually PowerLogic ION Enterprise User Guide

Page 194 © 2009 Schneider Electric. All rights reserved.


7 Designer
Use Designer to configure nodes on your network that are based on ION 
Architecture. The node can be a software component or a hardware device.

NOTE
Only nodes based on ION Architecture can be configured using Designer.

Designer’s graphical user interface helps visualize a nodeʹs configuration. You can 
link ION modules together to customize a node for your particular application. 
You can also cut, copy and paste functionality within a single node or between 
different nodes.

For more information on ION Architecture, ION modules or ION registers, see the 
ION Reference. 

In This Section

“Getting Started with Designer” on page 196
“Node Diagrams and the Designer Interface” on page 197
“ION Module Overview” on page 207
“Using ION Modules” on page 209
“Adding a New ION Module” on page 210
“Deleting or Cutting an ION Module” on page 211
“Linking ION Modules” on page 217
“Configuring ION Modules” on page 224
“Copying and Pasting ION Modules” on page 230
“Viewing Output Registers, Setup Registers, and Inputs” on page 239
“Time of Use (TOU) Program Management” on page 241
“Virtual Processor Service” on page 244

© 2009 Schneider Electric. All rights reserved. Page 195


Getting Started with Designer PowerLogic ION Enterprise User Guide

Getting Started with Designer


Designer is a programming tool intended for advanced users only. Familiarity 
with ION architecture is essential, as Designer is based on ION architecture.

The functions used in traditional power monitoring are treated as discrete 
modular objects that can be interconnected and customized. These objects, known 
as ION modules, are the basic building blocks that comprise a node.

Designer is used to make any changes to the operation of an ION‐compliant node. 
ION devices, the Virtual Processor and Log Inserter are all configured using 
Designer.

For those already familiar with Designer, see “Designer Shortcuts” on page 200 for 
a list of the most commonly used commands.

Starting, Logging into and Exiting Designer


To start Designer, use one of the methods outlined in “Starting a Component of 
ION Enterprise” on page 19 or open Management Console and select Tools > 
System > Designer.
For instructions on logging in to Designer, see “Logging into a Component of ION 
Enterprise” on page 19.

For instructions on exiting Designer, see “Ending a Session” on page 19.

Page 196 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Node Diagrams and the Designer Interface

Node Diagrams and the Designer Interface


This section describes the components of the Designer interface and of node 
diagrams.

Workspace with open Core module (indicated Toolbox


node diagram by double border)
Menu bar
Toolbar

Grouping object Shortcut icon Module link Module icon

Status line Time display Progress indicator Communication


status lights

The Designer Interface


The Designer interface consists of a main screen with a title bar, a menu bar, a 
toolbar, a workspace, and a status bar. When in Edit mode, the ION Modules 
toolbox is also displayed.

Title Bar
The title bar displays the name of the program, the user name (for example, 
“guest”) and the name of the active node diagram.

Menu Bar
Below the title bar is the menu bar. Click on a menu name to display a list of 
available commands.

© 2009 Schneider Electric. All rights reserved. Page 197


The Node Diagram PowerLogic ION Enterprise User Guide

Toolbar
The Toolbar offers quick access to the commands used most frequently. Each 
command offered on the toolbar is also available from the menu bar.

Open Reset Module Cut Paste

Save Create a Link Copy Help

When you point at a toolbar button, a description of it appears in the status bar at 
the bottom of the screen and on a small ToolTip beside the button.

Workspace
The main area in the center of the screen is the workspace, where you view and edit 
node diagrams.

Status Bar
The status bar displays status information. The components, from left to right, are:
Status line: Describes any active processes and provides brief descriptions of the 
currently selected command or toolbar button. For example, when you move 
the pointer over a toolbar button or click on a menu name, a brief description of 
the item appears in the status line.
Time display: Displays the current time on the workstation.
Progress indicator: Depicts the progress on an action being performed.
Communication status lights: Indicate if Designer is currently receiving and 
transmitting data on the ION Enterprise network.

The Node Diagram


A node diagram is a graphical representation of an ION‐compliant node. The node 
diagram displays the actual configuration of the node. Module icons represent the 
ION modules in the node, while lines drawn between these module icons show 
links between the ION modules.

In some cases, groups of modules are organized inside grouping windows. When 
closed, a grouping window appears as a grouping object (an icon that looks like a 
folder). Click a group object to open the grouping window that contains the 
module icons.

Using a Node Diagram


The node is graphically displayed as a node diagram in Designer. The node 
diagram contains a number of ION modules, which represent the nodeʹs current 
configuration. You can change the configuration of the node simply by editing its 
node diagram. For example, when you delete a module from a node diagram, the 
module is removed from both the diagram and the node. You can add, configure, 

Page 198 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide The Node Diagram

link and delete modules on the node by making the corresponding changes to the 
module icons in the node diagram. A module’s setup registers can be accessed and 
changed through the module icon.

Use Designer to configure hardware nodes (e.g., ION meters) or software nodes 
(e.g., Virtual Processor or Log Inserter).

Default Node Diagrams in Designer


When a meter is opened in Designer, the default diagrams for the appropriate 
meter and default template are loaded automatically.

Opening a Node Diagram


1. Select File > Open. The Select Node dialog box appears.
2. Select the node you want to open then click OK. 
When you select a node from the list, Designer communicates with the specified 
node and opens the applicable node diagram.

CAUTION
Do not open a node diagram if the node is currently being configured from its front panel.

When Designer loads a node diagram, it compares the diagram with the 
configuration of the node. If there are any discrepancies between the diagram and 
the node, Designer updates the diagram to match the node:
If a diagram depicts a module that does not exist on the node, Designer deletes 
the module icon from the diagram.
If a node contains a module that is not depicted in the diagram, Designer adds 
the module icon to the diagram.
If the links between modules differ from node to diagram, Designer adjusts the 
diagram to match the node.

A node diagram typically does not differ from the nodeʹs true configuration unless 
the nodeʹs configuration was changed through other means (for example, with a 
remote display unit.)

Saving a Node Diagram


Saving a node diagram serves two purposes: it saves your changes to the diagram, 
and applies your changes to the node.
To save the active node diagram, select File > Send & Save.
To save all open node diagrams, select File > Send & Save All.

Closing a Node Diagram


To close the node diagram(s):
Select File > Close to close the active diagram, or
Select File > Close All to close all open diagrams and windows.

© 2009 Schneider Electric. All rights reserved. Page 199


Display Mode versus Edit Mode PowerLogic ION Enterprise User Guide

If you attempt to close a diagram without saving your changes, Designer displays 
a warning with a list of the modules affected.
You can then do one of the following:
Click OK to return to the diagram and save your work before closing the 
diagram.
Click Close Anyway to discard any unsaved changes and close the diagram.

NOTE
If you reopen a diagram containing unsaved changes, Designer may list the unsaved changes as offline
modules.

Display Mode versus Edit Mode


There are two display modes in Designer, which affect how you navigate a node 
diagram. Whether or not the toolbox is shown indicates the mode you are in: if the 
toolbox is open, you are in edit mode; if it is closed, you are in display mode. 

Display mode allows you to view the node diagram without making changes. To 
prevent accidentally moving or deleting modules or links, use Display mode when 
navigating node diagrams. In Display mode, single‐click grouping objects to open 
associated grouping windows.

Edit mode allows you to configure the node and the appearance of the node 
diagram. In Edit mode, double‐click grouping objects to open associated grouping 
windows. Right‐click objects or icons to view configuration options

For more information on the Toolbox, see “Using the ION Modules Toolbox” on 
page 209.

Designer Shortcuts
Designer provides several shortcuts to assist in programming the nodes.

Input Output The following table lists the different mouse and keyboard combinations you can 


perform on a module’s input or output symbols, and their corresponding 
functions:

Action Result

Left-click on input The list of inputs appears - you can select an input and link it to another module's output register

SHIFT + left-click on input The list of inputs appears with the current input values displayed in square brackets

Right-click on input The Delete Links dialog appears - you can break links from this dialog.

SHIFT + right-click on input The Delete Links dialog appears, showing inputs and current input values in square brackets

Left-click on output The list of output registers appears


SHIFT + left-click on output The list of output registers appears with the current register value displayed in square brackets

Page 200 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Designer Icons

Action Result

CTRL + left-click on output The list of setup registers appears - these setup registers can be linked to inputs on other modules

SHIFT + CTRL + left-click on


The list of setup registers appears with the current register settings displayed in square brackets
output

Right-click on output The list of output register owners appears - you can break links from this dialog

CTRL + right-click on output The list of setup register owners appears - you can break links from this dialog

NOTE
To create a shortcut to an ION module, see “Creating a Shortcut to an ION Module” on page 214.

Designer Icons
In each node diagram, Designer uses icons to represent the configuration of the 
node. There are two basic types of icons: module icons and grouping icons.

Module icons represent ION modules located on the node. Grouping icons 
represent a group of module icons.

NOTE
A module icon with a symbol in the lower corner is a shortcut.

Module Icons
All module icons share four common elements: a label, a graphic, an input symbol 
and an output symbol.
 

Label Graphic

Input Symbol Output Symbol

The label displays the name of the module.
The graphic shows a picture to distinguish one type of module from another.
The input and output symbols provide access to the moduleʹs input and output 
registers. Click the left symbol to display a list of inputs; click the right symbol to 
display a list of output registers. See “Linking ION Modules” on page 217 for 
more information.

Module icons with a double border represent core modules; module icons with a 
single border represent standard modules. For more information on core and 
standard modules, see “Core Modules and Standard Modules” on page 208.

© 2009 Schneider Electric. All rights reserved. Page 201


Designer Icons PowerLogic ION Enterprise User Guide

Grouping Icons and Grouping Windows


Grouping icons represent grouping windows. Click a grouping icon (left) to open 
its associated grouping window (right).

A grouping window acts as a folder or sub‐window where you can store icons that 
you want to keep together. For example, you can use grouping windows to group 
module icons by application—a single grouping window may contain all module 
icons required for demand or advanced setup routines.

You can use a grouping window much like a standard window. You can create, 
rename or delete a grouping window; you can move a grouping window within a 
diagram, and you can move a module into or out of a grouping window.

When you finish editing the grouping window, close it to minimize the window to 
its corresponding grouping icon in the node diagram.

Opening a Grouping Window


Click on the grouping icon.

Closing a Grouping Window


Click the Close button  .

Moving Icons into a Grouping Window


To move an icon (or group of icons) to or from an open grouping window, select it 
and drag it to the new location.
1. Click on a grouping icon to open the grouping window.
Drag the grouping window by the title bar and position it so that you can see the 
icon(s) that you want to move.
2. Select the icon(s) you want to move and drag the selection into the grouping 
window.

When you move a linked module icon into a grouping window, the module 
remains linked but any lines that represent links to modules outside the window 
disappear.

Creating a New Grouping Window


To create a new grouping window, drag the grouping object  from the toolbox 
onto the node diagram.

Page 202 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Designer Icons

The ION modules toolbox is a collection of ION modules and generic tools that 
you can add to a node diagram. If the ION modules toolbox is not displayed, select 
Options > Show Toolbox. See “Using the ION Modules Toolbox” on page 209 for 
more information.

When you point to an object in the toolbox, the name of the object is displayed on 
a ToolTip. You can use ToolTips to identify the grouping object in the toolbox. 

Renaming a Grouping Window


When you create a new grouping window, the default name is that of the node 
diagram. To change the name of a grouping window, rename the grouping icon:
1. Right‐click on the grouping icon. The Grouping Object Configuration dialog 
box appears. 
2. Select Use Custom from the Caption section and type the new name into the text 
box. 
3. Click OK.

Changing the Font of a Grouping Window


To change the font, font style and size of a caption:
1. Right‐click on the grouping icon. The Grouping Object Configuration dialog 
box appears. 
2. In the Font section, do one of the following:
To use the font of the parent window, select Inherit from parent window.
To use a different font, select Custom, then click Font. The Font dialog box 
appears. Select the font options you want then click OK to continue.
3. Click OK.

Changing the Position of the Caption


To change the location of the caption:
1. Right‐click on the grouping icon. The Grouping Object Configuration dialog 
box appears. 
2. Select either Top or Bottom in the Position section to specify a caption position 
above or below the grouping icon.
3. Click OK.

Deleting a Grouping Window

NOTE
When you delete a grouping window, any modules inside are deleted as well. Designer warns you before
deleting modules. See “Deleting or Cutting an ION Module” on page 211 for more information on
deleting modules.

1. Select the grouping icon of the window you want to delete. 
2. Press the Delete key. If the grouping window contains modules, Designer 
displays a list of modules that will be deleted.

© 2009 Schneider Electric. All rights reserved. Page 203


Designer Icons PowerLogic ION Enterprise User Guide

Displaying Default or Custom Icon Labels


Module icons can display two types of labels: Default (left) and Custom (right).

Default labels: All modules have a default label. The default label identifies the 
module by type and, if applicable, by number. It appears in node diagrams, user 
diagrams and event logs unless a custom label is available. 
Custom labels: Custom labels are available only if they have been 
preconfigured by a user. A custom label usually identifies a module by its 
function or purpose. Custom labels are useful for describing modules, setup 
registers, output registers, and Boolean ON/OFF conditions. For information on 
adding custom labels, see “Customizing a Module Label” on page 227.

Displaying Default Labels or Custom Labels


Select Options > Show Default Labels to toggle the option on or off.
When Show Default Labels is selected, default labels are displayed.
When Show Default Labels is not selected, custom labels are displayed.

This is a global setting that applies to all node diagrams.

Moving Icons in a Node Diagram


You can move module and grouping icons anywhere in a node diagram. This is 
useful for organizing your diagram (for example, by function or type) so that you 
can easily find a particular module or visualize the workings of your nodeʹs 
configuration. You can move a single icon or group of icons within a single node 
diagram, or into an open grouping window.

NOTE
Moving the icons in a node diagram does not affect the function of the modules or the node in any way.

Moving Icons
1. Select the icon(s) you want to move. 
When a grouping icon is selected, all icons within its grouping window are 
automatically selected as well. 
2. Drag the selected icon(s) to the new location.

NOTE
When selecting a group of icons, you can only choose icons from within the active window.

Page 204 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Designer Icons

Arranging Icons in a Node Diagram


You can use the Align and Grid options in the Layout dialog box to adjust the 
spacing and layout of the module and grouping icons in your node diagram. Use 
the Align option to specify the horizontal and vertical arrangement of the selected 
icons and the Grid option to activate and configure invisible guidelines.

NOTE
Arranging the icons in a node diagram does not affect the function of the modules or the node in any way.

Changing the Order of Layered or Stacked Icons


If an icon appears on top of another icon that you want to bring to the front, select 
the icon that is sitting on top, then click CTRL+K (or click Edit > Send to Back). 

Aligning Icons
The Align tab in the Layout dialog box allows you to specify the horizontal and 
vertical alignment of selected objects.

To align objects:
1. Select the icons that you want to align.
2. Select Edit > Layout. The Layout dialog box appears.
3. Select the Align tab and set the horizontal and vertical alignment of the icons.
The options in each area determine the criteria by which you can align icons. For 
example, if you select Left sides under Horizontal and Space evenly under 
Vertical, Designer aligns all objects in the selection by their left sides (using the 
leftmost object for reference) and distributes them evenly along a vertical axis.
4. Click OK.

Using the Grid


The Grid tab in the Layout dialog box activates and configures an invisible grid. 
Icons placed onto the grid snap to the nearest gridline to help align and space them 
evenly.

To activate or deactivate the grid:
1. Select Edit > Layout. The Layout dialog box appears. 
2. Select the Grid tab.
3. Select one of the following options:
No Grid turns the grid off.
Grid size in pixels activates the grid. Type a number in the Grid size in 
pixels box to specify the size of the grid (distance between grid lines).
4. Click OK to save your changes.

© 2009 Schneider Electric. All rights reserved. Page 205


Designer Windows PowerLogic ION Enterprise User Guide

Designer Windows
To create links between several node diagrams or grouping windows, you need to 
position the open windows so you can see all the modules involved. Use the 
Window menu to organize open windows in the workspace.

Arranging Windows in your Workspace


To arrange windows, do one of the following:
To locate an open window and move it to the foreground, select the Window 
menu and select the window name from the list of open windows.
To arrange all open windows in the workspace, select Window > Arrange All.

Changing a Window’s Background Color


By default, the background color of all windows in a node diagram is light gray. 
To select a new background color for a window:
1. Right‐click on the background of the window and select Background Color. 
The Color dialog box appears. 
2. Select the color you want or click Define Custom Colors for more options.
3. Click OK.

When choosing a background color, consider how the color affects the visibility of 
icons and links. Links, highlights and shadow effects used to depict the various 
states of an ION module may not appear against certain background colors. For 
this reason, you should avoid using certain colors for your background, 
particularly white, dark gray and black.

Changing a Window’s Default Font


You can specify a default font to be used for all module icons, grouping icons and 
text boxes in a window. 
1. Right‐click on the background of the window and select Default Font. The 
Font dialog box appears. 
2. Specify a new default font, size and style.
3. Click OK.

Fonts can also be specified individually for grouping windows and text boxes. See 
“Changing the Font of a Grouping Window” on page 203 and “Changing the Font 
of a Text Box” on page 215 for more information. 

Page 206 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide ION Module Overview

ION Module Overview


After you have opened a node diagram, you can view the node’s configuration or 
edit it by working with its ION modules. As described earlier, each module 
performs a specific function. Using Designer, you can add, remove or link modules 
together to customize the function of the node.

This section explains how to add and remove ION modules from your node 
diagram. It describes the basic types of modules, and explains how you can 
organize your node diagram by grouping modules together, arranging them, and 
labeling them.

For more information on ION modules and architecture, refer to the ION Reference.

Working with ION Modules


The following sections outline some considerations to remember when working 
with ION modules.

Output and Setup Registers


A register is a type of memory bank that stores a moduleʹs linking and 
configuration information. Each module uses two types of registers: output 
registers and setup registers. 

Module Status: Online and Offline


The terms “online” and “offline” describe whether a module is currently active or 
not. A module is described as online when it is functioning normally (monitoring 
its input and updating its output registers). An offline module is inactive.

Anytime you send and save changes to a node, Designer temporarily takes the 
affected modules offline and programs them with your changes. After they have 
been programmed, the modules are then placed back online.

Normally, this is a routine procedure. However, certain circumstances may 
prevent a module from returning online. For example, if the node lacks sufficient 
processing power to operate the module, the module remains offline.

You can easily identify any offline modules: all offline modules are highlighted 
with a red outline. In addition, whenever you open a node diagram, Designer 
displays a list of all offline modules in the node.

NOTE
If you have offline modules in your node, you may be able to put them back online by selecting File >
Send & Save.

© 2009 Schneider Electric. All rights reserved. Page 207


ION Module Overview PowerLogic ION Enterprise User Guide

Module Status: Programmed vs. Pending


The terms “programmed” and “pending” refer to whether or not a moduleʹs 
representation in the node diagram matches the node itself.

Programmed Pending

Programmed: A programmed module is one that is the same both in the node 
diagram and in the node. The links, labels and setup register values in the node 
diagram exactly match those on the node. When you first open a node diagram, 
all the modules appear programmed since they are read directly from the node 
itself and then displayed in the node diagram.
Pending: A pending module is one where changes have been made to the 
module in the node diagram and not yet sent to the node, so the node diagram 
does not match the node. The borders of pending module icons appear as a 
dashed line. 

If you change a module in the node diagram (for example, re‐link it or edit its setup 
registers), it does not match the node until you select File > Send & Save. Until it 
is saved, the edited module is depicted as pending to indicate that it does not 
match the configuration on the node. When you send and save your changes to the 
node, the module becomes programmed.

Core Modules and Standard Modules


There are two basic types of ION modules: core (left) and standard (right).

Core modules are required ION modules that are fundamental to the operation 
of the node. You cannot add or delete core modules and, in some cases, you 
cannot configure them. Core module icons are identified by a double border 
around the edge. The Power Meter module is an example of a core module.
Standard modules are reusable ION modules. Generally, most modules in a 
node are standard modules. You can add or delete standard modules as 
required. Standard modules icons are identified by a single border. The Setpoint 
module is an example of a standard module.

Persistent Modules
Similar to core modules in that they cannot be added or deleted, persistent 
modules are standard modules that have been converted to core modules. These 
modules are created at the factory, and can never be removed from the meter 
frameworks. Persistent modules are represented by icons with single borders.

An example of a persistent module is External Pulse module #1 on the ION8600 
meter. This module pulses when the Demand Reset switch is pressed on the meter.

Page 208 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Using ION Modules

Using ION Modules


You can change the function of a node by editing the appropriate module(s) in the 
node diagram and linking modules together. 

This section describes how to locate an existing module, how to add a new module, 
and how to delete a module. It also explains how to create a shortcut to a module 
and how to view the contents of a module in text format.

After you have located or added the module you want, you can configure it using 
the procedure described in “Linking ION Modules” on page 217.

Using the ION Modules Toolbox


The ION Modules toolbox is a collection of ION modules and generic tools that 
you can add to a node diagram. To display the ION Modules toolbox, select 
Options > Show Toolbox.

The type and quantity of modules offered on the toolbox varies depending on the 
type of node you are configuring; however, the generic tools (the grouping and 
text objects) are available for all nodes.

NOTE
To identify a module in the toolbox, point to it with the mouse—the module type is displayed as a ToolTip
and on the status line at the bottom of the screen.

To add a module to your node diagram (and to the node itself), drag its icon from 
the toolbox into the diagram window.

Opening the ION Modules Toolbox


To open the toolbox, select Options > Show Toolbox.

Closing the ION Modules Toolbox


Click the Close button   or clear Options > Show Toolbox.

© 2009 Schneider Electric. All rights reserved. Page 209


Adding a New ION Module PowerLogic ION Enterprise User Guide

Locating an Existing ION Module


Before you can edit a module, you must first locate it in the node diagram. To find 
a module in a node diagram, you can use the module tray feature of the toolbox.

Locating an Existing Module from the Module Tray


1. To display the module tray, right‐click the toolbox icon for the type of module 
you want to locate. The module tray appears beside the toolbox.

The module tray displays links to all modules of that type that are currently in 
use on the node—for example, in the image above, there are eight Display 
modules in use by the node. To identify a link in the tray, point to it—the 
moduleʹs label is displayed on the status line at the bottom of the screen.
2. To locate a particular module, click its link in the module tray. Designer locates 
the module and displays it in the center of the workspace. If the module is 
located inside a grouping window, Designer opens the window to display the 
module.

TIP
To close the module tray, click on any module icon in the toolbox.

Adding a New ION Module


Most nodes are pre‐programmed at the factory to provide the most commonly 
required functions. However, if the factory default configuration is not 
appropriate for your application, you can add a new module.

Adding a Module on a Node


Drag the icon of the module you want to add from the toolbox onto the node 
diagram.

As you drag the icon, the cursor changes shape to indicate you are placing an 
object.

Designer adds the module and places a pending module icon into the diagram. 
You can then link and configure the module.

See “Linking ION Modules” on page 217 for more information on programming 
modules.

Page 210 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Deleting or Cutting an ION Module

Deleting or Cutting an ION Module


To remove a standard module from a node, delete its icon from the node diagram. 
By removing unnecessary modules from the node, you can free up resources for 
use elsewhere.

NOTE
Each time a module is deleted, all of its output registers, setup registers and input links are deleted as
well. Removing this information from the node affects the operation of any modules that depend on it.
For this reason, you should be aware of all dependent modules (also known as owners) before you delete
anything.

Checking for Dependent Modules


When two linked modules are located in the same window, Designer depicts the 
link as a line that runs from the output register of one module to the input of 
another. You can easily identify the dependent module (or owner) by the line 
running to its input. However, if one of the linked modules is located in a different 
window, the connection is not visible. A more effective way to locate a moduleʹs 
owners is to view the owners of its registers.

Viewing the Owners of a Module's Setup and Output Registers


You can view a registerʹs owners to quickly identify all dependent modules on the 
node. You can determine what purpose the modules serve, and then decide 
whether to delete them or not.
1. Do one of the following:
To view the owners of a module’s output registers, right‐click on the output 
symbol.
To view the owners of a module’s setup registers, hold the CTRL key and 
then right‐click on the output symbol.
The Owners dialog box appears. It lists all of the moduleʹs registers and any 
dependent modules on the node (dependent modules on other nodes are not 
displayed).
2. Click a register in the Registers list to display the owners of that register in the 
Owners list on the right. Owner information includes the module name or label 
and its relevant input. 
3. If necessary, delete the link between a register and one of its owners. Select the 
owner from the Owners list and click Unlink. (See “Deleting Links” on page 222 
for more information on deleting module links.)
4. When you have finished viewing the register owners, click OK.

Viewing Owners on Other Nodes


Displaying a moduleʹs register owners is an effective way to locate dependent 
modules on the selected node but it does not show any dependent modules located 
on another node.

If you remove a module with a dependent module on another node, the dependent 
moduleʹs inputs are not reset. It continues to look for the deleted output register.

© 2009 Schneider Electric. All rights reserved. Page 211


Deleting or Cutting an ION Module PowerLogic ION Enterprise User Guide

If you are not sure whether a module has dependents on other nodes, check with 
the person who programmed them to ensure you do not disrupt the operation of 
any modules on that node. If you still want to remove the module, you may want 
to directly delete the link on the other node first. This ensures that the module is 
not inadvertently linked to the next module to occupy the location of the deleted 
module.

Deleting or Cutting an ION Module


After you have determined that you can safely remove an ION module without 
disrupting other functions, there are two ways to remove it: delete and discard the 
module or cut the module to paste it in another location.
In either case, Designer immediately removes the icon from the node diagram and 
deletes the module from the node. The difference is, when you delete a module, it 
is discarded; when you cut a module, it can be restored (by selecting Edit > Paste).

NOTE
You do not have to select Send & Save Changes to delete a module. Designer immediately removes the
module from both the diagram and the node.

Removing an ION Module from the Node


1. Select the icon(s) of the module(s) you want to remove.
2. Do one of the following:
To cut the module(s) to paste it in another location, select Edit > Cut.
To discard the module(s), press the Delete key.

NOTE
If a module has a dependent module on another node, Designer does NOT alert you of the dependency
when you delete it. Before you delete a module, ensure that you are aware of all links to modules on other
nodes.

