PowerCommand Control ANSI Protective Functions Application Manual A058E477 - I1 - 201711
PowerCommand Control ANSI Protective Functions Application Manual A058E477 - I1 - 201711
PowerCommand Control ANSI Protective Functions Application Manual A058E477 - I1 - 201711
English
Original Instructions 11-2017 A058E477 (Issue 1)
Table of Contents
1. INTRODUCTION............................................................................................................................ 1
1.1 Overview ................................................................................................................................. 1
1.2 About This Manual.................................................................................................................. 1
1.3 Application Manuals................................................................................................................ 1
1.4 Safety...................................................................................................................................... 2
4. APPENDIX ................................................................................................................................... 43
4.1 AmpSentry Load Bank Test Calculations ............................................................................. 43
4.2 Time-Delayed and Integral-Based Protection Functions ...................................................... 44
4.3 ANSI Device Descriptions..................................................................................................... 47
T-034: Networking Application Manual. Communication networks have long been used to make equipment
and processes operate more reliably and efficiently. As power generation systems migrate from
centralized to distributed generation and control, the communications infrastructure will need to become
more comprehensive and standardized so that equipment from multiple suppliers will be able to
communicate with each other seamlessly. The purpose of T-034 is to educate engineers, system
integrators, distributors, and interested users in the fundamentals of networks, as they apply and are used
in on-site power generation systems.
1.4 Safety
Safety should be a primary concern of the facility design engineer. Safety involves two aspects: safe
operation of the generator set itself (and its accessories) and reliable operation of the system. Reliable
operation of the system is related to safety because equipment affecting life and health is often dependent
on the generator set, such as hospital life-support systems, emergency egress lighting, building
ventilators, elevators, fire pumps, security and communications.
Refer to any relevant codes and standards for information on applicable electrical and fire codes around
the world. Standards, and the codes that reference them, are periodically updated, requiring continual
review. Compliance with all applicable codes is the responsibility of the facility design engineer. For
example, some areas may require a certificate-of-need, zoning permit, building permit or other site-specific
certificate. Be sure to check with all local governmental authorities early in the planning process.
NOTICE
While the information in this and related manuals is intended to be accurate and useful, there is
no substitute for the judgment of a skilled, experienced facility design professional. Each end
user must determine whether the selected generator set and emergency/standby system is
proper for the application.
◦ Manually, with user input (via discrete input, Modbus input or PCCNet input), when the
generator breaker is closed, and the utility breaker is open (loads are on the generator set),
and the Sync Enable command is active
• Power Transfer Control: The synchronizer is enabled either automatically or manually, under the
following conditions:
◦ Automatically, when the PTC logic is about to initiate a closed transition transfer or re-transfer
◦ Manually, with user input (via discrete input, Modbus input or PCCNet input), when the PTC
function is in a manual operating mode, and the Sync Enable command is active.
The synchronizer is disabled and locked out under the following abnormal conditions:
• Circuit breaker fails to close while in PTC mode
• Generator set fails to sync to the bus, and the Fail To Sync Lockout trim is enabled. Consider
enabling the lockout function to prevent the generator from trying to sync with load or to an unstable
source.
Phase Match and Slip Frequency
Although the ANSI synchronizer function defines only frequency matching, the PowerCommand
synchronizer includes a voltage matching function as well.
The synchronizer can be configured for either a Phase Match or a Slip Frequency method.
• Phase Match: The control drives the generator set frequency to match the utility frequency and
drives the phase angle of the generator waveform to match the utility waveform phase angle.
• Slip Frequency: When this method is used, the control does not try to drive the generator set
waveform to be in sync with the utility but drives the frequency to be offset from the utility frequency
by some “slip” frequency. Typically, this frequency is on the order of 0.1 Hz so that the utility and
generator set will periodically be in sync with each other. With a slip frequency of 0.1 Hz, the phase
difference will complete one cycle every 10 seconds.
With this method, the control calculates the optimum time to close the breaker based on the breaker
closing time and the rate of change of phase angle to close at a phase difference of 0 degrees.
