INSTALLATION,
OPERATION AND
MAINTENANCE
MANUAL
59812-K007
The information contained in this manual is the property of Kidde Products Limited and may not be reproduced or
transmitted in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, nor stored
in any retrieval system or any nature without the express written authority of Kidde Products Limited.
TABLE OF CONTENTS
Chapter Page
3 MAINTENANCE ...........................................................................................................62
3.1 ROUTINE MAINTENANCE 62
3.2 DETECTOR HEAD REPLACEMENT 63
3.3 DETECTOR HEAD REFURBISHMENT 64
3.4 FAN REPLACEMENT 67
3.5 CABLE REPLACEMENT 67
3.6 CONTROL UNIT MEMBRANE 68
3.7 CONTROL UNIT PCB REPLACEMENT 68
3.8 DECOMMISSIONING 68
LIST OF ILLUSTRATIONS
Figure Title Page
REVISION HISTORY
2. KPL warrants for a period of 12 months from delivery that individual OMD‟s supplied as spares
shall be free from defects in workmanship or materials during normal usage.
f. any modifications to or installations performed on the OMD‟s and/or OMD system outside
the scope of normal routine maintenance or running repairs without the express prior
written approval of KPL;
g. deterioration, staining or corrosion of parts which will occur due to normal exposure and
usage;
h. alleged defects not materially affecting the quality or proper functioning of the OMD
system.
b. KPL shall be under no liability in respect of any defect or failure of the OMD‟s and/or OMD
System to operate in accordance with specifications, illustrations, descriptions or other
particulars due to their combination or use with any incompatible equipment or product.
6. The Warranties are conditional upon:
a. the buyer or OMD system owner giving written notice to KPL of the alleged defect, such
notice to be given immediately when the buyer or OMD system owner discovers or ought
to have discovered the defect;
b. the buyer or OMD system owner affording KPL a reasonable opportunity to inspect the
OMD‟s and/or OMD system;
c. the buyer or OMD system owner not altering or attempting to repair the OMD‟s and/or
OMD system without the written consent of KPL.
7. The Warranties can be transferred to any new owner of the OMD system provided KPL is
informed in writing within 30 days of the transfer. The OMD System Warranty cannot be
transferred to another KPL OMD system.
8. Save to the extent amended by the provisions set out above, KPL‟s standard terms and conditions
of sale shall apply.
1.1 INTRODUCTION
High temperatures, in excess of 200ºC that occur on bearing surfaces under initial failure
conditions, can lead to a rapid generation of oil vapour When the hot vapour contacts the
relatively cooler atmosphere of the crankcase it condenses into a fine mist, with typical particle
sizes of around 0.5 to 5 microns in diameter. When the density of these particles reaches
between 30 to 50 mg/I (Milligrams per litre), depending upon the type of oil, an explosive
condition exists.
Main Bearing
Bottom End
Bearing
Detector
Detector
Cable
Remote Display
Unit
Control Unit
1.2 DESCRIPTION
The system comprises three main components (refer to Figure 3):
Detectors 53836-K269 (with base) / 53836-K272 (replacement head)
53836-269-01 (Short sample pipe)
Control Unit 53836-K270 (With Membrane)
53836-K276 (Without Membrane)
Remote Display Unit 53836-K271
And connecting cables
Control Unit to Detector cable (Straight) 43682-K286-XX
Control Unit to Detector cable (Right Angle) 43682-K285-XX
The Graviner Mk 7 OMD system can comprise up to 100 detectors directly mounted on the
crankcases of up to 10 engines, allowing both main propulsion and auxiliary generators to be
monitored at the same time.
Each detector communicates electronically over a serial data link via the engine mounted
Control Unit with the optional Remote Display Unit designed to be mounted within the Engine
Control Room. This eliminates the need to enter the machinery space in alarm conditions.