Designer displays a summary of the proposed changes.

Page 212 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Viewing a Node or Module as Text

The summary lists all selected modules, and identifies those in the selection that 
will be deleted (including those with dependents on that node) and those that 
will not. Select a module in this list to display any additional information 
available in the field at the bottom of the dialog box.
3. Click OK to remove the selected modules (or Cancel to abort the procedure).
Designer removes the module icon from the node diagram and deletes the 
module from the node itself.

NOTE
If you delete a shortcut icon, the original module is not affected. However, when you delete the original
module, all shortcuts to that module are also deleted.

Viewing a Node or Module as Text


You can use the View Diagram Text command to display as text the complete 
contents of one or more modules or of an entire node. Use this option to view the 
specified information on your screen so you can sort it, perform analysis, create a 
detailed record of your node’s configuration, or print a copy for your records.

1. Select the module(s) that you want to display.

TIP
To select all modules in the node, left-click on the background of the main node window, being careful
not to click on a module icon, then select Edit > Select All.

2. Select Options > View Diagram Text. The Text View screen appears. The text of 
any modules that are offline appears in red.

© 2009 Schneider Electric. All rights reserved. Page 213


Creating a Shortcut to an ION Module PowerLogic ION Enterprise User Guide

The Text View screen offers several ways to view, sort and find information:
In the View dropdown list, select one of two view modes: 
Use Archive to display information useful for archiving the nodeʹs 
configuration. 
Use Diagnostic to display diagnostic information on the selected module(s).
In the Sort by dropdown list, select the criteria by which you want to sort the 
data: 

Archive View Diagnostic View Sorts by

Default Default Module label

Module Class Module Class Type of module

Module Name Module Name Default label

Displays offline modules first followed by online modules.


Module State
Sorts alphabetically within each group.

Displays event driven modules first, then inactive (not


Module Update updating) modules, followed by high-speed (one cycle
Period updates) modules, and finally high-accuracy (one second
updates) modules. Sorts alphabetically within each group

In the Find text field, type a text string and click Find to find that text string in 
the data.

To reset the text view after you have made a configuration change, click Refresh. 
If you want to print a copy of the text view information, click Print. When you are 
finished viewing the text view information, click Close.

Creating a Shortcut to an ION Module


To save time switching between modules in different windows, create a shortcut 
icon in one window that represents the original module in the other window.

A shortcut icon is identified by a  symbol in the lower left corner of a module 
icon.

Creating a Shortcut Icon


Hold down SHIFT+CTRL then drag the module icon(s) to the window where you 
want to place the shortcut(s).

After you have created a shortcut icon, you can use it in the same way you use the 
original module icon. Both icons support the same features. However, if you delete 
the shortcut icon, the original module icon is not deleted; whereas if you delete the 
module icon, it deletes all shortcuts to that module.

NOTE
You cannot create more than one shortcut icon per window for a single module.

Page 214 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Adding a Text Box to a Node Diagram

Adding a Text Box to a Node Diagram


You can place a text box anywhere in a node diagram, and move it or resize it as 
necessary. You can use a text box to describe any process or function in your 
system; for example, you can label individual components of your system or 
display a block of descriptive text or instructions. 

Adding a Text Box


1. Drag a Text Box object ( ) from the toolbox onto the node diagram.
A text box appears in the diagram with the default message: “Your text goes 
here.”
2. Right‐click on the text box to replace the default text with your own text. The 
Text Box Configuration dialog box appears.
3. Select the Edit Text tab, then do one of the following:
To display the name of the node in the text box, select Use Default.
To display your own message, select Use Custom and type your text into 
the field provided.
4. Click OK. The text box displays your specified text.

Resizing a Text Box


To resize a text box:
1. Select the text box.
2. Do one of the following:
To make the object larger or smaller, drag a corner handle.
To stretch the object horizontally or vertically, drag a middle handle.

Changing the Font of a Text Box


The font, size and style of the text used in the text box is based on the default 
setting specified for the active window. If you want to use a different font, you can 
specify a new font for the text box:
1. Right‐click on the text box. The Text Box Configuration dialog box appears.
2. Select the Text tab.
3. In the Font section, do one of the following.
To use the font specified for the parent window, select Inherit from parent 
window.
To use a different font, select Custom, then click Font. The Font dialog box 
appears. Specify a font, style, and size. Click OK to continue.
4. Click OK.

© 2009 Schneider Electric. All rights reserved. Page 215


Adding a Text Box to a Node Diagram PowerLogic ION Enterprise User Guide

Changing the Position of the Text


To change the position of the text in the text box:
1. Right‐click on the text box. The Text Box Configuration dialog box appears. 
2. Select the Text tab.
3. In the Position section, select Left, Center, or Right.
4. Click OK.

Adding a Border or Background Color to a Text Box


To add a border to a text box or change its background color:
1. Right‐click on the text box. The Text Box Configuration dialog box appears. 
2. Select the Box tab.
3. Do one or more of the following:
To add a border, select Show in the Border section and click Color to select a 
border color. 
To set the width of the border, type a border width in the “Width in pixels” 
field in the Border section.
To add a background color, select Custom in the Background Color section 
and click Color to select a background color.
4. Click OK.

Page 216 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Linking ION Modules

Linking ION Modules


Linking ION modules together is the foundation of programming ION‐compliant 
nodes in ION Enterprise. Although an ION module can perform a function in 
isolation, the strength and flexibility of the ION architecture comes from the ability 
to interconnect modules to build more sophisticated functions.

Choosing which ION Modules to Link


The first step in linking modules is to decide which modules you want to use. 
When choosing a module to link, you have two choices: you can add and link a 
new module or you can re‐link an existing module.

In some cases, you may not want to add a new module. For example, if all the 
modules of a particular type are already used, you need to re‐link one of them to 
perform the new function. Most devices are preconfigured at the factory to provide 
common measurements and calculations. If any of these factory defaults are 
unnecessary in your application, you can unlink the modules involved and reuse 
them.

Plan ahead before you add new modules. Unlinked modules are wasted resources.

You may find a linked module that you can use to add a new link, in order to 
augment the function it is performing. For example, if you have a Setpoint module 
that triggers a waveform recording, then later decide to use this trigger to reset a 
counter, you can link that Counter module to the same Setpoint that controls the 
Waveform Recorder module.

Linking ION Modules Graphically


Linking modules graphically means pointing and clicking a module’s input, then 
clicking another module’s output register to link it (note both input and output 
register classes must be compatible). You can use this method to link to modules 
on the same node or to create links across nodes.

You can use the autolinking feature to speed up the process of linking ION 
modules. Typically, linking ION modules involves connecting the output register 
of one module to the input of another. In many cases, only one of the moduleʹs 
inputs have the same register class as the selected output register.

If autolinking is enabled, Designer automatically selects the appropriate input and 
establishes the link. If necessary, it overwrites an existing link. This relieves you 
from having to manually select the input; however, it also prevents you from 
seeing what input you are linking to.

By default, autolinking is disabled. You should only use autolinking if you are 
thoroughly familiar with all the inputs and output registers of the modules you are 
working with to ensure you do not inadvertently create undesirable links.

© 2009 Schneider Electric. All rights reserved. Page 217


Linking ION Modules on the Same Node PowerLogic ION Enterprise User Guide

Enabling Autolinking
To enable autolinking, select Options > Enable Autolinking. A check mark beside 
the option indicates it is selected.

Disabling autolinking
To disable autolinking, clear Options > Enable Autolinking.

Linking ION Modules on the Same Node


If the selected node is a meter such as the ION7650, the process of configuring the 
node primarily involves creating links between modules on that node.

NOTE
To cancel a link-in-progress, click anywhere in the background of the window or press the ESC key.

Linking Modules Using the Point and Click Method


1. To list a moduleʹs output registers, click the output symbol on the right side of 
the module icon. To list the moduleʹs setup registers, hold the CTRL key while 
clicking the output symbol.
Either a pop‐up menu appears or, if the module has many registers, a dialog box 
appears listing the available registers.
2. Select the register you want to link:
In the menu, click the register you want to select. 
In the dialog box, double‐click the register (or click it then click Select).
3. Move the cursor towards the module you want to link to. The cursor changes 
and a dotted line follows it across the node diagram. This indicates you are in 
the process of creating a link and it shows where the connecting line will appear 
in the node diagram.
If you link to a module that is in a different window than the original module 
(either in a different node diagram or grouping window) the dotted line 
disappears but the cursor still indicates that a link is in progress.
If the module you want is obscured by another window, click on the title bar of 
the window containing the module. This brings the window to the foreground 
without canceling the link. (If you click on the background of the window, the 
link is cancelled.)
4. Click the input symbol of the module that you want to link to display the 
moduleʹs inputs. Either a pop‐up menu appears or, if the module has many 
registers, a dialog box appears listing the moduleʹs inputs. 
If the input is already linked, the label of the register it is linked to is displayed 
beside the input. If you select the input, the existing link is overwritten.
The inputs that are of a different class than the selected output register are 
grayed out to indicate you cannot select them.

Page 218 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Linking ION Modules Across Different Nodes

5. Select the input you want to link to:
In the menu, click the register you want to select. 
In the dialog box, double‐click the register (or click it then click Select).
6. Select File > Send & Save to save your changes to the node.

The procedure described above can also be performed in reverse order. You can 
select a moduleʹs input first and then link it to another moduleʹs output register.

Linking Modules with Variable Number of Inputs


Some modules, such as AND/OR modules, Data Recorder modules, and Log 
Acquisition modules have a variable number of inputs. In these cases, when you 
click on the input symbol, the pop‐up menu offers one instance of the variable 
input as well as any fixed inputs the module may have. When linking to one of 
these modules, you can select the NEW Source item to add a new link or you can 
select an existing link and overwrite it.

If the two modules are in the same window, the line remains on the screen to show 
the link between the modules—when you save this change to the node, the line 
changes from a dotted line to a thin black line to indicate that the link is now 
programmed on the node.

Linking ION Modules Across Different Nodes


If the selected node is a software node, such as the Virtual Processor or Log 
Inserter, many of the links you create are to modules on other nodes. When you 
create links across different nodes, it is important to keep track of these links and 
note what modules are dependent on others. This helps you determine what will 
happen if you ever want to delete a module that is linked to a module on another 
node.

NOTE
You cannot link modules on one device to another. For example, you cannot create a link between a
module on an ION7330 to a module on a different ION7330 or to a module on another meter.

1. Open the node diagrams that contain the modules you want to link.
2. Position the diagrams within the workspace so you can see the two modules you 
want to link.
3. In the first node diagram, click on the output symbol of the module icon. A pop‐
up menu or dialog box appears listing the moduleʹs output registers.
4. In the list of output registers, click the register you want. (In the case of the dialog 
box, click a register and then click Select.)
5. Drag the cursor from the first node diagram to the module you want to link to 
in the second node diagram. The dotted line ceases to follow the cursor if it 
crosses the window boundary but the cursor changes to indicate a link is in 
progress.

© 2009 Schneider Electric. All rights reserved. Page 219


Linking ION Modules Using the ION Tree PowerLogic ION Enterprise User Guide

6. Click on the input symbol of the module icon in the second node diagram. A 
pop‐up menu or dialog box appears listing the moduleʹs inputs. Those that are 
of a different class than the selected output register are grayed out to indicate 
you cannot select them.
7. Click the input you want, or in the case of the dialog box, click the input then 
click Select. Designer does not graphically represent links between modules on 
different nodes so you will not see a line connecting the modules.
8. Select File > Send & Save to save your changes to the node.

This procedure can also be performed in reverse order. You can select a moduleʹs 
input first and then link it to another moduleʹs output register.

NOTE
If the input is already linked, the label of the register it is linked to is displayed beside the input. If you
select this input, the existing link is overwritten.

A Note About Performance


While creating links, you may notice the circle at the end of the arrow cursor is 
sometimes black ( ).

This indicates that Designer is in the process of retrieving information about a 
module. You can still click on the inputs or outputs of other modules, but Designer 
aborts the original request. To minimize the amount of communications between 
Designer and the connected nodes, avoid unnecessary clicking on the input and 
output symbols.

If you click on several items in a row, you only see the menu for the last item you 
click; however, Designer initiates many requests for information, which may 
impact its performance.

Linking ION Modules Using the ION Tree


In some cases, you may want to use the ION tree to select the register for linking. 
The ION tree is a hierarchical listing of every node, manager, module, and register 
in the ION Enterprise network. It allows you to select a register on a node without 
opening the node diagram. Generally, you use the ION tree to create links across 
nodes.

The ION tree is also the only way to select registers from devices that are not ION‐
compliant (and use translators to make data available) such as 3000 series meters. 
For example, if you are programming a Virtual Processor node and you want to 
sum data from several 3720 ACMs, you must access the 3720 ACM register via the 
ION tree.

Page 220 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Linking ION Modules Using the ION Tree

Using the ION tree is faster than opening a node diagram. It is useful if you want 
to link to a register on a node whose diagram has not yet been opened. It is also 
useful if you want to link to a register, but you are not acquainted with the 
configuration of the node in which it resides. You can go straight to the register 
without having to navigate through an unfamiliar node diagram. Also, since a 
diagram can only be accessed by one user at a time, you can use the ION tree to 
link to a register on another node where the diagram is already open.

Linking Modules Using the ION Tree


1. Click the input symbol of the module icon. A list of the moduleʹs inputs is 
displayed.
2. In the list of inputs, select the input you want to link.
3. Click the  button in the toolbar. (To link a moduleʹs setup register, hold 
the CTRL key while clicking this button.)

The Create Link dialog box appears, providing access to the ION tree.

4. Specify a node, manager, module and output register: Double‐click the node 
you want in the Nodes box. All managers within the selected node appear in the 
Managers box. You can then double‐click the manager you want, and repeat this 
procedure for the modules and registers.
5. Click OK. The module whose inputs changed appears grayed‐out to indicate it 
is now pending. If both modules are in the same window of the same node 
diagram, a line appears to represent the link.
6. Select File > Send & Save. The new link is established and the module appears 
programmed.
The procedure described above can also be performed in the reverse order. You 
can click the  button first, select an output register, and then click the input 
symbol of a module icon to select one of its inputs.

© 2009 Schneider Electric. All rights reserved. Page 221


Deleting Links PowerLogic ION Enterprise User Guide

Deleting Links
If you want to disassemble a group of linked modules and use them for another 
function, you can delete the links between the modules rather than deleting the 
modules. Designer provides several ways to delete links.

Fixed Links
Most links between standard modules can be deleted. However, some links 
between core modules are fixed and cannot be deleted. These fixed links include:
Data Acquisition module and all Power Meter modules
Data Acquisition module and all FFT modules
FFT module and all Harmonics Analyzer modules
FFT module and all Symmetrical Components modules

If you attempt to delete a fixed link, Designer informs you that the link cannot be 
deleted. 

Deleting Visible Links


If the linked modules are in the same window, simply click on the link line and 
press the Delete key. This is the easiest method as long as you know which output 
register and input are involved. For example, in the image below, the easiest way 
to delete the link is to click on the line joining the Power Meter and the Sliding 
Window Demand module (its color reverses to indicate it is selected) and press 
Delete.

If there are multiple lines between the same modules and you only want to delete 
one of the links, you may want to use the method described in “Deleting Links that 
are Not Visible” on page 222.

Deleting Links that are Not Visible


If you cannot see a line that links the modules (for example, if they are in different 
windows), or you need to know which output registers and which inputs are 
involved, you must use a dialog box to delete the link between modules. You can 
look either at the output register owners of the first module or you can look at the 
inputs of the second module to see what they are linked to, and then delete the link 
from there.

Page 222 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Deleting Links

Deleting a Module's Input Links


Deleting links at a moduleʹs inputs is generally faster than deleting them at the 
moduleʹs output registers because Designer does not need to check the entire node. 
On the other hand, there is less information available if you view input links. All 
you see is the label of the output register that is linked to the input. If this is 
sufficient information, proceed with this method; if not, go to the output registers 
to delete the link.

Viewing a Module's Input Links


1. Right‐click on the input symbol of the module icon. The Delete Links dialog 
box appears.
2. Each input and the label of the output register it is linked to are displayed in the 
dialog box. To delete one or more of these links, select the input and click 
Unlink. The output register label is replaced with dashed lines.
3. When you have unlinked all the registers you need to, click OK.
4. Select Send & Save to unlink the modules on the node.

Deleting a Module's Output Links


You can also delete links from the Register Owners dialog box. This method gives 
you the most information about the link you are deleting (the output register label 
and the input and label of the module it is linked to).

Viewing a Module's Output Links


1. Right‐click on the output symbol side of the module icon. (To list the moduleʹs 
setup registers, hold the CTRL key while right‐clicking on the symbol.) 
The Register Owners dialog box appears. 
2. Select the output register you want from the Registers section. The Owners 
section lists all the module inputs to which the selected register is linked.
3. To delete one or more of these links, select the module input in the Owners list 
box and click Unlink. The input name is replaced with a dashed line.
4. When you have unlinked all of the module inputs you want, click OK.
5. Select Send & Save to unlink the module inputs on the node.

NOTE
Owners that reside on a different node are NOT displayed in this dialog box. If you need to delete a link
between modules on different nodes, use the procedure described in “Deleting a Module's Input Links”
on page 223.

© 2009 Schneider Electric. All rights reserved. Page 223


Configuring ION Modules PowerLogic ION Enterprise User Guide

Configuring ION Modules


After you have placed a module in a node diagram, you can configure the various 
setup parameters of the module. It is not necessary to do this before you link the 
modules but you should ensure the module is set up correctly before sending the 
configuration to the node.

Module setup parameters include the moduleʹs label; its setup registers, labels and 
values; and its output register labels. To access these, right‐click on the symbol in 
the center of the module icon.

The ION Module Setup dialog box appears.

The Setup Registers box lists all the setup registers of the module along with their 
current values or settings.To change any of the settings or assign a custom label to 
a setup register, select the register, then click Modify (or double‐click on the 
register). The Modify Register dialog box appears where you can make 
modifications.

In most cases, configuring a setup register is a simple matter of entering a number, 
entering text, or choosing an option from a list. (To determine the options or ranges 
available for a setup register, refer to the moduleʹs description in the ION 
Reference.)

When you have completed all your modifications to the module, click OK to 
return to the node diagram. The module icon appears pending until you send and 
save your changes.

Page 224 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Configuring ION Modules

Modifying Enumerated, Numeric Bounded, and String Setup


Registers
If the register you have selected is an enumerated, numeric bounded or string 
register, one of the following dialog boxes appear when you click Modify:

Enumerated Registers
To modify an enumerated register, select an option from the Options list.

Numeric Bounded Registers


To modify a numeric bounded register, type a number in the Value box. The 
allowable range is shown under the Value box; you are alerted if you type a 
number outside this range.

To enter a formatted numeric value, click Format. In the Time Interval Value 
dialog box, you can enter the numeric value as a date (offset from Jan 1, 1970) or a 
time interval.

String Registers
To modify a string register, type your text in the String box.

Note that when you click Modify for a string register that is the connection string 
for a Log Acquisition module or Query module, the Modify Database Connection 
Properties dialog box appears:

Modifying Calendar Setup Registers


The ION Scheduler module has a special class of setup register called a calendar 
register. Configuring a calendar register is only necessary for nodes that have a 
Scheduler module. For detailed information on how to configure a calendar 
register, see the description of the Scheduler module in the ION Reference.

© 2009 Schneider Electric. All rights reserved. Page 225


Configuring ION Modules PowerLogic ION Enterprise User Guide

Modifying Address Setup Registers


All Distributed Numeric, Distributed Boolean, and Distributed Pulse modules 
contain an address setup register that references another register. You can specify 
a new value or clear an existing value as required. (Currently, the Virtual Processor 
is the only node offering these types of modules.)

NOTE
Currently, you can only link the address setup register to External Numeric, External Boolean, and
External Pulse registers.

Modifying an Address Setup Register


1. Right‐click on a Distributed Numeric, Distributed Boolean or Distributed 
Pulse. The ION Module Setup dialog box appears.
2. In the Setup Registers section, select a register then click Modify. The Modify 
Address Register dialog box appears.

3. In the Modify Address Register dialog box, double‐click on the node, manager, 
module and output register you want to use. Click OK to continue.
4. In the ION Module Setup dialog box, click OK.

NOTE
You can clear the value of an address setup register. On the Modify Address Register dialog box, select
the Reset Register Value box, and then click OK.

Page 226 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Configuring ION Modules

Parent Module and Shared Setup Registers


Setup registers that are surrounded by asterisks (e.g., “**PM1 PT Sec**”) indicate 
that the module shares its setup registers with another (“parent”) module. An 
example of this is the High‐Speed Power Meter or Meter Units Power Meter 
module (“HS Power Meter”, “MU Power Meter”). They share their setup registers 
with the parent Power Meter module.

If you try to modify a shared setup register, a prompt identifies the register as 
shared and gives the name of the parent module.

Navigate to the parent module and change the setup register there.

Using Custom Labels


You can assign custom labels to modules, setup registers, output registers, and 
Boolean ON/OFF conditions. All modules and registers have a default label and 
this label is what you see in node diagrams, user diagrams and event logs unless 
you specify a custom label. 

Creating custom labels allows you to clearly describe what the module and its 
registers have been set up to do.

However, carefully consider which modules and registers should be assigned 
custom labels. There is a fixed number of labels available, but there are thousands 
of registers you can assign them to. Many of these registers do not benefit from 
custom labels. For example, most setup registers can be left at their default names 
since the only place their names might appear is in the event log.

NOTE
Some devices, such as the ION7300 and ION7700, have a 15-character limit for labels.

Customizing a Module Label


The ION Module Setup dialog box allows you to edit the module label. The 
module label is the text that appears across the top of the module icon in the node 
diagram. It is also the label that is used in event logs and in the dialog box for the 
ION tree.

1. In the ION Module Setup dialog box, do one of the following:
To create a custom label, select Use Custom Label and then type a name for 
the label in the box.
To use the default label, select Use Default Label.
2. Click OK to return to the node diagram.

© 2009 Schneider Electric. All rights reserved. Page 227


Configuring ION Modules PowerLogic ION Enterprise User Guide

Customizing an Output Register Label


By providing a custom label for an output register, you can clearly indicate the 
information that register contains. For example, if you have linked the Vlna output 
register of a Power Meter module to a Thermal Demand module, and in turn 
linked the ThrmDemand output register to a Maximum module, you may want to 
label the Maximum moduleʹs output register as “Va TD Maximum” (instead of 
using the default name of “Maximum 1”).

1. In the ION Module Setup dialog box, select the output register in the Output 
Registers box and then click Modify. The Modify Label dialog box appears.
2. Do one of the following:
To create a custom label, select Use Custom Label and then type a name for 
the label in the box.
To use the default label, select Use Default Label.
3. Click OK to return to the ION Module Setup dialog box.

Customizing Boolean ON/OFF Labels


If the output registers of the module are Boolean, you can create custom labels to 
associate with the ON and OFF conditions of these registers. These labels can 
clarify exactly what the ON or OFF conditions represent. For example, if a Boolean 
output register is used to switch a fan on and off, you could create a Boolean ON 
label called “Fan Running” and an OFF label called “Fan Not Running.”

1. In the ION Module Setup dialog box, select the Boolean output register and 
then click Modify. The Modify Boolean Register dialog box appears.
2. Do one of the following:
To create custom labels, select Use Custom Labels and then type names for 
the Register Label, ON Label and OFF Label in the appropriate boxes.
To use the default labels, select Use Default Labels.
3. Click OK to return to the ION Module Setup dialog box.

Customizing a Setup Register Label


1. In the ION Module Setup dialog box, select the setup register and click 
Modify. 
2. Do one of the following:
To create a custom label, select Use Custom Label and then type a name for 
the label in the box.
To use the default label, select Use Default Label.
3. Click OK to return to the ION Module Setup dialog box.

Resetting ION Modules in a Node Diagram


Designer allows you to undo certain changes you have made in a node diagram 
since the last time you saved and sent your changes to the node. It refreshes the 
selected module icons so they reflect what is actually on the node. Reversible 
changes include:

Page 228 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Configuring ION Modules

Changing the value of a setup register.
Changing module or register labels.
Changing the links between modules.

NOTE
Since adding and deleting modules happens immediately on a node, you cannot undo the deletion or
the creation of a module.

To reset ION Modules:
1. Select the module(s) you want to reset.
2. Select Edit > Reset.

All the changes made to the selected modules since the last time you sent and 
saved the node diagram are discarded. Modules not included in the selection are 
unaffected (that is, if they had pending changes, the changes are still pending.)

Fast-linking ION Modules in the Log Inserter


When linking modules in the Log Inserter, you can save time by using the Fast 
Linker utility. The Fast Linker automates much of the linking process, enabling 
you to quickly link any combination of event, data or waveform recorders. To 
access the Fast Linker options, press the CTRL key and click on the Log Inserter 
inputs.

For more information on using the Fast Linker utility, refer to the description for 
the Log Acquisition module in the ION Reference.

© 2009 Schneider Electric. All rights reserved. Page 229


Copying and Pasting ION Modules PowerLogic ION Enterprise User Guide

Copying and Pasting ION Modules


You can easily create a new function in a node diagram by copying and pasting 
modules. You can copy and paste a single module, a group of modules, grouping 
icons, text objects, or the entire node.

You can copy modules from one node and paste them into another, as long as the 
node you are pasting to supports the selected modules and has sufficient 
resources. When pasting modules, you can replace existing modules or add new 
ones.

You can also copy modules and save them as a framework. You and other users 
can then reuse this framework in other nodes. Saving a nodeʹs configuration as a 
framework provides a fast and easy way to program a large number of nodes at 
once.

NOTE
Persistent modules cannot be deleted, but they can be overwritten during a framework paste. Overwriting
a persistent module effectively relinks its outputs and rewrites its label, but its core functionality remains
intact (e.g., the Master Reset module may be relabelled, but pulsing this module still initiates a master
reset). When pasting a default framework onto a meter, use lock-paste to ensure that all persistent
modules in the "old" default framework are overwritten by the corresponding persistent module in the
"new" default framework. Persistent modules are listed in the "ION Device Template Reference".

Copying Modules
Designer offers two ways to create copies of modules: copy and paste using the 
ION Enterprise clipboard or copy or paste using a framework.