Note, a higher slip frequency results in faster synchronizing but can result in high current spikes at
the instant of closing a breaker. If done repeatedly, this can damage the alternator. This tradeoff of
fast synchronizing versus minimizing stress on the alternator needs to be considered. In a standby
application where speed of synchronizing is of paramount importance and there will be few
synchronizing events over the life of the generator set, it is permissible to have a higher slip
frequency. In applications where the generators will synchronize and close to a live bus often over
its life, it is important to minimize slip frequency (typically to values of less than 0.1 Hz), to minimize
stress on the alternator. Consult the generator set manufacturer for more insight into this.
NOTICE
Cummins Generator Technologies (CGT) recommends that frequency match within 0.1 Hz and
the rate of change of frequency should not exceed 0.1 Hz/second and the phase angle difference
between sources should be less than 10 degrees. CGT recommends that for isolated bus
paralleling the voltage difference between generator sets should be less than 3% and for
paralleling between a generator set and the utility the voltage difference should be less than
0.5%.
Similarly, the Synchronizer Voltage Control Method can be configured in InPower for either a Voltage
Match function or to allow an external device to manage the voltage matching using the voltage bias input.
Figure 2 shows the InPower screen for setting the synchronizer speed and voltage control methods as
well as the Slip Frequency settings.
• Faulty PT.
Code 1457 – Fail To Synchronize
Logic:
Synchronizer has not met the synch check conditions within the “Fail To Synchronize Time" parameter
that can be set in InPower as shown in Figure 2.
Possible Causes:
• Improper adjustment of bus or generator set voltage.
• Faulty PT.
• Permissive window parameters are set too tight.
Code 1458 – Synchronizer Phase Rotation (Sync Ph Rot) Mismatch
Logic:
Mismatch in phase rotation between the generator set output and the system bus.
Possible Causes:
• Generator set or system bus voltage cables are incorrectly wired to the paralleling breaker.
• Generator set or system bus voltage sensing connections are incorrectly wired at the base
• board.
Synchronizer has not met the synch check conditions within the “Fail To Synchronize Time" parameter
that can be set in InPower as shown in Figure 2.
Possible Causes:
• Improper adjustment of bus or generator set voltage.
• Faulty PT.
• Permissive window parameters are set too tight.
Code 1458 – Synchronizer Phase Rotation (Sync Ph Rot) Mismatch
Logic:
Mismatch in phase rotation between the generator set output and the system bus.
Possible Causes:
• Generator set or system bus voltage cables are incorrectly wired to the paralleling breaker.
• Generator set or system bus voltage sensing connections are incorrectly wired at the base
• board.
NOTICE
The Voltage Override test feature is not available for L3 on the 1.X control.
On the 1.X control, this diagnostic becomes active if the line voltage is lower than the lost AC voltage
threshold, or the control does not sense zero crosses of either the alternator output voltage (connector
J22) or the excitation voltage (connector J18).
For controls that rely on excitation zero cross to measure frequency (i.e., generator sets without a full
authority engine or a magnetic pickup), the Lost AC Voltage diagnostic will become active if speed
measured by excitation zero cross does not reach a level that enables the voltage to ramp up. This is
most likely due to a disconnection between the excitation source and the control (J18).
The Under Excitation diagnostic is an integral function where, if the AVR PWM is less than the “Under
Excitation AVR Duty Cycle minimum Threshold” for a period of time in excess of the “Under Excitation
Threshold Time," the control will shut the generator set down to avoid an unstable condition or a pole slip.
This event will not be active if the reverse kVAR level is less than 5%. To clarify, this event will only be
active if the generator set is running at a leading PF and the absolute value of the VARs exceeds 5%.
Also, this event will not be active if V/Hz is driving the voltage setpoint down.
Possible Causes
• Leading Power Factor, when the generator set is lightly loaded.
NOTICE
AMM should be turned off when a technician is not working in the area to prevent nuisance
tripping. When starting a large motor, the motor could commonly draw more than 300% of rated
current for several seconds. With time delays bypassed, this could result in the generator set
shutting down if AMM is enabled.