Control Unit
Enclosure Rating IP65
Max detector inputs 10
Output Relays Volt-free change over contacts rated at 30Vdc 1A
Back-up Alarm 1 set (de-energised during normal operation)
Pre Alarm 1 set (de-energised during normal operation)
Fault Alarm 1 set (energised during normal operation)
Engine Slowdown / Shutdown 1 set (de-energised during normal operation)
Alarm Ranges Pre Alarm 0.5mg/l to 1.2mg/l (adjustable)
Alarm 1.3mg/l to 2.4mg/l (adjustable)
Backup 3.0mg/l (fixed)
Power Consumption 3.9W
o
Temperature Rating 0 – 70 C
Dimensions
Height 186mm (110mm mounting centres)
Width 318mm (240mm mounting centres)
Depth 90mm
Weight 2.8kg
Alarm Philosophy
The system has 3 separate alarm levels as detailed below
1. Pre Alarm - This indicates that the oil mist levels are increasing in a particular
crank space and that investigation should be undertaken. This alarm will not operate
the slowdown or shutdown relays.
2. High Alarm - When any detector reaches this threshold then the slowdown or
shutdown relays will be operated if they are connected.
3. Back Up Alarm - In the event of a failure of either the Pre Alarm or High Alarm, then
the Back Up Alarm will operate, but it will not operate the slowdown or shutdown relay.
This is an additional functional precaution added by Kidde Products Ltd which can be
connected in any way the customer requires. This is usually connected to a warning
beacon or siren; however the customer may choose to connect the relay to another
device or the engine slow down circuitry.
On receipt of either a Pre Alarm or High Alarm the engine should, unless connected to a
slowdown / shutdown relay, be stopped if safe to do so and allowed to cool down so that the
background oil mist levels reduce before entering the engine room.
When the oil mist levels have returned to normal then the Accept and Reset buttons can be
operated from the Control Unit membrane if fitted or alternatively form the Remote Display Unit
and the system will then return to normal operation.
Fault Diagnosis
When a system fault is received, the information on the display should be noted and then the
appropriate Fault Finding procedure in Chapter 4 of the manual should be checked to enable
the fault to be rectified.
When the faults have been rectified the Accept and Reset buttons can be operated and the
system will return to normal
Event Log
All alarms, faults and events are recorded in an Event Log which is date and time stamped and
will indicate the type of event which enables analysis of the events at a later time. The Event
Log has a capacity of 1024 events and is a rolling buffer.
Relay Backup
Unit off Unit on Pre-Alarm Slowdown Fault
Description Alarm
Pre-Alarm
Alarm
Backup-alarm
Fault
The Control Unit 53836-K270 or 53836-K276 is designed for on-engine mounting and it is
recommended that the Control Unit is installed as near to the centre of the engine as possible
to minimise detector cable lengths.
Mounting is via the four M6 locating holes in the box. Sufficient space must be left around the
Control Unit to allow access to the cable glands and the routing of the cables and to facilitate
easy access to all aspects of the Control Unit.
Each detector is mounted to an individual crankcase via a ¾ inch BSP threaded hole.
Ensure all detectors fitted to the engine are locked tightly in place by means of the lock nut
supplied.
It is recommended that the detector be located at the upper part of the crankcase wall not in
the direct line of the oil throw. On smaller engines it is permissible to mount the detector on the
crankcase door if desired or as installation dictates, subject to vibration levels.
The detector must be fitted at a maximum of plus or minus 20 degrees from the vertical.
Horizontally the detector must be mounted level or with the detector body inclined towards the
engine to ensure oil drainage. Refer to Figure 8, and Figure 9.
Please ensure that Detector 1 is connected to position 1 on the Control Unit, Detector 2 to
position 2. Repeat for all Detectors fitted.
Each detector must be connected to the Control Unit by way of a supplied detector cable.
Refer Figure 10.
Ensure that the cables are run in a suitable cable tray and clipped at regular intervals to
ensure they cannot be subjected to mechanical damage caused by vibration.
o
Cable Length 90 Connector Straight Connector
m Part No. Part No.