NOTE
The ION Enterprise Clipboard is a temporary storage area that holds any information cut or copied from
Designer. This clipboard should not be confused with the Windows Clipboard.

When you copy a selection of ION modules, you can use Copy, Cut, or Copy to 
Framework: 
Copy saves the selection to the clipboard and leaves the original module(s) 
intact.
Cut saves the selection to the clipboard and removes the original module(s).
Copy to framework saves the selection as a file and leaves the original modules 
intact.

Additional considerations include pasting with shortcuts, modules that cannot be 
pasted, and cloning a node (copying and pasting a complete node configuration 
from one node diagram to another).

Page 230 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Copying and Pasting ION Modules

Cutting or Copying ION Modules to the Clipboard


Use the Cut or Copy command to save a temporary copy of the selected modules 
to the clipboard. You can then use the Paste command to transfer the selection 
from the clipboard into any node diagram. Each copy retains the setup register 
values, custom labels, link information and layout of the original selection.

NOTE
When selecting modules to be cut or copied, you can also include grouping icons and text objects. If you
select a grouping icon, all modules within the group are copied, as well as any nested grouping icons.

1. Select the module(s) you want to cut or copy.
2. Do one of the following:
To cut the selection to the clipboard and remove the original, select Edit > 
Cut.
To copy the selection to the clipboard and retain the original, select Edit > 
Copy.
Designer copies the requested information to the clipboard.
After the selection has been copied to the clipboard, you can select Edit > Paste to 
paste it into any user diagram.

Copying ION Modules to a Framework


You can use the Copy to framework command to create a framework from the 
selected modules. A framework is a template that you can use to reproduce a 
group of modules. Unlike regular copying and pasting, a framework is stored as a 
file so you can paste it later.

When you select Edit > Copy to framework, Designer copies the layout, linking 
and configuration information of each module in the selected group. It saves the 
framework as an .fwn file. You can then use the Paste from framework command 
to paste the group in another node diagram.

You can use frameworks to simplify the process of programming multiple devices 
with similar configurations. For example, if you wanted to program a single 
function into several nodes, you could program the first node and then copy the 
configuration to a framework. You could then quickly program the other nodes by 
simply opening their node diagrams and pasting the framework you created. You 
can also use frameworks to program an entire node at once, considerably reducing 
the amount of time required to set up a large installation.

Before you save a group of modules as a framework, consider carefully which 
modules you want to include. If you include core modules in your framework, you 
will not be able to paste them unless you overwrite the existing core modules that 
correspond to those in your framework. Another approach is to select the modules 
“downstream” of the core module and save them as a framework. Then when you 
paste the framework into another node diagram, you can use the Maintain 
External Inputs option to preserve your links to the original core modules. (See 
“Using the Paste Summary Dialog Box” on page 233 for more information.)

© 2009 Schneider Electric. All rights reserved. Page 231


Copying and Pasting ION Modules PowerLogic ION Enterprise User Guide

NOTE
After you have saved a framework, it can be used in another node diagram, as long as the node supports
the modules included in the framework. Although it is possible to create a framework from one node type
and use it with another node type, it is advisable to restrict your use of frameworks to nodes of the same
type.

Copying a Group of ION Modules to a Framework


1. Select the group of module icons you want to copy.
2. Select Edit > Copy to Framework. The Copy to Framework dialog box appears.
3. In the File Name box, type a name for the framework, then click Save. The 
framework filename extension (.fwn) is added automatically and the selection is 
saved as a framework file.

After you have copied a group to a framework, you can select Edit > Paste from 
framework to paste it into a node diagram.

Pasting ION Modules


You can paste a saved copy of one or more modules into any node diagram. 
Designer offers two ways to paste modules: 
Paste inserts a selection that has been placed on the clipboard using the Cut or 
Copy command
Paste from framework inserts a selection that has been saved as a file. 

Pasting modules is a little more complicated than copying them, because the action 
of adding modules to the node may require you to replace existing modules. 
Whether you choose Paste or Paste from framework, Designer displays a Paste 
Summary dialog box that explains each aspect of the proposed changes.

You can use the Paste Summary box to define how to integrate the source modules 
into the destination modules. For example, if a source module is being pasted to a 
destination that is already occupied, you can either lock paste the new module 
over the existing one or free paste the new module into the next available 
destination.

If you paste a selection that contains a shortcut, Designer may paste the shortcut as 
a module. (See “Pasting Shortcuts” on page 236 for more information.)

In some cases, Designer may not paste every module in your selection. (See 
“Modules that Cannot be Pasted” on page 237 for more information.)

Pasting ION Modules from the Clipboard or a Framework


When pasting modules, the first thing to do is select the node diagram and 
window where you want the modules to go. If you have more than one window 
open, you can click on the title bar of the window you want to make it the active 
window.

Page 232 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Copying and Pasting ION Modules

NOTE
You can paste modules into the same node diagram they were copied from or into a different one.

You can paste modules from two sources: the clipboard or a framework. When you 
paste a selection from either source, Designer describes the proposed changes in 
the Paste Summary dialog box. You can use the Paste Summary box to review your 
changes and make modifications as necessary.

NOTE
The lock paste option in the Paste Summary box instructs Designer to overwrite existing destination
modules as necessary. Use lock paste with caution to avoid accidentally overwriting required modules.
(See “Using the Paste Summary Dialog Box” on page 233 for more information.)

Pasting ION Modules into a Node Diagram


1. Open the window where you want the modules to go. Click in the background 
of the window to clear any selected modules.
2. Do one of the following:
To paste a selection from the clipboard, select Edit > Paste.
To paste a selection from a framework, select Edit > Paste from Framework. 
In the Paste from Framework box, select the file you want and then click 
Open.
3. The Paste Summary dialog box appears. Use the Paste Summary box to review 
the proposed changes (see “Using the Paste Summary Dialog Box”, below, for 
more information). When you are satisfied with the summary, click OK to 
complete the procedure.
The selection is pasted into the active window. The entire selection is automatically 
selected so you can easily move it to a clear area in the window. All module icons 
in the selection appears as pending until you click Send & Save to save the changes 
to the node.

Using the Paste Summary Dialog Box


Before Designer pastes a selection, it displays the Paste Summary dialog box. Use 
the Paste Summary dialog box to review and modify the proposed changes to the 
node diagram.

The Paste Summary dialog box lists each module to be pasted and indicates its 
destination in the node. For each module, this box provides a short summary of the 
proposed modification as well as a more detailed description of how the module 
is pasted or why it cannot be pasted as requested.

© 2009 Schneider Electric. All rights reserved. Page 233


Copying and Pasting ION Modules PowerLogic ION Enterprise User Guide

The following sections describe the various areas of the Paste Summary dialog box.

Source
The Source column lists each module that was copied to the clipboard or 
framework. Each source module is listed by its default label unless a custom label 
has been specified (in which case the default name appears in brackets after the 
label). Select a module in this column to view additional information in the Details 
box at the bottom of the dialog box.

Destination
The Destination column indicates where the copy of each source module will be 
placed in the node diagram. The module label listed in the Destination column 
may or may not match the module label listed in the Source column. (If the 
destination module is to be overwritten, it is reused; otherwise, the next available 
module is used.)

Summary
The Summary column indicates whether the source module is copied into the 
destination as a new module or if it replaces (overwrite) an existing module. This 
column also indicates if a module will not be pasted.

NOTE
You can sort the paste summary information alphabetically by source or destination, or by importance of
summary. Click on the Source, Destination, or Summary column headers to sort the list by the chosen
criteria.

Details
The Details box located at the bottom of the dialog box provides more detail than 
the description in the Summary column. When you click on a module in the Source 
column, you can view a description of the proposed transaction in the Details box. 
This description explains how a module is pasted or offers reasons why it will not 
be pasted.

Page 234 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Copying and Pasting ION Modules

TIP
You can create a copy of the information displayed in the Details section of the Paste Summary box. To
copy it, use the mouse to highlight the text you want, right-click on the selection, then select Copy. You
can then paste this selection into a word-processing program.

Maintain External Inputs


The Maintain External Inputs check box allows you to paste the module selection 
with all external links intact. If this check box is cleared, all external links (links to 
modules outside the selection) are discarded.

The following example depicts an external link to a Power Meter module.

external link

If you copied the two modules on the right but omitted the Power Meter module 
from the selection, the link to the Power Meter module would be external. Upon 
pasting the selection, the external link to this module would be lost unless you 
selected “Maintain external inputs” on the Paste Summary box.

Check Boxes (Free Paste/Lock Paste/No Paste)


The check boxes to the left of each module indicate the proposed action (that is, 
how the module will be pasted):

A green check mark  indicates a free paste.

A check mark with a lock symbol indicates a lock paste.

A red “X” symbol  indicates the module will not be pasted.

An “X” symbol without a check box  identifies a module that has no possible 
destination and cannot be pasted.

You can click on a check box to change the proposed action. For example, if you 
click on a “free paste”  or a “will not be pasted”  symbol, it changes to a “lock 
paste”  symbol. When you change the type of paste, the descriptions in the 
Summary column and the Details box also change to describe the new action. (See 
“Free Paste or Lock Paste?”, below, for more information.)

Free Paste or Lock Paste?


You can use the free paste and lock paste options to instruct Designer how to 
respond to potential conflicts. For example, if you want to paste the module 
“Setpoint 1” into a diagram that already has a “Setpoint 1” module, you have two 
options. You can either add the new module under a new name (for example, 
“Setpoint 2”) or you can overwrite the existing module with the new one and reuse 
the old name.

© 2009 Schneider Electric. All rights reserved. Page 235


Copying and Pasting ION Modules PowerLogic ION Enterprise User Guide

The first option in the above example is a free paste. It can be used to paste new 
modules into a diagram without deleting any existing modules. This is useful for 
integrating new functions into a node without disrupting the nodeʹs existing 
functionality. Although this may seem desirable, it is not always the best option. 
By leaving existing modules intact, a free paste can result in needless duplication 
of functions. In addition, some groups of modules are interdependent and may 
require a lock paste to operate correctly.

The second option in the above example is a lock paste. It instructs Designer to 
recreate the source modules exactly, even if this requires Designer to overwrite 
existing modules in the diagram. When used to quickly replace old modules with 
new ones, lock pasting is an efficient alternative to the time‐consuming process of 
deleting a module, adding a new one and then configuring it. 

You can use a combination of both free paste and lock paste within a single paste 
operation.

NOTE
You can pre-select modules for Designer to reuse when free pasting. In the actual diagram where you
paste the selection, press the SHIFT key and then click on any module icons that you don't want. When
you paste the new selection, Designer has the option of replacing any of the selected modules with the
new ones.

NOTE
Overwriting a module is not the same as deleting the module and then pasting a replacement module.
If a module is overwritten, links from the outputs of that module are retained at the inputs of other
modules. If a module is deleted, these links are also deleted and do not exist after the replacement
module is pasted.

Pasting Shortcuts
Identified by the symbol , a shortcut icon is a representation of a module icon 
that is located in another window.

You can copy a shortcut in the same way you copy the original module, but when 
you paste a shortcut, one of two things happens: It is either pasted as a shortcut to 
an existing module (if one is available) or as a new module. In either case, it 
continues to perform its function as before.

There is a basic reason for replacing a shortcut with a module: a shortcut cannot 
exist in a node without the module it represents. When you paste a selection 
containing a shortcut, Designer searches both the selection to be pasted and the 
destination to locate the module the shortcut represents. If it finds the module, it 
pastes the shortcut as a shortcut. If it doesnʹt find the module, it replaces the 
shortcut with a copy of the module. In this way, Designer ensures that the pasted 
selection is complete and not dependent on a module that is unavailable in the 
destination node.

Designer performs this process automatically; it requires no input from you.

Page 236 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Copying and Pasting ION Modules

Modules that Cannot be Pasted


Some modules cannot be pasted because their settings are non‐transferable 
between nodes. All Factory, Communications, and Diagnostics modules must be 
individually configured for each node.

When pasting a selection that contains a Factory, Communications or Diagnostics 
module, Designer pastes the location of the icons only.

Cloning a Node
You can quickly configure multiple nodes by cloning a node. Essentially, cloning 
a node involves copying a nodeʹs complete configuration to a framework then 
pasting it onto another node. This effectively reprograms the node receiving the 
framework as an exact copy of the original.

NOTE
When you paste an entire node's configuration, the Factory, Communications, and Diagnostics modules
are not pasted because they could disrupt the operation of the device's communications. If you need to
change the settings of these modules, you can do so manually.

Copying a Node's Complete Configuration


1. Open the node diagram of the node you want to copy. Ensure that you are in 
the main or root window of the diagram.
2. Select Edit > Select All. All core modules, standard modules, grouping 
windows and text icons are selected.
3. Select Edit > Copy to framework. The Copy to framework dialog box appears.
4. In the File name box, type a name for the framework and then click Save. The 
framework filename extension (.fwn) is added automatically and the complete 
node configuration is saved in this framework file.
After you have saved the source nodeʹs configuration as a framework, you can 
paste it to other nodes of the same type. This file can also serve as a backup in case 
you want to restore the configuration of the source node.

Pasting a Node's Complete Configuration into Another Node


1. Open the node diagram of the node to which you want to paste the 
configuration. Ensure that you are in the main or root window of the diagram.
2. Select Edit > Select All. Press the Delete key to remove the nodeʹs existing 
configuration. A dialog box appears listing the standard modules that will be 
deleted and the core modules that cannot be deleted. Click OK to continue.
The standard modules and text icons are deleted, and the core modules (and any 
grouping windows containing core modules) remain.
3. Select Edit > Select All to select the remaining module (and grouping) icons.

© 2009 Schneider Electric. All rights reserved. Page 237


Copying and Pasting ION Modules PowerLogic ION Enterprise User Guide

4. Select Edit > Paste from framework. In the Paste from framework dialog box, 
select the framework file that contains the node configuration you want to paste 
and then click Open.
The Paste Summary dialog box appears. (See “Using the Paste Summary Dialog 
Box” on page 233 for information on using the Paste Summary box.)
5. Select all modules in the list (click last item, hold the SHIFT key, and then click 
first list item ‐ the entire list appears highlighted).
6. Change the paste type to lock paste (hold the SHIFT key and then click the paste 
type check box until all modules are set to lock paste ).
7. Click OK to complete the procedure.

The selected framework is pasted into the node diagram. All module icons in the 
selection appear as pending until you select Send & Save to save the changes to 
the node.

Page 238 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Viewing Output Registers, Setup Registers, and Inputs

Viewing Output Registers, Setup Registers, and Inputs


Each module icon has an input symbol and an output symbol. The input symbol 
(on the left) provides access to the moduleʹs inputs and the output symbol (on the 
right) provides access to the moduleʹs output and setup registers.

Input

Output

A register is a type of memory bank that stores a moduleʹs linking and 
configuration information. Each module uses two types of registers:
Output registers store data that has been processed by the module (such as 
numeric values, event log entries, and waveform data). 
Setup registers store the moduleʹs configuration information.

Both types of registers serve as storage locations for the module. 

Viewing Output Register Information


Output register information includes the moduleʹs available output registers, the 
real‐time values of the output registers and the owners of the output registers. 
Each of these can be accessed from the output symbol located on the right side of 
the module icon.

Viewing Available Output Registers


Click the output symbol.

Viewing the Real-time Values of Output Registers


Press the SHIFT key and click the output symbol.

Viewing the Owners of Output Registers


Right‐click the output symbol. This displays an output registerʹs owners so you 
can identify all dependent modules on the node and determine the purpose of each 
dependent module. This is useful when determining the effects and consequences 
of deleting a module.

© 2009 Schneider Electric. All rights reserved. Page 239


Viewing Setup Register Information PowerLogic ION Enterprise User Guide

Viewing Setup Register Information


A moduleʹs setup registers contain its configuration information. When a module 
processes data, it manipulates the data according to the guidelines stored in its 
setup registers. Setup register information includes the moduleʹs available setup 
registers, the setup register settings, and the setup register owners. Each of these 
can be accessed from the output symbol located on the right side of the module 
icon.

Viewing Setup Registers


Press the CTRL key and click the output symbol or right‐click the graphic in the 
center of the module to display the ION Module Setup dialog box.

Viewing Setup Register Settings


Press CTRL+SHIFT and click the output symbol or right‐click the graphic in the 
center of the module to display the ION Module Setup dialog box.

Viewing Setup Register Owners


Press the CTRL key and right‐click the output symbol.

Viewing Input Information


Input information includes the moduleʹs inputs and a sample of its real‐time input 
values. Each of these can be accessed from the moduleʹs input symbol.

Viewing Inputs
Click the input symbol.

Viewing Real-time Input Values


Press the SHIFT key and click the input symbol.

Page 240 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Time of Use (TOU) Program Management

Time of Use (TOU) Program Management


Tariff schedules, or Time of Use programs, are easily created. After you have 
created a tariff schedule, you can manage these files using the TOU Program 
Manager. 

Creating a Time of Use Schedule


1. In Designer, select Options > Edit TOU Programs.
2. Click Make a New TOU Program.
A New Program appears in the left window of the display. Click on this to 
rename it.
3. Click Edit (Launch Program Editor).
4. Follow the instructions on screen and click Finish when you are done and Close.

Downloading a Time of Use Schedule into an ION meter


1. Start Designer and connect to your meter.
2. From the Factory Configuration screen (root window of the node diagram), 
right‐click the Sample TOU module under Time‐Of‐Use Setup. The ION 
Module Setup dialog box appears.
3. Click the Quick TOU button.
4. Select the TOU schedule you want and click OK.

Advanced TOU Schedule Configuration


The TOU program editor provides an advanced mode that lets you make 
configurations supported by the meter but that are not provided in the TOU Editor 
described above. The advanced TOU is useful in the following cases:
When TOU seasons do not use a fixed start or end date that is the same in every 
calendar year.
Alternate days defined as a specific date and are not a particular day of the 
week.

Accessing Advanced TOU Mode


1. In Designer, select Options > Edit TOU Programs. Select a TOU Program or 
create a new one and click Edit (Launch Program Editor).
2. Hold the CTRL key and right‐click on the text in the Seasons section of the 
Seasons and Rate Definitions screen.
A dialog appears that lets you add a setup register override or delete or modify 
an existing setup register override.

© 2009 Schneider Electric. All rights reserved. Page 241


Advanced TOU Schedule Configuration PowerLogic ION Enterprise User Guide

3. To add a new setup register override, click Add.

4. Select a setup register from the drop‐down list then type in the register value 
(available registers are: Seasons 1, 2, 3, and 4, and Alt 1, and 2 Days).

NOTE
Be sure to follow the syntax rules described in the TOU module section of the ION Reference. If the syntax
is incorrect, the meter will not accept the configuration.

To delete an existing setup register override, select it from the list and click 
Delete then OK.
To modify a register, select it from the list and click Modify. Make your 
changes and click OK.

Page 242 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Advanced TOU Schedule Configuration

5. Click OK to return to the TOU Program Editor.
6. Click the Summary tab in the TOU Program Editor. This compiles the schedule 
to include the setup register overrides you just defined.
The Device Setup Register Values section of the summary displays the register 
values that will be sent to the meter and includes the configured values. The 
TOU Program Log Output section of the summary displays the log generated 
while the TOU schedule is compiled. Any setup register overrides that are 
defined appear as entries in this log file.

© 2009 Schneider Electric. All rights reserved. Page 243


Virtual Processor Service PowerLogic ION Enterprise User Guide

Virtual Processor Service


The Virtual Processor is a service that operates on the ION Enterprise server, 
providing coordinated data collection, data processing, and control functions for 
groups of meters. This makes distributed operations possible, providing 
customized solutions to a variety of industrial, commercial, and power utility 
needs.

The Virtual Processor lets you to gather the information available from your 
network of power monitoring devices, and enables you to categorize, manipulate, 
and/or customize the data before distributing the information to the different 
departments in your company. You could think of the Virtual Processor as a 
virtual device, capable of collecting and processing data from several power 
monitoring devices, analyzing the information and performing control functions 
as required. The Virtual Processorʹs name implies its characteristics:
Virtual ‐ The Virtual Processor runs in the memory of your PC, not as a remote 
device.
Processor ‐ The Virtual Processor contains a wide selection of ION modules, 
which it uses to process information.

Using the Virtual Processor


The Virtual Processor is not configured at the factory. To perform data collection, 
data analysis, Modbus communications, or distributed control, you must first 
create ION module frameworks, using Designer. Refer to the ION Reference for 
information on ION modules.

Configuring the Virtual Processor with Designer


Use Designer to perform all Virtual Processor configuration, including adding 
new modules, configuring module setup registers, and linking module inputs and 
output registers to other modules. 

Creating a Second Virtual Processor


Create a second ION Virtual Processor Service and start it using the following 
steps:
1. Open a command prompt window.
2. Register the Virtual Processor as a service from the ION Enterprise\system\bin 
folder by typing: vip.exe ‐Service ‐N<custom Virtual Processor name>
3. Open Control Panel > Administrative Tools > Services and start the new 
registered Virtual Processor.

Page 244 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Distributed Control

Viewing Virtual Processor Data with Vista


After you have used Designer to add and link modules in the Virtual Processor, 
you can create a user diagram in Vista and link it to the modules in the Virtual 
Processor. You can then use your user diagram to display system data, monitor 
alarms, and control basic functions in your Virtual Processor framework.

Configuring the Virtual Processor to Interact with the Desktop


1. Open Control Panel > Administrative Tools > Services.
2. Right‐click the ION Virtual Processor Service and select Properties.
3. Select the Log On tab.
4. Select the “Allow service to interact with desktop” check box and click OK.
5. Stop and restart the ION Virtual Processor Service.

Distributed Control
Virtual Processor Distributed Control modules are a means of transferring 
information between the different devices in your network. These modules can be 
used to build frameworks for control processes such as alarm annunciation, plant‐
wide demand control, power factor control, load shedding, paging, and generator 
switching.

Before you decide to use a Virtual Processor to implement a control system, it is 
important to understand the various factors that influence the speed with which 
the Virtual Processor is able to generate a control action. Some of these factors 
include network traffic, the number of polled devices in your network, the 
reliability of your communications network, and the Virtual Processor 
workstationʹs CPU usage.

CAUTION
Do not use the Virtual Processor in any capacity where a failure to execute an expected control action
could result in equipment failure or danger to personnel. Do not use the Virtual Processor for time-critical
functions.

The information presented in this section assumes that you are familiar with the 
various ION modules and their functions. Refer to the ION Reference for details on 
Distributed Control and other modules.

Distributed Control Modules


The Virtual Processor uses four modules to implement Distributed Control 
frameworks. Three types of Distributed Control modules (Distributed Boolean, 
Numeric, and Pulse modules) receive data from devices or other Virtual 
Processors within your network and transfer this data to the node address 
specified in the moduleʹs setup registers. The Data Monitoring module is used as 
a means of disabling a control module, if the data at the source input (which is used 
to make the control decision) becomes “stale”.

© 2009 Schneider Electric. All rights reserved. Page 245


Distributed Control PowerLogic ION Enterprise User Guide

Distributed Control Module Setup Registers


All Distributed Control modules (Distributed Boolean, Distributed Numeric, and 
Distributed Pulse modules) have a Source input and an Activate input. The Activate 
input must be linked to another module, and it must be on for a Distributed 
Control module to function. These modules also contain a Destination setup 
register that specifies the node receiving the data.

Distributed Boolean Module


All Distributed Boolean modules have one input that must linked to an External 
Boolean output register. Whenever this register’s Boolean value changes state, the 
new value is sent to the node defined in the Destination setup register.

Distributed Numeric Module


A Distributed Numeric moduleʹs input must be linked to an External Numeric 
module. This input’s value is sent to the node specified in the Destination setup 
register. This module has two additional setup registers that are used to determine 
when and how often new data is sent to the Destination node.

Distributed Pulse Module


All Distributed Pulse modules have one input that must link to an External Pulse 
module. This module’s pulse is sent to the node defined in the Destination setup 
register.

Data Monitoring Module


The Data Monitor module provides a means of alerting you to communication 
problems that may occur between the Virtual Processor and any ION node 
referenced by the Data Monitorʹs Source inputs.

NOTE
ION meters with Advanced Security enabled do not accept control operations from the Virtual Processor.
In order to enable these control operations, you need to provide a device password in Management
Console for these applications to use. See “Accessing Meters with Advanced Security” on page 38 for
information on configuring Advanced Security.

Distributed Control Network Performance


It is important to maximize the speed at which the Virtual Processor receives the 
data used to make control decisions. The performance of a Virtual Processor using 
Distributed Control is sensitive to factors such as network traffic, the Virtual 
Processorʹs global parameters, and the workstationʹs CPU usage.

The following sections provide some guidelines for improving a distributed 
control networkʹs performance.

Page 246 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Distributed Control

System Configuration
Minimize the number of devices per site for sites including devices used for 
distributed control.
Minimize the number of applications (such as Vista diagrams) that are 
requesting data from the control site.
Decrease the Virtual Processorʹs Client Polling Period.
Maximize the siteʹs baud rate.

CPU Performance
Dedicate a single Virtual Processor for control purposes; an additional Virtual 
Processor can be run for less critical functions.
Do not run CPU intensive functions on the same workstation as your distributed 
control Virtual Processor.

Distributed Control Applications


The Virtual Processorʹs Distributed Control frameworks can perform various 
control processes; two examples are presented below. Ensure that you are familiar 
with the sections above before using any of these module frameworks in a control 
system.

Example: Passing a Value Between Devices


The following example shows how the numeric output of the Integrator modules 
in meter “A” is sent to an External Numeric module in meter “B”.

Virtual Processor

Distributed
Meter “A” Numeric Module
Meter “B”
Source
Activate External Numeric
Integrator
Module Output Destination: ION meter “B” Module Output

Data Monitor
Module Status

Source

Note that the Distributed Numeric module is disabled if the Data Monitor module 
detects a communication problem between the meter “A” and the Virtual 
Processor (e.g., timeouts or slow network connections). This helps to ensure that 
control actions are only performed based on up‐to‐date data.

© 2009 Schneider Electric. All rights reserved. Page 247


Modbus Communications PowerLogic ION Enterprise User Guide

Example: Device Control


This example framework monitors total harmonic distortion (THD), which could 
cause a piece of equipment (like a power transformer) to overheat. When a setpoint 
is reached, the system sends a network message to a workstation and turns on a 
fan.