Tests have shown that, with maintenance mode enabled, excitation is removed within 50 msec of the
overcurrent condition.
This function is used in conjunction with the AmpSentry overcurrent function (ANSI 51).
While running a generator set with a relatively large motor, a techician using InPower can use the disable
override function in AMM. To prevent nuisance tripping, the AMM Disable Override setting should be set
to Enable. This inhibits AMM from operating and causes the control to use the standard AmpSentry trip
curve. Note, the configurable input only enables AMM when the control is in "Auto" mode. If the control in
in "Manual" mode, then AMM can be enabled by plugging in the InPower Service tool only. When using
the tool to enable AMM, there is a walkaway timer of 5 minutes, so when the tool is unplugged, AMM
remains enabled for 5 minutes.
Be aware that this setting is volatile, because it reverts to its default value when control power is shut off.
The default value for the override is “Disabled,” which allows the AMM function to trip instantaneously
when current in any phase exceeds 300% of nominal standby rating.
NOTICE
If the generator set is restarted shortly after shutting down, the overcurrent shutdown time will
be limited based on the cool down time constant, as described in Section 2.10.
Possible Causes:
• Short in the load or load cables.
• Faulty CTs, incorrect CT ratio, CTs, CT connections.
Code 5399 – AmpSentry Maintenance Mode Active (Event)
Logic:
A technician enabled the Maintenance Mode function through either InPower or Configurable Input.
The benefit of current regulation is that it limits voltage rise on unfaulted phases. On the faulted phase,
voltage overshoot on fault clearing is also minimized. Be aware that AmpSentry does not limit current,
instantaneously. In the event of an overcurrent condition, the instantaneous current is a function of the
impedances of the fault and of the alternator itself. The time it takes for AmpSentry to reduce current to
300% is a function of the alternator reactances and time constants.
The i2*t integral is defined so that 300% of current will shut down the generator set in approximately 8
seconds, allowing ample time to start a large motor without nuisance tripping.
NOTICE
If the generator set is restarted shortly after shutting down, the overcurrent shutdown time will
be limited based on the cool down time constant, as described in Section 2.10.
Possible Causes:
• Short in the load or load cables.
• Faulty CTs, incorrect CT ratio, CTs, CT connections.
Code 1471 – High Current Warning
Logic:
Generator set output current has exceeded 110% for over 60 seconds or the overcurrent integral is over
the halfway point to the shutdown value.
Possible Causes:
• Overload.
• Incorrect CT Ratio, CTs, or CT connections.
Code 1472 – High Current Shutdown
Logic:
The AmpSentry High Current Shutdown threshold has been exceeded (the overcurrent integral has
reached the shutdown value). The High current Shutdown event will be active, if at the time of the
shutdown, the current is less than 1.75 per unit.
NOTICE
If the generator set is restarted shortly after shutting down, the overcurrent shutdown time will
be limited based on the cool down time constant, as described in Section 2.10.
Possible Causes:
• Short or overload.
• Incorrect CT Ratio, CTs, or CT connections.
NOTICE
Do not do this if the generator set has actually experienced an overload. If an overload
occured, run the generator set through the actual cool down sequence.
NOTICE
Do not do this if the generator set has actually experienced an overload. If an overload
occured, run the generator set through the actual cool down sequence.
NOTICE
Do not do this if the generator set has actually experienced an overload. If an overload
occured, run the generator set through the actual cool down sequence.
NOTICE
Do not do this if the generator set has actually experienced an overload. If an overload
occured, run the generator set through the actual cool down sequence.
• Faulty AVR.
• Faulty PMG.
• Governor preload offset percentage too high.
For the 1.X control, the underfrequency diagnostic is a fixed time function.
The extended underfrequency condition prevents overheating of the alternator, because of the reduced
cooling available due to slower rotation of the fan. Thermal damage time is relatively long compared to
other protective functions, but it needs to be accounted for.