1.0 43682-K285-1.0 43682-K286-1.0
1.5 43682-K285-1.5 43682-K286-1.5
2.0 43682-K285-2.0 43682-K286-2.0
2.5 43682-K285-2.5 43682-K286-2.5
3.0 43682-K285-3.0 43682-K286-3.0
3.5 43682-K285-3.5 43682-K286-3.5
4.0 43682-K285-4.0 43682-K286-4.0
4.5 43682-K285-4.5 43682-K286-4.5
5.0 43682-K285-5.0 43682-K286-5.0
5.5 43682-K285-5.5 43682-K286-5.5
6.0 43682-K285-6.0 43682-K286-6.0
6.5 43682-K285-6.5 43682-K286-6.5
7.0 43682-K285-7.0 43682-K286-7.0
7.5 43682-K285-7.5 43682-K286-7.5
8.0 43682-K285-8.0 43682-K286-8.0
8.5 43682-K285-8.5 43682-K286-8.5
9.0 43682-K285-9.0 43682-K286-9.0
9.5 43682-K285-9.5 43682-K286-9.5
10.0 43682-K285-10.0 43682-K286-10.0
10.5 43682-K285-10.5 43682-K286-10.5
11.0 43682-K285-11.0 43682-K286-11.0
11.5 43682-K285-11.5 43682-K286-11.5
12.0 43682-K285-12.0 43682-K286-12.0
12.5 43682-K285-12.5 43682-K286-12.5
15.0 43682-K285-15.0 43682-K286-15.0
17.5 43682-K285-17.5 43682-K286-17.5
20.0 43682-K285-20.0 43682-K286-20.0
22.5 43682-K285-22.5 43682-K286-22.5
25.0 43682-K285-25.0 43682-K286-25.0
For flush mounting details see below and Figure 13 and Figure 14.
For bulk head mounting details see Figure 15.
Cables should be segregated from high voltage cables and follow good installation
practice
2
Cable type-2 Cores + Earth, CSA 2.5mm (50/0.25mm), flexible stranded bare copper
conductors, low smoke halogen free insulation, cores laid up, braided screen, low smoke
halogen free sheath – grey, outside diameter 9.8mm, operating temperature 0ºC + 80ºC.
Suggested cables
2
Lapp Kabel CY cable 3 core 2.5mm
2
Prysmian LSM-HF 3 core 2.5mm
2
Helkama LKAM-HF 3 core 2.5mm
Modbus
Cable type – Individually screened 2 pair data cable, 24AWG, low capacitance, low smoke
halogen free. Outer diameter 7mm (max)
Cables should be segregated from high voltage cables and follow good installation
practice
Suggested cables
FS Cables 2402PIFFH
Beldon 9729
Helkama RFE-HF(i) 2x2x0.75
Jinro 60V RCOP(IS)
The above cable should be used to connect between the Control Unit and either the ships
AMS system or the Remote Display Unit.
Relay Outputs
The relay outputs are rated at 30v DC at 1amps.
2
2 Cores + Earth, CSA 2.5mm (50/0.25mm), flexible stranded bare copper conductors, low
smoke halogen free insulation, cores laid up, braided screen, low smoke halogen free sheath
– grey, outside diameter 9.8mm, operating temperature 0oC + 80oC.
Cables should be segregated from high voltage cables and follow good installation
practice
Approved cables
2
Lapp Kabel CY cable 3 core 2.5mm
2
Prysmian LSM-HF 3 core 2.5mm
2
Helkama LKAM-HF 3 core 2.5mm
USB Connection
Refer Figure 16 for connection location.
End of Line
Jumper
Modbus
Connector
End of Line
Jumper
USB
Connection
Relay Output
Connectors
24v DC input
Connector
Cables should be segregated from high voltage cables and follow good installation
practice
Suggested cables
2
Lapp Kabel 1.5mm Ölflex Classic 110CH - 10035068
2
Prysmian LSM-HF 3 core 1.5mm
2
Helkama LKAM-HF 3 core 1.5mm
Modbus
Cable type – Individually screened 2 pair data cable, 24AWG, low capacitance, low smoke
halogen free. Outer diameter 7mm (max)
Cables should be segregated from high voltage cables and follow good installation
practice
Suggested cables
FS Cables 2402PIFFH
Beldon 9729
Helkama RFE-HF(i) 2x2x0.75
Jinro 60V RCOP(IS)
The above cable should be used to connect between the control unit and either the ships AMS
system or the Remote Display Unit
24v DC
Connector Modbus
Connector
Exposed screen
Feed the cable into the control unit via a metal IP65 EMC gland supplied, ensuring that the
metal prongs make contact with the exposed cable screen as shown below.