Meter Virtual Processor

Setpoint Distributed
Status
Module Boolean Module
Harmonics Analyzer
Total HD Source
Module
Source
Activate
Data Monitor
Status Destination: ION meter,
Module
Digital Output Trigger External Boolean module,
External
State Module #1 State Switch register
Boolean Source
Module
Source

Launching
Module RunCommand = net send Workstation1
Digital “Current THD is high!
Outputs Launch Signal to turn on cooling fan has been sent”

Fan Switch

Modbus Communications
Modicon Modbus RTU is an industry standard communications protocol used in 
control and power monitoring industries. The devices in a Modbus network have 
a Master/Slave relationship with communication transactions occurring between 
the Master and one or many slaves (up to 247 slave devices can exist in one site).

The Virtual Processor can act as a Modbus Slave by responding to requests from a 
Modbus Master and providing it with power monitoring system data.

Providing Data for a Modbus Master


The following diagram illustrates how the Virtual Processor can make values in 
ION module registers available to a Modbus Master device. Assume the Modbus 
Slave moduleʹs source inputs are linked to numeric or Boolean output registers 
from other ION modules. In this example, the values obtained from those registers 
are converted to the proper Modbus format (according to how the Modbus Slave 
moduleʹs setup registers are configured). The Modbus Slave module responds to a 
read request from the remote Modbus Master device and sends the Modbus data 
to the specified Modbus registers (again, according to how the Modbus Slave 
moduleʹs setup registers are configured).

Page 248 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Modbus Communications

Virtual Processor 1. Read request by remote Modbus Master.

READ
Modbus Slave Modbus Value 1 Remote Modbus Device
Module Modbus Value 2
Modbus Register Map
Source 1
Source 2

. Modbus Value 32
.
. Modbus Base
Modbus Link
Event
Source 16

2. Requested data is sent from the Slave Module


to the specific Modbus registers.

The Virtual Processor's Modbus Slave Module


A standard Modbus Slave module can take up to 16 ION register values and make 
them available to a Modbus master. In the Virtual Processor, the Modbus Slave 
module can also be used to bring Modbus data into your power monitoring system 
(it permits a Modbus master to push data into the Virtual Processor). 

NOTE
Refer to the ION Reference for more information on the Modbus Slave module.

When a Modbus Slave module in the Virtual Processor has no links to its inputs, 
the output registers of the module show the contents of the Modbus register map. 
Currently, only the Modbus Slave modules in the Virtual Processor have this 
additional capability (the Modbus Slave modules in ION meters cannot do this). 

Use the Modbus Slave module to bring Modbus data into your power monitoring 
system as follows: 
1. Start the Virtual Processor and open it in Designer.
2. Drag a Modbus Slave module from the toolbox.
3. Leave the inputs of the Modbus Slave module unlinked. The Modbus Slave 
module will not read the Modbus register map if any of its inputs are linked (the 
module provides the linked data to the Modbus register map).
4. Configure the Modbus Slave moduleʹs setup registers.
The Modbus Slave module reads the register map starting at the address 
specified in BaseAddr setup register until each output register is filled.
If the Format setup register is a 
16 bit format, 16 bit data is put into each of the ModVal output registers. 
32 bit format, two pieces of 16 bit data are combined into one 32 bit ModVal 
output register. 
Packed Boolean, then the data is put into the ModVal 1 output register in 
Packed Boolean form. 
Ignore the Scaling, InZero, InFull, and OutZero, OutFull setup registers; there 
is no scaling applied to any of the Modbus register map values.
5. Link the outputs of the Modbus Slave module to the inputs of other modules in 
the Virtual Processor.

© 2009 Schneider Electric. All rights reserved. Page 249


Common Virtual Processor Applications PowerLogic ION Enterprise User Guide

Three examples of modules to link to are: 
Data Recorder modules for data logging 
Setpoint and Relative Setpoint modules for alarming 
Distributed Numeric module for redistribution to ION meters (for 
automated plant‐wide demand or power factor control) 

Common Virtual Processor Applications


The Virtual Processor can be used to create numerous analysis, recording, and 
control functions. This section describes three common Virtual Processor 
applications:
Event Driven Report Generation using Reporter
Data Aggregation
Logging Data from Meters

The examples shown on the following pages assume that you understand the 
functions and options of the various modules used. Refer to the ION Reference for 
module details. See the previous sections for common Modbus and Distributed 
Control applications.

Page 250 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Common Virtual Processor Applications

Example: Event Driven Report Generation using Reporter


The Virtual Processor can be used in conjunction with a device and the Log 
Inserter to generate reports in response to system events. In the following example, 
a Power Quality report is automatically generated in the event of a system 
disturbance.

Meter Log Inserter

Log Acquisition
Module
Trans Max Data Recorder
Transient Source
Module Trans Dur Module
Data
V1 Log 1
V2 Log Monitor Records
Processed
V3 Source 1 Module
V Nom Source 2 Source

Virtual Processor

Arithmetic Result Setpoint Trigger One-Shot Timer Trigger


Module Module Module
Source Source Start
Formula: IF(S1-P1(1)>0,1,0) High Limit: 0 Duration: 300 sec
Low Limit: 1
Eval Mode: Greater Than

Launching
Module
Launch
RunCommand: %PML_ROOT1%\bin\Repgen.exe -r Power_Quality

As transients often occur in groups, the five minute delay setup with the One‐Shot 
timer module allows multiple transients to appear in one Power Quality report.

NOTE
Using the Virtual Processor’s Launching module may require that the Virtual Processor be run as an
application instead of a service. Contact Technical Support if you require more information.

© 2009 Schneider Electric. All rights reserved. Page 251


Setting Global Parameters PowerLogic ION Enterprise User Guide

Example: Data Aggregation


In the following example, meters monitor average current values (I avg). Every 
day at a specified time (determined by the Periodic Timer module), the Data 
Recorder Module stores the maximum average current value for each meter.

Virtual Processor
Meter “A” Maximum
Module Maximum
Power Meter l avg Source
Module Reset

Maximum
Module Maximum

Meter “B” Source


Reset
Power Meter l avg
Module
Maximum
Module Maximum
Source
Reset
One-Shot Timer Trigger
Meter “C” Module Data Recorder
Start
Module Rec Log
Power Meter l avg Source 1
Module External Control Switch 1
Module Source 2
Source 3
Periodic Timer Enable
Trigger Record
Module

Example: Logging Data from Meters


The Virtual Processor can be used to log data from meters that do not have Data 
Recorders. In the following example, the total kWh from a meter’s Integrator 
module is recorded every 15 minutes by a Virtual Processorʹs Data Recorder 
module.

Meter
Virtual Processor Data Recorder Data Log
Module
Power Meter kW tot Integrator Module kW tot Source
Module Record
Integrand
Periodic Timer Trigger
Module
Period: 900 sec

Setting Global Parameters


The Virtual Processor global operating parameters and Modbus network setup are 
configured using Virtual Processor Setup. 

The global parameters do not need to be changed for normal operation. The 
Virtual Processor operates properly in most applications with the default settings. 
See “Modifying the Global Parameters” on page 79 for details.

Page 252 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Setting Global Parameters

To set up the Virtual Processor’s Modbus network, see “Configuring the Virtual 
Processorʹs Modbus Service” on page 75.

NOTE
The ION Virtual Processor Service must be restarted for any changes to take effect, as the Virtual
Processor only reads the vipsys.dat file once on startup. The ION Virtual Processor Service can be
restarted, like any other service, using the Services window found via the Control Panel service applet.

© 2009 Schneider Electric. All rights reserved. Page 253


Setting Global Parameters PowerLogic ION Enterprise User Guide

Page 254 © 2009 Schneider Electric. All rights reserved.


8 Database Manager
Database Manager helps you maintain the information contained in your 
databases through periodic backups and archives.

In This Section

“Database Manager Interface” on page 256
“Common Database Management Procedures” on page 258
“Manual Tasks” on page 260
“Scheduled Jobs” on page 267
“Optimizing Database Query Time” on page 273
“Log Inserter” on page 274
“Accessing the ION Database with 3rd‐Party Applications” on page 275

© 2009 Schneider Electric. All rights reserved. Page 255


Database Manager Interface PowerLogic ION Enterprise User Guide

Database Manager Interface


Use Database Manager to manually perform maintenance operations on the ION 
Enterprise databases or to configure scheduled tasks to perform these operations.

To access Database Manager:
Start Management Console then click Tools > Database Manager, or
Open the ION Enterprise Tools folder on the desktop and double‐click the 
Database Manager icon. 

Expand the items in the navigation tree to display the Databases and Scheduled 
Jobs items for each instance.

SQL Instance

Databases

Scheduled Jobs

SQL Server Instance


The default SQL Server instance that ION Enterprise uses for its databases is 
named COMPUTERNAME\ION, where COMPUTERNAME is the name of the 
server where the database resides.

Databases
Use the Databases section of the tree to view information about the databases or 
to perform manual tasks. 

For information on the manual tasks you can perform, see “Manual Tasks” on 
page 260.

Page 256 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Database Manager Interface

Viewing Database Properties


To view the properties of a particular database, right‐click on that database and 
select Properties. The properties listed are:
Size: The current size of the database.
Primary File Location: The file path for the primary database (.mdf) file.
Transaction Log Location: The file path for the transaction log (.ldf) file.
Creation Date: The date and time when the database was created.
Last Backup Date: The date when the last backup was performed.
Disk Space Available: The amount of free space available on the disk where the 
database resides.
Server Version: The type and version of the SQL Server instance that is hosting 
the database.

Scheduled Jobs
Use the Scheduled Jobs section of the tree to configure scheduled tasks or view 
information about the scheduled tasks. 

For more information on scheduled tasks, see “Scheduled Jobs” on page 267.

Show Archives
Select this check box (lower left‐hand corner) if you want the Databases list to 
include all archived databases along with the live databases. After Show Archives 
is selected, you have the option to perform any of the tasks available for the live 
ION databases on your archived databases (archive, backup, restore, detach, 
attach, and trim, depending on the type of database).

Clear the Show Archives check box to hide the archived databases from view and 
to prevent the tasks mentioned above being performed on database archives.

© 2009 Schneider Electric. All rights reserved. Page 257


Common Database Management Procedures PowerLogic ION Enterprise User Guide

Common Database Management Procedures


The following sections outline common procedures that you can perform using the 
manual tasks. For more details on individual manual tasks, see “Manual Tasks” on 
page 260.

Detaching then Re-attaching Databases


The following procedure explains how to detach a connected database and then re‐
attach a new database in its place.

Detaching and re-attaching a database


1. Stop all ION Enterprise services that are running.
2. Right‐click Databases then select Detach. The Detach Database dialog box 
appears.
3. Select the database you want to detach. Click Clear to ensure there are no 
connections to the database. In the “Detach options” section, select whether or 
not you want to update statistics prior to detach. Click OK.
4. Right‐click Databases then select Attach. The Attach Database dialog box 
appears.
5. Click the browse button   and navigate to the database you want to attach. 
Edit the Attach as field or leave the default name. Click OK.
6. Restart ION Enterprise services.

Attaching a Database Using Database Manager


If you attach a database to the ION Enterprise system via Database Manager, you 
must keep all ION Enterprise services running. This differs from the Detach/
Attach procedure described in “Detaching then Re‐attaching Databases”, above.

Attaching a Database Using Database Manager


1. Right‐click Databases then select Attach. The Attach Database dialog box 
appears.
2. Click the browse button   and navigate to the database you want to attach. 
Edit the Attach as field or leave the default name.
3. Click OK.

Page 258 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Restoring an ION Database from a Backup

Restoring an ION Database from a Backup


To recover a database after a full backup, replace the lost or corrupted database 
with the backup database file.

Restoring a Database Using Database Manager


1. Stop all ION Enterprise services.
2. Right‐click Databases then select Restore. The Restore Database dialog box 
appears.
3. Select the appropriate database to restore from the list in the “Select the backup 
to restore” section. To see the properties of the selected database, click 
Properties. 
4. Click Clear to ensure there are no connections to the database.
5. Edit the Restored database name field or select from the dropdown list.
6. In the “Database file location” field, click the browse button   and navigate to 
the location where you want to store the restored database.
7. Restart ION Enterprise services.

NOTE
There are blank database and transaction log backup files available in the event of a complete database
loss or corruption. They are located in the ...\ION Enterprise\system\etc\ directory. The task in Database
Manager called New ION Database uses these files.

© 2009 Schneider Electric. All rights reserved. Page 259


Manual Tasks PowerLogic ION Enterprise User Guide

Manual Tasks
The following sections provide information on the manual tasks that can be used 
to manage your databases.
To perform a manual task, do one of the following:
Right‐click Databases and select the task from the pop‐up menu, or
Right‐click the database on which you want to perform the task and select the 
task from the pop‐up menu.

When you right‐click on Databases to select a task, a task dialog box appears. You 
can select the database on which you want to perform the task. If the task can only 
be performed on one database, the database is pre‐selected.

When you right‐click on a database, only the tasks that apply to that database 
appear in the pop‐up menu and the database is pre‐selected in the task dialog box.

Alarm Configuration
Right‐click Databases and select Alarm Configuration to display the Alarm 
Configuration dialog box.

Select Events to Monitor


Database Size: This section lets you enable or disable local alarms that monitor 
the size of the ION_Data and ION_SystemLog databases. You can also set the 
size threshold that the ION_Data or the ION_SystemLog database must exceed 
before you receive an alarm notification. The ION_Network database is not 
monitored. 

Page 260 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Archive

Hard Drive Space: This section lets you enable or disable the alarm that 
monitors your hard drive(s). You can monitor all hard drives or just the hard 
drives that contain the ION Enterprise databases. You can also adjust the 
threshold for the minimum amount of space remaining before you receive an 
alarm notification.

Configure Alarming Method


This section lets you specify the name of the SMTP server as well as the email 
addresses of the recipients you want to send alarm notifications to.

Archive
Use this task to create an archive of the selected database.

NOTE
The Database to archive list only shows your live ION_Data database unless Show Archives is selected.

1. Right‐click on Databases or ION_Data and select Archive to display the 
Database Archive dialog box. If necessary, select the database that you want 
to archive.
2. Click the browse button   to select a location to save the archive to.
The directory ...\ION Enterprise\config\cfg\Archives\Data is the default 
location where the archive is saved, but you can specify another local directory 
(you can only save an archive to directory on the local machine, not to a location 
on the network). 
3. Type a name for the archive. 
After you select the location, the archive is given a default filename, but you can 
rename the archive to follow your conventions.
4. Select the data types you want to archive.
5. Specify the date range of the data that you want to archive. For the Start Date, 
select “The beginning of the database” or select “Date” and enter a date and 
time. Enter a date and time for the End Date.
6. Select whether or not you want to trim the database after the archive.
When you select a start date for the archive procedure instead of using the 
beginning of the database, the option to trim the live database is disabled, even 
if you selected the trim option before you set the date range.
7. Click OK. 

The Progress field displays the current progress of the archive task. If a manual 
archive fails, a message appears and the Database Archive dialog remains open 
with the OK button grayed out — you can examine the Progress field to discover 
where the task failed. If the archive is successful, the dialog box closes 
automatically. 

© 2009 Schneider Electric. All rights reserved. Page 261


Attach PowerLogic ION Enterprise User Guide

Attach
Use this task to reattach a detached database. 
1. Stop all ION Enterprise services.
2. Right‐click Databases then select Attach. The Attach Database dialog box 
appears.
3. Click the browse button   to navigate to the database that you want to attach. 
Specify a name in the Attach as field. 
4. Click OK.
5. Restart ION Enterprise services.

Backup
Use this task to create complete backups for the ION_Data, ION_Network, and 
ION_SystemLog databases. 
1. Right‐click on Databases, ION_Data or ION_Network and select Backup. 
The Backup Database dialog box appears. If necessary, select the database that 
you want to backup. 
If you have Show Archives selected, you can also backup your archives.
2. Click the browse button   to specify a location to which you want to save the 
backup.
Backups are stored in the directory ...\config\cfg\DBBackups\Data\ by 
default. You can save the backup to your local computer or to your network 
using a Universal Naming Convention (UNC) path or a mapped drive. 
3. Type a description in the Description of backup text field, if you want to 
provide information about the nature of the manual backup.
4. Click OK.

Defragment
Right‐click on Databases and select Defragment to display the Defragment 
Database dialog box. Select the database you want to defragment and click OK.

You can defragment the ION_Data, ION_Network, or ION_SystemLog database. 
These databases are defragmented as part of the scheduled maintenance if 10% or 
more of the database is fragmented. See “Scheduled Jobs” on page 267 for more 
information. 

Detach
This task lets you detach a database from SQL Server so that the existing database 
files can be copied, allowing the option to reattach alternate or default copies of 
these files if necessary.

Page 262 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Export Registry Setting

To detach a database:
1. Stop all ION Enterprise services.
2. Right‐click on Databases, ION_Data, ION_Network or ION_SystemLog and 
select Detach. The Detach Database dialog box appears. If necessary, select the 
database that you want to detach.
3. Click Clear to clear any existing connections to the database. In the “Detach 
options” section, select whether or not you want to update statistics prior to 
detach.
4. Click OK to detach the database.
5. Restart ION Enterprise services.

NOTE
Do not move the ION_Network or ION_SystemLog databases unless absolutely necessary.

Export Registry Setting


This task lets you export settings to a registry (.reg) file. This task is useful if you 
need to set up ION Enterprise clients in a system where the primary ION 
Enterprise server’s database settings (server instance name, database name, or 
password) are customized. After you export the settings to the registry (.reg) file, 
you can run that registry file on the client machine.

1. Right‐click on Databases and select Export Registry Setting. The Database 
Registry Key Export dialog box appears.
2. Type the path and filename for the file or click the browse button   to specify 
the location to which you want to save the database registry key. 
The directory ...\ION Enterprise\config\cfg\ is the default save location for the 
exported database registry key.
3. Click OK.

Modify Login
Use this task to change the password for the SQL Server instance used for the ION 
Enterprise databases.
1. Stop all ION Enterprise services.
2. Right‐click Databases then select Modify Login. The Modify Login dialog box 
appears.
3. Type your password in the Password field (this must be a SQL administrative 
password). Click OK.
4. From the Login Name dropdown list, select the instance for which you want to 
modify the login. Type the new password in the New Password and Confirm 
New Password fields. Click OK.
5. Restart ION Enterprise services.

© 2009 Schneider Electric. All rights reserved. Page 263


New ION Databases PowerLogic ION Enterprise User Guide

New ION Databases


Use this task to create a new, blank version of the ION_Data database. 
1. Right‐click on Databases and select New ION Databases. The New Historical 
ION Enterprise Database dialog box appears. 
2. Type a name for your new database.

NOTE
Do not name it “ION_Data” as this is the default name for the existing ION database.

3. Click the browse button   to specify a location for the database.
4. Click OK. 

Restore
Right‐click on Databases, ION_Data or ION_Network and select Restore to 
display the Restore Database dialog box.

Depending on the database you are restoring, this procedure replaces the existing 
ION_Network database, ION_SystemLog database, or ION_Data database with 
the database from the appropriate backup file. By default, these backup files are 
located in the directory ...\ION Enterprise\config\cfg\DBBackups\. 

NOTE
It is not possible to simply detach the live file, copy the backup file into the live file location, and reattach
the file. The backup file is a file copy of the live database, but it must have some operations performed
on it to allow it to replace the live database. The Restore command performs these operations.

The Restore Database dialog box has the following sections and fields:
Select the backup to restore: This section of the dialog box lists the available 
database backups. Click on a backup to select it. The selected database backup 
has an arrow next to it in the list.
Click Properties to display the name, size, start date, finish date, location, and 
description of the selected backup.
Restored database name: Select or type a name for the restored database.
Database file location: Select the location where you want to save the restored 
database.

Page 264 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide SQL Editor

SQL Editor
Right‐click on Databases and select SQL Editor to display the SQL Editor dialog 
box.

CAUTION
When you select this task, the following warning appears: “Any alterations made using the SQL Query
Editor may be irreversible”. Click OK to continue or Cancel to cancel. The SQL Editor is intended only for
advanced users who have a solid understanding of SQL and ION Enterprise databases — changes made
through the SQL Editor are, in some cases, irreversible.

The SQL Editor task is included within Database Manager for a number of reasons:
The SQL Editor lets you export database information for troubleshooting 
purposes.
With the SQL Editor, you can write custom queries that let you view whatever 
data you want.
The SQL Editor provides a method for implementing custom changes to the 
databases. For example, this allows you to execute a custom SQL script 
provided by Schneider Electric.

NOTE
Ensure that you select the appropriate database before you execute your SQL statement.

Trim
Use this task to remove data from a database. If Show Archives is selected, you can 
also perform a trim on archived databases. 

CAUTION
Trimming data from the database is permanent. It is recommended that you backup or archive data
before trimming.

© 2009 Schneider Electric. All rights reserved. Page 265


Update Statistics PowerLogic ION Enterprise User Guide

1. Right‐click on Databases, ION_Data or ION_SystemLog and select Trim. The 
Trim Database dialog box appears.
2. Select the database you want to trim from the “Database to trim” list.
3. In the Trim Range section, specify the date range of data you want to trim (for 
the ION_Data database) or set the maximum data age in days (for the 
ION_SystemLog database).
4. For the ION_Data database (or an archive), select the data types you want to trim 
(Data Records, Waveforms, Events) in the Data Types section. You can select any 
combination of data types to trim.
5. Click OK. A warning appears to notify you that the selected data will be 
permanently removed. Click Yes to continue or No to cancel.

Update Statistics
Right‐click on Databases and select Update Statistics to display the Update 
Statistics dialog box.

Statistics on numbers of rows and ranges of key values in the data provided can be 
used by SQL Server to determine the most efficient way to access the base tables, 
thus improving the performance of distributed queries. Update Statistics 
recalculates these values for better performance.

To update statistics, select the database you want to update and click OK.

Upgrade Database
Right‐click on Databases and select Upgrade Databases to display the ION 
Database Upgrade dialog box.

This task upgrades the selected database with the latest database schema.

The ION Enterprise installer automatically upgrades your databases with the new 
database schemas when you install ION Enterprise on an existing ION Enterprise 
server. If you install the latest version of ION Enterprise on a different server so 
that you can manually copy older database files to the new computer, you can run 
this task on the older databases (i.e., the ION_Data, ION_SystemLog, and 
ION_Network databases, and archives) to upgrade them with the new schema.

To upgrade a database, select the database you want to upgrade and click OK.

Page 266 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Scheduled Jobs

Scheduled Jobs
Database Manager has a number of preconfigured scheduled tasks, most of which 
are configurable and enabled by default. See the following table for details:

Enabled by
Database Scheduled Task Default Time Configurable
Default?

12:00 am, 1st Saturday of every third month or


Archive No of every quarter (depending on the version of Yes
SQL Server ION Enterprise is using)
ION database (ION_Data)
Backup Yes 12:00 am, Friday Yes

Maintenance Yes 2:00 am, daily No

Network Configuration database Backup Yes 1:00 am, daily Yes


(ION_Network) Maintenance Yes 7:30 am, daily No

System Events database Trim Yes 1:30 am, daily Yes


(ION_SystemLog) Maintenance Yes 7:05 am, daily No

Viewing Schedule Information


To view schedule information:
For all databases, right‐click on Scheduled Jobs and select Schedule 
Information, or 
For a specific database, right‐click on the database for which you want to view 
information and select Schedule Information. 

The Scheduled Jobs window appears. This window lists the following information 
for scheduled jobs: database name, job type, whether or not the job is enabled, the 
last run date and the next run date.

Editing Scheduled Tasks


To edit a scheduled task:
Double‐click a scheduled task in the Scheduled Jobs window, 
Right‐click on a database and select the task you want to edit, or
Right‐click on Scheduled Jobs and select the task you want to edit.

The scheduled task’s dialog box appears. See “Scheduled Archive” on page 268, 
“Scheduled Trim” on page 270 and “Scheduled Backup” on page 271 for 
information on editing these scheduled tasks.

NOTE
You cannot configure scheduled Maintenance tasks.

© 2009 Schneider Electric. All rights reserved. Page 267


Scheduled Archive PowerLogic ION Enterprise User Guide

Viewing History for a Scheduled Task


To view the history of a scheduled task, right‐click a database, select Job History 
then select the task for which you want to view the history. The Scheduled Job 
History window appears.

The run date, status (success or failed), and duration are available for all scheduled 
tasks.

Select a task from the list to view further information in the “Errors or messages 
from selected task step” text field.

Select Show only failed tasks to filter out completed tasks from the list.

Click Clear All to clear the job history for the selected scheduled task.

Scheduled Archive
Right‐click Scheduled Jobs or ION_Data and select Archive to display the 
Scheduled archive dialog box.

NOTE
When ION Enterprise is first installed, Scheduled Archive is disabled by default. You must open the
Scheduled archive dialog box and select the Schedule Enabled check box to enable it.

Page 268 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Scheduled Archive

You must select this


check box to enable
the scheduled archive.

Data Types
A scheduled archive is preconfigured to archive all data types and to trim each of 
the data types after the archive is complete. Clear the Trim after archive check box 
for a data type if you only want to perform an archive without subsequently 
deleting that data.

CAUTION
Trimming data permanently removes it from the database. Trimming without archiving is not
recommended for data records.

Amount of Live Data


This setting determines the number of complete months of live data that you want 
to keep in the ION_Data database.

Archive Interval
For SQL Server 2005 Express, click Select Months, then specify the months for 
which you want the archive to occur.
For SQL Server 2005 (Standard Edition), select one of the following options: 
Monthly, Bi‐monthly (every 2 months), Quarterly, Semiannually, Annually, Every 
2 years, Every 3 years, Every 4 years, and Every 5 years.

NOTE
The Database Manager scheduled jobs use the year and month in the archive file name. If you use SQL
Server Manager Studio or SQL Server Enterprise Manager to schedule the database archives, do not set
the archive frequency to more than once a month to prevent failures.

© 2009 Schneider Electric. All rights reserved. Page 269


Scheduled Maintenance PowerLogic ION Enterprise User Guide

Schedule
You can select any day of the week for your scheduled archive (the default is 
Saturday). The archive is performed at the specified time on the first occurrence of 
that day in the month. For example, if you configure the scheduled archive to occur 
monthly on Sunday at 5:30:00 AM, then Database Manager archives the ION_Data 
database at 5:30 AM on the first Sunday of every month.