Note, the underfrequency diagnostic is based on the target frequency communicated to the governor
rather than the system nominal frequency. The target frequency can vary based on paralleling functions,
Frequency Adjust (i.e., from the HMI or InPower), and external bias, and may not always be equal to the
system nominal frequency.
For the overfrequency condition, the delay time is fixed, and is based on the system nominal frequency.
Figure 23 illustrates this concept.
Note, the underfrequency diagnostic is referenced on the target frequency, which may be different from
the nominal frequency due to paralleling functions, frequency adjustment, and external bias. The
overfrequency diagnostic is referenced to the nominal system frequency.
Note, this test method is available in the 2.X and 3.X controls only but not the 1.X control.
PowerCommand controls have an AVR gain adjust parameter. The default setting is appropriate for most
applications. In some cases where the voltage is unstable or in paralleling applications, this parameter
may be decreased to improve stability. This should only be done by an experienced technician. Figure 22
displays the AVR Gain Adjust setting.
the parameter. In this context, the term "integral" refers to a sum of multiple readings of the same
parameter over time. An integral can be very simple, where the control is just counting the number of
readings that are above or below some threshold, or it can be a more complicated function in which the
integral sum is weighted by how far above or below the threshold the parameter is. The fundamentals of
time-based functions will be examined here.
Time-Delayed Protective Functions
Simple time-delayed functions are used to allow the generator set to ride through transient conditions. The
time delay should be set long enough so that the generator set does not shut down unnecessarily but not
so long that the generator set or other equipment is damaged. The main difference between a simple time
delay and an integral time delay is that a simple time delay requires that the parameter be outside of the
acceptable range continuously for the entire period. An integral time delay allows the variable to move in
and out of the acceptable range while the integral continues to accumulate.
The PowerCommand undervoltage diagnostic is an example of a simple time-delay diagnostic. In order for
this diagnostic to be "true," the measured voltage must be below the threshold continuously for the pre-set
time delay. For example, if the time delay is set for 5 seconds, and the control measures the voltage 100
times per second, the control would need to read the voltage as below the threshold for 500 consecutive
readings for the warning or shutdown to occur. The control effectively has a counter which increments for
every voltage reading below the threshold. When the counter reaches 500, the warning or shutdown
occurs. If any of the voltage readings are above the threshold, the counter is reset to 0.
Fixed Time Integral
As stated above, an integral is basically a sum of multiple readings of the same parameter over time. For
each reading, the integral sum can either be increased or decreased depending on whether a reading is
above or below a threshold. The difference between the integral and the time delay function is that with
the time delay function, any reading that does not exceed the threshold resets the timer back to its default,
where an integral function only decreases the sum by some value. For example, consider a system where
300 consecutive measurements exceeded the threshold and then one measurement was below the
threshold. With a time delay function, the sum would be reset to 0 at the first reading that was below the
threshold. With an integral function, the sum does not reset to 0 but decreases by 1. So with the integral
function, after 300 readings above the threshold followed by 1 reading below the threshold, the sum would
be 299.
The general equation for the integral is as follows:
• If measured value > threshold:
Integral sum = previous integral sum + (Time Constant) * Δt
• If measured value < threshold:
Integral sum = previous integral sum - (Time Constant) * Δt
Δt refers to the sampling rate of the control. If the control samples the parameter 100 times per second, Δt
= 0.01 (= 1/100).
The time constant sets the rate at which the integral sum increases or decreases. For a fixed time integral,
the time constant is simply 1/time delay. For a more complicated integral, the time constant will be a more
complex function.
Asymmetric Integral
In some cases, it is preferred to have the integral sum increase and decrease at different rates.
Overcurrent protection is an example of this, as components do not necessarily heat up and cool down at
the same rate. This can be achieved by simply using different time constants in the equations for
increasing and decreasing the integral sum.
Reverse kW and reverse kVAR are also examples where the integral sums increase and decrease at
different rates. This is because reverse power flow that oscillates about a threshold is a symptom of an
unstable system and this instability can lead to a pole slip or other catastrophic fault condition. Having an
asymmetric time constant inhibits the integral sum from "unwinding" during an unstable condition,
providing greater protection for the alternator.