Cable gland
Earthing Prongs
Press „OK‟
Press „OK‟.
Figure 32 will then be displayed.
To change the Time & Date press
„Set Time / Date
Press „OK‟.
Figure 32 will then be displayed.
To save the event Log press „Save
Logs‟
Press „OK‟.
Figure 48 will then be displayed.
Press „Back‟ to return to Figure 47.
Repeat setting Detector settings for
the number of Detectors connected.
USB
Connection
2.9.1.2 With the above cables connected, open the „Mk7 Oil Mist Engine Manger‟ software on the
computer.
Repeat the above for the number of Control Units installed per system.
After the address‟s have been changed, please ensure that the EOL jumpers are fitted to the last
Control Unit, all other Control Units need to have the EOL jumpers removed.
Refer Figure 16 for EOL jumper positions.
Note: Isolation of the output relays (Pre Alarm and Slow-Down Relays) is
required before commencing the smoke alarm test. If the Back-up Alarm Relay
is connected to the engine shut/slow down system this should be
disconnected.
Warning: Carrying out this test without isolation or disconnection of the output
relays will cause the engine shut/slow down system to operate if connected.
a. Cut a length of wick approximately 30 mm long. Assemble the smoke tester by pushing
the wick into the wick holder fitted with the pipette bulb. Press the nylon pipe into the pipe
connector (refer to Figure 56).
Pipette Bulb
Wick Holder
Wick
Pipe Connector
Nylon Pipe
b. Push the nylon pipe of the smoke tester into the connector on the side of the detector
base body (refer to Figure 57).
c. Dip the wick into the bottle of smoke oil and reseal the bottle firmly
Note: Only a small quantity of oil is required.
d. Ignite the wick of the smoke tester and blow out the flame. Squeeze the pipette bulb to
keep the wick smoking.
Note: Care to be taken with this activity at all times.
e. While the wick is still smouldering, insert it into the pipe connector and squeeze the
pipette bulb.
f. Observe the wick is still smouldering, insert nylon pipe into the pipe connector of the
detector and squeeze the pipette bulb.
g. After tests are completed the Detector Peak Level readings should be erased. This can be
done via the Engine Menu using Clear Peak. (refer Figure 44)
h. To release the pipe from the connector, press in the metal collar on the end of the
connector at the same time as pulling the pipe out
i. Remove the nylon pipe from the pipe connector for stowage purposes.
j. The wick is reusable and can be left in the wick holder. Fully extinguish the wick after use
at all times.
k. Refer to the Material Safety Data Sheet in the event of health or safety issues.
To prevent the possible activation of the Back-up Alarm Relay disconnect the cable from the
top of the detector unit.
Press „OK‟
Press „OK‟
You will be returned to Figure 64.
To Isolate the Pre-Alarm Relay, press
„Isolate‟
Press „OK‟
Press „OK‟
You will be returned to Figure 69.
To Isolate the Slow Down Relay,
press „Isolate‟
Press „OK‟
Press „OK‟
You will be returned to Figure 74.
Press „Exit‟ to return to Figure 59.
Press „Exit‟ to return to Engine 1
overview.
Press „Menu‟
Press „Isolate‟
Press „OK‟
Press „OK‟
You will be returned to Figure 82.
Press „Back‟ button to return to Figure 78.
Press „Back‟ button to return to Engine 1
overview screen (Figure 77).
Press „Back‟ button to return to Engines
overview screen.