Scheduled Maintenance
The schedule for the maintenance tasks is pre‐configured and cannot be changed. 
To view the history for a maintenance task, right‐click the database, select Job 
History > Maintenance. See “Viewing History for a Scheduled Task” on page 268 
for more information.
There are a number of tasks that are performed on the database when a 
maintenance job is executed. The following is an ordered breakdown of a 
scheduled maintenance:
1. Check database fragmentation and defragment if the fragmentation level is 
more than 10%.
2. Update statistics for all the tables in the database.
3. Check and track the database size.
4. Send an email alert if any maintenance step fails.

The maintenance schedule for each database is as follows:
ION_Data maintenance job occurs daily at 2:00 AM.
ION_SystemLog maintenance job occurs daily at 7:05 AM.
ION_Network maintenance job occurs daily at 7:30 AM.
(Note that the disk usage monitor starts at 7:00 AM and takes only a few seconds 
to complete.)

Scheduled Trim
Right‐click Scheduled Jobs or ION_SystemLog and select Trim to display the 
Scheduled Trim dialog box.
Ensure that “Schedule enabled” is selected if you want to enable the scheduled trim.

The System Events database has the scheduled trim task configured and enabled 
by default.

Changing the Schedule


Click the Change button in the Schedule section. The Edit Schedule dialog box 
appears where you can reconfigure the frequency and time of the scheduled trim.

The Edit Schedule dialog box differs depending on what you select in the Occurs 
section.

Page 270 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Scheduled Backup

Daily: Set the frequency in days. For example, to set the trim to occur every 
seven days, set the frequency to 7.
Weekly: Set the frequency in weeks and select the days of the week on which 
you want the trim to occur. You can select multiple days of the week. For 
example, to set the trim to occur every two weeks on Monday and Thursday, set 
the frequency to 2 and select Monday and Thursday from the list of days.
Monthly: Set the frequency then select Fixed Day or Relative Day to set the day 
of the month on which the trim occurs.
Frequency: Depending on your version of SQL Server, click Select Months 
to select the months in which you want the trim to occur or set the 
Frequency in number of months.
Fixed Day: The trim occurs on the specified date at the frequency specified 
(in months). For example, to set the trim to occur on the 15th day of every 
month, select every month (or set Frequency to 1) then set Fixed Day to 15.
Relative Day: The trim occurs on the specified day of the month at the 
specified frequency (in months). For example, to set the trim to occur on the 
second Sunday of every third month, set Frequency to 3 (or select which 
months you want to trim to occur in) and select 2nd and Sunday from the 
Relative day dropdown lists.

Scheduled Backup
Right‐click Scheduled Jobs, ION_Data or ION_Network and select Backup to 
display the Scheduled Backup dialog box.

Both the ION_Data and the ION_Network databases have scheduled backup tasks 
configured and enabled by default. The save location is a different folder for each 
database, although both databases share the same parent directory: \ION 
Enterprise\config\cfg\DBBackups\.

From the “Database to backup” list, select the database for which you want to 
configure the scheduled backup.
In the “Save backup to” field, enter the location where you want to save the 
backups.
In the “Number of backups to keep” section, specify the number of backups — 1 
to 4 — that Database Manager keeps available.
Ensure that “Schedule enabled” is selected if you want to enable the scheduled 
backup.

Changing the Schedule


Click the Change button in the Schedule section. The Edit Schedule dialog 
appears where you can reconfigure the frequency and time of the scheduled 
backup.

NOTE
Do not schedule scheduled backups to begin at the same time (i.e., do not schedule a backup of the
ION_Data and a backup of the ION_Network at the same time). This can cause problems with the task.

© 2009 Schneider Electric. All rights reserved. Page 271


Scheduled Backup PowerLogic ION Enterprise User Guide

The Edit Schedule dialog box differs depending on what you select in the Occurs 
section.
Daily: Set the frequency in days. For example, to set the backup to occur every 
seven days, set the frequency to 7.
Weekly: Set the frequency in weeks and select the days of the week on which 
you want the backup to occur. You can select multiple days of the week. For 
example, to set the backup to occur every two weeks on Monday and Thursday, 
set the frequency to 2 and select Monday and Thursday from the list of days.
Monthly: Set the frequency then select Fixed Day or Relative Day to set the day 
of the month on which the trim occurs.
Frequency: Depending on your version of SQL Server, click Select Months 
to select the months in which you want the backup to occur or set the 
Frequency in number of months.
Fixed Day: The backup occurs on the specified date at the frequency 
specified (in months). For example, to set the backup to occur on the 15th 
day of every month, select every month (or set Frequency to 1) and Fixed 
Day to 15.
Relative Day: The backup occurs on the specified day of the month at the 
specified frequency (in months). For example, to set the backup to occur on 
the second Sunday of every third month, set Frequency to 3 (or select which 
months you want to the backup to occur in) and select 2nd and Sunday from 
the Relative day dropdown lists.

Page 272 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Optimizing Database Query Time

Optimizing Database Query Time


There are steps you can take to optimize the database query time:
Use Database Manager to defragment the appropriate database.
Use Database Manager to Update Statistics on the appropriate database.
Run only one instance of SQL Server 2005.
Run SQL Server 2005 Standard Edition instead of SQL Server 2005 Express 
Edition.

NOTE
Instructions on how to perform the Defragment and Update Statistics operations can be found in the
section “Manual Tasks” on page 260.

Limiting SQL Server Memory Usage


By default, SQL Server 2005 Standard Edition and SQL Server 2005 Express Edition 
are configured to dynamically adjust the amount of memory used based on 
demand.

Under some circumstances, it is possible for SQL Server to use up memory to a 
point where the overall system performance is affected. You can adjust the amount 
of memory reserved by using a configuration tool such as Microsoft SQL Server 
Management Studio.

Using SQL Server 2005 Management Studio to Limit Memory Usage


1. On the Object Explorer pane, right‐click the SQL Server instance that 
corresponds to the ION Enterprise database (i.e., the database icon at the root 
level of the tree‐view), then select Properties.
2. In the “Select a page” section, select Memory.
3. Use the controls on the Memory page to adjust the memory allocation.
4. Click OK.

© 2009 Schneider Electric. All rights reserved. Page 273


Log Inserter PowerLogic ION Enterprise User Guide

Log Inserter
The Log Inserter component of ION Enterprise automatically configures itself to 
collect data from every available recorder in every device or ION Enterprise 
software component and inputs this data into the database. Log Inserter is 
typically run only on the Primary workstation. 

Most systems use only a single Log Inserter which is automatically configured to 
perform all required logging functions. The default configuration will work for 
most systems. Situations where changes may be required include systems with 
large numbers of devices with logs, systems with primary and secondary servers 
or cases where only specific devices and/or logs need to be monitored for new 
records. If any of these situations apply to your system, contact Technical Support 
for more information on the operation of Log Inserter, its different modes of 
operation and the functions of its internal components.

Page 274 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Accessing the ION Database with 3rd-Party Applications

Accessing the ION Database with 3rd-Party


Applications
The following example uses Microsoft Excel 2007 to retrieve data from the 
ION_Data database.

NOTE
The database uses Universal Coordinated Time (UTC) time. When you import data into Excel, the meter’s
Clock module’s Time Zone Offset register is applied.

1. To create a database query in Excel, click Data > From Other Sources > From 
Microsoft Query.
2. To create a new data source, select <New Data Source> from the list and click 
OK.
3. Type the name you want to give the data source. Once you type a name, the list 
of drivers for the database type becomes available. Select <SQL Server> from the 
list. Click Connect.
4. Choose your server from the list. Provide your LoginID and Password and click 
OK. Select a default table for your data source (optional). Click OK to continue.
5. Select the source name you created and click OK.
6. After you have selected the data you want to view, the Query Wizard appears. 
Use this to filter and sort the data.
7. Follow the steps in the Query Wizard to add data to the Spreadsheet.

© 2009 Schneider Electric. All rights reserved. Page 275


Accessing the ION Database with 3rd-Party Applications PowerLogic ION Enterprise User Guide

Page 276 © 2009 Schneider Electric. All rights reserved.


9 Modbus Device Importer
The Modbus Device Importer utility enables ION Enterprise software to recognize 
and easily integrate third‐party Modbus devices into the ION Enterprise network. 

In This Section

“Introduction” on page 278
“ION Object Descriptions” on page 281
“Main Console Screen” on page 283
“Main Toolbar” on page 284
“Editing a Register” on page 291
“Register Properties Defined” on page 291
“Shortcut Keys” on page 296
“Data Formats” on page 299
“Configuring Logging and Calculation” on page 301

© 2009 Schneider Electric. All rights reserved. Page 277


Introduction PowerLogic ION Enterprise User Guide

Introduction
The Modbus Device Importer is a tool for advanced users that creates the files and 
software support necessary to display data from any Modbus device using the 
Vista component of ION Enterprise. The Modbus Device Importer user interface 
sets up useful common Modbus parameters by default, but also allows you to 
configure all Modbus‐specific and device‐related parameters. The Modbus Device 
Importer also has built‐in error checking to validate the files you created, or those 
from other sources.

Process Overview
Creating a new Modbus device type involves the following steps:
1. Identify the new device type (device name, file name, etc.)
2. Create a Modbus map file for the device type:
Identify a Modbus register to be added.
Find an appropriate register to map to in the ION tree.
Select appropriate data format, scaling factors, etc.
3. Configure additional Modbus device functionality (if required).
4. Validate and check the device type.
5. Add the new Modbus device type to the ION_Network database.

After it is defined in the ION_Network database, the new Modbus device is 
available in ION Enterprise just like any other device. Simply select the Modbus 
device type from the dropdown list.

Default Modbus Device Types


ION Enterprise is shipped with numerous pre‐configured Modbus device types. 
For a complete list, navigate to Tools > View current Device Types from the 
Modbus Device Importer main console. These pre‐configured device types can 
also be modified as required, using the Modbus Device Importer.

The ION Tree File


The Modbus Device Importer creates and edits ION tree files (.ion) for the device, 
which are then saved and entered into the ION_Network, allowing ION Enterprise 
to recognize and use the device. The tree file defines the organization of the ION 
managers, modules and registers.

The Modbus Map File


The Modbus Device Importer creates and edits mapping files for the device, 
linking Modbus registers with ION registers. A Modbus map file is an XML file 
that must refer to the XML schema defined in /.../ config/translators/modbus‐
schema.xml. 

Page 278 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Introduction

It also defines how to convert the module register value into the value shown in 
the ION register.

Map File Format


Each distinct Modbus device type has its own special address ranges and requires 
its own Modbus map file. Vln avg, on an ION6200, for example, is located at 40103. 
It could be in a different location on any other device. In either case, it would be 
most logically mapped to the Power Meter Moduleʹs Vln avg output register 
(0x5803) in the default tree.

The example map file shown below illustrates the map file format:
<?xml version=ʺ1.0ʺ encoding=ʺUTF‐8ʺ?>

<!‐‐Created by Modbus Device Importer v 3.21.0 at: 3/22/2007 10:41:56 AM‐‐>

<ModbusMap xmlns=ʺx‐schema:modbus‐schema.xmlʺ>

<DeviceInfo Type=ʺExample Deviceʺ MultiplePresetSupported=ʺ0ʺ 
GlobalNotAvailable=ʺNotSpecifiedʺ MaxRequestRegisters=ʺ125ʺ 
LowSpeedUpdateRate=ʺ30ʺ HighSpeedUpdateRate=ʺ5ʺ/>

<ModbusInfo IONHandle=ʺ134217729ʺ Name=ʺBaud Rateʺ 
ModbusAddress=ʺ40001ʺ RequestType=ʺRWʺ Format=ʺUINT16ʺ Scale=ʺ1ʺ 
Offset=ʺ0ʺ Multiplier=ʺ1ʺ DefaultEnumValue=ʺInvalid Dataʺ>

<Enumeration Value=ʺ300 Baudʺ/>

<Enumeration Value=ʺ2400 Baudʺ/>

<Enumeration Value=ʺ9600 Baudʺ/>

<Enumeration Value=ʺ115200 Baudʺ/>

</ModbusInfo>

<ModbusInfo IONHandle=ʺ134217985ʺ Name=ʺVoltsA@!!DeviceName!!Meter01ʺ 
ModbusAddress=ʺ40002ʺ RequestType=ʺRʺ Format=ʺUINT16ʺ Scale=ʺ1ʺ Offset=ʺ0ʺ 
Multiplier=ʺ1ʺ/>

<ModbusInfo IONHandle=ʺ134217986ʺ Name=ʺVoltsB@Meter01ʺ 
ModbusAddress=ʺ40003ʺ RequestType=ʺRʺ Format=ʺUINT16ʺ Scale=ʺ1ʺ Offset=ʺ0ʺ 
Multiplier=ʺ1ʺ/>

<ModbusInfo IONHandle=ʺ134217987ʺ Name=ʺVoltsC@Meter01ʺ 
ModbusAddress=ʺ40004ʺ RequestType=ʺRʺ Format=ʺUINT16ʺ Scale=ʺ1ʺ Offset=ʺ0ʺ 
Multiplier=ʺ1ʺ/>

<CalcInfo IONHandle=ʺ135266304ʺ Name=ʺAveraging 1ʺ 
Function=ʺAveraging_Moduleʺ/>

<CalcInfo IONHandle=ʺ136314880ʺ Name=ʺMinimum 1ʺ 
Function=ʺMinimum_Moduleʺ/>

© 2009 Schneider Electric. All rights reserved. Page 279


Introduction PowerLogic ION Enterprise User Guide

<CalcInfo IONHandle=ʺ137363456ʺ Name=ʺMaximum 1ʺ 
Function=ʺMaximum_Moduleʺ/>

<CalcInfo IONHandle=ʺ138412032ʺ Name=ʺData Rec 1ʺ 
Function=ʺDataRecorder_Moduleʺ/>

<CalcInfo IONHandle=ʺ139460608ʺ Name=ʺFeedback 1ʺ 
Function=ʺFeedback_Moduleʺ/>

<CalcInfo IONHandle=ʺ140509184ʺ Name=ʺPeriodic Tmr 1ʺ 
Function=ʺPeriodicTimer_Moduleʺ/>

<CalcInfo IONHandle=ʺ131072000ʺ Name=ʺDiagnostics 1ʺ 
Function=ʺDiagnostics_Moduleʺ/>

</ModbusMap>

Page 280 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide ION Object Descriptions

ION Object Descriptions


ION objects are software items that are recognized by ION Enterprise software. 
ION objects consist of device managers, modules, and registers. Managers 
separate different module types and groups together modules of the same type. 
Modules group registers into convenient or logical groups. Registers are the 
objects that actually hold the Modbus register information.

For more information on ION architecture, refer to the ION Reference.

Managers
Managers organize the Modbus map file into a formatted structure. There are three 
different types of managers supported in the Modbus Device Importer:
External Boolean Manager: holds Boolean type registers
External Numeric Manager: holds Numeric type registers
External Pulse Manager: holds Pulse type registers

You can create up to 127 managers. After you create a manager, you cannot change 
its manager type.

Modules
Similar to managers, modules also help organize the map file structure. You can 
create up to 4095 modules inside a given manager. Use modules to arrange 
registers into logical groupings or similar register types. When naming a module, 
choose a name that is relevant to the type of registers it contains. Modules inherit 
the class type of their parent manager, so you cannot change a module type after 
is has been created.

Registers
A register is an object that can be linked to a physical register on a Modbus device, 
where data is read from or written to. You can map registers to a Modbus address, 
then use Vista to read and write data to this Modbus device.

When you create a register, it inherits the type of its parent module. You can create 
up to 255 registers per module.

There are three different register types:

Boolean Registers
Boolean registers hold Boolean data, i.e., a logical True or False (1 or 0). You can 
attach a label to the register to indicate an ON or OFF state. If a numeric register is 
mapped to a Boolean register, a value of “0” (zero) puts the Boolean register in an 
OFF state, while any other value turns the Boolean register ON (unless a mask is 
applied).

© 2009 Schneider Electric. All rights reserved. Page 281


Registers PowerLogic ION Enterprise User Guide

If any of the bits exposed by the mask are set, the value is interpreted as a ‘True’. 
Otherwise it is interpreted as ‘False’. MaskedBool can be used to sift out individual 
Booleans that are stored as arrays of bits in Modbus. If no mask is specified, all bits 
are relevant. Boolean registers can be 16 or 32 bits long.

Numeric Registers
Numeric registers hold numeric data.

Pulse Registers
Pulse registers are used in Vista to send a pulse to the specified address. They are 
used specifically to write values to a device. The user can specify the exact value to 
send out as a pulse for each register. Pulse registers can only write 16 bits worth of 
data.

Factory Registers
You cannot add or remove Factory objects but you can edit them. All Factory 
registers are initially set to a default constant value. You can change these constant 
values, or map the registers to a valid Modbus address (see “Editing a Register” on 
page 291). There are four user defined factory registers that you can change if the 
required registers are not already present in the default list.

Page 282 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Main Console Screen

Main Console Screen


To open Modbus Device Importer, start Management Console then select 
Tools > System > Modbus Device Importer.

The main console screen appears:

Configure Logging and


Calculation button

ION Map Information Pane Modbus Register Information Pane

The main console is where most actions are performed and ION objects are 
managed. The device managers, modules, and registers are displayed in the ION 
Map Information Pane on the left hand side of the screen. Information specific to 
registers is displayed on the right hand side of the screen in the Modbus Register 
Information Pane. If you select an object in the tree, all registers below it have their 
information displayed. 

Navigate through the tree‐view by clicking on the specific objects or by using the 
arrow keys on the keyboard.

When the application is started or the File > New menu is selected, a default 
configuration is loaded. The only object included in the default configuration is the 
factory manager and associated registers. By default you cannot specifically see 
the factory objects so a blank template is displayed. 

© 2009 Schneider Electric. All rights reserved. Page 283


Main Toolbar PowerLogic ION Enterprise User Guide

Main Toolbar

File Menu
Select File on the main toolbar to access the following menu items:
New: Creates a new, blank map file.
Open: Opens an existing map file.
Save: Saves the current map file template and the corresponding ION tree file 
template.
Save As: Lets you save the current map template to a different location.
Exit: Closes the program.

The File menu also lists the most recently opened device templates.

Edit Menu
You can add new objects by either right‐clicking in the ION Map Information pane 
or selecting the appropriate option from the Edit menu.

Objects are placed either as children or siblings. For example, you may add a new 
manager to the device (sibling of an existing manager) or a new module to an 
existing manager (child of a manager). The same relationship applies to modules 
and registers.

New Manager: Adds a new manager.

Adding a New Manager


1. Click Edit > New Manager. The Add New Manager dialog box appears. 
2. Type a name for the manager.
3. Select a manager type from the drop‐down list: External Boolean Manager, 
External Numeric Manager, or External Pulse Manager.

NOTE
The manager type you choose determines parameters in the modules and registers under it.

4. Click OK.

Page 284 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Edit Menu

New Module: Adds a new module.

Adding a New Module


1. Click Edit > New Module. The Add New Module dialog box appears.
2. Type a name for the module. 
The default is the next available number of that module type within the current 
manager (e.g., Ext Num 3). The name of the module determines the default 
names of the registers under it. Note that the module name can be changed later, 
if required.
3. Click OK.

NOTE
Duplicate names are permitted but not recommended.

New Register: Adds a new register. See “Editing a Register” on page 291 for 
more information on using this dialog box.
New Register (Quick): Adds a new register, using all default settings. No dialog 
box is associated with this command unless no registers currently exist in the 
target module (in that case, it is treated as creating a new register with a dialog 
box).
The Modbus address is automatically incremented as appropriate based on the 
register type and size.

Copying and Pasting Objects


You can copy and paste modules and registers. After you copy an object, you can 
paste it into a different location in the tree. You cannot paste registers or modules 
from one class type to another (i.e., you cannot copy a Boolean register and paste 
it into a numeric module).

Copy: Copies your selection(s) to the clipboard.

There are three different paste options: Paste, Paste Clone and Paste Multiple.
Paste: Pasting registers will normally automatically increments the Modbus 
address based on the register data type. In the case of MaskedBool, it increments 
the bit mask by one until it reaches 0x8000, when the Modbus address 
increments by one and the mask resets to 0x0001.   
The new register label is reset to a default label such as “Power Meter 
Module.0004”.
Paste Clone: Pasting a Clone is the same as pasting normally with the exception 
that the Modbus address of the register is not increased. This is a useful feature 
for pasting multiple registers with the same Modbus address but applying 
different masks.
The new register label is reset to a default label such as “Power Meter 
Module.0004”.

© 2009 Schneider Electric. All rights reserved. Page 285


View Menu PowerLogic ION Enterprise User Guide

Paste Multiple: Pasting multiple copies simply performs a normal paste a 
determined number of times, each copy incrementing the address the 
appropriate number of addresses.

Moving Objects
You can move both modules and registers. This is done by selecting the desired 
object(s) in either the ION Map Information pane or Modbus Register Information 
pane and then holding down the ALT key. You can move the module or register 
to any other holding object, but it must be moved to the same data type.

Editing Objects
To edit objects in the Modbus Device Importer, right‐click on them and select 
Advanced Properties. See “Editing a Register” on page 291 for more information.

Deleting Selected <type of object>


To delete objects in the Modbus Device Importer, right‐click on them and select 
Delete selected <type of object>. If you delete an object, all children (objects 
beneath it) are also deleted. To delete multiple registers at once, select them in the 
Modbus Register Information pane and then click “Delete selected Registers”.

Advanced Properties
Select this menu item to open the Device Properties dialog box. You can also open 
this dialog box using View > Device Properties. For more information regarding 
device properties, see “View Menu” on page 286.

View Menu
The following menu items are accessed by clicking View on the main toolbar.
Refresh: Refreshes the main console screen.
Collapse All: Collapses the tree view.
Device Properties: Click View > Device Properties (or right‐click on the tree‐
view root and select Properties). The Device Properties dialog box appears:

Device Properties Tab
Device Type: Type the name of the Device Type.
Default Diagram Template Label field: This is used if the device has a 
default Vista diagram. The string entered in this field is an internal identifier 
and is only used if the “Add Generate Network Diagram Support” feature is 
used; see “Tools Menu” on page 287 for more information. 

NOTE
Changes made here are not be reflected in ION Enterprise until you add or update the device type.

Factory Information Tab

Page 286 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Tools Menu

These fields are used to identify the device type. By default, all values are 
constant values, but you can map them to Modbus registers if required.
Advanced Tab
Maximum number of registers for a single request setting: The maximum 
number of registers requested for the device can be set anywhere from 1 to 
125. It is recommended that you do not change this setting unless the 
specific device has special requirements.
Multiple Preset Write check box: Be sure that you match this check box 
with the device type. Select the check box if the device type supports 
Multiple Preset Write for registers and coils; clear the check box if the device 
type only supports Single Preset Write.
Disable “‐1” check box: This is a special feature for ION meters. ION meters 
return a “‐1” if a specified register is not available and the system interprets 
that value as a control signal. Most devices use the value of –1 as a valid data 
value, so it is recommended that this feature is turned off for all non ION 
meters.
Requested update period for any calculated registers setting: Enter a 
number (in seconds) to specify how often the physical Modbus device is 
polled to update the registers used for calculations.

Tools Menu
Select the Tools menu on the main toolbar to access the following menu items:
Add Device Type: After you correctly configure and save a device, you can add 
it to the ION_Network database.
By adding a device to the ION_Network database, you can now create new 
devices of the device type in Management Console. Before you can add the 
device type, you must go to the Device Properties and configure the device (See 
“View Menu” on page 286).

© 2009 Schneider Electric. All rights reserved. Page 287


Tools Menu PowerLogic ION Enterprise User Guide

To add the device type click Tools > Add Device Type. After the device type is 
added, a new screen appears that shows the device types currently in the 
ION_Network database (See “View Current Device Types”). Ensure that the 
device type you added is present and the configuration is correct. 
Update Device Type: If you add a device type to the ION_Network database 
but changes were made to the template, then you can update the ION_Network 
database to reflect these changes.
You are notified if the update is successful or not. If it fails, you must remove 
any devices of the specified device type from Management Console and then 
update to the ION_Network database again.

NOTE
The ION_Network database update may fail if the device type you are updating is currently being used
in Management Console. If this occurs you must remove all devices of the specified type before the
update will be successful, or contact Technical Support for possible workarounds.

Add “Generate Network Diagram” Support: If a Vista diagram has been 
created for a device type, then you can set it up as the default network diagram 
in Vista.
This enables all devices which are of the new device type to have default 
diagrams in Vista when the “Generate Network Diagram” feature is utilized. It 
is recommended that the default Vista diagram is created before running this 
feature.
You must configure the following factory registers in order for this feature to 
work correctly:
FAC1 Device Type register 
This register must have a constant value. This is set in the Device Properties 
window as the Device Type. Use a descriptive name that easily identifies the 
device.
FAC1 Template register 
This register must have a constant value. Use something specific to the current 
register. For example, a device called “Test_Device” could be 
“Test_Device_Rev1.0.3”.   The template should reflect the device type, as well 
as the current version, to avoid future confusion if similar devices are added.

NOTE
Both of these registers must have constant values. Modbus Device Importer does not support the “Add
Generate Network Diagram support” feature for devices that get either of these register values
dynamically (i.e., mapped to a Modbus register).

After you enter the correct register values, you can find the “Add Generate 
Network Diagram support” feature under the Tools menu. This feature is very 
useful if you have multiple versions of a specific device type. 
This feature creates the necessary registry keys and set up the required 
directory structure for generating a network diagram. 

Page 288 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Tools Menu

NOTE
By default, the diagram is a blank diagram. You must modify this diagram to actually correspond to the
specified device.

Save ION Handle List: This command saves a list of the registers along with 
their corresponding ION handles. You can use this list to create a Vista diagram 
without an active device connected. 
The list is saved as a text file in the current Modbus Device Importer installation 
folder. The name of the text file is in the format <currentDeviceName>.csv.
Validate Template: This command lets you validate the current configuration.
Doing this performs various validation and integrity tests on the current 
configuration of the ION and Modbus objects. It lists potential errors such as 
registers that share the same Modbus register address or registers that have 
conflicting masks. The error checks that are performed can be toggled on or off, 
using the check boxes in the dialog box: general issues, address conflicts, 
handle conflicts, label conflicts, and name conflicts.