Inverse-Time Integral
Under some conditions, it is desired for the protective function to act faster or slower depending on the
amount by which the parameter exceeds the threshold. An overvoltage condition is one example of this.
The trip time is shorter for higher voltages, longer for lower voltages. The trip time is inversely proportional
to voltage in excess of the threshold.
One form of the general equation for an inverse time integral is as follows:
• If measured value > minimum threshold
From this equation, if the measured value is low, the value being added to the integral sum is also
relatively low because the denominator is higher. As the measured value approaches the instantaneous
threshold, the value added to the integral sum will be very high (because the denominator becomes very
low), approximating an instantaneous trip. Figure 27 illustrates that for a constant voltage in excess of the
threshold, the time to shut down will be proportional to the:
Trip Time = Constant * (Instantaneous threshold – Measured Voltage).
Inverse-Squared Integral
Overheating effects caused by overcurrent conditions are a function of the square of the current, so
overcurrent protective devices often use an inverse squared integral based on an i2*t characteristic.
PowerCommand controls use different forms of inverse-squared integrals. Using these integral equations,
the expected shutdown time can be estimated based on a maximum current measured in the three
phases. Note, in an overcurrent condition, the current is rarely constant, so the actual trip times will vary
due to varying current. Even with AmpSentry’s current regulation function, the initial current at the onset of
the fault will exceed the 300% current regulation setpoint of AmpSentry for several electrical cycles before
current is effectively regulated. Because of this, AmpSentry will shut the generator set down in less time
than it would take if the current were constant at 300% from the onset of the overcurrent condition.
AmpSentry uses the following integral form:
• Integral sum = previous integral sum + (Time Constant) * Δt *(current – threshold)2
• Trip time is proportional to 1/*(current – threshold)2
The Negative Sequence Overcurrent protection uses an overcurrent ratio, defined as the ratio of actual
current to the overcurrent threshold. It uses the following integral form:
• Integral sum = previous integral sum + (Time Constant) * Δt *(overcurrent ratio)2
• Trip time is proportional to 1/*(Overcurrent ratio)2
The Custom Overcurrent protection uses a variation of the overcurrent ratio. It uses the following integral
form:
• Integral sum = previous integral sum + (Time Constant) * Δt *((overcurrent ratio)2 – 1)
• Trip time is proportional to 1/*((Overcurrent ratio)2 -1)
The common points about overcurrent protective functions is that they are proportional to time constants
and to the amount at which the current exceeds a threshold. Integrals increase when current exceeds the
threshold and decrease when the current is less than the threshold, but integrals may not increase and
decrease at the same rate, and rates may vary based on incoming signals.
Device
Function and Description
Number
Master Element is the initiating device, such as a control switch, voltage relay, float switch, etc.,
1 which serves either directly or through such permissive devices as protective and time-delay relays
to place equipment in or out of operation.
Time-Delay Starting or Closing Relay is a device that functions to give a desired amount of time
2 delay before or after any point of operation in a switching sequence or protective relay system,
except as specifically provided by device functions 48, 62, and 79.
Over-Speed Device is usually a direct-connected speed switch which functions on machine
12
overspeed.
A device that forces operating equipment to match and hold the speed of another machine or source
15
of power.
Valve is one used in a vacuum, air, gas, oil, or similar line, when it is electrically operated or has
20
electrical accessories such as auxiliary switches.
Device
Function and Description
Number
Distance Relay is a relay that functions when the circuit admittance, impedance, or reactance
21
increases or decreases beyond predetermined limits.
Synchronizing or Synchronism-Check Device is a device that operates when two AC circuits are
25 within the desired limits of frequency, phase angle, or voltage, to permit or to cause the paralleling of
these two circuits.
27 Undervoltage Relay is a relay that functions on a given value of undervoltage.
Annunciator Relay is a nonautomatically reset device that gives a number of separate visual
31 indications upon the functioning of protective devices, and which may also be arranged to perform a
lockout function.