Note: with the detector isolated the Back-up Alarm Relay may be activated if the oil mist level
increases above 3mg/l or light is introduced in to the detector. To prevent the possible
activation of the Back-up Alarm Relay disconnect the cable from the top of the detector unit.
Press „OK‟
You will be returned to Figure 88
To Test the Pre-Alarm Relay, press
the „1‟ button.
Press „OK‟
You will be returned to Figure 88.
To Test the Fault Relay, press the „0‟
button.
Press „OK‟
You will be returned to Figure 88.
To Test the Backup Alarm, press the
„Test‟ button.
Note – This is a software test only.
Press „OK‟
You will be returned to Figure 88.
To Test the Optics, press the „Test‟
button.
Press „OK‟
You will be returned to Figure 88.
To Test the Front Panel, press the
„Test‟ button.
Press „OK‟
You will be returned to Figure 88.
Press „Exit‟ to return to Engine 1
overview.
Note - This will also reset all Tests.
Press „Test‟
Press „Accept‟
Press „OK‟
Press „Reset‟
Press „OK‟
You will now return to Figure 87.
Press the „Back‟ button to return to
Engine Overview, Figure 86.
The Event Log enables the user to interrogate the past 1024 events and can be accessed via
the menus below. The Event Log is a rolling buffer and when the events exceed 1024 then the
oldest event is dropped off the Event Log.
To access the Event Log from Figure 87, press „Event Log‟ button.
Note - If there are no Events matching your search then this screen will be blank.
3 MAINTENANCE
3. Using a 4mm hexagon key, unscrew 2 off screws from the underside of the detector head
(refer to Figure 110). The screws are self-retaining.
4. Remove and invert the top part of the detector head. Examine the base moulding seal and
replace if damaged or perished (refer to Figure 112).
5. Using the Pulling Tool (refer to Figure 113), remove the Fan Retaining Plug by capturing
the shoulder and pulling. Carefully remove the Fan from its mountings (refer to Figure
114).
Compression
Spring
Fan
Fan Retaining
Plug
6. Examine the 4 off compression springs and the fan retainer plug; replace any bent or
damaged items from the spares.
7. Examine the fan for free running and clogging due to oil residues. If damaged, refer to
paragraph 3.4 in the instruction manual. Although not necessary for service cleaning,
spares of the M3 screw and the fan connector seal are included in the kit.
8. Using a foam bud with glass cleaner applied, wipe carefully around the inside of the
smoke detecting orifice (refer to Figure 115).
3.8 DECOMMISSIONING
All the components of the Graviner Mk7 OMD system must be disposed of as
electrical/electronic equipment waste. i.e. using waste disposal methods in accordance with
current local waste disposal regulations.
4 FAULT FINDING
4.1 GENERAL
The table below lists a series of failure modes and the likely faults that would be indicated
should that failure mode appear. Also listed are Actions, numbered 1 to 19, which should be
followed if the associated fault appears. On the following pages, Actions 1 to 19 are shown as
flow charts which will assist with fault finding on the Graviner Mk7 OMD system
Supply Failure
Control Unit Power indicator is off All Control Unit LED‟s off 1.
Membrane failure
Control Unit fault Control Unit fault LED on. Control Unit fault 2.
No indication on the
detectors.
All detector Power On (Green) Control Unit fuse.
Control Unit fault LED on, all 3.
indicators are off. Detectors disconnected.
detector fault LED‟s flashing
1sec on 1sec off
Control Unit Power indicator is off Communications fault with Supply Failure 6.
the engine indicated on the
Remote Display
No indication on the
detectors.
Control Unit fault LED on, all
All detector Power On (Green) detector fault LED‟s flashing Detectors disconnected.
3.
indicators are off. 1sec on 1sec off Power Supply failure
Remote Display indicates
communications fault on all
detectors for that engine.
Modbus communications
cable fault
Remote Display indicates a
Remote Display communications
communications fault on all End of line termination 12
with all engines fault.
engines incorrect.