NOTE
You must manually fix any errors or else you cannot add or update the device type.

View current Device Types: This command allows you to view the device types 
currently in the ION_Network database.
 

From here you can delete old device types that are not being used. 
Note that you may see multiple entries for the same physical device in the 
device type listings (for example, 6200 RTU and 6200 ModTCP). The Modbus 
Device Importer classifies each different protocol as a separate device type.

© 2009 Schneider Electric. All rights reserved. Page 289


Settings Menu PowerLogic ION Enterprise User Guide

NOTE
You cannot delete a device type that is currently being used by Management Console.

Calculator: This loads the default Windows calculator.

Settings Menu
Select Settings on the main toolbar to access the following menu items:
Change Default Template Path: The default template path is used for loading a 
new template. Use this command to change the path if required.
Enable Auto‐Validation: This is selected by default.
Start Application Maximized: This sets the Modbus Device Importer window 
to open in a maximized state.
Show Properties Window on Double‐Click: Allows an object’s property 
window to open if the object is double‐clicked in the ION Map Information 
pane.
Auto Select Text on Edit in Register Information: Allows a field that is clicked 
on in the Modbus Register Information pane be fully selected when the edit 
screen opens. This is useful if you need to change the entire field.
Advanced: You can access two features from this sub‐menu:
Show Factory Objects: Makes the factory objects visible in the ION Map 
Information pane. With this feature enabled, you can edit the properties of 
the Factory objects.
Show Modbus Addresses Offset in Hex: With this feature enabled, all 
Modbus addresses in the Modbus Register Information pane are displayed 
in hexadecimal format.

NOTE
If this setting is enabled, registers cannot be edited in the Modbus Register Information pane.

Help Menu
Select Help on the main toolbar to access the following menu items:
About: Provides version information for the program.
Modbus Device Importer Help: Opens the Help file for the program.

Configure Logging and Calculation Button


Click this button to enter the Configure Logging and Calculation utility. This 
screen allows you to configure advanced functions for Modbus devices, such as 
enabling logging, and should only be used by advanced users. See the 
“Configuring Logging and Calculation” on page 301 for more information.

Page 290 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Editing a Register

Editing a Register
To edit a register, right‐click on the register in the ION Map Information pane and 
select Advanced Properties. The following dialog box displays the register 
information. Depending on the type of register being edited, different data fields 
may appear.

You can also double‐click the register in the Modbus Register Information pane to 
edit it. This is a faster way to edit basic register properties. When the Edit Mode is 
initiated in the Modbus Register Information pane, the selected register opens up 
into an edit mode:

To scroll through the list in Edit mode, use the PAGE UP and PAGE DOWN keys. 
After editing the values, press ENTER to save the changes.

NOTE
If you use the PAGE UP and PAGE DOWN keys, the changes made are saved as if ENTER was pressed.

To cancel any changes, press the ESC key.

Register Properties Defined


The following register properties can be configured:

Register Label
The label is a description attached to the register. You can change this value at any 
time; it is only an identifier for the register.

© 2009 Schneider Electric. All rights reserved. Page 291


Register Properties Defined PowerLogic ION Enterprise User Guide

NOTE
The register label string has a maximum character limit of 50, including spaces. Keep this in mind
especially when creating labels for downstream devices since they may require additional space in the
label name.

Make this Register a Constant Value


If this check box is cleared, then the ION register is mapped to a Modbus register 
and, when viewing it in Vista, you see the real values from the meter. If this check 
box is selected, then it is set to a constant value. You can use a constant value to 
hold dynamic constant values, device identification or other values. 

ION Setup Register


You can configure any register to be an ION setup register. Setup registers do not 
appear in the Vista register list unless you select to view the setup registers.

NOTE
This does not affect the read/write capabilities of a valid Modbus register; it is a feature specific to Vista.

Data Type
This data type is used for decoding the values returned from the meter. The 
selected data type format must match the format delivered by the device. Each 
supported data type is explained in “Additional Information” on page 299.

Register Type
This is a convenient way to change the Modbus register type. It only changes the 
most significant number in the Modbus address to correspond to the specified 
register type. This register type must match the register type specified by the 
device documentation. The register type also determines the Modbus function 
code used when talking to the device.

Modbus Address
This is the physical address of the specified register. You can find this number in 
the device documentation, and you can enter the number in either decimal or 
hexadecimal format. Address ranges correspond to register types as follows:

COIL STATUS = 0xxxx
INPUT STATUS = 1xxxx
INPUT REGISTER = 3xxxx
HOLDING REGISTER = 4xxxx

NOTE
When entered in hexadecimal format, the value is only the register offset and does not include the
Register Type identification.

Request Type
This tells the system whether or not it can read (R), write (W) or do both (RW) 
actions to the specified register.

Page 292 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Register Properties Defined

Register Mask
This mask is applied to the raw data received from the register. The mask is 
applied in an AND fashion. 

For example, if the mask “0x4” is applied, then the register value displayed is only 
nonzero if the 3rd least significant bit in the register is a 1. 

You can apply masks to both numeric and Boolean data types. To apply custom 
masks, scroll down the list and select Custom. When prompted, enter the value in 
Decimal, Binary, or Hexadecimal format.

NOTE
For integer values, the bit order of the mask corresponds to the bit order of the actual data and NOT the
order in which the bytes representing the data are returned over Modbus. The high-order nibble of a 32-
bit value is selected as ‘0xf0000000’ regardless of whether the format is U32_4321 or U32_2143. It
should also be noted that the resulting value of a masked integer is NOT bit shifted. A mask of ‘0xf000’
applied to a 16-bit value of ‘0x1234’ results in ‘0x1000’ (4096 decimal) and NOT 1.

Register Scale and Register Multiplier


This specifies what the scale factor of the data being requested should be. The scale 
can be set to any constant decimal value within the range of ‐3.402823466 E + 38 to 
3.402823466 E + 38. If you can obtain the scale for a specific register from the device, 
then you can map the scale value to another register. You can only map the scale 
factor to registers already created in the Modbus Device Importer. 

The mapped register used can be a valid Modbus mapped register or a register 
with a constant value. Mapping the scale to a constant register is a convenient 
feature; you can change the scale for many registers by changing the constant 
value in one location.

Mapping the Scale Factor to Another Register


1. Select the Reference another register for the scale check box. The Select 
Register for Reference dialog box appears.

2. Use the dropdown lists to navigate to the required register. Click OK.
The scale to be used now appears in the Register Scale field.

© 2009 Schneider Electric. All rights reserved. Page 293


Register Properties Defined PowerLogic ION Enterprise User Guide

Register Offset
The register offset is used if the register value returned must be offset by a value. 

The scale can be set to any constant decimal value within the range of ‐3.402823466 
E + 38 to 3.402823466 E + 38

NOTE
If “10” is entered, then 10 is subtracted from the received value. To add 10, enter “-10”.

Scale / Multiplier and Offset applied:

Modbus value = scale * ION value + offset (1)

multiplier

OR

ION value = (Modbus value - offset) * multiplier (2)

scale

If the offset for a specific register can be obtained from the device then you can map 
the offset value to another register. You can only map the offset factor to registers 
already created in the Modbus Device Importer. 

The mapped register used can be a valid Modbus mapped register or a register 
with a constant value. 

Mapping the offset to a constant register is a convenient feature; you can change 
the offset for many registers by changing the constant value in one location.

Mapping the Offset Factor to Another Register


1. Select the Reference another register for Offset check box.
2. Use the drop‐down menus to navigate to the required register. Click OK.
The offset to be used now appears in the Register Offset field.

Register Not Available Value


If the register has a control signal value to indicate that the register is currently not 
available, then you can set the value here. The value must match the data that is 
received from the register on the device. If a value is received that matches this 
property value, the string “Not Available” is displayed when viewing the register 
in Vista.

Boolean Labels
This option is only available for Boolean registers. It allows you to set default labels 
for Status Objects in Vista.

Page 294 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Register Properties Defined

Value to Send Out as a Pulse


This option is only available for pulse registers. It allows you to specify the exact 
Modbus value sent to the device when a pulse register is activated in Vista.

Constant String Value


A constant for manipulating data retrieved from the device. 

Number of Registers to Request


This option is only available if the data type is set to ASCII, ASCII‐Reverse or 
Packed BCD. It allows you to specify the number of registers to retrieve from the 
device on a request.

Enumeration
Enumeration is useful for converting numeric value representation into human 
readable string values.

For example, you can use enumeration on a Baud rate register. The value is 
represented as a number from 0 to 3, where 0 = 300 Baud and 3 = 115200 Baud. With 
enumeration you can map the return values to corresponding string values. In 
Vista, when you view the register, it displays the corresponding string value 
instead of the actual return value.

You can also use enumeration to generate non‐contiguous scaling values for other 
registers. For example, a Modbus scale register returns ‐2, ‐1, 0, +1 and +2, which 
indicate scaling of 10‐2, 10‐1, 1, 101 and 102 respectively. In this case, use an 
enumerated ordinal of ‐2 through +2 with enumerated labels “0.01” through “100”.

You can access enumeration for a register from the register properties window, the 
Edit Mode window and also from the toolbar. 

When selected, the following screen appears:

To add or remove enumeration values, select them and click Add New or Remove. 
When new enumerations are added, they are appended to the bottom of the list 
and are given the next sequential ordinal value. You can relocate values up and 
down with the up and down arrow and buttons. 

To change the ordinal value for the enumerations, double‐click in the Ordinal 
Values list. The change propagates down to the bottom of the list, ensuring that the 
list goes from smallest number to largest number.

© 2009 Schneider Electric. All rights reserved. Page 295


Shortcut Keys PowerLogic ION Enterprise User Guide

Shortcut Keys

General Key Shortcuts

Keystrokes Action

CTRL-N Opens a new template (after a save prompt).

CTRL-O Opens an existing template (after a save prompt).

CTRL-S Quick saves the current template.

CTRL-A Saves the current template in a new location.

CTRL-D Adds the device to the ION_Network database.

CTRL-U Updates the device in the ION_Network database.

CTRL-G Adds Network diagram support for the device to the system.

CTRL-P Opens the device properties window.

Refreshes the ION Map Information pane, collapsing all nodes except the
F5
currently selected node.

F6 Collapses all nodes in the tree-view.


F11 Saves the current ION Handle list.

F12 Views the current device types in the ION_Network database.

Register Quick Edit Mode

Keystrokes Action

TAB Cycles through the data fields.

Enter Saves the changes to the current register and exits edit mode.
Saves the changes to the current register and displays the edit mode for the
Page Up
register above the current register.
Saves the changes to the current register and displays the edit mode for the
Page Down
register below the current register.

Escape or Mouse-
Cancels the changes to the current register and exits edit mode.
Wheel Click

Page 296 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide ION Map Information Pane

ION Map Information Pane

Keystrokes Action

Right Arrow Expands a node or selects a child if children are already expanded.

Left Arrow Collapses a node or selects a parent node if no children are expanded.

Up Arrow Scrolls up through the list of nodes.

Down Arrow Scrolls down through the list of nodes.

Mouse Right-
Brings up the pop-up edit menu.
Click

Enter, Space Bar


Opens the properties window for the selected object.
or CTRL-X

If the root device type is selected, a new manager is created and the manager
F1
properties window is displayed.

If a manager is selected, a new module is created and the module properties


F2
window is displayed.

If a module is selected, a new register is created and the register properties


F3
window is displayed.

If a module is selected, a new register is created but the register properties


F4
window is not displayed.

- It is equivalent to F1, F2 or F3 depending on which object is currently selected.


Insert
- If a register is selected then the enumeration window is displayed.

- If a manager is selected, a prompt to delete the manager is displayed.


Delete - If a module is selected, a prompt to delete the module is displayed.
- If a register is selected, a prompt to delete the register is displayed.

- If the object is a module it can be dragged and dropped into another manager
ALT + dragging of a similar class.
an object - If the object is a register it can be dragged and dropped into another module
of a similar class.

- If a module is selected, then the module is copied.


CTRL-C
- If a register is selected, then the register is copied.

- If a manager is selected and a module has been copied, then the module is
pasted.
CTRL-V
- If a module is selected and one or more registers have been copied, then the
registers are pasted.

If a module is selected and one or more registers have been copied, then the
CTRL-B
registers are clone pasted.

If a module is selected and one or more registers have been copied, then a
CTRL-Z
prompt comes up asking how many copies to paste.

© 2009 Schneider Electric. All rights reserved. Page 297


Modbus Register Information Pane PowerLogic ION Enterprise User Guide

Modbus Register Information Pane

Keystrokes Action

Up Arrow Scrolls up through the list of registers.

Down Arrow Scrolls down through the list of registers.

Mouse Right-
Brings up the pop-up edit menu.
Click
Enter, Space Bar
Opens the quick edit window for the selected register.
or CTRL-X
A new register is created in the module of the currently selected register and the
Insert or F3
register properties window is displayed.
A new register is created in the module of the currently selected register but the
F4
register properties window is not displayed.
Delete A prompt is displayed asking to confirm the delete of the selected registers.

ALT + dragging
The selected registers can be dragged and dropped over to a new module of
one or more
similar class in the tree-view.
objects

It is equivalent to F1, F2 or F3 depending on which object is currently selected. If


Insert
a register is selected then the Enumeration window is displayed.

- If a manager is selected a prompt to delete the manager is displayed.


Delete - If a module is selected a prompt to delete the module is displayed.
- If a register is selected a prompt to delete the register is displayed.

- If the object is a module it can be dragged and dropped into another manager
Holding ALT
of a similar class.
while dragging
- If the object is a register it can be dragged and dropped into another module
an object
of a similar class.

CTRL-C The selected registers are copied.

CTRL-V The registers that have been copied are pasted into the current module.

CTRL-B The registers that have been copied are clone pasted into the current module.

The registers that have been copied are pasted multiple times into the current
CTRL-Z
module. A prompt comes up asking how many copies to paste.

Page 298 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Additional Information

Additional Information

Data Formats
Typically, Modbus data is transmitted in big ENDIAN (big end in) format but 
alternates in which the individual 16‐bit words are swapped are not uncommon. 
The formats supported by ION Enterprise 6.0 are:

Format Type Description

SINT16 A 16-bit signed value in 2-1 (or big ENDIAN) format. The high order byte is first, the low-order byte second.

UINT16 A 16-bit unsigned value in 2-1 (or big ENDIAN) format. The high order byte is first, the low-order byte second.

A 32-bit signed value returned in two consecutive 16-bit registers. The high-order word is returned in the first
SINT32 or S32-4321
register, the low order word in the second. In effect, the 4 bytes are returned in 4-3-2-1 (or big ENDIAN) format.

A 32-bit unsigned value returned in two consecutive 16-bit registers. The high-order word is returned in the first
UINT32 or U32-4321
register, the low-order word in the second. In effect, the 4 bytes are returned in 4-3-2-1 (or big ENDIAN) format.

A 32-bit signed value returned in two consecutive 16-bit registers. Contrary to S32_4321, the high-order word is
S32-2143
returned in the second register, the high-order word in the first. In effect, the 4 bytes are returned in 2-1-4-3 format.
A 32-bit unsigned value returned in two consecutive 16-bit registers. Contrary to U32_4321, the high-order word is
U32-2143
returned in the second register, the low-order word in the first. In effect, the 4 bytes are returned in 2-1-4-3 format.
A 32-bit signed value returned in two consecutive 16-bit registers. The word stored in the first 16-bit register is
S32-MFP or
multiplied by 10000 and added to the word stored in the second 16-bit register. Also known as ‘signed Modulo
S32-M10k-4321
10000’.

A 32-bit unsigned value returned in two consecutive 16-bit registers. The word stored in the first 16-bit register is
U32-MFP or
multiplied by 10000 and added to the word stored in the second 16-bit register. Also known as ‘unsigned Modulo
U32-M10k-4321
10000’ or mod-10K.

A 32-bit signed value returned in two consecutive 16-bit registers. Contrary to S32_M10k_4321, the word stored in
S32-M10k-2143
the second 16-bit register is multiplied by 10000 and added to the word stored in the first 16-bit register.

A 32-bit unsigned value returned in two consecutive 16-bit registers. Contrary to U32_M10k_4321, the word stored
U32-M10k-2143
in the second 16-bit register is multiplied by 10000 and added to the word stored in the first 16-bit register.

A 48-bit signed value returned in three consecutive 16-bit registers. R3*10,000^2 + R2*10,000 + R1, where R3 is
S48-M10k-21-65
the last register and R1 is the first register. Each registers range is -9,999 to +9,999

A 48-bit unsigned value returned in three consecutive 16-bit registers. R3*10,000^2 + R2*10,000 + R1, where R3
U48-M10k-21-65
is the last register and R1 is the first register. Each registers range is 0 to +9,999

A 64-bit signed value returned in four consecutive 16-bit registers. R4*10,000^3 + R3*10,000^2 + R2*10,000
S64-M10k-21-87
+ R1, where R4 is the last register and R1 is the first register. Each registers range is -9,999 to +9,999

A 64-bit unsigned value returned in four consecutive 16-bit registers. R4*10,000^3 + R3*10,000^2 +
U64-M10k-21-87
R2*10,000 + R1, where R4 is the last register and R1 is the first register. Each registers range is 0 to +9,999

A 64-bit signed value returned in four consecutive 16-bit registers. The highest order word is returned in the first
S64-87-21 register, the lowest order word in the fourth. In effect, the 8 bytes are returned in 8-7-6-5-4-3-2-1 (or big ENDIAN)
format.

A 64-bit unsigned value returned in four consecutive 16-bit registers. The highest order word is returned in the first
U64-87-21 register, the lowest order word in the fourth. In effect, the 8 bytes are returned in 8-7-6-5-4-3-2-1 (or big ENDIAN)
format.

A 64-bit signed value returned in four consecutive 16-bit registers. The highest order word is returned in the fourth
S64-21-87 register, the lowest order word in the first. In effect, the 8 bytes are returned in 2-1-4-3-6-5-8-7 (or little ENDIAN)
format.

© 2009 Schneider Electric. All rights reserved. Page 299


Data Formats PowerLogic ION Enterprise User Guide

Format Type Description

A 64-bit unsigned value returned in four consecutive 16-bit registers. The highest order word is returned in the
U64-21-87 fourth register, the lowest order word in the first. In effect, the 8 bytes are returned in 2-1-4-3-6-5-8-7 (or little
ENDIAN) format.

A 16 bit signed value. Bits 1 to 15 bits are unsigned data. If bit 16 is 0 the value is positive, if bit 16 is 1 the value is
S16-1-15
negative.

A 32-bit IEEE floating point value returned in two consecutive 16-bit registers. The high-order word is returned in the
IEEEFloat or F32-4321
first register and the low order word in the second. In effect, the 4 bytes are returned in 4-3-2-1 format.

A 32-bit IEEE floating point value returned in two consecutive 16-bit registers. Contrary to F32_4321, the high-
SwappedFloat or
order word is returned in the second register and the low order word in the first. In effect, the 4 bytes are returned in
F32-2143
2-1-4-3 format.

A 16-bit value that is interpreted according to the bit pattern described by the Mask attribute. Bits exposed by the
mask can be read or written without affecting the value of other bits. Unmasked bits are interpreted as 0 on a read
MaskedBool or and are unaffected on a write. Undeclared bits of a mask are interpreted as unmasked (i.e., mask="0x7F" is
PackedBool interpreted as 0x007F). The value that is read or written is determined by using enumeration ordinals, described
below. If used for read-only Boolean data, enumerations are not required. If no mask is specified, all bits are
relevant.

PF-Nexus A 16 bit unsigned value, range 0 to 3999, representing 3 decimal places of accuracy.

BCD (Binary Coded A number is expressed as a sequence of decimal digits and then each decimal digit is encoded as an 8-bit binary
Decimal) number For example, decimal 92 is encoded as 00001001 00000010.

The following data types can have their length specified by the “Number of Registers to Request” setting.

A number is expressed as a sequence of decimal digits and then each decimal digit is encoded as an 4-bit binary
Packed BCD
number (nibble) For example, decimal 92 is encoded as 1001 0010.

A sequence of bytes representing the ASCII character set. Each word stores two ASCII characters. Trailing spaces are
ASCII
removed.

ASCII-Reverse Same as ASCII except every second character is in the reverse order.

Page 300 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Configuring Logging and Calculation

Configuring Logging and Calculation


Use the Configure Logging and Calculation utility to perform additional Modbus 
device configuration, including:
enabling register logging, including setting log frequency
enabling low (minimum), high (maximum) and mean (average) calculations and 
logging
configuring stale data settings
appending downstream device information to labels

NOTE
Only numeric output registers can be calculated and logged. All other types of registers (for example,
enumerated) do not appear on the Configure Logging and Calculation screen.

Screen Overview
Click the Configure Logging and Calculation button from the main Modbus 
Device Importer screen to open the application. 

The following screen appears:

Select this check box to


make the downstream Per-register Stale data
device columns appear edit area link Low area High area Mean area Help link

Global register edit area


Use this area to globally edit all
rows selected in the upper pane

© 2009 Schneider Electric. All rights reserved. Page 301


Configuring Register Logging PowerLogic ION Enterprise User Guide

All the register information from the main MDI screen is pre‐populated in this 
table when you open the application.

Show downstream device columns: Select this to show all the columns for 
selecting and setting the downstream device properties for registers.

Per‐register area: Use this area to individually configure registers.

Low area: Use this area to enable calculation and set logging of low values.

High area: Use this area to enable calculation and set logging of high values.

Mean area: Use this area to enable calculation and set logging of mean values.

Global register edit area: Use the bottom half of the screen to edit individual 
registers or multiple registers, after selecting them in the list.

Help link: Click this link to open the Modbus Device Importer online help.

Stale data link (All): Click this link to open the Configure Stale Data Settings 
dialog.

Filtering and sorting columns


See “Sorting Data in a Column” on page 24 and “Filtering Data in a Column” on 
page 24 for instructions on filtering and sorting.

Configuring Register Logging


To edit registers on an individual basis, select the row of the register and edit the 
cells in the row or use the editing tools in the Global area.

To edit more than one register, select the rows you want to configure similarly and 
use the editing tools in the Global area. 

Log: Select to enable logging of the register. 

Interval: This value determines the logging frequency for the register. Note that 
this value also controls the reset interval for the min, max and averaging modules, 
even if these calculations are not being logged. The valid range is 1 to 4,000,000 
seconds.

Page 302 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Configuring Low, High and Mean Calculation and Logging

Configuring Low, High and Mean Calculation and Logging


To edit the suffix used for Low, High and Mean, click on the applicable link. For 
example, if you change the suffix to Maximum, VoltsA High becomes VoltsA 
Maximum. 

Low
Select Calculate to enable calculation of low (minimum) values for this register. 
Select Log to enable logging of this value. Note how the label is appended to reflect 
that this is the low value.

High
Select Calculate to enable calculation of high (maximum) values for this register. 
Select Log to enable logging of this value. Note how the label is appended to reflect 
that this is the high value.

Mean
Select Calculate to enable calculation of mean (average) values for this register. 
Select Log to enable logging of this value. Note how the label is appended to reflect 
that this is the mean value.

Configuring Stale Data Settings


The “staleness” of data is measured from time data was last read from a physical 
device until the current time. 

Click the All (Stale Data) link to open the Configure Stale Data Settings dialog 
box.

Mark data stale after: Enter the time you want to elapse before data from this 
register is marked stale in the data recorder. The valid range is 0 to 7200 seconds.

When data is stale: Select how you want stale data values logged. The setting “log 
an empty row” logs an empty row in the data recorder, while “use last known 
value” logs the last non‐stale value in the data recorder until the end of the current 
interval.

NOTE
Stale data settings are global (they apply to all registers).

© 2009 Schneider Electric. All rights reserved. Page 303


Configuring Downstream Device Functionality PowerLogic ION Enterprise User Guide

Configuring Downstream Device Functionality


You must select the Show downstream device columns check box before you can 
edit downstream device functionality.

The screen appears as follows:

Select this check box to


make the downstream Is Downstream Downstream Include Name
device columns appear Device Device of Device

Is Downstream Device: Select this to indicate the register belongs to a 
downstream device. 

Downstream Device Name: Enter the name of the downstream device in this field. 
The register label is appended with this name. For example, if the device name is 
Meter01, the register label becomes VoltsA@Meter01.

NOTE
Using this option without also using the Include Name of Device Instance option causes multiple devices
to appear as a single device in your energy management system. Do not use this option on its own unless
only a single instance of this device is present in your system.

Include Name of Device Instance: Select this to append the actual device instance 
name to the register label. The placeholder !!DeviceName!! is then added to the 
label — the name of the actual device instance gets inserted when it is created in 
Management Console. 

Page 304 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Saving and Exiting

For example, if the device instance is named Device01:

VoltsA@!!DeviceName!!Meter01

is replaced with

VoltsA@Device01Meter01

This allows easy creation of unique names within ION Enterprise, as well as 
enabling each device instance to appear in ION Enterprise as multiple virtual 
devices.

For more information on downstream devices and naming conventions, see 
“Downstream Device Assistant” on page 313.

Saving and Exiting


To exit the Configure Logging and Calculation screen:
Click OK to save your settings.
Click Cancel to exit without saving.

You are returned to the main Modbus Device Importer console screen.

1. Click File > Save to save the template files.
2. Click Tools > Update Device Type to send the template file changes to the 
ION_Network database.

© 2009 Schneider Electric. All rights reserved. Page 305


Saving and Exiting PowerLogic ION Enterprise User Guide

Page 306 © 2009 Schneider Electric. All rights reserved.


10 ION Alert Monitor
The ION Alert Monitor receives and processes alarm notifications coming from 
modem‐connected meters on remote power monitoring locations.

In This Section

“ION Alert Monitor” on page 308
“How It Works” on page 308
“Setting Up the ION Alert Monitor” on page 309
“Starting the ION Alert Monitor” on page 312

© 2009 Schneider Electric. All rights reserved. Page 307


ION Alert Monitor PowerLogic ION Enterprise User Guide

ION Alert Monitor


ION Alert Monitor is a Windows service (“ION Alert Monitor”) that replaced the 
“Alarm Server” program that was available in ION Enterprise 5.5 and earlier (the 
legacy alarmsrv.exe program is still functional and available in the ...\system\bin 
folder).

