VFD Appl
How to Program LTMR Relay for Proper Operation
Directions to resolve fault light and reset issue on VFD Panels
Load the custom file, “Rolls Royce iff into the LTMR located in the VFD panel. This custom file
sets up input 16 to control the output 0.1, This change enables contol of the drive while in
remote Auto mode. Please be sure the overioad behaves the way you want on a fault,
conditions.
To apply the logic file, do the following in Powersuite:
41. Connect the communication cable from your laptop to the overload relay (TeSys T LTMR),
2. Tum on lap top and run the Schneider Electric PowerSuite program. Launch LTM
‘configuration,
3. Click on Custom Logic to expand the directory.
4, Click on Structured Text.
5, Select Logic Functions (on top toolbar in between tools and settings) --> Open Logic File
woe6. Change the file type to logic files and open the Rolls Royce logic fle (see below)
7, Select Logic Functions ~> Compile
8 Select Logic Functions > Download Program to Device
9. After a successful download select Settings -> Motor Control
(Sitesyst programmer 1.6.0.0
My conouter| [Birols Royce.
MyRecent Jy Network Paces
Decunents | yapplcaton Syctrrization
[Gaur cash
(Be Biorusemce
Decne | feRCestom D5 Fes
aeswe
= (Gui tec
B \@nro
[Boroereer
My Documents
ye (@shintech 2
¢ Barestea networks
My Computer P
Fle ns10. Change the operating mode to custom and change the Custom ID to 256 as shown below.
@ ae
11. Verify the settings have been accepted in the relay and then disconnect the communication
cable. Repeat steps for the next VFD panel TeSys T LTR,