Remote Display failure
Action 1
No Is 24v present
at the supply
input terminals
(TB1)
Yes
Action 2
No Is 24v supply
between 18 –
31.2v
No Do all of the
membrane LED‟s
operate correctly
Yes
Action 3
No Are all
connections
made correctly
Yes
No On power up are
the detector
power LED‟s on
Yes
Action 4
No
Does the
Yes communications
fault move with
the cable
No
Action 5
No Is the fan
operating
correctly
Yes
Yes
Replace the
detector End
Action 6
No Is 24v present
at the supply
input terminals
(TB1)
Is the 24v
No Yes
input power
supply cable
connected
correctly
Yes
Action 7
No Do all of the
LED‟s operate
correctly?
Yes
Action 8
Replace the
Control Unit
PCB
Action 9
No
Replace the
End Detector
Action 10
Yes
Optics test
passed?
No
Replace the
End Detector
Action 11
No Does the
watchdog fault
reoccur?
Yes
Replace the
End Detector
Action 12
No Are all
connections
made correctly
5 SPARE PARTS
Detector Spares
Item Description Part No.
Detector Complete 53836-K269
Detector Complete (Short Sample Pipe) 53836-K269-01
1 Detector Head Assembly 53836-K272
2 Fan Assembly D5622-005-02
3 Base Unit sub-Assembly D5622-101
4 Connector Push In B5465-307
5 Base moulding O Ring C1513-802
Cable Assemblies
90º Connector
43682-K285-1.0 1.0m Cable with 90° Connector 1.0 Metres
43682-K285-1.5 1.5m Cable with 90° Connector 1.5 Metres
43682-K285-2.0 2.0m Cable with 90° Connector 2.0 Metres
43682-K285-2.5 2.5m Cable with 90° Connector 2.5 Metres
43682-K285-3.0 3.0m Cable with 90° Connector 3.0 Metres
43682-K285-3.5 3.5m Cable with 90° Connector 3.5 Metres
43682-K285-4.0 4.0m Cable with 90° Connector 4.0 Metres
43682-K285-4.5 4.5m Cable with 90° Connector 4.5 Metres
43682-K285-5.0 5.0m Cable with 90° Connector 5.0 Metres
43682-K285-5.5 5.5m Cable with 90° Connector 5.5 Metres
43682-K285-6.0 6.0m Cable with 90° Connector 6.0 Metres
43682-K285-6.5 6.5m Cable with 90° Connector 6.5 Metres
43682-K285-7.0 7.0m Cable with 90° Connector 7.0 Metres
43682-K285-7.5 7.5m Cable with 90° Connector 7.5 Metres
43682-K285-8.0 8.0m Cable with 90° Connector 8.0 Metres
43682-K285-8.5 8.5m Cable with 90° Connector 8.5 Metres
43682-K285-9.0 9.0m Cable with 90° Connector 9.0 Metres
43682-K285-9.5 9.5m Cable with 90° Connector 9.5 Metres
43682-K285-10.0 10.0m Cable with 90° Connector 10.0 Metres
43682-K285-10.5 10.5m Cable with 90° Connector 10.5 Metres
43682-K285-11.0 11.0m Cable with 90° Connector 11.0 Metres
43682-K285-11.5 11.5m Cable with 90° Connector 11.5 Metres
43682-K285-12.0 12.0m Cable with 90° Connector 12.0 Metres
43682-K285-12.5 12.5m Cable with 90° Connector 12.5 Metres
43682-K285-15.0 15.0m Cable with 90° Connector 15.0 Metres
43682-K285-17.5 17.5m Cable with 90° Connector 17.5 Metres
43682-K285-20.0 20.0m Cable with 90° Connector 20.0 Metres
43682-K285-22.5 22.5m Cable with 90° Connector 22.5 Metres
43682-K285-25.0 25.0m Cable with 90° Connector 25.0 Metres
43682-K285-27.5 27.5m Cable with 90° Connector 27.5 Metres
43682-K285-30.0 30.0m Cable with 90° Connector 30.0 Metres
43682-K285-32.5 32.5m Cable with 90° Connector 32.5 Metres
43682-K285-35.0 35.0m Cable with 90° Connector 35.0 Metres