Alert Monitor resides on the ION Enterprise workstation, where it receives and 
processes incoming alarms from a remote ION meter’s Alert module.

With the implementation of the ION Alert Monitor, alarm notification is improved 
and simplified:
Since Alert Monitor runs as a Windows service, a user is no longer required to 
log in to ION Enterprise in order to start monitoring the system for alarm 
conditions.
Alert Monitor can handle incoming calls from multiple communications ports.
When alarms are received, Alert Monitor uses the ION Connection Management 
Service to establish a modem connection, rather than using the legacy command 
line executable “conman.exe”.
ION Connection Management Service allows you to set up specific modem 
connection request properties, such as Minimum/Maximum Connection Time, 
Disconnect on Caught‐up, etc. These properties are set up in the Alert Monitor’s 
configuration file — see “Setting Up the ION Alert Monitor” on page 309.

NOTE
Alert Monitor does not support TAPI modem drivers for Windows (WinModems).

How It Works
The ION Alert Monitor responds to alarm messages originating from the Alert 
module in an ION meter. For example, an alarm message is initiated as a result of 
a power quality event:
1. An alarm condition prompts the ION module (e.g., Setpoint module) to send 
a pulse signal to the Trigger input of the ION meter’s Alert module. Refer to 
the description of the Alert Module in the ION Reference for more information.
2. The Alert module initiates modem communication, and calls the phone number 
specified in the Alert module’s Destination setup register. 
3. The ION Enterprise workstation answers the modem call from the ION meter 
and completes the communication connection. The meter then sends the 
following information to ION Enterprise: a timestamp indicating when the 
alarm condition occurred, the node name, and the message (i.e., contents of the 
Alert module’s Message setup register).
4. Alert Monitor receives the alarm data and places it in the queue for processing. 
When the alarm is processed, the commands specified in the COM port 
configuration settings are executed. At the same time, a connection request is 
sent to the node specified in the alarm data.

Page 308 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Setting Up the ION Alert Monitor

5. The new connection request is received and placed in the queue. If other 
connection requests to the same site already exist, the new request is merged 
with the others.
6. ION Connection Management Service establishes a connection to the meter that 
originated the alarm, then Log Inserter downloads all outstanding event and 
data logs.

NOTE
ION Connection Management Service uses a modem (from the modem pool) to establish connection to
the remote site.

7. ION Connection Management Service disconnects after the ION Log Inserter 
Service has finished downloading all outstanding logs. When this has been 
completed, the status of the site is considered “Caught‐up”.

Setting Up the ION Alert Monitor


NOTE
This section is intended for advanced users. Contact Technical Support if you need assistance.

The configuration settings for Alert Monitor are stored in a config file that follows 
the file naming convention “{MachineName}.AlertMonitor.config“. An example 
config file with this name is provided in the ...\ION 
Enterprise\config\AlertMonitor folder. An XML schema file named 
“AlertMonitor‐Schema.xml” is also provided in the same folder, for your 
reference. You can use this schema to validate the config file using available XML 
validation tools.

Use a text editor or XML authoring tool to create and edit the configuration file. 
Remember to rename the config file to match the machine name (e.g., if the 
primary server is named “ComputerOne”, rename the config file to 
“ComputerOne.AlertMonitor.config”).

Configuration File Components


Channels define the communication port and modem that the Alert Monitor uses, 
while Actions define the commands to be carried out in response to an alarm.

A Channel contains the modem definition and configuration settings for the port. 

© 2009 Schneider Electric. All rights reserved. Page 309


Setting Up the ION Alert Monitor PowerLogic ION Enterprise User Guide

The following table lists the attributes you can assign for a Channel:

Channel attribute Description

Name of the communications port the modem is connected to. The


Name
default value is COM1.
The type of modem. The value entered here must exactly match the
ModemType displayed value under “Modem Type” property in the “Dial Out Modem
Options” dialog.

BaudRate The modem’s baud rate. The default value is 9600.


The node name, as it appears in the system log messages. The text
AlertMonitorNodeName specified here defines the value for the %a command parameter
(described below). The default value is AlertMonitor.[ComputerName]

This controls whether all alarms are logged to the ION Enterprise system
NoLog log. The default value is “YES” (log all alarms). A value of “NO” disables
all alarm logging.

This specifies how many times a connection attempt should be retried if


NumTries
there are communication errors.

TIP
Open the example file “{MachineName}.AlertMonitor.config” in a text editor program and refer to it
when reading this section to see the proper usage of the elements and attributes in the ION Alert Monitor
configuration file.

Actions are grouped inside ActionSet elements, which contain connection 
requests and/or commands to execute when alarms are received. Specify 
“ConnectionRequest” to set up an ActionSet to send a connection request; specify 
“Command” to set up an ActionSet to execute an operating system command 
when the alert is received. You can specify attributes for ActionSets:
If the Channel attribute is used in the ActionSet (for example, <ActionSet 
Channel=ʺCOM1ʺ>), then the actions (commands) listed in the ActionSet are 
executed for all alarms coming through the communications port and modem 
specified for that Channel (i.e. ,“COM1”).
If the Location attribute is used in the ActionSet, then the actions (commands) 
listed in the ActionSet are executed for all alarms originating from the specified 
Location (regardless of Channel).
If no attribute is specified, then the actions (commands) listed in the ActionSet 
are executed for all alarms originating from any communication port or location.

If there are two ActionSets (one specifying a Channel attribute, the other 
specifying Location attribute), then the one that specifies the Location attribute 
takes priority.

NOTE
The value of the “Location” attribute is specified in the Location setup register of the Alert module for the
meter that is sending the alert. For details, refer to Alert Module description in the ION Reference.

Page 310 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Setting Up the ION Alert Monitor

Commands (i.e., command lines that run separate applications such as “net send”) 
contained in the ActionSet can include parameters that return data values, as 
described in the following table:

Command Parameter Description

%U Universal time: seconds since January 1, 1970

%u Universal time: YYYY-MM-DD HH:MM:SS.FFF

%T Local time: seconds since January 1, 1970


%t Local time: YYYY-MM-DD HH:MM:SS.FFF

%n Node name (e.g., device name)

%g Gate name (e.g., site name)

%p Priority name

%P Priority number

%m Alarm message without delimiters


%M Alarm message with “ “ delimiters

The value of the AlertMonitorNodeName attribute. If this attribute is not


%a
used, the default value is “AlertMonitor.[ComputerName]”.

The “ConnectionRequest” element contained in the ActionSet has attributes that 
you can define, as described in the following table:

ConnectionRequest Attribute Description

Maximum time (in seconds) a connection to the site is maintained.


MaxConnectTimeSeconds
The default value is 300 seconds.

Minimum time (in seconds) a connection to the site is maintained.


MinConnectTimeSeconds
The default value is 60 seconds.

Defines how many hours a connection request remains valid


RequestLifetimeHours before it is discarded (even if attempts to connect to the site fail).
The default value is 0.

Priority of the connection request, which ranges from 0 to 2000.


RequestPriority
The highest priority is 2000. The default value is 1999.

This specifies to automatically disconnect from the site after Log


DisconnectOnCaughtUp Inserter has finished downloading all outstanding logs, including
event and data logs. The default value is “No”.

This explicitly defines which specific device to connect to in the site.


Device
This attribute overrides data contained in the alarm message.

This explicitly defines which site to connect to. This attribute


Site
overrides data contained in the alarm message.

Multi-Station Setup
It is possible to run the ION Alert Monitor on more than one machine in the ION 
Enterprise system. However, the configuration files must be stored in the primary 
server, following the convention “ComputerName.AlertMonitor.config”.

© 2009 Schneider Electric. All rights reserved. Page 311


Starting the ION Alert Monitor PowerLogic ION Enterprise User Guide

For example, the Alert Monitor running on a secondary server named 
“ComputerTwo” uses the configuration file named 
“ComputerTwo.AlertMonitor.config” located in the primary server.

Diagnostics
Diagnostic and error messages are logged in the ION Enterprise system log, with 
the source “Alert Monitor”.

Starting the ION Alert Monitor


By default, the ION Alert Monitor is stopped, and set to “Manual” startup type. To 
automatically start Alert Monitor on Windows startup, change the startup 
properties of this Windows service to “Automatic”, then start the service. Refer to 
your Windows documentation for details.

Page 312 © 2009 Schneider Electric. All rights reserved.


11 Downstream Device Assistant
Downstream Device Assistant lets you manage downstream devices. With this 
tool, you can rename downstream sources, change which measurement is 
associated with specific data from a source, and apply these changes to previously 
recorded data in ION_Data (historical database). You can also display and manage 
all the physical sources (devices) in your network.

Downstream Device Assistant is an advanced application and should only be used 
by users with advanced technical skills and a clear understanding of how data is 
interpreted and stored in the ION Enterprise databases.

In This Section

“Detecting Downstream Devices” on page 314
“Downstream Device Assistant Basics” on page 315
“Basic View versus Advanced View” on page 315
“Columns Descriptions” on page 316
“Displaying Physical Sources” on page 318
“Downstream Device Assistant Options” on page 318
“Downstream Device Assistant Functions” on page 321
“Renaming the Assigned Source” on page 321
“Changing the Measurement Mapping” on page 322
“Adding a New Downstream Device Mapping” on page 322
“Updating the Historical Data at a Later Time” on page 323
“Downstream Device Assistant Commands” on page 324

© 2009 Schneider Electric. All rights reserved. Page 313


Detecting Downstream Devices PowerLogic ION Enterprise User Guide

Detecting Downstream Devices


A downstream device is one whose data is logged by a remote data recorder, for 
example:
A Modbus slave device whose output registers are logged by a device with 
Modbus Mastering capability (see illustration below).
A Modbus device whose outputs are logged by the Virtual Processor.
Any of various multiple sources in which the same measurement is being 
logged on a single device, e.g., an RTU that is collecting kWh pulses from 
multiple sources or a single branch circuit monitor that is collecting current 
readings on multiple circuits.

Data Recorder

kW

Etherne
t kW
RS - 4 kW
ION Enterprise server 85
Physical Source
(Modbus Master)
RS -485

Downstream Devices
(Modbus Slaves)

ION Enterprise automatically detects downstream devices. The Log Inserter 
component does this by looking for devices (called “physical sources”) that record 
or host data coming from various downstream devices (for example, an ION meter 
that utilizes a Modbus Import module to pass through data originating from a 
“downstream” Modbus device). 

Log Inserter resolves the data from each of these downstream devices to the 
appropriate measurement (for example, the label “Vll ab” resolves to the 
measurement “Voltage Phases AB”). For data that cannot be resolved, Log Inserter 
creates measurements whose names are based on the ION register labels.

Log Inserter uses a logical naming scheme to assign names to the downstream 
devices. For example, “Modbus.34” is the name assigned to the downstream 
Modbus device with a slave address “34”. 

Page 314 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Downstream Device Assistant Basics

Downstream Device Assistant Basics


Use Downstream Device Assistant to edit the names assigned to downstream 
devices or to assign the correct measurement label for a register that has an 
incorrect measurement mapping.

IMPORTANT: Before using the Downstream Device Assistant, make sure you 
save a copy of the ION_Network and ION_Data databases, in case you need to 
revert to the original configuration of these databases.

Starting the Downstream Device Assistant


1. Run the program named “DownstreamDevices.DownstreamAssistant.exe” in 
the ...\ION Enterprise\system\bin folder.
2. Log in using your ION Enterprise credentials.
A message displays to remind you to back up your ION_Network and 
ION_Data databases. Click OK to continue.
3. Downstream Device Assistant opens in Basic view or Advanced view, 
depending on the last view it was in before it was closed. The first time 
Downstream Device Assistant is started, it opens in Basic view.

Basic View versus Advanced View


The view determines what columns are available as well as whether an action is 
global (applied to all rows containing a parameter) or specific to a row.

© 2009 Schneider Electric. All rights reserved. Page 315


Basic View versus Advanced View PowerLogic ION Enterprise User Guide

Columns Descriptions
Columns in Both Basic and Advanced View

Column Name Description

The IsDownstream column identifies which devices in the Assigned Source column are downstream
devices. If IsDownstream is selected, it means that the device identified in the Assigned Source column is
IsDownstream1 downstream to a physical device, whose name is indicated in the Physical Source column. If IsDownstream
is cleared, this indicates that the device is a physical source. Note also that a physical source has the same
Assigned Source name and Physical Source name, by default.

This is the default name that Log Inserter assigned to a downstream or physical device. For example,
“Modbus.109:MainFeed.PM7650” is the default name assigned for the downstream Modbus device with
Assigned Source
unit ID “109”, whose measurements are being logged to a data recorder on a Modbus Master device
named “PM7650” that is part of the “MainFeed” site (group).
This text field allows you change the current name under Assigned Source.
In Basic view, all rows that contain the same Assigned Source name are automatically updated to the new
name when you enter it in the Updated Assigned Source column.
Updated Assigned Source
In Advanced view, you can select one or more rows and rename the source using the Updated Assigned
Source column, while leaving the other rows unchanged.
See “Renaming the Assigned Source” on page 321 for more details.

This identifies the name of the physical device (e.g., a Modbus Master device or the Virtual Processor) that
Physical Source2 is performing the data logging for a downstream device.

This column displays either the ION label (e.g., “Vln avg”) or the descriptive name of the measurement
Measurement (e.g., “Average Voltage Line-to-Neutral”), depending on the setting in the Options dialog box; see
“Downstream Device Assistant Options” on page 318.

Additional Columns in Advanced View Only

This lets you redefine what is currently assigned in the Measurement column. Click the cell to display the
list of measurements to choose from. Depending on the setting in the Options dialog box, you can select
Updated Measurement
from a list containing only the most common measurement definitions or from a complete list of all
available measurements; see “Downstream Device Assistant Options” on page 318.

This column displays a measurement’s register handle either in hexadecimal format or decimal format,
Handle depending on the setting in the Options dialog box; see “Downstream Device Assistant Options” on
page 318.

Entered By This identifies which user made a change to the source-measurement definition.

The Update Historical Database check box is automatically selected after entering changes in the Updated
Assigned Source or Updated Measurement cell. This means that all historical database entries that contain
Update Historical Database the old Assigned Source name or Measurement will be updated with the new name or measurement.
If you want to leave the existing data in the database unchanged, clear the Update Historical Database
check box before saving the changes.
By default, Log Inserter automatically associates the proper measurement to the appropriate piece of data
in the data log. Normally, the Manual check box should remain cleared. However, if you want to
Manual (see Caution below) specifically change the measurement or register handle associated with a particular address definition,
select the Manual check box for that measurement. This manually overrides Log Inserter so that it uses this
new address mapping from now on (i.e., Log Inserter does not attempt to resolve that address ever again).

1
Do not change the value of “IsDownstream” when making changes to source/measurement
definitions, as it is automatically set by the Downstream Device Assistant.
2
Do not use the Physical Source column to modify the existing name of a valid physical device, as Log
Inserter uses this name to perform proper data logging.

Page 316 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Basic View versus Advanced View

NOTE
It is not recommended that you select the Manual check box. This reserves the ION register for which
Manual is checked for the selected measurement. This mapping remains in place even if the device is
reconfigured such that this register is used in an entirely different context. This may cause unexpected
problems in the ION_Data database. It should be used only if you are certain that the configuration you
have chosen is permanent.

Basic View
To switch to Basic view, click View > Options. In the Advanced section of the 
Options dialog box, clear the enable advanced features check box. Click OK.

In Basic view, when you enter a new name in the Updated Assigned Source 
column, all rows that contain the same Assigned Source name are automatically 
filled in with the new name. Existing data in the historical database (ION_Data) is 
also automatically updated to reflect the change.

Advanced View
To switch to Advanced view, click View > Options. In the Advanced section of the 
Options dialog box, select the enable advanced features check box. Click OK.

In addition to the columns displayed in Basic view, Advanced view displays all the 
other columns for editing individual source‐measurement definitions (i.e., 
Updated Measurement, Handle, Entered By, Update Historical Database, and 
Manual). In Advanced view, you can:
Select and make changes to a specific row without affecting the other rows. For 
example, you may want to change the source name for one particular 
measurement while leaving the original source name unchanged for all the 
other measurements.
Select a different measurement for one that is incorrectly mapped to a particular 
register handle.
Select whether or not to update historical data for a changed source name or 
measurement definition, by selecting or clearing the Update Historical Data 
check box, respectively. Changing a name or definition automatically selects this 
check box.
Select whether or not to allow Log Inserter to resolve the register handle to a 
particular source measurement, by clearing or selecting the Manual check box, 
respectively. The default setting is cleared (i.e., Log Inserter automatically 
resolves the register handle to the source measurement definition). If you want 
to force the change so Log Inserter does not resolve the handle to the new 
measurement, select the Manual check box.

© 2009 Schneider Electric. All rights reserved. Page 317


Displaying Physical Sources PowerLogic ION Enterprise User Guide

Displaying Physical Sources


The default view for Downstream Device Assistant displays only the downstream 
devices. To display the physical sources as well:
1. Click View > Select Physical Sources.
2. Select the check box beside the physical sources you want to display. Select the 
Select/Clear All check box to select all physical sources or clear it to select none. 
Click OK.

NOTE
The Physical Sources are not displayed if you restart Downstream Device Assistant. By default, only
downstream devices are displayed when Downstream Device Assistant is started.

Sorting Data
Click a column heading to sort the row entries in ascending or descending 
alphanumeric order, according to that column.

Downstream Device Assistant Options


Click View > Options to display the Options dialog box:

Certain options such as “show all measurements” and the “Handles” display 
options are disabled in Basic View. To enable them, switch to Advanced View first 
(see “Advanced” on page 320).

Page 318 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Downstream Device Assistant Options

Measurements
This section allows you to select whether to display the default ION label (e.g., 
“Vln avg”) in the Measurement column or to display the full descriptive name of 
the measurement (e.g., “Average Voltage Line‐to‐Neutral”).

In Advanced view only, you can also select whether to display all available 
measurements or only the most common measurements in the list when picking a 
measurement in the Updated Measurement column.

Displaying ION labels versus measurement names


To change the setting:
1. Click View > Options.
2. In the Measurements section, select display ION labels to display the ION label 
or display measurement names to display the full name of the measurement.

NOTE
In some situations, if "display ION labels" is selected, the displayed label may not match the label on your
meter (for example, if a custom label was used). Instead, it displays the known default label for that
particular measurement.

Updated Measurement Column display


To change the setting:
1. Click View > Options and ensure Advanced is selected.
2. In the Measurements section, select the show all measurements check box to 
display all available measurements in the Updated Measurement column. To 
display only the most common measurements, clear the show all 
measurements check box.

Historical Data
If the show connection dialog check box is cleared, the ION_Data database is 
automatically set as the “Default Connection” (for historical data).

If you want to select a different database, select the show connection dialog box. 
With this setting enabled, the database connection dialog box is displayed every 
time you save your changes. When the dialog box displays, select Custom 
Connection and specify your database connection details. 

© 2009 Schneider Electric. All rights reserved. Page 319


Downstream Device Assistant Options PowerLogic ION Enterprise User Guide

Advanced
The enable advanced features check box sets the view to Basic View if it is cleared 
or Advanced View if it is selected.

Handle
Available in Advanced View only, this option specifies whether register handles 
are displayed as the hexadecimal value (with the “0x” prefix) or as the decimal 
value.

To change the setting:
1. Click View > Options and ensure the Advanced is selected.
2. In the Handles section, select display hex to display the register handle in 
hexadecimal format or display decimal to display it in decimal format.

If you want to manually resolve a register handle to a specific measurement, edit 
the value in the Handle cell, then select the Manual check box before saving the 
changes.

Page 320 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Downstream Device Assistant Functions

Downstream Device Assistant Functions


This section describes different functions you can perform using the Downstream 
Device Assistant.

Renaming the Assigned Source


One of the primary reasons for using the Downstream Device Assistant is to 
change the default name assigned to a downstream device by the Log Inserter. For 
instance, instead of “Modbus.34”, you may want to rename that device to 
something more meaningful such as “SM_Bldg2_Boiler7”.

Renaming an Assigned Source typically only applies to downstream devices.

Renaming the Assigned Source for ALL its Measurements


1. Switch to Basic View.
2. Find the source you want to rename. Enter the new name in the Updated 
Assigned Source column. All rows with measurements associated with the 
renamed source are automatically updated.

NOTE
If you do not want to assign the existing data in the database to the new source name, switch to Advanced
View first, then clear the Update Historical Database check box for all appropriate rows.

3. Click File > Save.
4. A dialog box prompts you with a summary of the changes. Click Yes to continue. 
or No to cancel.
5. When the operation has completed, click OK, then Close.

Renaming the Assigned Source for one or more Measurements


1. Switch to Advanced View.
2. Select the row(s) you want to rename. To select a row, click the area just to the 
left of the first column. The row is highlighted to indicate that it is selected.
3. Click Edit > Rename Source.
4. In the Source Rename box, type the new name for the downstream source. Click 
OK.

NOTE
By default, the Update Historical Database check box is selected for all affected rows — this applies the
change to existing data in the database. To make the change only to data going into the database from
this point forward, clear the Update Historical Database check box for the affected rows.

5. Click File > Save. A dialog box prompts you with a summary of the changes.
6. Click Yes to continue or No to cancel.
7. When the operation has completed, click OK, then click Close.

© 2009 Schneider Electric. All rights reserved. Page 321


Cancelling Changes PowerLogic ION Enterprise User Guide

Cancelling Changes
1. To undo all unsaved changes:
Click Edit > Reset, or
Click View > Refresh.
2. Click Yes to confirm.

Changing the Measurement Mapping


Log Inserter automatically associates logged data with a measurement by 
searching for a mapping between the label and the measurement. However, in 
cases where no mapping exists, Log Inserter creates a “measurement” that is based 
on the register label. To manually change this measurement mapping:
1. Switch to Advanced View.
2. Click the Updated Measurement cell that you want to change, then select the 
new measurement you want to map from the list.
3. Select the Manual check box.
4. By default, the Update Historical Database check box is selected — this applies 
the change to existing data in the database (if, for example, the source and 
measurement mapping you are adding already exists). To make the change only 
to data going into the database from this point forward, clear the Update 
Historical Database check box.
5. Click File > Save. A dialog box prompts you with the changes. Click Yes.
6. If prompted, select which database to update. Click OK.

Adding a New Downstream Device Mapping


To add a new address mapping that associates the source and measurement to a 
specific logged quantity in the database:
1. Scroll down to the end of the table and click the last row (the one with the 
asterisk beside it).
2. Fill in the Updated Assigned Source and Physical Source columns. If the source 
is a physical device (i.e., not downstream), the same name must be entered 
exactly in both columns.
3. Click the Updated Measurement cell, then select the measurement from the list.
4. In the Handle cell, type the register handle for this measurement.
5. By default, the Update Historical Database check box is selected — this applies 
the change to existing data in the database (if, for example the source and 
measurement mapping you are adding already exists). To make the change only 
to data going into the database from this point forward, clear the Update 
Historical Database check box.
6. Click File > Save. A dialog box prompts you with the changes. Click Yes.
7. If prompted, select which database to update. Click OK.

Page 322 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Updating the Historical Data at a Later Time

Updating the Historical Data at a Later Time


When you save your changes using the Downstream Device Assistant, a record of 
changes to the source‐measurement definitions is saved in the folder:

...\ION Enterprise\config\Diagnostic\Downstream Device Assistant\

with the following filename:

“Downstream Device DefinitionsYYYY‐MM‐DD_hh.mm.ss.csv”

where “YYYY‐MM‐DD_hh.mm.ss” means current YEAR‐MONTH‐
DAY_hour.minute.second.

If you cleared the Update Historical Database check box when you saved your 
changes the first time, you can update the existing data in the database at a later 
time, through the use of this csv file.

How to use the Downstream Device Assistant .csv file


To update the existing data in the database with the source‐measurement changes 
contained in the csv file:
1. Click Edit > Historical Data. The Update Historical Data window appears.
2. Click File > Import CSV.
3. Downstream Device Assistant opens the folder that contains the csv files. Select 
the Downstream Device Definitions file you want to use, then click Open.
4. Click File > Update Historical Data.
5. The Historical Data Update prompt displays how many source‐measurement 
pairs will be updated. Click Yes.
6. Click Yes at the Historical Data Update prompt.
7. After the operation has completed, click OK, then Close.

You can update only one ION database at a time. To select a different database, 
first make sure the show connection dialog check box is selected under 
View > Options. You can then use the database connection dialog box to specify 
which database you want to update.

NOTE
If you update address definitions that affect multiple historical databases, only the first historical database
you select is automatically updated. To update the remaining historical databases, you must import the
address definitions to each one, using Select Edit > Update Historical Data.

Activity Log
All saved changes in the Downstream Device Assistant are stored in a log file 
named “Downstream Device Historical UpdatesYYYY‐MM‐DD_hh.mm.ss.txt”, 
that contains a description of the activities carried out when Downstream Device 
Assistant was updating the source‐measurement definitions.

© 2009 Schneider Electric. All rights reserved. Page 323


Downstream Device Assistant Commands PowerLogic ION Enterprise User Guide

Downstream Device Assistant Commands


The following summarizes the commands available in the Downstream Device 
Assistant:
File > Save: Saves your changes. A copy of the changes are saved for future 
reference, in a comma‐separated value (.csv) data file in the 
...\config\Diagnostic\Downstream Device Assistant\ folder.
File > Exit: Closes the Downstream Device Assistant.
Edit > Reset: Clears all modifications made since the last save.
Edit > Delete: Deletes the selected rows.
Edit > Rename Source: Lets you change the name of an Assigned Source. See 
“Renaming the Assigned Source” on page 321.
Edit > Update Historical Data: Opens the “Update Historical Data” window 
that allows you to open a previously‐saved source‐measurement definition data 
file (with a .csv file extension), for the purpose of updating existing data in the 
database. You can also manually add, edit or delete data entries. See “Updating 
the Historical Data at a Later Time” on page 323.
View > Refresh: Loads the current downstream definitions from the database. 
Functionally the same as Edit > Reset, as this command clears all modifications 
made since the last save.
View > Options: Displays the Options dialog box where you can change the 
settings that control what level of detail is displayed for the source‐
measurement definitions.
View > Select Physical Sources: Displays the Select Physical Sources dialog 
box where you can select which physical devices you want displayed in the 
Downstream Device Assistant.