Directional Power Relay is a device that functions on a desired value of power flow in a given
32 direction or upon reverse power resulting from arc-back in the anode or cathode circuits of a power
rectifier.
Position Switch is a switch that makes or breaks contact when the main device or piece of apparatus
33
which has no device function number reaches a given position.
Undercurrent or Underpower Relay is a relay that functions when the current or power flow
37
deceases below a predetermined value.
Field Relay is a relay that functions on a given or abnormally low value or failure of machine field
40 current, or on an excessive value of the reactive component of armature current in an AC machine
indicating abnormally low field excitation.
41 Field Circuit Breaker is a device that functions to apply or remove the field excitation of a machine.
Running Circuit Breaker is a device whose principal function is to connect a machine to its source of
running or operating voltage. This function may also be used for a device, such as a contactor, that
42
is used in series with a circuit breaker or other fault protecting means, primarily for frequent opening
and closing of the circuit.
Manual transfer or Selector Device is a manually operated device that transfers the control circuits in
43
order to modify the plan of operation of the switching equipment or of some of the devices.
Unit Sequence Starting Relay is a relay that functions to start the next available unit in a multiple-unit
44
equipment upon the failure or nonavailability of the normally preceding unit.
Reverse-Phase or Phase-Balance Current Relay is a relay that functions when the polyphase
46 currents are of reverse-phase sequence, or when the polyphase currents are unbalanced or contain
negative phase-sequence components above a given amount.
Phase-Sequence Voltage Relay is a relay that functions upon a predetermined value of polyphase
47
voltage in the desired phase sequence.
Incomplete Sequence Relay is a relay that generally returns the equipment to the normal, or off,
position and locks it out if the normal starting, operating, or stopping sequence is not properly
48
completed within a predetermined time. If the device is used for alarm purposes only, it should
preferably be designated as 48A (alarm).
Instantaneous Overcurrent or Rate-of-Rise Relay is a relay that functions instantaneously on an
50 excessive value of current or on an excessive rate of current rise, thus indicating a fault in the
apparatus or circuit being protected.
AC Time Overcurrent Relay is a relay with either a definite or inverse time characteristic that
51
functions when the current in an AC circuit exceeds a predetermined value.
Device
Function and Description
Number
AC Circuit Breaker is a device that is used to close and interrupt an AC power circuit under normal
52
conditions or to interrupt this circuit under fault or emergency conditions.
Power Factor Relay is a relay that operates when the power factor in an AC circuit rises above or
55
falls below a predetermined value.
Field Application Relay is a relay that automatically controls the application of the field excitation to
56
an AC motor at some predetermined point in the slip cycle.
Short-Circuiting or Grounding Device is a primary circuit switching device that functions to short-
57
circuit or to ground a circuit in response to automatic or manual means.
Rectification Failure Relay is a device that functions if one or more anodes of a power rectifier fail to
58
fire, or to detect an arc-back or on failure of a diode to conduct or block properly.
59 Overvoltage Relay is a relay that functions on a given value of overvoltage.
Voltage or Current Balance Relay is a relay that operates on a given difference in voltage, or current
60
input or output, of two circuits.
Time-Delay Stopping or Opening Relay is a time-delay relay that serves in conjunction with the
62 device that initiates the shutdown, stopping, or opening operation in an automatic sequence or
protective relay system.
Ground Protective Relay is a relay that functions on failure of the insulation of a machine,
64
transformer, or of other apparatus to ground, or on flashover of a DC machine to ground.
NOTE: This function is assigned only to a relay that detects the flow of current from the frame of a
machine or enclosing case or structure of a piece of apparatus to ground, or detects a ground on a
normally ungrounded winding or circuit. It is not applied to a device connected in the secondary
circuit of a current transformer, or in the secondary neutral of current transformers, connected in the
power circuit of a normally grounded system.
Governor is the assembly of fluid, electrical, or mechanical control equipment used for regulating the
65 flow of water, steam, or other medium to the prime mover for such purposes as starting, holding
speed or load, or stopping.
