Product data sheet 33230

Characteristics circuit breaker Compact NS800N - 3 poles - 800 A


- fixed - without trip unit

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product NS630b...1600
Product or component type Basic frame
Device short name Compact NS800N
Device application Distribution
Circuit breaker name Compact NS800N
Poles description 3P
Network type AC
Breaking capacity code N
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B

Complementary
Network frequency 50/60 Hz
Control type Toggle
Rotary handle
Mounting mode Fixed
Mounting support Backplate
Upside connection Front
Downside connection Front
[In] rated current 800 A ( 50 °C )
[Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Circuit breaker CT rating 800 A
Breaking capacity Icu 40 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Icu 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Icu 40 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
Icu 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Dec 01, 2017
1
Icu 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity Ics 30 kA 660/690 V AC 50/60 Hz manual operation conforming to IEC 60947-2
Ics 40 kA 500/525 V AC 50/60 Hz manual operation conforming to IEC 60947-2
Ics 50 kA 220/240 V AC 50/60 Hz manual operation conforming to IEC 60947-2
Ics 50 kA 380/415 V AC 50/60 Hz manual operation conforming to IEC 60947-2
Ics 50 kA 440 V AC 50/60 Hz manual operation conforming to IEC 60947-2
Protection type Without protection
Mechanical durability 10000 cycles conforming to IEC 60947-2
Electrical durability 2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
4000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
5000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Connection pitch 70 mm
[Icw] rated short-time withstand current 19.2 kA ( 1 s ) conforming to IEC 60947-2
Integral instant protection 40 kA
Height 327 mm
Width 210 mm
Depth 147 mm

Environment
Standards IEC 60947-2
Product certifications LCIE
ASTA
ASEFA
Pollution degree 3 conforming to IEC 60947
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C

Contractual warranty
Warranty period 18 months