Page 324 © 2009 Schneider Electric. All rights reserved.


Appendix A: Reporter
Reporter is the legacy program from ION Enterprise version 5.6 and earlier that 
defined, generated and managed comprehensive reports, based on information 
contained in your database. Reporter processes selected data and generates a 
finished report in Microsoft Excel format.

NOTE
Microsoft Excel 2003 must be installed on your machine for Reporter to function. Microsoft Outlook 2003
must be installed if you require reports to be emailed.

For information on using Web Reporter (the replacement for Reporter), see “Web 
Reporter” on page 171.

In This Section

“Introduction” on page 326
“Creating a Report” on page 327
“Generating a Report” on page 330
“Modifying the Finished Report” on page 330
“Types of Default Reports” on page 331
“Creating a Report Without a Template” on page 335
“Automatic Report Generation” on page 336
“Using Reporter on Secondary Server or Client” on page 337
“Troubleshooting” on page 338
Introduction PowerLogic ION Enterprise User Guide

Introduction
Reporter features a wizard that guides you through the report creation process. 
This involves selecting a report template and database, which then allows the 
wizard to display those sources in the ION Enterprise network that contain the 
type of data required to create the report.

When the report is generated, Reporter retrieves data from the ION_Data 
database, uses the report template to process the data, then creates a finished 
report in Microsoft Excel format.

Report templates are preconfigured for the most common reporting needs. The 
following report templates are supplied with ION Enterprise 5.6:
“Energy and Demand”
“Load Profile”
“Power Quality”
“EN50160_General”
“EN50160_Summary”
“EN50160_Mains_Signal”
“IEC61000‐4‐30_10Min”
“IEC61000‐4‐30_2Hr”
“IEC61000‐4‐30_3Sec”

Starting Reporter
To start Reporter, navigate to the ../ION Enterprise/system/bin/ folder and double‐
click on RepGen.exe. 

TIP
If you plan to use this program frequently, create a shortcut to the .exe file on your desktop.

Reporter opens with either “Manage Reports” or “Generate Reports” pre‐selected, 
depending on whether or not any reports have already been created. You cannot 
generate reports until you have created at least one.

Page 326 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Creating a Report

Creating a Report
1. Start Reporter.
2. Select Manage Reports, then click New. This starts the new report wizard.

Step 1: Select Template


1. Type the name of the report in the Report Name box.
2. Select the template you want to use in the Report Template list.
3. Click Next.

Step 2: Select Database and Sources


1. Specify your database (ION_Data is selected by default). To connect to a 
different database (e.g., an archived database), select it from the Database 
dropdown list, or click More.
2. Select the box beside each source name (“device”) that you want to include in 
your report. Select the Show Details box if you want to see additional 
information for the devices. 

NOTE
“Show Details” is only available when "Show only sources applicable to the template" is selected.

3. If the report template you are using requires a TOU schedule (such as “Energy 
and Demand”), the TOU Schedule section appears on the dialog box. Select a 
TOU schedule from the list or click Manage to create a new one.

TOU Schedules
A typical TOU schedule has On Peak, Off Peak and Shoulder Peak periods. The 
Energy and Demand report template requires a TOU schedule. If you do not want 
to use a TOU schedule, simply create a TOU schedule with a single Tariff period.

To create a new TOU schedule:
1. Click Manage in the TOU Schedule section of Step 2. The TOU Schedules 
dialog box appears.
2. Click New. The TOU Schedule Properties dialog box appears with a blank TOU 
schedule with a single tariff.
Use the lefthand pane to select the item you want to edit, then use the righthand 
pane to enter, modify or set the values. 

NOTE
If an existing (configured) TOU Schedule appears in the list, you can use it as a template to create a new
one with similar On Peak/Off Peak periods. See “Copying an Existing TOU Schedule” on page 328.

3. Select “New TOU Schedule”, then use the TOU Schedule Name box to rename 
it (for example, “2007 TOU Schedule”).

© 2009 Schneider Electric. All rights reserved. Page 327


Creating a Report PowerLogic ION Enterprise User Guide

4. Select “Tariff 1” to display the Tariff Details on the right pane, then use the Name 
box to type a name for it (for example, “Off Peak”).
Use the rate boxes ($/kWh, $/kW, etc.) to enter the tariff rates.
5. On the left pane, click the “+” beside the tariff to expand it. Select the text 
underneath it (“All Day, Every Day...”) to display the Tariff Period fields. Use the 
From and To boxes to set a time range and a date range for the tariff period.
To create another tariff period, select the tariff period you just configured, then 
click New to add a new tariff. Set the time range and date range for this new 
tariff period.
6. To create a new tariff (for example, “Off Peak”), select the tariff name, then click 
New. Repeat the above steps to rename the tariff, set the rates, and set the tariff 
periods.

Holidays
1. Select one of the “Off Peak” periods, then click New.
2. Rename the tariff (for example, Holidays) and click on the day and times 
underneath to configure the tariff period. 

3. Select the appropriate country holidays from the list.
4. Add or remove individual holidays as required.

NOTE
Make sure there are no gaps or overlapping date or time ranges in the TOU Schedule.

Copying an Existing TOU Schedule


To create a TOU Schedule using an existing one as a template, select it then click 
Copy. Rename the copy and modify its properties as needed.

Step 3: Set Up the Report Options


The report options are organized in the different tabs of the window, named as 
follows: Date Range, Distribution, Validation, Display, and Notes.

Page 328 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Creating a Report

Date Range
Select the date range you want to use for your report:
Ask for Date Range when report is generated prompts you to supply a date 
range when the report is run (interactive mode).
Pre‐specified Date Range lets you select a specific period. For example, select 
Last Month to set Reporter to run the report using data from the previous 
month. Select Fixed Range to specify a start and end time/date. Select Custom 
Relative Range to specify a date range relative to the current time and date.

NOTE
In applications where a report is generated based on a power quality system event or similar setpoint
condition, specifying “Custom Relative Range” can include data that shows how the system was behaving
before the event occurred.

Distribution
Select any or all of the Distribution options (you must select at least one):
Show report on screen is selected by default; this displays the report on screen 
each time the report is generated. Clear this box to disable displaying of the 
report.
Save Excel report to folder stores the report in the folder you specify using the 
Browse button.
Save HTML report to folder saves an HTML version of the report in the folder 
you specify using the Browse button.
Note that there are certain elements and behaviors in the HTML report that 
may appear differently from the original Excel report. This is due to the HTML 
conversion process in Excel. Search the Microsoft support knowledgebase for 
more information.
Send report to printer prints the report each time it is generated. Select the 
printer you want to use from the list.
Email report to recipients sends the report (in Excel format) to an email address, 
using Microsoft Outlook 2003. Click New to add a new email address or Delete 
to remove an existing one from the list.

Validation
Select Report duplicate and missing entries to enable error checking.
Use the Hours, Minutes and Seconds boxes to specify an expected time interval 
between each record.
Select Remove duplicate records to delete redundant records from the report.
If you want Reporter to insert records automatically for ones that are missing, 
select Replace missing records with: then select Values from the previous row, 
An empty row, or A zero value.

Display
Select one of the options to control how Reporter handles raw data sheets in the 
report (Show, Hide, or Delete).

© 2009 Schneider Electric. All rights reserved. Page 329


Generating a Report PowerLogic ION Enterprise User Guide

NOTE
The “Delete” (raw data sheets) option is useful when you want to reduce the report’s file size (this
particularly applies to those reports that contain a significantly large amount of data).

The Display Options grid lists other options you can turn on or off. Double‐click 
the appropriate row to turn the option on or off.

Notes
Use the Notes tab to enter details about your report template, such as revision 
history. To insert a line break, hold down CTRL and press ENTER.

Previewing the Report


To see what the report will look like, without saving or distributing it, click 
Preview. Click Back To Report Generator button to return to the main Reporter 
window. Modify the settings, if necessary. Otherwise, click Finish to save your 
report and return to the main Reporter screen.

Generating a Report
1. On the main Reporter screen, select Generate Reports.
2. Select the name of the report you want to run. If you want to view its option 
settings, click Summary. Click OK to close the summary window.
3. Click Generate. A window displays the progress of the report generation.
4. Click Close to view the report.

Modifying the Finished Report


This describes how to edit the Microsoft Excel presentation sheet for your report:
1. On the main Reporter window, select the report you want to modify, then click 
Preview.
2. Use the Presentation Sheet to create references to elements in the data sheets that 
you want to include in the final report. Use Microsoft Excel’s data analysis and 
charting tools to process the information in the data sheets, then add the 
appropriate references to the presentation sheet.

NOTE
The company name that appears in the report is the “Company” name entered when Microsoft Excel was
installed on the computer.

3. Lay out and format the elements as you want them to appear in the report.
4. Save your changes.

Page 330 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Types of Default Reports

Types of Default Reports


This section shows basic characteristics of the Microsoft Excel reports generated 
from the Reporter templates. The first tab in the workbook is created from the 
“Presentation sheet” of the report template. You can modify the look and 
functionality of a report by editing its presentation sheet. See “Modifying the 
Finished Report” on page 330 for details.

NOTE
The presentation sheet contains references that automatically update the data each time the report is
generated. Be careful not to overwrite these references.

Energy and Demand


Use the Energy and Demand template to create a tabular report on energy 
consumption and peak demand levels over a period of time, categorized by time 
of use. TOU (Time Of Use) schedules are typically set up to match an energy 
provider’s tariff schedule.

The Energy and Demand template uses quantities from the Energy and Demand 
log (kWh, kVARh, kVAh, kW Demand, kVAR Demand, kVA Demand) that is 
available on most ION devices.

TOU Schedule
Reporter requires a TOU schedule when creating a report using the Energy and 
Demand template. A sample TOU schedule is included — this allows you to define 
time periods that coincide with time periods in your energy provider’s tariff 
schedule, such as On Peak and Off Peak times. If you do not need to use a TOU 
schedule, simply create a new TOU schedule with only one time period defined.

The Aggregate Energy & Demand tab contains a summary of the combined energy 
and demand values. Energy and demand information from different sources are 
stored in separate tabs in the workbook.

Load Profile
Use the Load Profile template to create a graphical representation of demand or 
load levels over a period of time. The profile shows peak loads — points on the 
graph where peak electricity demand is high. A load profile report can be used to 
analyze the electrical loads at the time of maximum demand. This information 
creates opportunities for developing strategies to improve energy management.

Similar to the Energy and Demand template, the Load Profile template uses data 
from the Energy and Demand log (kW Demand, kVAR Demand, kVA Demand), 
except it does not use a TOU schedule.

The Load tab contains a graphical representation of the power usage of your 
system over time (total load profile). Load profiles from different sources are 
stored in separate tabs in the workbook.

© 2009 Schneider Electric. All rights reserved. Page 331


Types of Default Reports PowerLogic ION Enterprise User Guide

Power Quality
Use the Power Quality template to create a report that summarizes the number 
and severity of voltage sags, swells and transients over a period of time. The 
finished report also includes a graphical representation of the disturbances, and an 
interactive selection of group events.

The Power Quality template uses data from all three Power Quality log files that 
are found on devices with sag/swell and transient detection capabilities:
Sag/Swell Log
Transient Log
Waveform Log

Sample Power Quality Report

This graph displays the worst


disturbances recorded.

Click on any incident’s


timestamp to view its
details.

The Power Quality Summary tab displays a chart that identifies the worst line 
disturbances and a list of incidents linked to their details. An incident is made up 
of several disturbances.

The Power Quality report shows a system’s line fluctuations for the specified date 
range. Use the Interactive Power Quality toolbar to change the time interval 
between incidents:

Select the incident


interval (time between
power quality events)

Click the timestamp of the incident in the Waveforms tab to view a graphical 
representation of the disturbance.

Page 332 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Types of Default Reports

Click “Show Complete” to


display individual waveforms.
Click the magnify buttons to
zoom in or out.

EN50160
EN50160 is a set of power quality standards used by energy suppliers and energy 
consumers in European countries. Three EN50160 templates are available in 
Reporter:

EN50160_General
Use the EN50160_General template to create a report containing detailed analysis 
of all EN50160 compliance data logged by a single meter. Data is recorded for each 
observation period. The worksheets contain percentages of non‐compliant 
EN50160 measurements such as Power Frequency, Supply Voltage Magnitude, 
and Flicker.

The EN50160_General template uses data from these fourteen EN50160 log files:
EN50160 Vlt Dp1 to EN50160 Vlt Dp5 (supply voltage dips)
EN50160 Ovrvlt1 to EN50160 Ovrvlt3 (temporary overvoltages)
EN50160 Vunbal (supply voltage unbalance)
EN50160 Hrm Vlt (harmonic voltage)
EN50160 Ihm Vlt (interharmonic voltage)
EN50160 Frq/Mg (frequency and magnitude)
EN50160 Flicker (flicker)
EN50160 Intrp (short‐ and long‐term interruptions)

EN50160_Summary
Use the EN50160_Summary template to create a report containing comprehensive 
analysis of all EN50160 compliance data logged by multiple meters. The 
compliance summary is based on the EN50160 limits for each observation period: 
each default EN50160 measurement indicates a pass or fail on the compliance test 
with a Y (yes) or N (no) respectively.

The EN50160_Summary template uses data from the same log files as the 
EN50160_General template.

© 2009 Schneider Electric. All rights reserved. Page 333


Types of Default Reports PowerLogic ION Enterprise User Guide

An observation sheet is generated for every observation period; however, it is 
hidden by default. You can access specific observation sheets by unhiding the 
specific sheet for the generated report in Microsoft Excel (Format > Sheet > Unhide 
> “observation sheet”).

EN50160_Mains_Signal
Use the EN50160_Mains_Signal template to create a report for signal line 
frequency statistics for a single meter, for each observation period.

The EN50160_Mains_Signal template uses data from the EN50160 MSignal log.

IEC 61000-4-30
IEC 61000‐4‐30 are power quality standards that define measurement methods for 
50 Hz and 60 Hz power quality instruments. Three IEC 61000‐4‐30 templates are 
available in Reporter:

IEC61000-4-30_10Min
Use this template to create the IEC 61000‐4‐30 report based on a 10‐minute interval 
sampling period.

IEC61000-4-30_2Hr
Use this template to create the IEC 61000‐4‐30 report based on a 2‐hour interval 
sampling period.

IEC61000-4-30_3Sec
Use this template to create the IEC 61000‐4‐30 report based on a 3‐second interval 
sampling period (i.e., 150 cycles for 50 Hz; 180 cycles for 60 Hz).

Waveforms
To generate a report from logs that contain voltage and current waveform data, 
select <no template> and set the Log to Waveforms. See “Creating a Report 
Without a Template” on page 335 for details.

After the report is generated, click the tab named for the waveform query to view.

The left pane contains timestamps that link to the waveform chart on the right 
pane. Click a timestamp to view the waveform.

To view the waveforms for each current and voltage phase, click Show Complete 
on the Waveforms toolbar. Use the magnifying glass icons to zoom in or zoom out.

Page 334 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Creating a Report Without a Template

Custom Templates
Contact Technical Support if you require other specialized report templates.

Creating a Report Without a Template


You can use Reporter to copy raw data from a database and paste it into Microsoft 
Excel:
1. In the main Reporter window, select Manage Reports, then click New.
2. Fill in the Report Name box, select <No Template>, then click Next.
3. Click New to create a source/log query for the report. Set the Query Properties:
Name: New queries are automatically named in a sequential manner, but 
you can also rename them as required.
Source: Select the source of the query (e.g., power meter).
Log: Choose the data log that you want to copy raw data from.
Database: ION_Data<SQL> is the default setting. To change the database 
source, select one from the list, or click More.
If a TOU schedule is required, select Apply TOU Schedule to database queries, 
then select one from the list, or click Manage to create one.
4. To add another query, click New, then set the query properties as described 
above.
5. When you have added and configured all your queries, click Next.
6. Configure the report options as described in the section, “Step 3: Set Up the 
Report Options” on page 328.

© 2009 Schneider Electric. All rights reserved. Page 335


Automatic Report Generation PowerLogic ION Enterprise User Guide

Automatic Report Generation


You can use the Windows Scheduled Tasks utility to generate reports on a set 
schedule:
1. Click Start > Settings > Control Panel. Double‐click Scheduled Tasks.
2. Double‐click Add Scheduled Task. Use the wizard to select Reporter from the 
list of programs.
3. Assign a name for this new scheduled task and specify how often this task 
should be performed.
4. Set the start time and other relevant data for your schedule. Click Next.
5. When prompted, enter your user name and password (and confirm the 
password). Click Next.
6. A summary screen of your schedule appears. Select Open advanced properties 
for this task when I click Finish, then click Finish.
7. The Properties screen of your task opens. The Task tab displays the command 
line to run Reporter. Add a space at the end of the command line and append “‐
r<ReportName>” (where “ReportName” is the name of the report you want to 
schedule for automatic generation ‐‐ note that spaces in the report name are not 
supported):
...\system\bin\repgen.exe ‐r<ReportName>
Reporter also supports multiple report generation. Separate the report names 
with a comma. For example, if you have reports named “Rep1” and “Rep2”, the 
command line might look like this:
D:\Schneider Electric\ION Enterprise\system\bin\repgen.exe ‐rRep1, Rep2
8. Verify your schedule settings in the Schedule tab. To create more schedules, 
select the Show multiple schedules check box. Click New to create a new 
schedule.
9. Click OK.

NOTE
Check the properties of your report to make sure you have specified a valid Date Range for your report
and that the “Show Report on screen” option is cleared.

Page 336 © 2009 Schneider Electric. All rights reserved.


PowerLogic ION Enterprise User Guide Using Reporter on Secondary Server or Client

Using Reporter on Secondary Server or Client


When Database Manager archives ION_Data, it creates a registry key export file 
that includes the DSN (data source name) it created. The registry file is called 
ION_DsnKeys.reg, and is stored on the primary server in this folder: 
...\ION Enterprise\config\cfg\

If you want an ION Enterprise secondary server or client installation to report on 
the ION Enterprise SQL database using Reporter, import this registry key to the 
secondary server or client before generating the reports.

Importing the registry key export file


1. Locate the primary server’s ION‐Ent share (typically 
\\ComputerName\ION‐Ent, where “ComputerName” is the computer name 
of the Primary Server) on your network and navigate to the ...\ION 
Enterprise\config\cfg folder.
2. Double‐click the file named ION_DsnKeys.reg to import it into your registry.

© 2009 Schneider Electric. All rights reserved. Page 337


Troubleshooting PowerLogic ION Enterprise User Guide

Troubleshooting
Excel file does not open when you double-click its icon
This might occur when a Microsoft Excel process hangs. To fix this, start Excel and 
open a file (or create a new one). Click Tools > Options, then in the General tab, 
clear Ignore other applications. Close and exit Excel.

If this does not work, try rebooting the computer.

Page 338 © 2009 Schneider Electric. All rights reserved.


A create new database 264
defragment 262
add detach 262
connection schedule 39 export registry setting 263
Ethernet device 35 manual 260
modem 36 modify login 263
network component 33 optimize query time 273
OPC device 35 restore 264
serial device 34 scheduled 267
server 33 scheduled maintenance 270
advanced security (access meters with) 38 SQL editor 265
alarm trim 265, 270
acknowledge (Vista) 105 update statistics 266
silence (Vista) 106 upgrade database 266
alarm options 144 Designer
alert monitor 308 clone a node 237
configuration file 309 ION modules toolbox 209
setup 309 node diagram 198
annunciation options 144 window configuration 206
Designer.See  ION  modules,  see  node  dia‐
C gram 207
device
CBEMA 125 Ethernet 32
configuring multiple devices 48 serial 32
connection schedule 39 diagnostics
control object communications 68
action options 143 server 67
display options 141 diagram object 93
control object (Vista) 129 caption options 134
preview pane 133
D direct site
add serial device 34
data display
copy data to another application 101 adjust column width 23
filter data 24 arrange columns 23
plot 101, 108 customize interface 22
real‐time 98 dock (pin) pane 22
sort 24 filter data in column 24
stale data settings (Vista) 96, 159 grid tables 23
view logged data 100 group table data by column 24
data log viewer 100 hide (unpin) pane 22
diagram object 128 resizing panes 22
link to data source 147 select columns to display 23
database 18 sort data in column 24
access via 3rd‐party application 275 downstream device 314
ION (ION_Data) 18 downstream device assistant
network configuration  add new device mapping 322
(ION_Network) 18 basic versus advanced view 315
system events (ION_SystemLog) 18 change measurement mapping 322
database management columns 316
alarm configuration 260 display physical sources 318
archive 261, 268 options 318
attach 262 rename assigned source 321
backup 262, 271 update  historical  data  after  changes
323 add events 119
duplicating a device 45 calculations window 110
customize 121
E de‐index parameters 114
display curve data in table 111
Ethernet device 32 graph options 110
add 35 harmonics analysis tab 115
Ethernet gateway legend 109
add device 34 overlay curves 125
event log viewer 100, 102 phasor diagram tab 116
diagram object 129 plot display tab 112
display 103 remove parameters 125
link to data source 147 specify y‐offsets 114
event watcher 62 symmetrical components 117
add event watcher 64 X‐parameter 149
create template 63
exit a component 19
M
G management applications 14
Management Console
global event log viewer 100, 102 customize the display 29
add 104 manager 281
display 103 Modbus
grouping object (Vista) 93, 128 add device type 278
display options 140 configure  advanced  device  functions
grouping window (Vista) 93 301
groups (of users) configure advanced functions 290
add/edit 58 default device types 278
edit register 291
H map file 278
Modbus gateway
harmonics analysis 115 add device 34
calculate  using  more  than  one  cycle modem
115 add 36
dial‐out 32
I remote modem setup 74
WinModem 36
ION module 207, 281 monitoring applications 14
configure 224
core versus standard module 208
online versus offline module 207 N
output register 207 navigating
parent module 227 tree structures 22
persistent module 208 network component 31
programmed versus pending 208 add 33
setup register 207 delete 37
view as text 213 edit 36
ION tree 220, 278 network diagram
generate 94
L node diagram 198
add module 210
large system setup 43 add text box 215
log inserter configure module 224
fast‐link option 229 copy module 230
log into a component 19 to framework 231
log off from a component 19 create shortcut to module 236
log view plotter 108 custom labels 227
add data from another application 120 default versus custom labels 204
add data from data log viewer 119 delete links between modules 222
display/edit mode 200 inputs 180
find dependent modules 211 load profile report 177
icons 201 power quality report 177
link modules 217, 220 print 185
link modules across nodes 219 save 185
linking modules 217 share 187
locate existing ION module 210 subscription 188
paste module 232 subscription configuration 61, 172
free paste or lock paste 235 system configuration report 178
from framework 232 tabular report 179
reset module 228 trend report 179
shortcut to module 214 upload reports/report packs 191
view as text 213
view input information 240
view output register information 239
S
view setup register information 240 selecting multiple items 22
numeric object 98, 128 serial device 32
display options 136 add 34
numeric object (Vista) server 31
flags 98, 138 add server 33
services, Windows 16
O site
direct site 31
OPC device 32 Ethernet gateway site 31
OPC Server 15 modem site 31
OPC site OPC site 32
add device 35 SQL Server 18
SQL Server instance 256
P start a component 19
status object 99, 128
phasor diagram 116 display options 139
power factor, display in Vista 114 subscription
PQDIF Exporter 15 event watcher 62
programming applications 15 Web Reporter 188
symmetrical components 117
Q system log events 41

query database, Vista 148
query server 148
T
querying database text box object (Vista) 128
query wizard 150 Time of Use (Designer)
advanced configuration 241
R time of use (Designer) 241
time of use (Web Reporter) 80
register 281
Reporter 325
reports
U
100 ms report 175 upgrade device 71
administration 187 user diagram 93
default definitions 175 add diagram object 128, 129
EN50160 report 175 background color 155
energy cost report 176 background image 156
energy period‐over‐period  communication errors 97
comparison report 176 copy/paste diagram objects 129
energy usage by shift report 176 create new 127
event log report 176 customize 127
export 186 customize diagram object 133
generate 180 default 94
IEC 61000‐4‐30 report 176 default action for window 158
default node 158 save report 185
default query server 157 share report 187
diagram objects, types 128 subscription configuration 61, 172
edit/display mode 92 upload reports/report packs 191
enable undo option 128 WebReach
font 155 access WebReach 163
layout 131 advanced configuration 168
navigate 95 communication errors 167
save 127 network diagram 163
specify for particular user 95 RMS waveform plotting 165
stale data 96, 159 stale data 167
users troubleshooting 170
add/edit 56 view events 166
user groups 58 view global events 166
view historical data 164
V WinModem 36

virtual processor (VIP)
common applications 250
Modbus communications 248
modify global parameters 79
set global parameters 252
setup 75
Vista
customizing diagram window 155
framework 130
generate network diagram 94
navigate 95
plot data 101
query wizard 150
view diagrams online (WebReach) 163
view logged data 100
view real‐time data 98
Vista diagram object
action options 142
alarming options 144
annunciation options 144
box options 143
display options 136
edit text options 135
link options 135
link to data source 146
query server options 136
text options 134

W
waveforms
plot 118
Web Reporter
default report definitions 175
display 174
export report 186
generate report 180
inputs 174, 180
navigation 174
print report 185
report administration 187
report subscription 188
PowerLogic ION Enterprise

User guide

For further assistance please contact us at:

Schneider Electric
Power Monitoring and Control
2195 Keating Cross Road
Saanichton, BC
Canada V8M 2A5
Tel: 1-250-652-7100

295 Tech Park Drive, Suite 100


Lavergne, TN 37086 ION, ION Enterprise, Modbus, Modicon, Power Measurement, PowerLogic and
USA Schneider Electric are either trademarks or registered trademarks of Schneider
Tel: 1-615-287-3400 Electric in France, the USA and other countries. All other trademarks are property of
their respective owners.
Electropole (38 EQI)
31, rue Pierre Mendès France Electrical equipment should be installed, operated, serviced, and maintained only by
F - 38050 Grenoble Cédex 9 qualified personnel. No responsibility is assumed by Schneider Electric for any
Tel : + 33 (0) 4 76 57 60 60 consequences arising out of the use of this material.

Getting technical support: 70002-0298-00


Contact your local Schneider Electric sales representative © 2009 Schneider Electric. All rights reserved.
for assistance or go to the www.powerlogic.com website. 06/2009