AC Directional Overcurrent Relay is a relay that functions on a desired value of AC overcurrent
67
flowing in a predetermined direction.
Blocking Relay is a relay that initiates a pilot signal for blocking of tripping on external faults in a
68 transmission line or in other apparatus under predetermined conditions, or cooperates with other
devices to block tripping or to block reclosing on an out-of-step condition or on power savings.
Permissive Control Device is generally a two-position, manually-operated switch that, in one
69 position, permits the closing of a circuit breaker, or the placing of equipment into operation, and in
the other position prevents the circuit breaker or the equipment from being operated.
Rheostat is a variable resistance device used in an electric circuit, which is electrically operated or
70
has other electrical accessories, such as auxiliary, position, or limit switches.
Alarm Relay is a relay other than an annunciator, as covered under device function 30, that is used
74
to operate, or to operate in connection with a visual or audible alarm.
Pulse Transmitter is used to generate and transmit pulses over a telemetering or pilot-wire circuit to
77
the remote indicating or receiving device.
Phase-Angle Measuring or Out-of-Step Protective Relay is a relay that functions at a predetermined
78
phase angle between two voltages or between two currents or between voltage and current.
Device
Function and Description
Number
A-C Reclosing Relay is a relay that controls the automatic reclosing and locking out of an a-c circuit
79
interrupter.
Liquid or Gas Flow Relay is a relay that operates on given values of liquid or gas flow or on given
80
rates of change of these values.
Frequency Relay is a relay that functions on a predetermined value of frequency (either under or
81
over or on normal system frequency) or rate of change of frequency.
D-C Reclosing Relay is a relay that controls the automatic closing and reclosing of a d-c circuit
82
interrupter, generally in response to load circuit conditions.
Automatic Selective Control or Transfer Relay is a relay that operates to select automatically
83 between certain sources or conditions in an equipment or performs a transfer operation
automatically.
Operating Mechanism is the complete electrical mechanism or servomechanism, including the
84 operating motor, solenoids, position switches, etc. for a tap changer, induction regulator, or any
similar piece of apparatus which otherwise has no device function number.
Carrier or Pilot-Wire Receiver Relay is a relay that is operated or restrained by a signal used in
85
connection with carrier-current or d-c pilot-wire fault directional relaying.
Locking-Out Relay is an electrically operated hand, or electrically reset relay or device that functions
86 to shut down or hold and equipment out of service, or both, upon the occurrence of abnormal
conditions.
Differential Protective Relay is a protective relay that functions on a percentage or phase angle or
87
other quantitive difference of two currents or of some other electrical quantities.
Auxiliary Motor or Motor Generator is one used for operating auxiliary equipment, such as pumps,
88
blowers, exciters, rotating magnetic amplifiers, etc.
Line Switch is a switch used as a disconnecting, load-interrupter, or isolating switch in an a-c or d-c
89 power circuit, when this device is electrically operated or has electrical accessories, such as an
auxiliary switch, magnetic lock, etc.
Regulating Device is a device that functions to regulate quantity, or quantities, such as voltage,
90 current, power, speed, frequency, temperature, and load, at a certain value or between certain
(generally close) limits for machines, tie lines or other apparatus.
Voltage Directional Relay is a relay that operates when the voltage across an open circuit breaker or
91
contactor exceeds a given value in a given direction.
Voltage and Power Directional Relay is a relay that permits or causes the connection of two circuits
when the voltage difference between them exceeds a given value in a predetermined direction and
92
causes these two circuits to be disconnected from each other when the power flowing between them
exceeds a given value in the opposite direction.
Field-Changing Contactor is a contactor that functions to increase or decrease, in one step, the
93
value of field excitation on a machine.
Tripping or Trip-Free Relay is a relay that functions to trip a circuit breaker, contactor, or equipment,
94 or to permit immediate tripping by other devices; or to prevent immediate reclosure of a circuit
interrupter if it should open automatically even though its closing circuit is maintained closed.